FINAL CONSTRUCTION REPORT
NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE
HOUSE #2 BUNKER HILL – HOME HEADQUARTERS
November 2011
Submitted to:
NYSERDA 17 Columbia Circle Albany, NY 12203
Submitted by:
HOMEPIC Team
CDH Energy Corp.
PO Box 641 Cazenovia, NY 13035
315-655.1063
and
Syracuse Center of Excellence in Energy and Environmental Systems Northeast Green Building Consulting
Camroden Associates Building Performance Contractors Association of New York
Bunker Hill
HomePIC Team 1 November 2011
House Description Home Headquarters (HHQ) purchased this partially completed 4-unit townhome (basement only, shown in Figure 1) and then completed construction as part of this project. The HomePIC team helped to develop an energy efficient design for the units. The four "redesigned" units were started in 2009 and completed in stages in 2010 and 2011. The HomePIC project supported the improvements to the end unit in the Town of Onondaga, which was the last to be completed in the summer 2011. The 3 units in the City of Syracuse were supported with funding from the Syracuse COE.
Figure 1. Unfinished Foundations as Purchased by Home Headquarters
Figure 2. Four Townhomes Under Construction
As shown in Figure 2 above, SIS panels were used for exterior sheathing instead of traditional OSB or Zip Panels. The SIS panels from Dow nominally have 1 inch of foam which provides R-5 (compared to R-0.8 for OSB) while still providing adequate structural support and racking strength. The SIS foam panels are taped to provide a water seal as well as an air barrier. SIS panels were applied to insulated wall areas as well on the attic gable ends and the exterior garage walls. The HHQ construction staff were generally pleased with the installation process using these panels. Zip panels were used for the roof deck. The Zip system is a structural panel with factory-applied underlayment that replaces the need for felt paper and H-clips that provides a moisture barrier. Panel seams are taped and shingles are directly installed on the panels.
City of Syracuse
Town of Onondaga
Bunker Hill
HomePIC Team 2 November 2011
Figure 3. Finished Building from Unit 5303 (Top) and Unit 301 (Bottom) Ends (Source: Google Maps)
Bunker Hill
HomePIC Team 3 November 2011
Tape applied to SIS panel at Doorway
Figure 4. SIS Panels (with 1 inch Rigid Foam) on All Exterior Walls, Zip Panels on Roof Deck
These two-story townhome units were designed starting with the existing 10 inch CMU foundation. Two (2) inches of rigid foam board was added on the interior basement walls. There was no foam board under the basement floor. A combination of XPS with a protective coating (thermal barrier) and Thermax was used on the basement walls.
Tape applied to seams
Bunker Hill
HomePIC Team 4 November 2011
Foam Board Specs XPS Foam Board w/ Protective cover (thermal barrier)
2 inches Thermax on Basement Walls (front of house)
Figure 5. Rigid Foam Board Installed on Interior Basement Walls
The Blow-in-Blanket System (BIBS) was used in the 2x6 exterior frame walls of the home, providing R23 in addition to the continuous R5 provided by the SIS panels. Blown in cellulose (nominally, 11 inches, R42) was also used in both the cathedral ceilings and open attic areas. “Quiet Zone” fiberglass batts were installed on the common wall between the units for noise reduction and privacy.
Bunker Hill
HomePIC Team 5 November 2011
Figure 6. Exterior Wall Details
BIBS System Fiberglass in Above
Grade Walls Windows Air Sealed
with Foam
Supply Duct Encased in Closed Cell Foam
Bunker Hill
HomePIC Team 6 November 2011
Figure 7. Intersection of Common Wall, Exterior Wall and Roof at Back of Building
Figure 8. Area Before Insulation is Installed
BIBS System in Exterior Walls
Fiberglass batts in common wall for sound proofing
Spray foam seals “proper vent” and SIS panel to rafter and top sill at the raised heal truss
Closed Cell Spray Foam
Bunker Hill
HomePIC Team 7 November 2011
Scissor Trusses
Raised-heal truss at back of house
Figure 9. Scissor Trusses in Cathedral Ceiling Areas
SIS panels with BIBS were also used for the “cold partition” between the second floor living space and the attic space above the garage.
Figure 10. SIS Panels with BIBS Used for “Cold” 2nd Floor Wall (shown from attic side above garage)
Raised heal truss
Bunker Hill
HomePIC Team 8 November 2011
Figure 11. Another View of SIS Panels On Exterior and 2nd Floor to Garage Space
Figure 12. Extra 2 inches of Foam Board Insulation Added to Garage Wall on 5303 (with dry wall)
The HHQ staff used their in-house labor to cut scrap foam pieces left over from the exterior foam installation to fill in between the rim and band joists. Then they used cans of spray foam to seal in the foam pieces. This resulted in a cost-effective means of achieving 4 inches of foam in the rim and band joists while using up scrap material and effectively utilizing their lower skilled staff.
SIS Panels on 2nd Floor to Attic Wall
over Garage
Bunker Hill
HomePIC Team 9 November 2011
Figure 13. Foam Board and Spray Foam in the Rim Joist and Energy Complete™ Airsealing System Applied in Exterior Wall Cavities (back of SIS panel)
The Energy Complete™ Airsealing system from Owens Corning was used to seal every seam between the SIS panels and framing as well as the gaps between framing lumber. This material was applied by the HHQ staff before the BIBS insulation was installed.
Nearly all the windows in the house were Casement style with a U-Factor of 0.28 and a Solar Heat Gain Coefficient (SHGC) of 0.32 (dual low-e with Argon).
Figure 17. Casement Windows Used on Project
4 inches foam board with spray foam in rim joist
Bunker Hill
HomePIC Team 10 November 2011
HVAC System
The heating system is a 92.5% efficient, sealed combustion Rheem Gas Furnace. As per Home Headquarters normal policy, cooling was not installed in the home. The returns are ducted to hallways on the first and second floors.
Rheen 92.5% efficient furnace Sealed combustion furnace unit
Central return ducts to 1st and 2nd floors
Central return grill (1st floor) Figure 14. Furnace and Return Ducts
Bunker Hill
HomePIC Team 11 November 2011
A conventional 40-gallon gas-fired water heater (Bradford White, Defender, Model M1TW40S6FBN) provides the water heating.
Figure 15. 40 gallon Gas-Fired Water Heater Figure 16. Exhaust Fan in Bathroom
Table 1 compares the base design and the originally proposed improvements to actual implemented features of the house. The installed windows were better than proposed. The amount of cellulose in the attic was less than expected. The proposed HRV was not installed in the end unit and exhaust only ventilation was used instead. The installed furnace was slightly less efficient than was originally proposed or anticipated.
Bunker Hill
HomePIC Team 12 November 2011
Table 1. Summary of Thermal Envelope Details
Base Design Proposed Design Actual Construction Walls Wafer Board Siding w/ OSB
Sheathing; 2x6 Frame wall with Fiberglass Batt (R19)
Wafer Board Siding SIS Panel (1 inch foam, R5) ; 2x6 frame wall w/ BIBS (R23 cavity+ R5 Continuous)
Wafer Board Siding SIS Panel (1 inch foam, R5) ; 2x6 frame wall w/ BIBS (R23 cavity+ R5 Continuous)
Open Attic Scissor Truss with 2x4 Bottom Cord 11.5 inch Fiberglass Batt (R38)
Scissor Truss with 2x4 Bottom Cord 16 inch Cellulose (R60)
Scissor Truss with 2x4 Bottom Cord 11 inch Cellulose (R42)
Cathedral/Vaulted Ceiling
2x6 Parallel Cord Truss with Fiberglass Batt (R38)
2x6 Parallel Cord Truss with 11 inch Cellulose (R42)
2x6 Parallel Cord Truss with 11 inch Cellulose (R42)
Basement Walls CMU Block with Fiberglass Batt 5 ft down from ceiling (R11)
CMU Block with 2 inch rigid foam (Thermax) on inside (R10)
CMU Block with 2 inch rigid foam (Thermax & XPS) on inside (R10)
Garage-to-Exterior Wall
Wafer Board Siding w/ OSB Paneling Sheathing on 2x4 frame wall
Wafer Board Siding SIS Panel (1 inch foam, R5) on 2x4 frame wall
Wafer Board Siding SIS Panel (1 inch foam, R5) on 2x4 frame wall
Garage-to-Interior Wall
Fiberglass Batt, OSB Panel, 2x6 Framing (R19)
BIBS System, SIS Panel, 2x6 framing (R23+ R5 Continuous)
BIBS System, ZIP Panel, 2x6 framing (R23) + 2 inches XPS foam board (R10)
2nd Floor-to-Attic Wall
Fiberglass Batt, OSB Panel, 2x6 Framing (R19)
BIBS System, SIS Panel, 2x6 framing (R23+ R5 Continuous)
BIBS System, SIS Panel, 2x6 framing (R23+ R5 Continuous)
Windows U=0.31, SHGC=0.35 (double hung) U=0.31, SHGC=0.35 (double hung) U=0.28, SHGC=0.32 (casement)
Rim/Band Joists 5.5 inches of Fiberglass (R21) 4 inches Rigid Foam w/ 1 inch exterior SIS foam (R25)
4 inches Rigid Foam w/ 1 inch exterior SIS foam (R25)
Air Tightness & Thermal Bypass
5 ACH50 (with basement) 2 ACH50 (with basement) Various air sealing and thermal bypass improvements
3.8 ACH50 (w/o basement) Various air sealing and thermal bypass improvements
Heating 90% Efficient Gas Furnace 95% Efficient Gas Furnace 92.5% Efficient Gas Furnace
Ventilation Exhaust Only Ventilation HRV Inside Unit: HRV Outside Unit: Exhaust Only Ventilation (58 cfm)
Bunker Hill
HomePIC Team 13 November 2011
Table 2 and Table 3 summarize the incremental costs of the implemented improvements. The cost for SIS panels was based on the calculated area and the per panel costs. The calculated area of SIS panels was within 4% of the area of SIS panels purchased for all four units. The area of SIS Panels was typically about 25-35% greater than the actual area of the insulated walls since the SIS panels were also installed on the garage walls and the gable end of all the attics. The net cost increase per unit area compared to ZIP panel sheathing was about $0.50 per square foot.
The Energy Complete materials used to improve air tightness were about $1097 per unit. We estimate that HHQ spent about $1000 spraying on the material in each unit.
Table 2. Summary of Incremental Costs (End Unit)
End Unit Improvement Costs (5303 Bunker Hill Way)Units Quanity Unit Cost Total Cost Notes
Exterior Walls1 inch SIS foam on all exterior walls ft2 3150 0.86$ 2,709.00$ SIS Tape rolls 21 17.08$ 358.68$ Deduct for ZIP on all exterior walls ft2 3150 0.36$ (1,132.03)$ Add for BIBS instead of FG Batts ft2 2480 -$ -$
1,935.65$ Air TightnessEnergy Complete Material ft2 2480 0.44$ 1,097.14$ Actual material costAirsealing Labor hrs 30 35$ 1,050.00$ est labor cost
2,147.14$ Basement Walls2 inch Thermax on block walls ft2 696 0.90$ 626.40$ Deduct for 5' Hanging FG batt ft2 435 0.50$ (217.50)$
408.90$ Rim/Band Joists, Framed Floors, Shed roofsClosed Cell rim/band joist & shed/floor ft2 321 3.50$ 1,123.50$ Other Misc Spray foam ft2 200 3.50$ 700.00$ Deduct for FG rim/band/dam joist ft2 321 0.65$ (208.65)$
1,614.85$ CeilingR41 Cellulose in Attic Floor ft2 817 0.75$ 612.75$ Actual cost was $750R41 Cellulose in Cathedral Ceiling ft2 583 0.75$ 437.25$ Deduct for R38 FG in Ceiling ft2 1400 0.60$ (840.00)$
210.00$ Heating and Ventilation92.5% Efficient Gas Furnace 1 7,400$ 7,400.00$ Deduct for 90% Efficient Gas Furnace 1 6,800$ (6,800.00)$ HRV not installedHRV -$
600.00$
NET Total 6,916.54$
Bunker Hill
HomePIC Team 14 November 2011
Table 3. Summary of Incremental Costs (Inside Unit)
The total incremental costs for the improvments at all four units was $28,565.
Inside Unit Improvement Costs (303 & 305 Bunker Hill Way)Units Quanity Unit Cost Total Cost Notes
Exterior Walls1 inch SIS foam on all exterior walls ft2 2116 0.86$ 1,819.76$ SIS Tape rolls 14 17.08$ 239.12$ Deduct for ZIP on all exterior walls ft2 2116 0.36$ (760.44)$ Add for BIBS instead of FG Batts ft2 1557 -$ -$
1,298.44$ Air TightnessEnergy Complete Material ft2 1557 0.70$ 1,097.14$ Actual material costAirsealing Labor hrs 30 35$ 1,050.00$ est labor cost
2,147.14$ Basement Walls2 inch Thermax on block walls ft2 696 0.90$ 626.40$ Deduct for 5' Hanging FG batt ft2 435 0.50$ (217.50)$
408.90$ Rim/Band Joists, Framed Floors, Shed roofsClosed Cell rim/band joist & shed/floor ft2 203 3.50$ 710.50$ Other Misc Spray foam ft2 105 3.50$ 367.50$ Deduct for FG rim/band/dam joist ft2 203 0.65$ (131.95)$
946.05$ CeilingR41 Cellulose in Attic Floor ft2 633 0.75$ 474.75$ R41 Cellulose in Cathedral Ceiling ft2 470 0.75$ 352.50$ Deduct for R38 FG in Ceiling ft2 1103 0.60$ (661.80)$
165.45$ Heating and Ventilation92.5% Efficient Gas Furnace 1 7,400$ 7,400.00$ Deduct for 90% Efficient Gas Furnace 1 6,800$ (6,800.00)$ HRV 1 1,800$ 1,800.00$ estimated HRV cost
2,400.00$
NET Total 7,365.98$
Bunker Hill
HomePIC Team 15 November 2011
The predicted energy use and savings for the proposed and as-built homes compared to the base assumptions are shown in Table 4. The as-built units are estimated to use about 40% less than the baseline assumptions. The savings are estimated to be $481 for the end units and $288 for the inside units assuming a gas cost of $1.50 per therm. The total savings for all four units are $1,539. Based on the calculated incremental costs that simple payback is about 18 years.
Table 4. Summary of Energy Use and Savings
Table 5 summarizes the differences between the units in the building. Table 5. Summary of Differences between the Four Units at Bunker Hill
Unit 301 City
Unit 303 City
Unit 305 City
Unit 5303 County
Outside Inside Inside Outside HERS Index Score
61 88
59 88
Floor Area 2265 sq ft w/o basement
2750 sq ft w/ basement
2750 sq ft w/ basement
2265 sq ft w/o basement
Ventilation Exh Fan / timer HRV HRV Exh Fan / timer Air tightness 3.8 ACH50
948 cfm50 2.69 ACH50 1101 cfm50
2.99 ACH50 781 cfm50
Effective Leakage Area
52 in2 0.83 in2 per 100 ft2
60.4 in2 1.53 in2 per 100 ft2
67.3 in2 1.7 in2 per 100 ft2
Garage Wall Insulation
Additional 2 in board foam
- - Additional 2 in board foam
Framed Floor R-30 5.5” cavity insulation thickness
R-38 fiberglass 11.5” cavity insulation thickness
R-38 fiberglass 11.5” cavity insulation thickness
R-30 5.5” cavity insulation thickness
End Unit SavingsHeating Peak Htg HT Fuel Relative Annual(MMBtu) (MBtu/h) (MMBtu) Heating Cost
Base (5 ACH50) 67.4 37.4 76.4 100% 1,146.00$ ‐$ Proposed (2 ACH50) 30.4 21.5 32.0 42% 480.00$ 666.00$ As Built (3 ACH50) 40.1 26.0 44.3 58% 664.50$ 481.50$
Inside Unit SavingsHeating Peak Htg HT Fuel Relative Annual(MMBtu) (MBtu/h) (MMBtu) Heating Cost
Base (5 ACH50) 43.4 27.3 49.4 100% 741.00$ ‐$ Proposed (2 ACH50) 20.0 16.8 21.1 43% 316.50$ 424.50$ As Built (3 ACH50) 27.3 19.6 30.2 61% 453.00$ 288.00$
Cost Savings
Cost Savings
Appendix
Appendix Table A-1 below shows the calculated installed area for SIS panels on an outside unit, inside unit, and the whole building. The whole building area is just 4% less than the amount of purchased SIS panels. Originally 12,864 square feet of SIS panels were purchased. Then 60 unused full (4x8) sheets were later returned. The 12,864 sq ft represents a typical 20% estimate overage when ordering to account for unforseen circumstances. Table 3 also confirms the estimated 30% usage on 5303 (unit located on the county side).
Table A-1. Comparing Calculated SIS Panel Area to Purchased SIS Panels
Outside Unit, (sq ft)
Inside Unit, (sq ft)
Total Building, (sq ft)
SIS Area Purchased,
(sq ft)Overage/Waste
Insulated Area 2,712 1,760 8,943 Uninsulated Area 438 356 1,589
SIS Area 3,150 2,116 10,532 10,944 4%30% of SIS panels used on county side (5303)
AIR LEAKAGE REPORT
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Whole House InfiltrationBlower door test
Heating Cooling
Natural ACH: 0.24 0.18ACH @ 50 Pascals: 3.80 3.80CFM @ 25 Pascals: 604 604CFM @ 50 Pascals: 948 948Eff. Leakage Area: [sq.in] 52.0 52.0Specific Leakage Area: 0.00016 0.00016ELA/100 sf shell: [sq.in] 0.83 0.83
Duct Leakage Leakage to Outside Units AllCFM @ 25 Pascals: 61CFM25 / CFMfan: 0.0469CFM25 / CFA: 0.0269CFM per Std 152: N/ACFM per Std 152 / CFA: N/ACFM @ 50 Pascals: 96Eff. Leakage Area: [sq.in] 5.25Thermal Efficiency: N/ATotal Duct Leakage Units CFM25Total Duct Leakage: 61.00
Ventilation Mechanical: Exhaust Only Sensible Recovery Eff. (%): 0.0 Total Recovery Eff. (%): 0.0 Rate (cfm): 58 Hours/Day: 24.0 Fan Watts: 22.0Cooling Ventilation: Natural Ventilation
ASHRAE 62.2 - 2010 Ventilation Requirements
For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low-RiseResidential Buildings, a minimum of 53 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjustedaccordingly. For example, a 105 cfm mechanical ventilation system would need to operate 12 hours per day, as long as thesystem operates to provide required average ventilation once each hour.
BUILDING FILE REPORT
File Name: OutsideUnitAsBuilt-2011.blg Date: October 13, 2011
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Property/Builder: Rating Building Name: Bunker Hill Outside Org. Name: CDH Energy
Owner's Name: Address: 2695 Bingley Rd
Property Address: City, St, Zip: Cazenovia, NY 13035
City, St, Zip: , Phone No: 315-655-1063
Phone No: Website: www.cdhenergy.com
Builder's Name: Rater's Name: Kevin Stack Reproduction (JPW)
Phone No: Rater's Email:
Email Address: Rater's ID:
Model:
Development: Rating Date:
Rating Type: Post Improvement
Reason: Informational
Rating No.:
Registry ID:
General Building Information Area of Cond. Space(sq ft): 2265
Volume of Cond. Space: 14974
Year Built: 2011
Housing Type: Townhouse, end unit
Level Type(Apartments Only): None
Floors on or Above-Grade: 2
Number of Bedrooms: 3
Foundation Type: Conditioned basement
Enclosed Crawl Space Type: N/A
Thermal Boundary Location: REM Default
Foundation Wall Info: 1 2 3
Name Basement Amb Basement Adia Basement Garage
Library Type R-10 2" Foam Uninsulated Uninsulated
Length(ft) 87.0 45.0 22.0
Total Height(ft) 8.0 8.0 6.0
Depth Below Grade(ft) 6.0 8.0 6.0
Height Above Grade(ft) 2.0 0.0 0.0
Location Cond->ambient/grnd Cond -> another cond unit Cond->garage/grnd
Uo Value (wall, airfilm, & soil) 0.064 0.141 0.168
Uo Value (wall assembly only) 0.092 1.506 1.506
BUILDING FILE REPORT
Bunker Hill Outside Page 2
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Foundation Wall: R-10 2" Foam Type: Block: uninsulated cores
Thickness(in): 2.0
Studs: None
Interior Insulation:
Continuous R-Value: 10.0
Frame Cavity R-Value: 0.0
Cavity Insulation Grade: 1
Ins top: 0.0 ft from top of wall
Ins Bottom: 0.0 ft from bottom of wall
Exterior Insulation:
R-Value: 0.0
Ins top: 0.0 ft from top of wall
Ins bottom: 0.0 ft below grade
Note:
Foundation Wall: Uninsulated Type: Solid concrete or stone
Thickness(in): 8.0
Studs: None
Interior Insulation:
Continuous R-Value: 0.0
Frame Cavity R-Value: 0.0
Cavity Insulation Grade: 1
Ins top: 0.0 ft from top of wall
Ins Bottom: 0.0 ft from bottom of wall
Exterior Insulation:
R-Value: 0.0
Ins top: 0.0 ft from top of wall
Ins bottom: 0.0 ft below grade
Note:
BUILDING FILE REPORT
Bunker Hill Outside Page 3
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Slab Floor Info: 1
Name Basement Flr
Library Type Uninsulated slab
Area(sq ft) 1401
Depth Below Grade(ft) 6.0
Full Perimeter(ft) 154
Exposed Perimeter(ft) 132
On-Grade Perimeter(ft) 0
Slab Floor: Uninsulated slab Slab Covering Carpet
Perimeter Insulation (R-Value): 0.0
Perimeter Insulation Depth (ft): 0.0
Under-Slab Insulation (R-Value): 0.0
Under-Slab Insulation Width (ft): 0.0
Slab Insulation Grade: 1
Radiant Slab: No
Note:
Frame Floor Info: 1 2
Name Front Garage
Library Type R-30 HDF R-30 HDF
Area (sq ft) 8 55
Location Btwn cond & ambient Btwn cond & garage
Uo Value 0.039 0.039
BUILDING FILE REPORT
Bunker Hill Outside Page 4
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Frame Floor: R-30 HDFInformation From Quick Fill Screen:
Continous Insulation R-Value 0.0
Cavity Insulation R-Value 30.0
Cavity Insulation Thickness (in.) 5.5
Cavity Insulation Grade 1.0
Joist Size (w x h, in) 1.5 x 11.5
Joist Spacing (in oc) 16.0
Framing Factor - (default) 0.1300
Floor Covering HARDWOOD
Note:
Layers Paths
Cavity Framing GradeInside Air Film 0.920 0.920 0.920
Floor covering 0.680 0.680 0.680
Subfloor 0.820 0.820 0.820
Cavity ins 30.000 0.000 0.000
Continuous ins 0.000 0.000 0.000
Framing 0.000 6.875 0.000
0.000 0.000 0.000
Outside Air Film 0.920 0.920 0.920
Total R-Value 33.340 10.215 3.340
U-Value 0.030 0.098 0.299
Relative Area 0.870 0.130 0.000
UA 0.026 0.013 0.000
Total Component UA: 0.039
Total Component Area: 1.0
Component Uo: 0.039
BUILDING FILE REPORT
Bunker Hill Outside Page 5
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Rim and Band Joist: 1 2 3
Name Rim Amb Rim Adia Rim Garage
Area(sq ft) 87.0 45.0 22.0
Continuous Ins 5.0 10.0 10.0
Framed Cavity Ins 25.0 10.0 10.0
Cavity Ins Thk(in) 2.0 2.0 2.0
Joist Spacing 16.0 16.0 16.0
Insulation Grade 1 1 1
Location Cond -> ambient Cond -> another cond unit Cond -> garage
Uo Value 0.046 0.047 0.047
Rim and Band Joist: 4 5 6
Name Band Amb Band Garage Band Adia
Area(sq ft) 39.0 22.0 15.0
Continuous Ins 10.0 10.0 10.0
Framed Cavity Ins 25.0 25.0 11.0
Cavity Ins Thk(in) 4.5 4.5 3.5
Joist Spacing 16.0 16.0 16.0
Insulation Grade 1 1 1
Location Cond -> ambient Cond -> garage Cond -> another cond unit
Uo Value 0.031 0.031 0.043
Above-Grade Wall: 1 2 3
Name Ambient Garage Adiabatic
Library Type R-23,CE1,2-6,+10 R-23,CE1,2-6,+10 R-23,CE1,2-6,+10
Gross Area(sq ft) 2217.00 198.00 719.00
Exterior Color Medium Medium Medium
Location Cond -> ambient Cond -> garage Cond -> another cond unit
Uo Value 0.033 0.033 0.033
BUILDING FILE REPORT
Bunker Hill Outside Page 6
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Above-Grade Wall: R-23,CE1,2-6,+10Information From Quick Fill Screen:
Standard Wood Frame
Continuous Insulation (R-Value) 10.0
Frame Cavity Insulation (R-Value) 23.0
Frame Cavity Insulation Thickness (in) 5.5
Frame Cavity Insulation Grade 1
Stud Size (w x d, in) 1.5 x 5.5
Stud Spacing (in o.c.) 24.0
Framing Factor - (default) 0.1988
Gypsum Thickness (in) 0.5
Note:
Layers Paths
Cavity Framing GradeInside Air Film 0.680 0.680 0.680
Gyp board 0.450 0.450 0.450
Air Gap/Frm 0.000 0.000 0.000
Cavity ins/Frm 23.000 6.875 1.030
Continuous ins 10.000 10.000 10.000
Ext Finish 0.940 0.940 0.940
0.000 0.000 0.000
Outside Air Film 0.170 0.170 0.170
Total R-Value 35.240 19.115 13.270
U-Value 0.028 0.052 0.075
Relative Area 0.801 0.199 0.000
UA 0.023 0.010 0.000
Total Component UA: 0.033
Total Component Area: 1.0
Component Uo: 0.033
BUILDING FILE REPORT
Bunker Hill Outside Page 7
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Window Information: 1 2 3
Name Front Left Rear
Library Type Dbl/LoE/Arg - Vinyl Dbl/LoE/Arg - Vinyl Dbl/LoE/Arg - Vinyl
U-Value 0.330 0.330 0.330
SHGC 0.450 0.450 0.450
Area(sq ft) 28.00 97.50 84.50
Orientation East North East
Overhang Depth 1.0 1.0 1.0
Overhang To Top 10.0 14.0 4.0
Overhang To Bottom 14.0 19.0 12.0
Interior Winter Shading 0.85 0.85 0.85
Interior Summer Shading 0.70 0.70 0.70
Adjacent Winter Shading None None None
Adjacent Summer Shading None None None
Wall Assignment AGWall 1 AGWall 1 AGWall 1
Window: Dbl/LoE/Arg - Vinyl U-Value: 0.330
Solar Heat Gain Coefficient: 0.450
Note:
Door Information: 1 2
Name Front Door Int Garage Door
Opaque Area(sq ft) 21.0 21.0
Library Type Steel-polyurethane Steel-polyurethane
Wall Assignment AGWall 1 FndWall 3
Uo Value 0.283 0.283
Door: Steel-polyurethane R-Value of Opaque Area: 2.6
Storm Door: No
Note:
Roof Information: 1 2
Name Flat Cathedral
Library Type R41,CE11",4-24 R39,CE,12-16,C
Gross Area(sq ft) 583.00 817.00
Color Medium Medium
Radiant Barrier No No
Type(Attic) Attic Vaulted
Uo Value 0.024 0.029
Clay or Cement Tiles: No No
Sub Roof Ventilation: No No
BUILDING FILE REPORT
Bunker Hill Outside Page 8
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Ceiling: R41,CE11",4-24Information From Quick Fill Screen:
Continous Insulation (R-Value) 27.8
Cavity Insulation (R-Value) 13.0
Cavity Insulation Thickness (in) 3.5
Cavity Insulation Grade 1
Gypsum Thickness (in) 0.500
Bottom Chord/Rafter Size(w x h, in) 1.5 x 3.5
Bottom Chord/Rafter Spacing (in o.c.) 24.0
Framing Factor - (default) 0.1100
Ceiling Type Attic
Note:
Layers Paths
Framing Cavity GradeInside Air Film 0.610 0.610 0.610
Gyp board 0.450 0.450 0.450
Cavity Ins/Frm 4.375 13.000 0.000
Continuous ins 27.800 27.800 27.800
0.000 0.000 0.000
0.000 0.000 0.000
0.000 0.000 0.000
Outside Air Film 0.610 0.610 0.610
Total R-Value 33.845 42.470 29.470
U-Value 0.030 0.024 0.034
Relative Area 0.110 0.890 0.000
UA 0.003 0.021 0.000
Total Component UA: 0.024
Total Component Area: 1.0
Component Uo: 0.024
BUILDING FILE REPORT
Bunker Hill Outside Page 9
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Ceiling: R39,CE,12-16,CInformation From Quick Fill Screen:
Continous Insulation (R-Value) 0.0
Cavity Insulation (R-Value) 39.5
Cavity Insulation Thickness (in) 11.5
Cavity Insulation Grade 1
Gypsum Thickness (in) 0.500
Bottom Chord/Rafter Size(w x h, in) 1.5 x 11.5
Bottom Chord/Rafter Spacing (in o.c.) 16.0
Framing Factor - (default) 0.1412
Ceiling Type Vaulted
Note:
Layers Paths
Framing Cavity GradeInside Air Film 0.610 0.610 0.610
Gyp board 0.450 0.450 0.450
Cavity Ins/Frm 14.375 39.500 0.000
Continuous ins 0.000 0.000 0.000
Plywood 0.930 0.930 0.930
Shingles 0.400 0.400 0.400
0.000 0.000 0.000
Outside Air Film 0.170 0.170 0.170
Total R-Value 16.935 42.060 2.560
U-Value 0.059 0.024 0.391
Relative Area 0.141 0.859 0.000
UA 0.008 0.020 0.000
Total Component UA: 0.029
Total Component Area: 1.0
Component Uo: 0.029
Mechanical Equipment: General Number of Mechanical Systems: 2
Heating SetPoint(F): 68.00
Heating Setback Thermostat: Present
Cooling SetPoint(F): 78.00
Cooling Setup Thermostat: Present
BUILDING FILE REPORT
Bunker Hill Outside Page 10
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Heat: 92.5AFUE Gas Furn60K SystemType: Fuel-fired air distribution
Fuel Type: Natural gas
Rated Output Capacity (kBtuh): 60.0
Seasonal Equipment Efficiency: 92.5 AFUE
Auxiliary Electric: 542 Eae
Note: Location: Conditioned area
Performance Adjustment: 100
Percent Load Served: 100
Number Of Units: 1
Water Heating Equipment: BW 40/Defender Water Heater Type: Conventional
Fuel Type: Natural gas
Energy Factor: 0.61
Recovery Efficiency: 0.77
Water Tank Size (gallons): 40
Extra Tank Insulation (R-Value): 0.0
Note: Location: Conditioned area
Percent Load Served: 100
Performance Adjustment: 100
Number Of Units: 1
Duct System Information: Name All
Heating System 92.5AFUE Gas Furn60K
Cooling System N/A
Supply Area(sq ft) 458.7
Return Area(sq ft) 169.9
Conditioned Floor Area(sq ft) 2265.0
# of Registers 2 Duct Leakage
Qualitative Assessment - Not Applicable
Duct Leakage to Outside: 61.00 CFM @ 25 Pascals
Supply Duct Leakage - Not Applicable
Return Duct Leakage - Not Applicable
Total Duct Leakage: 61.00 CFM @ 25 Pascals
Duct Tightness Test: Postconstruction Test
BUILDING FILE REPORT
Bunker Hill Outside Page 11
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Duct Information: 1 2
Type Supply Return
Percent Area 100.0 100.0
R-Value 0.0 0.0
Location Conditioned basement Conditioned basement
Infiltration and Mechanical VentilationWhole House Infiltration
Measurement Type: Blower door test
Heating Season Infiltration Value: 948 CFM @ 50 Pascals
Cooling Season Infiltration Value: 948 CFM @ 50 Pascals
Shelter Class 4
2009 IECC Verification: Tested
Mechanical Ventilation for IAQ
Type: Exhaust Only
Rate(cfm): 58
Sensible Recovery Efficiency(%): 0.00
Total Recovery Efficiency(%): 0.00
Hours per Day: 24.00
Fan Power (watts): 22.00
Ventilation Strategy for Cooling
Cooling Season Ventilation: Natural Ventilation
Lights and Appliances Simplified Audit
Oven/Range Fuel Type: Natural gas
Clothes Dryer Fuel Type: Natural gas
Percent Fluorescent - Pin-Based: 10.00
Percent Fluorescent - CFL: 0.00
Refrigerator KWh: 775
Dishwasher EF: 0.46
Ceiling Fan CFM / Watt: 0.00
BUILDING FILE REPORT
Bunker Hill Outside Page 12
REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Mandatory RequirementsIECC Requirements
Verified IECC 04: true
Verified IECC 06: true
Verified IECC 09: true
Verified IECC 12: false
Verified IECC NY: false
ENERGY STAR Version 2 Checklist
Thermal Bypass Checklist: true
ENERGY STAR Products: true
ENERGY STAR Version 3 Checklists
Thermal Enclosure Checklist: false
HVAC System Quality Installation Contractor Checklist: false
HVAC System Quality Installation Rater Checklist: false
Water Management System Builder Checklist: false
Indoor airPlus Verification Checklist: false
ENERGY STAR Version 3 Appliances
Has Refrigerators: false
Number Of Refrigerators: 0
Has Ceiling Fans: false
Number Of Ceiling Fans: 0
Has Exhaust Fans: false
Number Of Exhaust Fans: 0
Has Dishwashers: false
Number Of Dishwashers: 0
ENERGY STAR Version 3 Basements
Basement Wall Area 50% Below Grade: false
Basement Floor Area: 0
Number of Basement Bedrooms: 0
FUEL SUMMARY
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Bunker Hill Outside
Annual Energy Cost ($/yr) Natural gas $ 573
Electric $ 718
Annual End-Use Cost ($/yr) Heating $ 380
Cooling $ 0
Water Heating $ 158
Lights & Appliances $ 753
Photovoltaics $ -0
Service Charges $ 180
Total $ 1471
Annual End-Use Consumption Heating (Therms) 431
Heating (kWh) 297
Water Heating (Therms) 197
Lights & Appliances (Therms) 89
Lights & Appliances (kWh) 5686
Annual Energy Demands (kW) Heating 0.1
Cooling 0.0
Water Heating (Winter Peak) 0.0
Water Heating (Summer Peak) 0.0
Lights & Appliances (Winter Peak) 0.6
Lights & Appliances (Summer Peak) 1.1
Total Winter Peak 0.7
Total Summer Peak 1.1
Utility Rates: Electricity: Niagara Mohawk-Elec
Gas: National Grid - Gas
EQUIPMENT SIZING SUMMARY
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Bunker Hill OutsideHEATING Calculated Peak Load (kBtu/hr) 26.1 Sizing Factor (%) 100.0
HEATING EQUIPMENT CAPACITY (kBtu/hr) Required 26.1 Specified 60.0
COOLING Calculated Peak Load (kBtu/hr) 0.0 Sensible 0.0 Latent 0.0 Sizing Factor (%) 0.0
COOLING EQUIPMENT CAPACITY (kBtu/hr) Required Total 0.0 Specified Total 0.0
Required Sensible 0.00 Specified Sensible 0.00
Required Latent 0.00 Specified Latent 0.00
PERFORMANCE SUMMARY
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Bunker Hill Outside
Annual Load (MMBtu/yr) Heating 39.9 Cooling 0.0 Water Heating 15.2
Annual Consumption (MMBtu/yr) Heating 44.2 Cooling 0.0 Water Heating 19.7 Lights & Appliances 28.3 Photovoltaics -0.0 Total 92.2
Annual Energy Cost ($/yr) Heating $ 380 Cooling $ 0 Water Heating $ 158 Lights & Appliances $ 753 Photovoltaics $ -0 Service Charges $ 180 Total $ 1471
Design Loads (kBtu/hr) Space Heating 26.1 Space Cooling 0.0
Utility Rates: Electricity: Niagara Mohawk-Elec Gas: National Grid - Gas
PERFORMANCE SUMMARY
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
0
10
20
30
40
Hea
t
Coo
l
Wat
er H
eatin
g
MMBtu/yr
Annual Load
020406080
100
Hea
ting
Coo
ling
Wat
er H
eatin
g
Ligh
ts &
App
Pho
tovo
ltaic
s
Tota
l
MMBtu/yr
Annual Consumption
0200400600800
1000120014001600
Hea
ting
Coo
ling
Wat
er H
eatin
g
Ligh
ts &
App
Pho
tovo
ltaic
s
Ser
vice
Cha
rge
Tota
l
$/yr
Annual Energy Cost
Bunker Hill Outside
PERFORMANCE SUMMARY
Bunker Hill Outside Page 2
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
0
10
20
30
Spa
ce H
eatin
g
Spa
ce C
oolin
g
KBtu/Hr
Design Loads Utility Rates: Electricity: Niagara Mohawk-Elec
Gas: National Grid - Gas
EMISSIONS REPORT
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Total Emissions
Bunker Hill Outside
Type of EmissionsCarbon Dioxide (CO2) - tons/year 6.7
Sulfur Dioxide (SO2) - lbs/year 14.7
Nitrogen Oxides (NOx) - lbs/year 16.1
Emissions By End-Use
Bunker Hill Outside
Carbon Dioxide (CO2) - tons/yearHeating 2.7Cooling 0.0Water Heating 1.2Lights & Appliances 2.8Photovoltaics 0.0
Sulfur Dioxide (SO2) - lbs/yearHeating 0.8Cooling 0.0Water Heating 0.0Lights & Appliances 13.9Photovoltaics 0.0
Nitrogen Oxide (NOx) - lbs/yearHeating 6.7Cooling 0.0Water Heating 3.0Lights & Appliances 6.4Photovoltaics 0.0
Site-to-source energy multipliers and air emission data were taken from the US EPA eGRID2007 database.
2005 EPACT ENERGY EFFICIENT HOME TAX CREDIT
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Normalized, Modified End-Use Loads (MMBtu/year)2004 IECC
50% Target As Designed
Heating: 32.7 24.7
Cooling: 6.1 6.7
Total: 38.8 31.4
Envelope Loads (MMBtu/year)2004 IECC
90% Target As Designed
Heating: 58.9 38.7
Cooling: 11.0 8.4
Total: 69.9 47.1
This home MEETS the requirements for the residential energy efficiency tax credits underSection 1332, Credit for Construction of New Energy Efficient Homes, of the Energy Policy Act of 2005.
As demonstrated above, this dwelling unit has a projected level of annual heating and cooling energy consumption that is at least 50% below theannual level of heating cooling energy consumption of a reference dwelling in the same climate zone, and the building envelope componentsimprovements alone account for at least 10% of those savings. The projected heating and cooling energy savings above have been calculated in themanner prescribed in Section 2.02 of Notice 2006-27 of the Internal Revenue Service. Field inspections of the dwelling unit performed by theundersigned eligible certifier during and after the completion of construction have confirmed that all features of the home affecting such heatingand cooling energy consumption comply with the design specifications provided to the undersigned certifier.
Building FeaturesCeiling Flat: R-41 Slab: R-0.0 Edge, R-0.0 Under
Vaulted Ceiling: R-40 Duct: Uninsulated
Above Grade Walls: R-33 Window: U-Value = 0.330, SHGC = 0.450
Foundation Walls: R-11.1, R-0.0 Heating: Fuel-fired air distribution, Natural gas, 92.5 AFUE.
Exposed Floor: R-30 Cooling N/A
This report provides information useful in determining whether the home qualifies for Energy Efficiency Tax Credits.It is not valid for tax purposes, as homes must be inspected and approved by a certified HERS rater in order to qualify.
ENERGY STAR VERSION 2 HOME REPORT
Date: October 13, 2011 Rating No.:
Building Name: Bunker Hill Outside Rating Org.: CDH Energy
Owner's Name: Phone No.: 315-655-1063
Property: Rater's Name: Kevin Stack Reproduction (JPW)
Address: , Rater's No.:
Builder's Name:
Weather Site: Syracuse, NY Rating Type: Post Improvement
File Name: OutsideUnitAsBuilt-2011.blg Rating Date:
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.
Normalized, Modified End-Use Loads (MMBtu/year)ENERGY STAR As Designed
Heating: 52.3 24.7
Cooling: 9.8 6.7
Water heating: 9.9 11.6
Lighting & Appliances: 22.7 28.3
Total: 94.7 71.4
HERS Index: 80 60NY HERS Score: 84.0 88.0
ENERGY STAR Mandatory Requirements
X Thermal Bypass Inspection Checklist X ENERGY STAR Products
X Ductwork Requirements X ENERGY STAR Scoring Exceptions
This home MEETS OR EXCEEDS the energy efficiency requirements for designation as an EPA ENERGY STAR Qualified Home.
Pollution PreventedType of Emissions Reduction
Carbon Dioxide (CO2) - tons/yr 4.2
Sulfur Dioxide (SO2) - lbs/yr 3.0
Nitrogen Oxides (NOx) - lbs/yr 10.4
Energy Cost Savings ($/year)Heating: $573
Cooling: $65
Water Heating: $4
Lights & Appliances: $2
Total: $644
The energy savings and pollution prevented are calculated by comparing the Rated Home to the Reference Home as defined inthe "Mortgage Industry National Home Energy Rating Systems Standards" as promulgated by the Residential Energy ServicesNetwork (RESNET) . In accordance with these guidelines, building inputs affecting setpoints, infiltration rates, window shadingand the existence of mechanical systems may have been changed prior to calculating loads.
,
5 Stars PlusPost Improvement
Rating Number:Certified Energy Rater: Kevin Stack Reproduction (JPW)
Rating Date:Rating Ordered For:
Estimated Annual Energy CostPost Improvement
Use MMBtu Cost Percent Heating 44.2 $380 26%
Cooling 0 $0 0%
Hot Water 19.7 $158 11%
Lights/Appliances 28.3 $753 51%
Photovoltaics -0.0 $-0 -0%
Service Charges $180 12%
Total $1471 100%
This home meets or exceeds the minimumcriteria for all of the following:
TITLECompanyAddressCity, State, ZipPhone #Fax #
Uniform Energy Rating System1 Star 1 Star Plus 2 Stars 2 Stars Plus 3 Stars 3 Stars Plus 4 Stars 4 Stars Plus 5 Stars 5 Stars Plus0-19 20-39 40-49 50-59 60-69 70-79 80-81 81-82 83-85 86-100
Energy Efficient
NY HERS Score: 88.0 / HERS Index: 60General Information
Conditioned Area: 2265 sq. ft. HouseType: Townhouse, end unitConditioned Volume: 14974 cubic ft. Foundation: Conditioned basement
Bedrooms: 3Mechanical Systems Features
Heating: Fuel-fired air distribution, Natural gas, 92.5 AFUE.Water Heating: Conventional, Natural gas, 0.61 EF, 40.0 Gal.
Duct Leakage to Outside: 61.00 CFM.Ventilation System: Exhaust Only: 58 cfm, 22.0 watts.
Programmable Thermostat: Heating: Yes Cooling: Yes
Building Shell FeaturesCeiling Flat: R-41 Exposed Floor: R-30
Vaulted Ceiling: R-40 Window Type: Dbl/LoE/Arg - VinylAbove Grade Walls: R-33 Infiltration:
Foundation Walls: R-11.1, R-0.0 Rate: Htg: 948 Clg: 948 CFM50Slab: R-0.0 Edge, R-0.0 Under Method: Blower door test
Lights and Appliance FeaturesPercent Fluorescent Pin-Based: 10.00 Clothes Dryer Fuel: Natural gas
Percent Fluorescent CFL: 0.00 Range/Oven Fuel: Natural gasRefrigerator (kWh/yr): 775.00 Ceiling Fan (cfm/Watt): 0.00
Dishwasher Energy Factor: 0.46
The Home Energy Rating Standard Disclosure for this home is available from the rating provider.
REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.
© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.