GUtech _ Main Building
Mechanical Services
1. HVAC air ducts runningwithout sufficient supports,
not acceptable.
2. HVAC air ducts with poorquality cladding works, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
2/20
3. HVAC large ducts supportedon the AHU with
Polyurethane foam
(Thermocole) , not
acceptable.
4. AHU flexible connectionseems to be twisted, not
acceptable.
5. HVAC duct supported onPolyurethane foam
Thermocole) , not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
3/20
6. Unprofessional non-standard way of duct work
supporting, not acceptable.
7. Unprofessional non-standard way of duct work
supporting, not acceptable.
8. HVAC large ducts runningwithout sufficient supports,
not acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
4/20
9. Damaged HVAC duct andthermal insulation, not
acceptable.
10.Volume control damperpenetrated into the GI duct
and its thermal insulation,
not acceptable.
11.Poor way of sitemanagement, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
5/20
12.Electrical cables are notproperly tied, not
acceptable.
13.AHU flexible connectionseems to be twisted and
damaged, not acceptable.
14.HVAC Duct and thermalinsulation got cut and
damaged by its supports,
not acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
6/20
15.Chilled water pipessupported on the duct
works and the duct
supported on the masonry
block, poor way of
installation, not acceptable.
16.Chilled water pipessupported ineffectively, not
acceptable.
17.Unprofessional way ofequipment / ductwork
installations, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
7/20
18.Chilled water pipes sittingon the HVAC duct, not
acceptable.
19.Fresh air intake duct on theroof with no sand trap
louver or temporary
protection arrangement,
not acceptable.
20.HVAC Duct and thermalinsulation got cut and
damaged by its supports,
not acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
8/20
21.AHU flexible connection gotpressed and damaged due
to insufficient supports, not
acceptable.
22.Chilled water pipes with nosufficient supports, not
acceptable.
23.Chilled water pipes with nosufficient supports. Duct
end damaged by support,
not acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
9/20
24. Inconsistency in providingchilled water pipe supports,
not acceptable.
25.Duct and thermal insulationdamaged by supports, not
acceptable.
26.Application of sealant withno care or quality check, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
10/20
27.Fresh air intake with nolouver or protection, not
acceptable.
28.HVAC Duct sitting on theAHU and not properly
aligned or supported, not
acceptable.
29.HVAC duct supportpenetrated in to the
insulation, unprofessional
way of duct work
installation, not acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
11/20
30.Large HVAC duct saggingdue to no supports, not
acceptable.
31.Unprofessional way ofservices installation, notacceptable.
32.Undersized supportingelements, not acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
12/20
33.Thermal insulation got cut,no quality check observed
at site, not acceptable.
34.Installation of equipmentand fresh air intake
arrangement, absolutely
not acceptable.
35.Large HVAC ducts runningwith insufficient /
undersized supports, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
13/20
36.HVAC duct supported byfire sprinkler pipe, not
acceptable.
37.HVAC duct work and itsthermal insulationdamaged, not acceptable.
38.HVAC duct work andinsulation damaged and
supported on the AHU, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
14/20
39.Chilled water insulation gotdamaged and accessories
start rusting, not
acceptable.
40.Chilled water insulation gotdamaged and flanges startrusting, not acceptable.
Thermal insulation to be
replaced with new.
41.Chilled water insulation gotdamaged and flanges start
rusting, not acceptable.
Thermal insulation to be
replaced with new.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
15/20
42.AHU condensates drain pipetermination, not
acceptable.
43.Undersized (thin andsmaller) anti vibration pads,not acceptable.
44.Unprofessional way of ductwork installation, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
16/20
45.Unprofessional way of ductwork supports, not
acceptable.
46.Unprofessional way of ductwork supports, notacceptable.
47.Unprofessional way of ductwork supports, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
17/20
48.Unprofessional way of ductwork supports, not
acceptable.
49.Unprofessional way of ductwork supports, not
acceptable.
50.Unprofessional way of ductwork supports, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
18/20
51.Unprofessional way ofequipment/duct work
supports, not acceptable.
52.Unprofessional way ofequipment/pipes supports,not acceptable.
53.Damaged thermal insulationand regulating valve, not
acceptable and to be
replaced with new.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
19/20
54.Damaged thermal insulationand regulating valve, not
acceptable and to be
replaced with new.
55.Damaged thermal insulationand regulating valve, notacceptable and to be
replaced with new.
56.Rain water outlet notprotected as required, not
acceptable.
-
7/27/2019 Notice of defect dated 05-09-2012.pdf
20/20
57.Fresh air intake ductsupported with
Thermocole, unprofessional
way of site supervision not
acceptable.