nyc department of education - nycsca · sa : q105 architectural - senior 2018-10-12 7:46 am...

49
Asset: P.S. 105 - QUEENS, 420 BEACH 51 STREET, New York, 11691 Inspection Id Inspection Type Time In Last Edited SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment 2nd Floor Shower Room (Storage); 1st Floor Locker Room and Shower Room (Storage). Principal(s) Information Principal Name Laurie Shapiro Organization P.S./M.S. 105 - Queens Did you meet with this Principal? No Did this Principal provide feedback? Yes Summary of Principal's Feedback A Principal questionnaire form was returned with the following comments: 1.The building is in need of an electrical upgrade to support the present technology. 2. Some exterior doors and hardware need to be replaced. 3. The Classrooms are in need of an A/C System. Custodian Kevin White Fireman Edward Lewis Building Square Footage 86000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 43 Comments on the Year Built 1958 Student Population 833 Staff Population 125 Weather Fair Facade Photo Corner of Elizabeth Avenue and Beach 51st Street - Southeast view NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q105 PB/A&W Print Date: 6/21/2019 Page 1 of 49

Upload: others

Post on 21-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Asset: P.S. 105 - QUEENS, 420 BEACH 51 STREET, New York, 11691

Inspection Id Inspection Type Time In Last Edited

SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM

AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment 2nd Floor Shower Room (Storage); 1st Floor Locker Room andShower Room (Storage).

Principal(s) Information

Principal Name Laurie Shapiro

Organization P.S./M.S. 105 - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? Yes

Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomments: 1.The building is in need of an electrical upgrade to supportthe present technology. 2. Some exterior doors and hardware need tobe replaced. 3. The Classrooms are in need of an A/C System.

Custodian Kevin White

Fireman Edward Lewis

Building Square Footage 86000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Number of Classrooms 43

Comments on the Year Built 1958

Student Population 833

Staff Population 125

Weather Fair

Facade Photo

Corner of Elizabeth Avenue and Beach 51stStreet - Southeast view

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 1 of 49

Page 2: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Main Entrance Photo

Facade A - Beach 51st Street

Roof Photo

Roof 1 - South view

Have any Systems/Major Building Components been upgraded? Yes

Systems: Partial Foundation Walls waterproofing

Year: 2016

Systems: Auditorium Stage rebuilding

Year: 2013

Systems: Exterior Walls repointing and repairs

Year: 2011

Systems: Exterior Modernization Program including Windows,Window Guards replacement (except at Staircases,Auditorium and Gymnasium); Partial Window Lintelsrepainting; Metal/Glass Panels replacement; Parapets andCoping replacement; Perimeter Roofing and Flashingreplacement.

Year: 2010

Systems: Exterior Walls, Parapets, Chimney and Bulkheadrepointing and repairs.

Year: 2009

Systems: Roofing and Flashing replacement

Year: 2000

Have there been any New Building Additions? Yes

Comments on New Building Additions 1963 + 25,000 S.F.

Tandem Schools? No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 2 of 49

Page 3: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

Yes Tripping Hazard Damagedconcrete stairtread is apotentialtripping hazard.

EXTERIOR |STAIRS/RAMPS: EXTERIOR |STAIRS/RAMPS

South exit ataddition facingBeach ChannelDrive

Kevin White Custodian

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? No

Are SOME floors other than the 1st floor and basement accessible through compliantmeans?

No

Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs

Yes

For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes

Boys and Girls or Unisex accessible toilets exist on the 1st floor? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms Room 214 Yes No Not on Accessible Route

Auditorium 1st Floor Yes Yes No Yes

Cafeteria 1st Floor Yes Yes No Yes

Classrooms 1st Floor Yes Yes

Computer Rooms No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 3 of 49

Page 4: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Gymnasium 1st Floor Yes Yes No Yes

Library Room 101 Yes Yes

Main Office Room 110 Yes Yes

Multi-purpose Room No

Nurse's Room Room 108 Yes Yes

Pool No

Science Lab Room 106 Yes Yes

Toilet Rooms (Boys) 1st Floor - Inspected Room 115 Yes No Accessory ArrangementClear opening < 32"Sink ArrangementTurning RadiusUrinal ArrangementWater ClosetArrangement

Toilet Rooms (Girls) 1st Floor - Inspected Room 113 Yes No Accessory ArrangementClear opening < 32"Sink ArrangementTurning RadiusWater ClosetArrangement

Toilet Rooms (Staff) 1st Floor - Inspected Rooms 116 and 118 Yes No Accessory ArrangementClear opening < 32"No Lever-type HardwareSink ArrangementTurning RadiusUrinal ArrangementWater ClosetArrangement

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 4 of 49

Page 5: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

AREAWAY Does not Exist

AWNINGS AND CANOPIES Inspected

Condition 2 - Between Good and Fair

Deficiency CONCRETE: MAJOR CRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade E

Violations No violations recorded.

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 5 of 49

Page 6: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 4

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 6 of 49

Page 7: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

DOORS

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 3 - Fair

Deficiency METAL: BROKEN GLASS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

3rd Floor exit to Roof 2

Violations No violations recorded.

Deficiency METAL: DENTED, MAJOR RUSTING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 7 of 49

Page 8: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

DOORS

TRANSOM/SIDE LIGHT

Deficiency Photo1

Facade C

Violations No violations recorded.

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Steel

Replacement Quantity 35,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 35,000

Instance Quantity Uom S.F.

Deficiency BRICK: MINOR CRACKS AND SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 8 of 49

Page 9: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency BRICK: EFFLORESCENCE

Roof Plan reference

Elevation

Deficiency Quantity 2,000

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 1

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 9 of 49

Page 10: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency BROKEN/ DENTED BLADES

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 10 of 49

Page 11: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

LOUVER

Roof Plan reference

Elevation

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 8,000

Replacement Uom C.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 8,000

Instance Quantity Uom C.F.

Deficiency BRICK: EFFLORESCENCE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 11 of 49

Page 12: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

PARAPETS

Roof Plan reference

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 1

Deficiency Photo1 No photo recorded

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 39,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency DAMAGED/MISSING

Roof Plan reference

Deficiency Quantity 15

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 12 of 49

Page 13: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Roofing

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

Deficiency Photo1

Roof 1

Violations No violations recorded.

ROOF BARRIER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: All Roofs

Instance Condition 3 - Fair

Instance Quantity 39,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2000

Source of Installation Custodial Staff

Deficiency BUILT-UP: ROOFING: LOSS OF GRAVEL

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action INSTALL NEW GRAVEL

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 13 of 49

Page 14: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BUILT-UP: FLASHING: PITCH POCKET- POOR CONDITION

Roof Plan reference

Deficiency Quantity 20

Quantity Uom EACH

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 4 - Between Fair and Poor

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 14 of 49

Page 15: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - Bulkhead 3

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 15 of 49

Page 16: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

Roof 1 - Bulkhead 1

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: CMUCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - Bulkhead 1

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: CMU OPENJOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 16 of 49

Page 17: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - Bulkhead 2

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:EFFLORESCENCE

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 1

Deficiency Photo1 No photo recorded

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 17 of 49

Page 18: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Specialties

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Inspected

Material Type(s) Glass

Condition 3 - Fair

Deficiency DAMAGED GUARDS

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BROKEN GLASS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 18 of 49

Page 19: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

ROOF

Specialties

SKYLIGHT/ROOF VENT Inspected

Deficiency Photo1

Roof 1

Violations No violations recorded.

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

RAILINGS Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 19 of 49

Page 20: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

STAIRS/RAMPS Inspected

Condition 4 - Between Fair and Poor

Deficiency CONCRETE: CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 20 of 49

Page 21: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo1

Facade F

Violations No violations recorded.

Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade E

Violations No violations recorded.

Deficiency STONE: OPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 21 of 49

Page 22: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 10,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency DETERIORATED/TORN-OUT/MISSING

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 22 of 49

Page 23: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Other: All Facades (except All Staircases,Auditorium, Gymnasium)

Instance Condition 2 - Between Good and Fair

Instance Quantity 9,700

Instance Quantity Uom S.F.

Installation Year 2010

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Aluminum - Other: All Staircases, Auditorium, Gymnasium

Instance Condition 3 - Fair

Instance Quantity 300

Instance Quantity Uom S.F.

Installation Year 1963

Source of Installation Custodial Staff

Deficiency ALUMINUM - OTHER: BEYOND USEFUL LIFE

Deficiency Location/Instance Aluminum - Other: All Staircases, Auditorium, Gymnasium

Deficiency Quantity 300

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 23 of 49

Page 24: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

EXTERIOR

WINDOWS

WINDOWS

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 4 - Between Fair and Poor

Deficiency CONCRETE SLAB ON GRADE: WATER INFILTRATION IN NON-INSTRUCTIONAL SPACE

Deficiency Location/Instance Basement - Fan Room, Corridor, Storage, Shop

Deficiency Quantity 400

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Fan Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 3 - Fair

Deficiency CRACKS, SPALLING

Deficiency Location/Instance Basement - Fan Room Access Vault

Deficiency Quantity 30

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 24 of 49

Page 25: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Foundation Walls

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Fan Room Escape Vault

Violations No violations recorded.

Slab Structure Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Vault/Ash Hoist Doors and Framing Inspected

Condition 5 - Poor

Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING

Deficiency Location/Instance Basement - Fan Room Access Vault

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Basement - Fan Room Access Vault

Violations No violations recorded.

AUDITORIUM Inspected

InspectedInstance on 1st Floor (400 Seats)

Ceiling

InspectedInstance on 1st Floor (400 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor (400 Seats)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 25 of 49

Page 26: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

AUDITORIUM

Door(s)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 1st Floor (400 Seats)

Fixed Seating

InspectedInstance on 1st Floor (400 Seats)

Condition 3 - Fair

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats B/2, E/2, F/6, O/1, 3, and others

Deficiency Quantity 18

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Seats O/1, 3

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor (400 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor (400 Seats)

Stage

InspectedInstance on 1st Floor (400 Seats)

Stage Inspected

InspectedInstance on 1st Floor (400 Seats)

Condition 3 - Fair

Deficiency DAMAGED FLOOR

Deficiency Location/Instance Right side

Deficiency Quantity 35

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 26 of 49

Page 27: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

AUDITORIUM

Stage

Stage

Deficiency Photo1

Right side

Violations No violations recorded.

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor (400 Seats)

Condition 1 - Good

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 1st Floor (400 Seats)

Condition 1 - Good

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor (400 Seats)

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Right rear near entrance

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Right rear near entrance

Violations No violations recorded.

Window Curtains/Shades/Blinds

InspectedInstance on 1st Floor (400 Seats)

Condition 1 - Good

Deficiency No deficiencies recorded

CAFETERIA Inspected

InspectedInstance on 1st Floor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 27 of 49

Page 28: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

CAFETERIA

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Center near ductwork, near servery

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center near ductwork

Violations No violations recorded.

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Corridor near Rooms 216, 301, 310, 321, 324, Room 126, and others

Deficiency Quantity 200

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 28 of 49

Page 29: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 324

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency METAL: DAMAGED LOUVER

Deficiency Location/Instance Room 120A

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 120A

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 126, 212, 221, 224

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 29 of 49

Page 30: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Deficiency Photo1

Room 212

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Rooms 224, 319

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 30 of 49

Page 31: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Room 319

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Room 224, Corridor near Room 323

Deficiency Quantity 320

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 323

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Corridor near Rooms 211, 301A, 304, 308, Room 212, and others

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 211

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Corridor near Room 216

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 31 of 49

Page 32: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Photo1

Corridor near Room 216

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Corridor near Room 323

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 323

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 32 of 49

Page 33: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

GYMNASIUM

Floor Finish

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Office

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Near Drinking Fountain

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Drinking Fountain

Violations No violations recorded.

Seating

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 33 of 49

Page 34: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

GYMNASIUM

Walls

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Office

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency DETERIORATED/TORN-OUT/MISSING

Deficiency Location/Instance Stairs A/2, B/1, C/2, 3 #6/3, and others

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/2

Violations No violations recorded.

KITCHEN Inspected

InspectedInstance on 1st Floor (600SF)

Ceiling

InspectedInstance on 1st Floor (600SF)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 34 of 49

Page 35: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

KITCHEN

Ceiling

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Office

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Deficiency METAL PAN: DAMAGED/MISSING

Deficiency Location/Instance Center, near sink

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Door(s)

InspectedInstance on 1st Floor (600SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor (600SF)

Condition 5 - Poor

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance Office

Deficiency Quantity 20

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 35 of 49

Page 36: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

KITCHEN

Floor Finish

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Center, north, south, east, west sides, near Office

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Walls

InspectedInstance on 1st Floor (600SF)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 101

Built-in Furnishing

InspectedInstance on Room 101

Condition 1 - Good

Deficiency No deficiencies recorded

Ceiling

InspectedInstance on Room 101

Condition 1 - Good

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 36 of 49

Page 37: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

LIBRARY

Door(s)

InspectedInstance on Room 101

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 101

Condition 1 - Good

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 101

Condition 1 - Good

Deficiency No deficiencies recorded

LOCKER ROOM Inspected

InaccessibleInstance on 1st Floor

InspectedInstance on 2nd Floor (24 Lockers)

Alternative use Yes

Ceiling

InspectedInstance on 2nd Floor (24 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 2nd Floor (24 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 2nd Floor (24 Lockers)

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Near Gymnasium stair

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Gymnasium Stair

Violations No violations recorded.

Locker Room Lockers

InspectedInstance on 2nd Floor (24 Lockers)

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 37 of 49

Page 38: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

LOCKER ROOM

Locker Room Lockers

Deficiency No deficiencies recorded

Walls

InspectedInstance on 2nd Floor (24 Lockers)

Condition 2 - Between Good and Fair

Deficiency MASONRY: CRACKS/SPALLING

Deficiency Location/Instance Near Gymnasium stair

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Gymnasium stair

Violations No violations recorded.

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Inspected

InspectedInstance on Room 106

Alternative use No

Fixed Equipment

InspectedInstance on Room 106

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Inspected

InaccessibleInstance on 1st Floor

InaccessibleInstance on 2nd Floor

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Partially

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Stair C/1

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 38 of 49

Page 39: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Ceiling

Deficiency Photo1

Stair C/1

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair B/1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/1

Violations No violations recorded.

Door(s) Inspected

Condition 3 - Fair

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Stair B/1

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 39 of 49

Page 40: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s) Inspected

Stair B/1

Violations No violations recorded.

Partition Does not Exist

Railings Inspected

Condition 3 - Fair

Deficiency METAL: MISSING

Deficiency Location/Instance Stair on right side of Stage (Exit 7), Exit to Corridor from left side ofStage

Deficiency Quantity 14

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Stair on right side of stage (Exit 7)

Violations No violations recorded.

Stairs and Landings Inspected

Condition 3 - Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Stairs C/1, 3, #6/1, 2

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair #6/2

Violations No violations recorded.

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Stairs C/1, #6/1, Main Entrance Vestibule

Deficiency Quantity 40

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 40 of 49

Page 41: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/1

Violations No violations recorded.

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance Stairs A/2, C/2, Exit to Corridor from Auditorium Stage (left side)

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/2

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Stairs A/1, 2

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 41 of 49

Page 42: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Deficiency Photo1

Stair A/2

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Stair C/1 (both Vestibules)

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair C/1 (Vestibule)

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Inside Room 108, Room 216A

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 42 of 49

Page 43: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

TOILET ROOMS - STAFF

Door(s)

Deficiency Photo1

Room 216A

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 5 - Poor

Deficiency RUST - MAJOR

Deficiency Location/Instance 3rd Floor Staff Toilet Room near Room 316

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

3rd Floor Staff Toilet Room near Room 316

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 213, 215, 222A, 223A, 313, 315

Deficiency Quantity 6

Quantity Uom EACH

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 43 of 49

Page 44: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s)

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 315

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room 213

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 213

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency BROKEN/MISSING

Deficiency Location/Instance Room 215

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 44 of 49

Page 45: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Stalls

Deficiency Photo1

Room 215

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance North side of Building, Beach Channel Drive

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Building

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 45 of 49

Page 46: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

SITE

FENCES

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED POST/RAIL

Deficiency Location/Instance Beach 51st Street, Beach Channel Drive

Deficiency Quantity 30

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 51st Street

Violations No violations recorded.

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance Beach 51st Street, Beach Channel Drive

Deficiency Quantity 120

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 51st Street

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Elizabeth Street (fenced-off disposal area)

Deficiency Quantity 75

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 46 of 49

Page 47: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

SITE

PAVING

Student Non-Use

Concrete

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Elizabeth Street

Violations No violations recorded.

Pavers Does not Exist

Student Use Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance North side of Building, Beach 51st Street

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach 51st Street

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 47 of 49

Page 48: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Location/Instance Elizabeth Street, Beach 51st Street, Beach Channel Drive

Deficiency Quantity 425

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Elizabeth Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Along Beach Channel Drive

Benches

Does not ExistInstance on Along Beach Channel Drive

Fence

Does not ExistInstance on Along Beach Channel Drive

Pavement

Does not ExistInstance on Along Beach Channel Drive

Play Equipment

InspectedInstance on Along Beach Channel Drive

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Along Beach Channel Drive

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Along Beach Channel Drive

PLAYING SURFACE Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Beach Channel Drive

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 48 of 49

Page 49: NYC Department of Education - NYCSCA · SA : Q105 Architectural - Senior 2018-10-12 7:46 AM 2019-06-03 9:16 AM AA : Q105 Architectural - Associate 2018-10-12 7:56 AM 2018-10-12 2:53

Question Response

SITE

RETAINING WALLS

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Beach Channel Drive

Violations No violations recorded.

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS: EXTERIOR Inspected

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Cheek/flank Walls Inspected

Condition 2 - Between Good and Fair

Deficiency STUCCO CEMENT SURFACE: CRACKS/SPALLING - MINOR

Deficiency Location/Instance Beach Channel Drive

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Stairs/ramps Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q105

PB/A&W Print Date: 6/21/2019Page 49 of 49