november, - electrical part manual s · 2011-08-18 · anti-hunt device electromagnets _____ _...
TRANSCRIPT
type BJ-30 main control element
projection mounting
INDIRECT ACTING GENERATOR VOLTAGE REGULATORS-TYPE OJ-3D provide automatic voltage control of medium
and large size a-c generators such as those in electric utilities and large municipal and industrial generating stations. They are also used with synchronous condensers and synchronous motors.
The basic equipment consists of a control element mounted on a switchboard panel with necessary control devices, a motor-operated rheostat through which the exciter field cur
rent is varied, and a contactor panel for either "normal" or "quick"
change in the excitation current.
These regulators provide dependable
ope r a t i o n w i t h m i n i m u m m a in
tenance, at the same time meeting
the demand for control of quick-response excitation necessary for im
proving stability of interconnected
systems under fault conditions and large load changes.
Supersedes DescriptiYe Bulletin 31-270 dated May, 1953 Mailed to: E/259/DB; D64-5A; C/458/DB; C26-5L
flush mounting
WESTINGHOUSE SPECIAL FEATURES
.... HIGH SPEED OPERATION-Regulator operates within three cycles after a volt.
age change. Voltage is settled after a disturbance in minimum time.
.... FIELD FORCING-The regulator has the ability to force the exciter field quickly
to the limit and hold it there indefinitely, if necessary.
.... REGULATOR ElEMENT RESPONSIVE TO AVERAGE THREE-PHASE VOLTAGE, e l i m i
nating the danger of false regulator operation upon the occurrence of a n un
balanced system fault.
.... LOW MAINTENANCE-Since there are no continuously rotating parts and no
moving parts when voltage is normal, wear of moving parts is kept to a minimum
and long life without readjustment or replacement is assured.
.... UNIQUE ANTI-HUNTING ACTION provides for corrective effect proportional to
deviation from normal voltage, yet leaves the light weight moving element
free at all times to respond to voltage changes.
.... INHERENT COMPENSATION FOR TEMPERATURE OF REGULATOR maintains the reg
ulated voltage within the normal sensitivity band whether the regulator is hot
or cold.
.... SIMPLE ELECTRICAL CIRCUITS make operation easy to understand.
.... VERSATILITY-Regulator can be adjusted readily to match the individual char
acteristics of various a-c machines, such as slow speed water-wheel driven
a-c generators, high speed turbine driven a-c generators, synchronous motors,
and synchronous condensers. No modification of the standard regulator is
necessary to make such adjustments.
NOVEMBER, 1959 www . El
ectric
alPar
tMan
uals
. com
Construction
SIal Ion bus
2--------------------------------+-�-------------------------------- 2 3 3
® CD
Current transformer 1,.------1-*--("" "'_.(Required when
Type BJ-30 regulator main control element
® Currenl limiting device_
(When used)
® Cross -currenl compensator (Required when application
involves parallel operation)
1] (---" I
I I I
r----' .-1 l I I L ____ .-J
o Indicating lamps
/Name plate
® Voltage adjusling rheasta t
o E<ciler rheaslal conlrol swilch
Cul out switch
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
I I
3
application involves parallel operation)
L@��Genera,or field
/� ... Moi n exciter
/ Shunl field
Pilol exciter
l-:::�===t Differenlial � field
(When used)
o Motor operated rhe ostat
Pilot e<ciler shunt field
o Contaclor panel
\
�l
, - -- ' , / "\ I \ I \ I I \ I \ I
" " ....... _--/
14 Wires 10 conlactor panel and rheostat assembly
I <> Conduil J L ___ C��u� __ J I � ___ ��- - __ -_-��= ______ .£o�d.!!!t _____________________ J
Layout of a typical type BI-30 regulator installation showing conduit runs and external wiring required to inter_ connect the various units of equipment. Where there are paralleled a-c generators, current transformer connections are also required as shown.
The Type BJ·30 regulator is of the indirect·acting exciter rheo·
static type; that is, it controls the voltage of an a·c machine by
varying the resistance in the field circuit of the exciter that ex·
cites the a-c machine. The exciter should be separately excited
from a pilot exciter or other source. When the a-c voltage is
normal all parts of the regulator are at rest.
For small deviations from normal voltage, the regulator operates
a motor·operated rheostat in the main exciter field circuit to
effect the required change in exciter field current to bring the
a-c voltage back to normal. For large changes from normal
voltage the regulator operates high speed contaclors to insert
or short circuit suitable blocks of resistance in the main exciter
field circuit, to effecl quickly a relatively large change in the
exciter field current, at the same time operating the motor·
operated exciter field rheostat to a corresponding new position.
It is to be particularly noted that the restoration of normal a·c
voltage after a change in load is not determined by the time reo
quired for the rheostat to move from one position to another,
except for voltage changes which are relatively small. For
large changes in voltage, the high speed contaclors cut in or
short out resistance in the main exciter field circuit to obtain
maximum voltage response of the exciter, while the rheostat is turning at maximum speed to its new position. www .
Elec
tricalP
artM
anua
ls . c
om
o MAIN CONTROL ELEMENT
Test term,in'als .. ______________________ ___ Control element main coil _____________ _
Lever arm ________________________ �� Control element core __________________ "" Quick response contacts _____________ """
Normal response contacts _____________ _ Anti-hunt device electromagnets _ __ __ __ _
Dashpots ____________________________ _
The main coil 01 the control element consists of a voltage winding which is energized by a doc voltage, rectified from the three phase a-c source being regulated. A movable iron core is located in the main coil and is supported at its lower end by an aluminum alloy lever arm which carries the normal response and quick response contacts. The pull of the voltage winding on the core is balanced by an adjustable calibrating spring attached to the lever arm. The lever arm is made of aluminum alloy so that relatively little energy to move it through its range of travel is required.
There are two groups of contacts in the main element assembly: the normal response R-L contacts mounted near the right hand end of the lever arm and the quick response AR-AL contacts mounted near the center of the lever arm. The lever arm is so mounted that its movement prcduces a sufficient wiping action of the contacts to insure reliable contact. The contacts are made of a precious metal alloy, designed to stand severe duty and long service with a relatively little maintenance. Tests involving one-half million operations of these contacts have been made and their excellent condition after such tests indicated that several times as many operations could be made without maintenance being required.
ANTI-HUNTING DEVICES-Each group of contact assemblies in· cludes an anti-hunt device. Each anti-hunt device consists of a small electro-magnet, the armature of which is connected by a link to support the stationary parts of one group of contacts. Whenever one of these electro-magnets is energized, the movement of its armature causes the gap distance between the upper and lower stationary contact faces to be increased. With this arrangement the anti-hunt devices prevent hunting or overshooting by means of this contact spreading action, which sep· arates stationary contacts from the moving contacts on the lever
arm without disturbing the position or balance of the lever arm.
Thus, the moving lever arm is free at all times to follow the voltage.
The anti-hunt devices operate with a time delay action which is provided by a dashpot coupled to both the armature of each anti-hunt device and to the main element lever arm. The dashpot uses a piston having rounded edges which eliminates the problem of alignment. With this design the piston does not
have to be a particularly close fit in the dashpot and wear is minimized, since the liquid used acts as a lubricant. This special liquid is relatively non-evaporating and non-gumming, and reo tains approximately the same viscosity over wide ranges of temperature. Such dashpots need to be inspected only at regular intervals and it is seldom necessary to replace the liquid except after long periods of time. The dashpot's position is fixed by doweling and it can be easily removed and replaced with a screw-driver, without dismantling any other parts.
MOUNTING-The main control element is designed for switchboard panel mounting in either projection or flush mounting case. The control element in projection type case is mounted on a base and protected by a removable glass cover. On the back of the base there is a sub-base which supports the Rectox rectifier and a terminal board. The sub-panel assembly projects to the rear of a switchboard mounting panel and is covered by a protective metal screen. The terminal board and its connecting studs for outgoing leads is exposed at the rear. The front of the flush type case is provided with a removable cover having a glass insert. When the cover is removed, the element may be drawn forward by removing the holding thumb nuts, which permits the element to slide out on supporting rods. Suitable stops prevent withdrawing the element entirely away from the case. This construction permits an easy inspection of the element and provides for unhampered maintenance and adjustment when necessary. With the flush type case design the Rectox rectifier is mounted as a separate unit apart from the regulator on the rear of the switchboard. www .
Elec
tricalP
artM
anua
ls . c
om
o VOLTAGE ADJUSTING RHEOSTAT
The voltage adjusting rheostat provides a means of setting the
regulator to regulate the voltage at the value at which it is to be
maintained. A plate type rheostat of type He or LK design is
normally used, with the rheostat connected in series with the
regulator coil. The standard rheostat is manually operated and
normally mounted on the switchboard panel below the main
control element. The rheostat provides a range of regulated
voltage control of approximately plus or minus 10 per cent from
normal.
The voltage adjusting rheostat can also be supplied with a
motor-operated mechanism, where desired. This makes pos
sible remote control of this rheostat from a control room, or in
the case of unattended stations remotely controlled by super
visory control it can be readily operated through the medium
of the supervisory control.
o RHEOSTAT CONTROL SWITCH
The rheostat control switch provides for manual control of the
motor-operated main exciter field rheostat. This switch is of the
type W design and arranged for panel mounting. It has a pistol
grip handle which is normally in the "off" position. The handle
is spring return either from the "lower" or the "raise" position.
o CUTOUT SWITCH
The cutout switch provides for changing from manual to regula
tor control and vice versa. The Type W switch is designed
for panel mounting and has a round notched handle that stays
in whichever position it is set. The switch has three positions:
"manual," "indicating" and "regulating." In the "manual"
position the regulator is removed from control. In order to
change machine excitation with the cutout switch in this posi
tion, the rheostat control switch must be turned manually to
either its "lower" or "raise" position. When the cutout switch
is in the "indicating" position only the regulator element is
energized with the motor-operated main exciter field rheostat
still under manual control of the rheostat control switch. In
this position it is possible to balance the control element by means
of the voltage adjusting rheostat, thereby insuring no disturbance
to the system voltage when the cutout switch is turned to the
"regulating" position. With the cutout switch in the "regulat
ing" position the regulator has complete control of the motor
operated main exciter field rheostat and its associated field
forcing up and field forcing down contactors.
o INDICATING LAMPS
Two standard, switchboard type indicating lamps enable the
operator to adjust the regulator control element so that the trans
fer in and out of service may be made only when the excitation
is correct, and not during periods of excitation change. When
the a-c voltage is normal both lights burn brightly. When the
regulator is changing the position of the motor-operated ex
citer field rheostat, either the raise or lower lamp is short-cir-
cuited, which indicates not only that a change is taking place
but also the direction of the change.
o CONTACTOR PANEL
The contactor panel mounts the contactors that control the op
eration of the motor-operated main exciter field rheostat. This
panel also mounts the high-speed, heavy-duty, field.forcing and
field-reducing contactors which are used to insert and short
circuit resistance in the exciter field.
Two rheostat motor-control contactors are located on the lower
part of the contactor panel. An adjustable capacity condenser
is connected in parallel with the coil on each of these contactors
and this arrangement causes them to operate as definite time
delay devices. The time setting may be changed to suit the in
dividual installation by changing the amount of condenser ca
pacity.
Two high·speed, field forcing contactors are mounted on the
upper part of the contactor panel. One of these contactors is
used to insert resistance in the exciter field circuit and the other
to short circuit resistance. These contactors are designed to be
capable of handling the maximum exciter field current and at
the same time are very high speed in operation. They are de
signed to stand severe service and silver contacts and effective
blowout coils make them capable of handling high exciter field
currents, such as encountered in applications involving the
slow-speed, water-wheel driven a-c generators. A single-pole,
double-throw knife switch is provided on the contactor panel
for cutting out of service the main contacts of the field forcing
contactors for inspection or maintenance. A small single-pole
knife switch is also provided to render inoperative the contacts
of the high speed "field forcing up" contactor in the exciter
differential field circuit, when such a field circuit is used.
The contactor panel is usually located on the frame of the motor
operated main exciter field rheostat, since this minimizes the
wiring and decreases the number of conduit runs that would be
required if it were mounted at some other point. If Westing
house furnishes the exciter rheostat with the regulator the con
tactor panel is mounted integral with the rheostat assembly and
all interconnecting wiring is installed in the factory.
FIELD FORCING AND FIELD REDUCING RESISTORS-The field forcing
and field reducing resistors, are usually mounted in the motor
operated exciter field rheostat assembly. This resistor limits the
maximum exciter field current under manual control, and to
gether with a portion of the main exciter rheostat, provides for
field forcing when it is short circuited by the field forcing con
tactor under control of the regulator.
The field reducing resistor is provided with slider or taps for
adjustment. By varying the connections, either to different taps,
or by slider adjustment, any required value of resistance may
be secured. This resistor is introduced into the circuit of the
exciter field by the opening of the normally closed field re
ducing contactor. www . El
ectric
alPar
tMan
uals
. com
Cuhicle type combination contactor panel and plate ..
type m.otor-operated m.ain exciter field rheostat for
medium. size exciters.
Faceplate type motor�operated main exciter field
rheostat and contactor panel for large size exciters.
o MOTOR-OPERATED MAIN EXCITER FIELD RHEOSTAT
The Type BJ-30 regulator controls the a-c voltage by operating a motor-operated
main exciter field rheosta!. This rheostat must necessarily be 01 special design
for regulator service with its moving parts designed to withstand frequent
operation. The motor mechanism is quiet in operation and has practically no
over-travel after the motor is de-energized. This aids in quickly settling the
voltage, in that the regulator anti-hunt device need not compensate for other
than the electrical inertia 01 the exciter and its a-c machine.
A doc motor 01 the split-field series-wound type is used to operate the rheostat.
This type of motor permits adjustment of speed to meel different operating
conditions and requires minimum control apparatus. Tapped resistors for use
in the motor field circuits are included in the exciter rheostat frame.
The faceplate of the rheostat is usually provided with approximately 200 but
tons in circular arrangement which connect to the necessary resistance. The
rheostat assembly, in addition to the necessary regulating resistance, also in
cludes the exciter field permanent resistance, the field forcing and field re
ducing resistors, and where required the differential field resistance. Pro
vision is made for those sections 01 resistance which are subject to adjustment
so thai the proper values 01 resistance may be selected with minimum effort
to insure the best performance under any given set of field conditions.
Two general forms of construction are used for the motor-operated exciter
field rheostat:
FOR MEDIUM SIZE EXCITERS a cubicle type assembly is used. The rheostat
resistance is of the plate type with the resistance element completely embedded
in vitreous enamel which provides rigid mechanical support, good heat con
duction, and complete protection against moisture and corrosion. The rheo
stat and its motor mechanism are mounted in the lower portion of the cubicle.
The upper portion of the cubicle is used for mounting the contactor panel,
which gives a compact, factory assembled and tested unit.
FOR LARGE SIZE EXCITERS where relatively heavy field current has to be han
dled, a rheostat having large current capacity is required. A heavy-duly molar
operated faceplate is used and Ihe faceplate buttons or contact segments are
connected on the rear to suitable resistance units. The resistance units are
mounted in a frame on the rear of the faceplate. The rheostat frame is designed
so that the contactor panel may be mounted on the front upper portion.
TYPES OF RESISTANCE-�The connections of the rheostat vary according to the
requirements of the exciter and the a-c machine with which it is used. A
"series" type rheostat is used with an exciter having a standard shunt field
where it is not necessary to reduce the exciter voltage below "residual" volt
age. A "series" type rheostat is also used with an exciter having shunt field
and differential field where it is necessary to reduce the exciter voltage to zero
or to reverse the field current momentarily. Where Ihe application would
normally require an exciter with a differential field and when the exciter can
not be equipped with such a winding, other types of rheostats, such as the
potentiometer or Wheatstone bridge types are used.
PERMANENT EXCITER FIELD RESISTANCE-For quick-response excitation the ex
citer field circuit is usually made to have relatively low resistance. For this
reason a block of resistance, called the "permanent" resistance, is sometimes
required lor use in series with the exciter field to limit the current when full
pilot exciter voltage is applied. This resistance is mounted in the assembly
01 the molar-operated excitel' field rheostat, where it is readily accessible.
DIFFERENTIAL FIELD RESISTOR -The differential field resistor, when supplied,
is usually mounted in Ihe assembly of the motor-operated exciler field rheostat. www . El
ectric
alPar
tMan
uals
. com
Accessories
Cross�current compensator for use with Type BJ .. 30 regulator. (The line drop compensator is 5im�
ilar in appearance.)
Current�Brniting device in projection type caS0
for use with Type BJ-30 regulator. (Flush type
case to :rn.atch main control elernent as shown on
page I is also available.)
� COMPENSATORS
When two or more regulators are operated in parallel, a means must be provided to keep the reactive kva properly proportioned between the paralleled a-c machines controlled by the regulators. If suitable reactance for this purpose is not available in the form of an existing tranSlormer bank, it is obtained by providing each regulator with a cross-current compensator operated from a current transformer.
In the case of line drop compensation, line drop compensators energized from current transformers are used, the number required depending on the individual requirements of each particular application. Line drop compensation involves the drop in the line and transformers between the station bus and distrib· uting center. With suitable current transformers and line drop compensators, a voltage component may be introduced into the potential circuits which feed the regulating element to properly compensate for the line drop.
The cross-current and line-drop compensators are of similar construction and each is housed in an adequately ventilated case. The amount of compensation may be adjusted by means of the
dial switches, the contacts of which are connected to taps on an auto-current transformer. The movable arm of each dial switch can be solidly fastened to the desired contact point by means of a machine screw. This provides a reliable contact, which is an
important factor in a current transformer circuit. Insulating trans· formers are also mounted in the compensator case and are used to eliminate all electrical connections between the potential and current circuits. With this arrangement the usual grounding of
potential and current transformers may be made in accordance
with standard practice.
Two dial switches are provided on each compensator. One of these switches gives a coarse adjustment and the other a fine adjustment of the compensation. A total of 24 steps are available on the two switches, which in the case of the standard 12 % com
pensator gives a V2% change in compensation per step. Each
compensator imposes a burden of 94 volt-amperes at 80% power factor on the current transformer to which it is connected at 4 amperes secondary current, when set at 12 % compensation. The burden is 17 volt-amperes at 80% power factor when set at 5% compensation, which is ample for the usual application.
o CURRENT LIMITING DEVICE
WITH DELAYED ACTION
The current limiting device with delayed action is used with the
Type BJ regulator to limit the load current carried by the a-c ma
chine by taking control away from the regulator main control
element when the desired load limit is reached. This equipment
is usually used on synchronous-condenser applications.
The current limiting device is essentially a current regulating
element mounted in a suitable case. This device imposes a bur
den of 60 volt-amperes at 20% power factor on the current trans
former to which it is connected, at 4 amperes secondary current. In addition, three auxiliary relays are used consisting of a type
SC relay, a type MG relay and a type CV relay. The type SC relay is a current relay which functions to distinguish between a
slowly increasing overload and sudden overload. The type CV relay is a timing relay and controls taking the regulator in and
out of control by means of the type MG auxiliary relay. These
relays function only on sudden overloads and delay cutting out
the regulator for a period that may be adjusted from one to sev·
eral seconds. www . El
ectric
alPar
tMan
uals
. com
® POTENTIAL TRANSFORMERS
Each regulator requires two potential transformers connected
in open delta to supply energy to the regulator. This provides
a source of energy to operate the regulator control element from
the average three phase voltage of the system and insures a
positive raise impulse with resultant increase in machine ex
citation on the occurrence of any type of fault.
The volt-ampere burden of the regulator is relatively low, (ap
proximately 75 volt-amperes at 86.6% power factor on each
potential transformer.) For this reason standard potential trans
formers with a ratio to give 115 secondary volts at normal pri·
mary volts may be used as a source of potential for the regulator.
High tension fuses, with current limiting resistances where sys·
tem requirements indicate they are needed, are recommended
for use in the primary side of the transformers. This is desirable
in order to isolate the transformers from the bus in case of high
tension winding faults. No secondary fuses should be used.
There should not be any other load on the potential transformers
used with the regulator, unless as shown on the speCific diagram
furnished with the equipment. With regard to the a-c volt-meter
usually supplied as a part of the switchboard control equipment
for voltage indication purposes, this may be connected normally
to any one of the a-c machine phases. In cases of appreciable
phase load unbalance it should be remembered that the usual
single phase voltmeter does not indicate the average a-c three
phase voltage to which the regulator responds.
@ CURRENT TRANSFORMERS
Current transformers are required for cross-current compen·
sation purposes in connection with the parallel operation of
regulators or when it is desired to provide for line drop com
pensation. These transformers may be used with indicating in
struments in addition to the regulator but their use with walthour
meters is not recommended as the regulator load may introduce
some error in the readings.
For cross-current compensation on three-phase, three-wire sys
tems, one current transformer is required for each a·c machine
and its regulator. The primary rating is determined by the full·
load current of the generator multiplied by the factor 1.25.
For line·drop compensation the number of current transformers
required is dependent upon the individual requirements of each
particular application. The primary rating of each transformer
should be selected equal to the normal full·load current of the
circuit to be compensated, multiplied by the factor 1.25 and the
nearest standard ratio selected.
Where the current limiting device is used one standard current
transformer is required and selected according to the normal
full load current of the machine to be protected, multiplied by
the factor 1.25.
In all cases current transformers of sufficient capacity should
be supplied so that the volt·ampere burden of the devices con·
nected to them does not exceed their rating as specified by
their manufacturer.
Sensitivity
The rated sensitivity of the Type BJ·30 regulator is plus or
minus one·half of one per cent of normal voltage. The
rated sensitivity represents the band or zone of voltage,
expressed in terms of percentage of the normal value of
regulated voltage, within which the regulator will nor
mally hold the voltage under steady load conditions. When
the regulated voltage varies more than the percentage sen·
sitivity from the regulator setting, due to sudden changes in
load or other conditions, the regulator will immediately
apply corrective action to restore the voltage to the sen
sitivity zone.
Regulator sensitivity should not be confused with overall
regulation, which involves not only regulator sensitivity but
also the time constants of the machines, and the character
and magnitude of load changes. The magnitude and rate
of load change determines how far the voltage will vary
outside of the regulator sensitivity zone and the time con·
stant of the machines chiefly determine the time required to
restore the voltage to the sensitivity zone of the regulator.
For these reasons, only sensitivity can be specified insofar
as the regulator is concerned, rather than over·all regula·
tion which involves factors over which the regulator has no
control.
www . El
ectric
alPar
tMan
uals
. com
Operation
I +_4>-,C_u _rr_e_ n_1 _Ir_o_o_s-" 2�--��----��� 3�'---+--r-�--�-4� HI. fuses
Grd,
cs CS RI RI
Rectox recli fiers
Test link
on contoctor
panel
NOTE*-Current Transformer and
Cross .. Current Compensator Re ...
quired When Application Involves
P arallel Operation.
Symbols 1 Open contact
Closed contact Ope rating coil of device Indicating lamp
Resistor
Rheostat
Conde nser Rectax rectifier
K oi Ie switch
A-C gen field
rheo ,
Pilot exc,
Diff fld res,
Pilot exciter field rheostol
shunt field
Pilot exciter field series field �eg'COil
Te�nk I
Knife switch
QH
I I
I I
I ------ �
BJ -30 Regulator e lement (Front view)
Main exc rheo, motor
Res,
Rheo, limit switches
CS RI
Res ,
CS CS ReI} MI
Device Nomenclature
DEVICE
R·L AR-AL NR·NL QR-QL QH-NH CS-R � CS-L j CS-Reg. CS-RI CS-MI RL-LL CP MG
DESCRIPTION
Regulator Element Raise and Lower Normal Response Contacts. Regulator Element Raise and Lower Quick Response Contacts. Raise and Lower Rheostat Motor Control Contactors. Raise and Lower High Speed Field Forcing Contactors. Anti-Hunt Devices for Regulator Quick and Normal Response Contacts.
Rheostat Control Switch (Manual) Raise and Lower Contacts.
Regulator Cutout Contacts Closed in "Reg." Position Only. Regulator Cutout Contacts Closed in "Reg." and "Ind." Positions. Regulator Cutout Contacts Closed in "Man." and "Ind.'t Positions,; Raise and Lower Indicating Lamps. A-C Undervoltage Relay Auxiliary Relay
(+l
CP D-C
contro l bus
CP
(-)
Fig. I-Schematic wiring diaqrarn of Type BJ -30 generator voltage regulator for oontrol of an a-c generator excited by a main exciter which is
separately excited from a pilot exciter. Current transformer and cross .. current compensator shown are required only when two or more a-c gen
erators, under control of individual regulators. operate in parallel, Lines in red are added to provide "Loss of Potential" protection.
The main control element of the regulator is energized from two
single phase potential transformers connected to the a-c machine
leads. There are two sets of contacts on the movincg lever arm
of the regulator element: the "normal response" contacts R·L
and the "quick response" contacts AR·AL. The normal response
R-L contacts control the rheostat motor contactoTs NR and NL,
to raise or lower a-c machine voltage. The quick response AR
and AL contacts control the high speed contactors QR and QL,
which are the field forcing and field reducing contactors re
spectively. When OR is closed all external resistance is shorted
out of the main exciter field circuit and when OL is energized
a block of resistance is inserted in the field circuit. www . El
ectric
alPar
tMan
uals
. com
NORMAL RESPONSE
When the a-c voltage is normal, the regulator lever arm will be balanced and in this position neither the normal response contacts R-L nor the quick response contacts AR-AL will be closed. Both indicating lamps LL and RL will be brightly lighted.
Should the a-c voltage fall below normal by a small amount, depending upon the sensitivity setting of the regulator, the normal response contacts R will close, energizing the rheostat motor control contactor NR. The contacts on contactor NR complete the circuit to the motor of the main exciter field rheostat. The motor then turns the rheostat in a direction to cut resistance out of the exciter field circuit which increases the voltage applied to the exciter field circuit.
The rheostat motor control contactor NR has three contacts which close in independent circuits simultaneously. The one circuit is that just described which operates the rheostat motor. The second is the circuit of the anti-hunting winding NH of the regulator main control element and the third set of contacts on contactor NR complete the timing condenser circuit. The antihunt device operates to increase the gap distance between the contact faces of the regulator contacts R and L, thereby opening the circuit at the R contacts. This change in position of the R contact is equivalent to changing the regulator setting to a lower voltage, so far as the R (raise) contacts are concerned (and to a higher voltage so far as the L (lower) contacts are concerned.) This change in regulator setting or calibration is the anti-hunting effect and it can be varied to suit the individual characteristics of different types of a-c machines.
Where the deviation from normal voltage is small and within the recalibration effect of the anti-hunt device, the immediate results of the closing of the contacts on contactor NR is to cause the opening of the regulator R contacts, which in turn opens the circuit to the coil of contactor NR, to stop the motor of the exciter field rhEostat and thus stop the rheostat moving arm. However, contactor NR does not immediately open due to a time delay circuit around its coil. Thus, the rheostat arm is permitted to move a definite distance, for example, from one button to the next on the rhEostat faceplate. At the end of its time delay, contactor NR opens to stop the rheostat motor and de-energize the anti-hunt device.
After the rheostat motor stops, it is desirable to provide some time delay to allow the a-c machine voltage to reach its final normal value. Such delay is obtained by means of a dashpot on the anti-hunt device, which prevents the regulator contacts from immediately returning to their normal position. After this time delay has passed and the contacts have returned to their normal position, the normal response contacts R will again close if the a-c voltage has not returned to normal. This will start another cycle of operation such as just described and these cycles will continue until normal a-c voltage is established.
Where the original voltage deviation is large enough the regulator contacts will make continuously even though the antihunt device changes the contact setting. In this case the regulator lever arm is caused to follow up the change in contact position made by the anti-hunt device, and the R contacts and contactor NR will remain closed. This causes the rheostat motor to run continuously until the a-c voltage gets within the zone for which the anti-hunt device is set, at which time notching action as previously described will take place to bring the voltage to normal.
By means of the continuous or notching action of the rheostat, dependent lIlp!Jn the magnitude of the voltage change, time is allowed as the voltage approaches normal, for the machine to settle betwekn each voltage correction. The action of the dashpot is also such that the time required for contacts to remake is
longer as the lever arm approaches the normal voltage position. In other words, the time that the motor is de-energized, is an increasing ratio as normal voltage is approached. This results in a decreased motor speed as the rheostat arm moves nearer to its new position. Thus overshooting of the rheostat position is prevented and the voltage is brought to normal in a minimum length of time.
The foregoing discussion covers deviations in voltage lower than normal. Where the voltage rises above normal the regulator normal response contacts L will close, energizing the rheostat motor control contactor NL, which in turn operates the rheostat motor to increase the resistance in the exciter field circuit. At the same time, contacts on contactor NL energize the anti-hunt device NH to spread the contacts and de-energize the rheostat motor contactor as previously described.
QUICK RESPONSE
When a large drop in voltage occurs, such as might be caused by a large block of load being thrown on the system or by a fault, the normal response contacts R on the regulator close, followed by the closing of the quick response contacts AR. Contacts AR close the circuit to the high speed field forcing contactor OR, which short circuits all of the external resistance in the exciter field circuit, thus applying full exciter voltage to the field circuit. This causes the a-c machine voltage to start to return to normal very rapidly.
When the field forcing contactor OR closes, an auxiliary contact on this contactor closes at the same time in the circuit of the anti-hunt device OH. This device operates to spread the AR and AL contacts, in the same manner as described for the NH device and the R and L contacts. Therefore, if the deviation from normal voltage is within the recalibration effect of the OH anti-hunt device, the field forcing contactor will close and open rapidly while the rheostat arm approaches the required new position. If the deviation from normal voltage is greater than the recalibrating setting of the OH anti-hunt device, the field forcing contactor will close and remain closed until the voltage is brought within the setting the anti-hunt device.
When the a-c voltage gets within the setting of the AR contacts, the normal response contacts R take control and by notching the rheostat, return the a-c voltage to normal. Since the rheostat turns at maximum speed while the quick response contacts are closed it takes only a minimum of additional movement after the normal response contacts take controL to return the voltage to normal.
In a similar manner, when a large block of load is removed from the system, thus causing a large increase in voltage, the quick response contacts AL will close and energize the high speed field reducing contactor OL, whose main contacts are normally closed. This contactor then opens its main contacts and inserts a block of resistance in the exciter field circuit, causing the exciter voltage to fall with extreme rapidity and in turn the a-c machine voltage falls very rapidly. When the a-c voltage gets within the setting of the quick response contacts AL, the normal response contacts L take control and settle the voltage by notching action of the rheostat.
LOSS-Of-POTENTIAL PROTECTIVE EQUIPMENT
To insure against over voltage on the generating system, should the potential to the regulator be interrupted, a type CP a-c undervoltage relay may be used to actuate a type MG doc relay to block the BJ-30 _ regulator "raise" circuits. The connections of such a set of loss-of-potential protective equipment, consisting of two relays and a resistor, is shown in red on Fig. I. This equipment can be furnished with the regulator, and is applicable specifically to turbogenerator installations. www .
Elec
tricalP
artM
anua
ls . c
om
Cur I��-�----���-�--�
24-+-�--------���-1 34-+-��-------+-+-/
Step· up current aula t ransformer
Rectox reclifiers
CS RI
Motor oper. main�
exc. rheo. C ndsr.
Pilol exc. series fld.
(+)
D-C control
bus
cs CoZ�Clor I C d
NR
panel n sr. � __ + __ --l L-__ -+ ____ -. L
Symbols
1 Open contact
Closed contac!
Operating coi 1 of device
Indicating lamp
Resistor
Rheostat
Condenser
RecIo. rectifier
Knife switch
CS Rl
CS Ml
Device Nomenclature DEVICE DESCRIPTION
R·L AR-AL RI-LI ARI NR-NL QR-QL QH-NH RH-LH
CS-R 1 CS-L f CS·Reg. CS-RI
CS-MI
RL-LL RC-LC SC CV MG
Regulator Element Raise and Lower Normal Response Contacts. Regulator Element Raise and Lower Quick Response Contacts. Current Limiting Element Raise and Lower Normal Response Contacts. Current Limiting Element Quiclr Response Contacts. Raise and Lower Rheostat Motor Control Contactors. Raise and Lower High Speed Field Forcing Contactors. Anti-Hunt Devices for Regulator Quick and Normal Response Contacts. Anti-Hunt Devices for Current Limiting Element Quick and Normal Response
Contacts.
Rheostat Control Switch (Manual) Raise and Lower Contacts.
Cutout and Indicating Switch Contacts Closed in "Reg." Position Only. Cutout and Indicating Switch Contacts Closed in "Reg." and "Ind." Positions
Only. Cutout and Indicating Switch Contacts Closed in "Man." and "Ind." Positions
Only. Raise and Lower Indicating Lamps. Raise and Lower Anti-Hunt Auxiliary Relays on Current Limiting Element. Overcurrent Relay. Timing Relay. Auxiliary Timing Relay.
Fig. 2�Schernatic wiring diagrarn of Type EJ .. 30 generator voltage regulator for control of a synchronous condenser excited by a m.ain exciter
which is separately excited £rom a pilot exciter. Diagrarn shows the current liITliting device and associated auxiliary relays recommended for
this type of application. www . El
ectric
alPar
tMan
uals
. com
OPERATION WITH SYNCHRONOUS CONDENSERS
The Type BJ-30 regulator may be used with a synchronous con
denser to maintain constant voltage on a transmission line by
varying the condenser field excitation. When the excitation of
a synchronous condenser is increased above normal it fur
nishes a leading current to the line, thereby causing the volt
age to rise. In a similar manner, decreasing the excitation
lowers the voltage. Thus, when a generator voltage regulator
is applied, it will hold the line voltage constant by varying the
excitation of the synchronous condenser, provided there is suf
ficient corrective kva capacity in the synchronous condenser.
When a synchronous condenser is used for transmission line
voltage regulation, it is ollen necessary that it furnish not only
leading kva but also at times lagging kva. In order to supply
lagging kva the excitation of the condenser must be reduced to
an extremely low value. In fact it is sometimes necessary to reo
duce the exciter field excitation almost to zero. In such cases,
where it is necessary for the exciter to operate at less than 30%
CURRENT LIMITING DEVICE WITH DELAYED ACTION
In the operation of a synchronous condenser under abnormal
conditions a situation may occur where the condenser does not
have sufficient corrective kva capacity to handle all, or the
most severe, system requirements. At such a Hme, the regulator
in trying to hold up line voltage, would so over excite the con·
denser that it would draw excessive current and become over·
heated. To protect against this condition, a current limiting de·
vice has been designed for use in such cases. This same device
may also be employed where the regulator is used with an a-c
generator, with a·c generator being subject to over-current
which might result in damage to the a-c machine if maximum
excitation was maintained too long.
The current limiting equipment consists of a current limiting
element and three auxiliary relays, which consist of a type SC,
type CV and type MG relay, connected as shown in Fig. 2. The
current element has its contacts connected in series with the
main control contacts of the voltage regulator so that when the
load current increases, the current element takes control to pre·
vent a further increase in excitation. When the load conditions
change and the current drops below the setting of the current
element, control is restored to the voltage regulator.
The current limiting equipment has been designed to recognize
two conditions; first, the case of slowly rising load current to a
predetermined limiting or unsafe value, and second, a sudden
increase in load current such as might be caused by a fault or
short-circui!. The distinction between a slowly increasing over·
load and a sudden overload is made by a type SC curren! relay,
which is set to pick up at a current somewhat above the regulat.
ing point of the current limiting elemen!.
In the first case, for slowly rising load current, where the current
limiting element takes control from the voltage regulating el.
ement during the period of overload and returns control to the
voltage regulating element when the overload has passed, the
following sequence of operation takes place. Referring to Fig.
2, the current limiting contacts Rl open the circuit to and take
the control away from the R contacts of the voltage regulator
of its rated voltage, this requires that it be separately excited
from a pilot exciter or other source.
In order to seCure low or reversed field excitation, the exciter
must be equipped with a suitable differential field winding. The
differential field is energized in the opposite direction to the
main shunt field and has enough effect to reverse the exciter
voltage a small amount. Where the differential field scheme is
used the simple series type of motor operated main exciter field
rheostat is recommended. If the differential field scheme is not
used it is possible to use an alternate arrangement consisting of
some special form of exciter rheostat such as a potentiometer
type, or Wheatstone bridge design. In the latter rheostat, two
opposite arms of the bridge are fixed and the other two are va
riable, the variable arms having sufficient resistance to balance
the bridge and reduce to zero the voltage applied to the exciter
field.
element. Contacts Ll of the current limiting element then close
to energize the circuit to the rheostat motor control contactor
NL, which in turn causes the excitation to be reduced until the
load carried is the desired value. In this sequence of operation
only the "normal response" circuits of the voltage regulator are
used.
In the second case, where a sudden overload occurs, quick re
sponse excitation may be required. Contacts ARI of the cur·
rent limiting element operate in conjunction with the quick reo
sponse contacts AR of the voltage regulator in the same manner
as described for contacts Rl of the current limiting element with
the normal response contacts R of the voltage regulator. The
sequence of operation is initiated by the type SC current relay
opening its contacts. One set of these contacts de-energizes the
type CV timing relay and the other set de-energizes the type
MG auxiliary relay. With the type MG relay in the de·energized
position this permits the contacts of the voltage regulating ele
ment to remain in control for the time setting of the type CV
timing relay, thus providing the use of both the normal and quick
response excitation for stability purposes under fault conditions.
The time element may be varied from about one second to sev·
eral seconds. At the end of the time setting, the timing CV relay
contacts energize the type MG auxiliary relay, which in turn
removes control from the voltage regulator and transfers the
control to the current limiting element.
When the sudden overload is past, the type SC current relay
resets, in turn closing the circuit which maintains the type MG
auxiliary relay energized and at the same time closing the cir
cuit which resets the type CV timing relay. Should the decreas·
ing overload remain for a time at a value below the pickup of
the SC relay but within the setting of the current limiting ele
ment, the lalter will maintain control to prevent increase in ex·
citation. When the overload falls below this value, the contacts
RI and ARI cf the curren! limiting element return to their normal
closed position thus returning complete control of the voltage
to the voltage regulator. www . El
ectric
alPar
tMan
uals
. com
PARALLEL OPERATION
Slation bus I�--------------------�----------------
2 -4�------------------4-�--------------3 �-+�----------------�-+�-------------
A - C Generator No.1
'/ Voltage regul alor No. I
A-C Generator No.2
Voltoge regulator No.2
Veclor Diagram
I2 O"loP.F.
C
!
�Y2 i Compensator Int ernal Diagram
Fig. 3-Diagram of connections for cross-current compensation when awe generators operate in parallel, each under control of an individual
regulator. Vector diagrarn and internal wiring diagram of compensator show compensating voltages supplied by compensator to regulator.
The Type BJ-30 regulator can control only one exciter at a time.
Where two or more a-c machines are operated in parallel, each
provided with an individual exciter, it is necessary that each one
be provided with its own individual regulator. With this scheme
of operation the exciters must be operated non· parallel.
The division of the kw load among paralleled a-c generators is
dependent upon the power supply to each generator and is
controlled by the governor of its prime mover. Thus the divi.
sion of the kw load is practically independent of the excitation.
However, changes in the field excitation of paralleled a-c mao
chines does affect the reactive kva or waltless component of
the output. Since the voltage regulator acts directly on the field
excitation, it will be seen that although the division of kw load
between machines is unaffected by the voltage regulator, the
division of wattless current is directly affected by the operation of the regulator.
Thus, when a-c machines are operated in parallel, each under
control of an individual regulator, this will cause circulating
wattless current between the a·c machines unless some pro·
vision is made to cause each machine to shirk wattless current.
To secure stability in parallel operation it is, therefore, necessary
to give the regulated voltage a droop with increase in the walt·
less component of the machine current. In general, a satisfac.
tory droop in the regulated voltage will be obtained if there is
from four to six per cent reactive drop between two a·c machines.
This reactive drop may be either in the form of a power trans·
former bank or where the station layout does not provide such
an arrangement, it may be obtained artificially by giving the reg·
ulator a drooping characteristic from a cross-current compen·
sator energized from a current transformer.
Where the cross current compensator scheme is used, one com·
pensator and one current transformer is required for each a·c
machine and its regulator as shown in Fig. 3. The compensator
is designed to supply compensating voltages in two legs of the
three·phase regulator potential circuit. This insures applying
a balanced three-phase voltage to the regulator element, which
would not be the case if only one leg was compensated.
In the vector diagram, Fig. 3, the potential transformer secondary
voltages on the regulator are represented by vectors E1.2, E2.3 and E3-1. The current applied to the auto·transformer in the
compensator is taken from the secondary of a current trans
former located in phase 2. Two compensating voltages are pro
duced, one between terminals XI-X2 designated as Ez on the
vector diagram and the other between terminals Yl-Y2, desig
nated as ER on the vector diagram. Voltages ER and Ez are 1200
apart in time phase and, therefore, can be added to another
three-phase voltage without unbalancing it.
By referring to the vector diagram it will be noted that Ez and
ER are shown for zero power factor at which condition maximum
compensation is obtained. As the power factor approaches
unity these vectors swing through an arc of 90° and give zero
compensation at 100% power factor. At zero power factor vee·
tors Ez and ER add directly to vectors EI-2 and E3-1 respec·
tively. For power factors greater than zero only a proportionate
component of these voltages Ez and ER add directly to voltages
El.2 and E3-1. The addition of these compensating voltages to
line voltages EI.2 and E3_1 as the load increases or the power
factor changes gives the regulator element a high voltage indi
cation, resulting in a reduction or droop in regulated voltage.
Usually the compensator should cause from 4% to 6% droop in
voltage at zero power factor full load. The compensator is de·
signed to give 12% of 115 volts compensation, on the maximum
dial setting, when 4 amperes are flowing in the current trans·
former secondary. It is not necessary to use all of the 12 % com·
pensation, however, the 4% to 6% values mentioned above
usually being sufficient for good parallel operation. www . El
ectric
alPar
tMan
uals
. com
LINE DROP COMPENSATION
Phase rota lion 1 - 2 - 3 .
� __ '
_
Ja
_
Od
_
{di� 3 -I---��-+-+_+-----./
o I 2
CROSS CURRENT
CO G REACTANCE LINE DROP
XI X2 VI
Ex ....
REACTANCE L I N E DROP
Y2
Ev -
co c RESI STANCE LINE DROP
XI X2 YI Y2
Ex �
R ESISTANCE LINE DROP
12 E coil' -Ex +E23 - Ev
Fig .. 4-External connection diagram. for Type BJ compensators�
Outgoing line 10 load center
Current transformer
Voltoge regulator
Vector d iagram
Fig. 5-Line drop compensation diagraln for one a-a generator and
single outgoing line.
The wide use of interconnecting power systems has eliminated to a large extent the need for line drop compensation. However, it is sometimes desirable 10 regulate for a conslant voltage 10 he maintained at some point on the system external to or dis·
lant from the station where Ihe a-c machine and its regulator are located. The principle by which this is accomplished is shown by the vector diagram of line drop shown in Fig. S.
EI is the station voltage, E2 the feeder terminal voltage or the voltage at the load center, HI is the ohmic drop of the line and Xl the reactive drop. If it were possible to supply the regulator with pilot wires running back from the end of the line, it would receive the voltage E2 and could adjust the excitation of the generator to maintain E2 constant. Since in actual practice it is impractical to run pilot wires, the regulator potential winding is energized from the generator bus voltage, that is, by EI, and the two components Xl and HI are subtracted from it artifi. cially by the compensation, so as to supply the regulator with a resultant voltage E2. In this manner the regulator acts the same as if it were energized by pilot wires from the end of the transmission line, provided the components HI and Xl are actually proportioned to and in phase with the corresponding values in the line.
In general, since the reactance component Xl of the transmission line predominates, it is necessary to compensate mainly for this component of the line drop, the resistance component HI having a relatively small effect. In the following typical examples the compensation for the reactance component only is discussed. However, for those applications where compensation for the resistance component is also desired, such compensation can be included.
For those cases where system operating requirements will permit or favor the use of line drop compensation, the scheme of compensation to be used can be selected only alter a careful analysis is made. The following information is required and should be supplied in connection with any given application in order that recommendations covering proper equipment may be made.
1. The approximate regulation of transmission line, at its rated capacity and zero power factor.
2. Length of transmission lines. 3. Wire spacing. 4. Size of wire. S. Frequency of system. 6. Total capacity of transformer banks at each station that oper-
ates on the line.
For the first example, refer to Fig. 5, which shows the connections for line drop compensation when used with a single a·c generator which feeds a single transmission line. By means of one current transformer and a suitable line drop compensator, a voltage component is introduced into the regulator element potential circuit which is in proportion to the reactance drop to the load center at the far end of the transmission line. The compensator functions to lower the voltage impressed on the regulator main control element as the station load is increased, thus causing the regulator to maintain normal voltage at the load center at the end of the transmission line.
The next example is shown in Fig. 6. In this case it is desired to make several a-c machines, each controlled by an individual regulator, operate in parallel and yet have the station bus voltage increase with both kw and reactive load. It is in this phase of line drop compensation that many different schemes are avail· able. However, whatever scheme is used must include pro· vision to prevent interference from the cross-current compensation. For example, where a slightly rising bus voltage is de· sired, line drop compensation can be used in conjunction with the cross-current compensation required for parallel operation, provided all the individual line drop compensators are operated
continued on page 14 • www . El
ectric
alPar
tMan
uals
. com
LINE DROP COMPENSATIONContinued
from the totalized secondary current of
current transformers, so connected that
they carry the entire load of the station.
The example shown in Fig. 6 is pre
sented as a typical case and requires
the use of one current transformer, one
cross-current compensator and one line
drop compensator with each a-c ma
chine and its regulator. No changes
in line drop compensator setting or cur
rent transformer secondary connections
are necessary when an a-c machine is
removed from the system, providing the
number of outgoing feeders remains
unchanged. Any change in the num
ber of outgoing feeders changes the
system impedance and thus requires
readjustment of the setting of the line
drop compensators.
� ____ �----__ ----------------_S�t a�r�io�n�B�u�s--�------------------------------ 1 2 2 3 3
C u r re n t Iran sformer
Gener a tor No. 1
Cross currenl leom pensa tor I
2
L i n e drop 'compens a to r
Vol l a g e regu l ator No. 1
Current tran sfor m e r
/
Cross c u r r e nt c o m p e n s a t o r
/
2
L i ne drop compensator
transform ers Vol t a g e r e gulator N o . 2
Generator No. 2
Fig. G-Line drop and cross�current compensation diagram for paralleled a-c generators.
PILOT �EXCITER OVER-VOLTAGE PROTECTIVE EQUIPMENT
A- C Generator
Generator f ie ld
Motor operated rheostat
On applications involving water-wheel driven a-c generators with the main exciter separately excited from a direct connected pilot exciter,
there is danger of excessively high pilot exciter voltage if runaway con·
ditions should be encountered in operation of the unit.
Main excit e r
f Main exciter shunt field
Pilot exciter
Pi lot exciter shunt field
p __ �C�o�nt�r�o�l �b�us� __ �_ N ---_--+_
I I
Voltage � ';:--6...!--+6-t�)r-o-+, sensit ive I relay
To alarm
circu i t Protective resistance
Pilot exciter
field rheostat
Fig. 7-Pilot-exciter over-voltage protective equipment diagram .
CONTROL VOLTAGE
The protective equipment consists of a voltage sensitive relay, an auxil
iary contactor and a protective resistance, as shown in Fig. 7. The con· tacts of the voltage sensitive relay are normally open and are adjustable so that they may be set to close when the pilot exciter voltage reaches a
predetermined value above normal. Operation of the voltage sensitive relay on over-voltage energizes the auxiliary contactor, causing it to open its normally closed main contacts and insert the protective resistance in series with the pilot-exciter field. This limits the voltage to a safe value while runaway speed conditions exist on the unit.
When the auxiliary contactor is energized it electrically locks in that
position through one of its auxiliary contacts_ When the speed returns to normal and the voltage drops, the voltage sensitive relay contacts
return to their normal position and in so doing cause the auxiliary con
tactor to be de-energized by means of a shunting down circuit. In this
manner the protective equipment is automatically reset to normal. This
scheme of protection is independent of the voltage regulator, which op
erates automatically to protect the a-c generator and its main exciter
from over-voltage.
A separate source of doc power is required for operation of the
exciter rheostat motor and certain parts of the regulating equip
ment, as shown in Figs. 1 and 2. This doc power may be obtained
from the station battery or other reliable doc source. Where the
main exciter is separately excited from a pilot exciter it is prefer-
able to obtain the doc power from the pilot exciter, since the
pilot exciter is independent of any load except the field of the main exciter. The rheostat motor and regulating equipment
draws approximately 3 amperes intermittently and are designed
for operation from 125 or 250 volts doc. www . El
ectric
alPar
tMan
uals
. com
Dimensions in inches
Approximate only. Do not use for construction purposes.
Typical Steel Panel Layouts
II j
18
4tJ t -90 /1
51 7 2 ,
I 35
I I
_ _ _ -.1
r-2
[if � . ! . I I I • '
'-ll
7 .J..J-J I - �
l$J ... -t
� 8 � ro- 16
Steel panel ( E bony asbestos or slate
panel may also be u sed )
Type BJ - 30 moin control e lement in proje c t ion type case
Indicating
Nome p l a t e
VOltage adjusting r h eo stat �.,. {Manua l l y operotedl
�/:;�
/> 'if Transf e r switch / 2 16 /
/ Exciter rheostat control switch
Cross c u rrent compensator (Required when appl ication
involves par a l l e l operat ionl
// Terminal block I
/ Channe I iron bose
Rectox unit
43 84
3 - -+ 7iS I"'� 9
.. i y! �91 �t�
8
Type BJ-30 regulator equipment on steel panel. Main control ele
ment is shown with projection case.
Typical Motor-Operated Rheostat Assemblies
High speed f i e l d forc ing contactors
F i e l d forcing res istors
J,
NOle : Top, back S bottom of f ronl are of perforated metal screen
Cubicle type assem.bly of regulator contactor panel and plate-type
m.otor-operated rheostat for medium size exciters.
T 12
�f 16
t
2
Steel pan e l (Ebony asbestos o r
slate pa net m a y a l so be used)
Vollage adjusting r h eostat (Man ually operated)
Channel iron base 8 Type BJ ... 30 regulator equiprn.ent as used with synchronous condens�
ers. Main control and current limiting elements are shown in flush
type case.
High speed f ie ld forcing contactors
Combined assembly of regulator contactoL" panel and faceplate type
motor .. operated rheostat for large size exciters. www . El
ectric
alPar
tMan
uals
. com
Data Sheets for Generator Voltage Regulators
Complete data on generator, excitation, load, etc. must be sup·
plied to determine the size and type of motor· operated main· exciter field rheostat and other apparatus required. This infor·
mation should be supplied on Westinghouse Form 1046, copies
of which are available through your Westinghouse office or
representative.
D AT A SHEET F O R V O LTAGE REGULATOR (I NFORMATION REaUIRED I N A D O I T I ON T O MACHr",r:: OAtAJ
P1JReHASEA� ___ � __ ... __________ 'OIlOER HO.
MACHINES
1, Indicate aaiure oj the load on d'C generator: Lighting . Motor,.
(Ii is important 10 note the charader of any load causing serious voltage *2. Will the a-c generator operate in paraUel with any othet a·c
generator? . . . . . . . . . . . . . . . , . , (U SO, cross curren! compensalion and a current IransIormer may be {Excilers must operate non-paralleL)
3, If speed variahon is greater than ± 5%, range. *4, Is the d·c generator sell or separately
5. Wlll the d,c generator operate shunt, or compound? .
(When controlled by a voltage regulator, Ihe exciter shou'd be shunt or
REGULATOR
6. Is regulator 10 be dupncale of, or 10 match up wilh a previous order':--.-� i Ii so, give order number. . '
{Avoid ordering "dupllca!e" regula lor unless machines have the same �7. Is regulafor required for projection or semi·llush mounting?
(The SRA�D·Jr and SRA·D· 1 are not ava.lable for flush mounting,) 8. Is bracket moun�ing required? .
Ii so, give type 01 !rame: steel, 9. Indicate if installalion will De
a lroplea' 10.
1 1 . panel on H..->gulalor order? If so, slale Pdnel; height .
12. I s compensation for line drop required?
thk:kness. beveL . ' hame .
% Reactive? (:� Resistive?
13, Is the voltage rheos131 required for separate mounting? .. give panel !hickness,
14, Give range in vcllage ad;usting rheostat, i:! 15. Give d::J.y spccidl requirements [or sellsil:vlly
from published values . (Nole that s3nsitivily b:Her than the value publtshed in lhe Ga:r.erator Dala lor machine rating: and conespond .ng class 0.1 regulator, may regulator)
Hi U oil cut·out or lrans!er switch is included in the order give panel ihickness . .
• Minimum requirements.
WHTIHCMOU5E 1'0rtM Hue ali. SHEETS�$HE.ET l
Literature Reference
• PRICES-Refer to Price List 56·320
DATA S H E ET F O R V O LT AGE R E G U L AT O R S
PI.HtCItASER ..
A. C. MACHINE
1. Manufaclurer .. ___ .. �� ___ .. �_
Serial No. or 2. Mfgr's Order No.
3. Shop Order No, ,
4. Kva Capacity , , .
Rated Volts, S. Ph.ase-lo·Phase . .
6. Raled Speed
7. 1, 2 or 3 pr.as,�
B. Frequency
fIeld 9. Resistance at 75"'C.
Generator or condenser hek1 excilalion at no load and normal A·C operallng voltage;
10. Field Volts
1 1 . Field Amps, .
Generalor o r condenser held el!::citallon under mdl(lmum condItions;
12. Field Volts
1 3 F1C!d Amps.
14. Xva Load .
15 Type of Drive . .
Regulation 16. Movers .
17.
Give any special condition such held ampere, and vol!:! on
or Conden�r which under-excited:
Field Volts . . " .
Field Amps . . . . . . . ______ _
Wlt$TIN(;HOUS£ FOAM IOU I" r SHEETS-SHEET I
EXCITER OR O. C. GENERATOR
18. Mdnulactu,e, __ _ .. . __ . __ ...
19.
20.
2 l .
22.
23.
24.
25.
26.
27.
No. or Order No
Shop Order No. ,
Type .
Kw Capacity .
Hated Voltage
Rated Speed ,
excIter wllhoul
SATURATION CURVE OATA
NO lO�O ON UC!TfR
Shunt Field Amps. at-
28. rated exclter volfs . 29. faled exciter valls . 30. rated excifer volts . . _______ .
3 1 , exciler volts ��_& Amps,
32.
fULL lOAD ON ElClTER
taken at constant cur� cons!anl resislance
Data taken shun! or compound? .
Shullt Field Amps. at--
34. 100% raled volts , 35. Max. e:xciter vO"' � _ __ .• "'mp" . __ .�_
EXCITE. fiElD RH,[OSTi\.T
36. Variable Resistance . • . . _____ _
37. fi%:ed Resistance.
Type of 38. Drive for £x:dter . . . ,
Speed Regulation 01 39. Exciter Prime Mover
• SILVERSTAT Dl RECT·ACTlNG REGU LATORS-Small size a-c and d·c generators-refer to Descriptive Bulletin 56-350
Medium size a-c and d·c generators-refer to D�scriptive Bulletin 56·351
W E S T I N G H O U S E E L E C T R I C C O R P O R A T I O N EAST PITTSBURGH PLANT • POWER CONTROL AND COMM. DEPT. • EAST PITTSBURGH, PA.
Printed in U.S.A. www . El
ectric
alPar
tMan
uals
. com