Page 1: O&M - Geo1 SIM-AUTO- 95% - Geoflow

 

 

 

1‐800‐828‐3388 

GEO Installation & Operation Manual 

 

 

Model PREC‐GEO1‐SIM‐AUT 

Manual # 

 

 

 

 

Geoflow Subsurface Drip Systems 

506 Tamal Plaza Corte 

Madera, CA 94925, USA 

Office: 415.927.6000 

Toll Free: 800.828.3388 

Fax: 415.927.0120 

 

 

Page 2: O&M - Geo1 SIM-AUTO- 95% - Geoflow

 

Blank 

 

Page 3: O&M - Geo1 SIM-AUTO- 95% - Geoflow

i of ii 

Table of Contents 

1 Warnings ...................................................... 1 

2 Installation Instructions ................................ 2 

3 Panel Wiring Diagram ................................... 4 

4 Panel Operation ........................................... 8 

5 Connecting Via WiFi ..................................... 9 

6 Setting Instructions ‐ WiFi Connected ........ 12 

7 Setting Instructions – PLC Interface ............ 16 

8 Time‐Date & Contrast Settings ................... 23 

9 PLC Alarm Troubleshooting Guide .............. 26 

 

 

   

Page 4: O&M - Geo1 SIM-AUTO- 95% - Geoflow
Page 5: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388     Page 1 

1 Warnings 

To help prevent severe injury or property damage, please carefully read 

through each of the following warnings. 

Electrical Hazards 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

Page 6: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 2   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

2  Installation Instructions 

Before Installing Panel 

1.  Read all instructions before proceeding with the installation.  Improper installation may result in serious injuries and void warranties. 

2.  Inspect your order for completeness and shipment damage to components.  If something is missing or damaged, you will need to contact your supplier to obtain replacements. 

3.  Check to be sure the instructions and items supplied comply with state and local regulations. 

4.  A qualified electrician must be employed to install and service the panel and ancillary wiring.  The equipment must be installed in compliance with the National Electric Code, as well as state and local codes. 

 

Placement of the Control Panel 

5. Install the electrical control panel within view of the pump vault.  The panel should be attached to a structure capable of supporting the panel and resisting any wind load that may be encountered.  Panels containing motor contactors make a thumping sound, each time a pump is started or stopped. Therefore, these panels should not be mounted to an exterior wall of bedrooms or living areas, unless adequate vibration and sound suppression is provided.  If possible, position the panel such that it is protected from direct sunlight and snow or rain.  Extreme temperatures can cause inconsistent performance of the electrical components. Locate the panel at a convenient height (usually about five feet above the ground) and where it will be accessible for maintenance. 

 

Install Floats and Pumps 

6.  Install an electrical splice box(es) for the floats and pump(s) before installing the actual floats and pumping equipment.  The splice box(es) should be installed in grommet(s) near the top of the pump vault riser. 

7.  Install the floats.  Thread the float and pump cords through the cord grips into the PVC splice box, leaving adequate lengths of electrical cord coiled inside the riser to allow easy removal of the pump and float assembly.  Do not remove the colored markers or the paper tags from the float cords, and do not try to thread the markers and tag through the cord grip.  These should be left on the float cord, outside the splice box.  Tighten the cord grips, using hand pressure or a wrench if necessary, until the cord will no longer move in the cord grip. If the cord grips are not tight enough, the seal will not be watertight, but overtightening may damage the cord or the cord grip, so use only as much force as necessary. Adequate lengths of cord should be left within the splice box to allow for easy removal for future disconnecting and re‐splicing. 

8.  Run the wires from the control panel to the splice box.  The wires can be brought through a conduit or can be buried using suitable direct‐burial wire.  Conduit that enters the splice box must be sealed, even if the wires are direct‐buried, to prevent the infiltration of water into the splice box.  Use an electrically approved sealant to plug the wires coming in through the conduit hub. The number of wires 

Page 7: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388     Page 3 

required depends on the number of floats and pumps used.  This can be determined by consulting the panel wiring diagram.  

Wire should be sized at 14 AWG for the floats.  Refer to Figure 1 to determine the proper size for the pump wires.  When calculating wire size, the length and size of the branch circuit wires from the service entrance panel to the pump control panel must also be taken into account.  Wire that’s too small can cause an excessive voltage drop and poor pump performance.  Wires should be color coded or otherwise marked to aid in wiring the control panel. 

9.  All splices made in the splice box should use waterproof wire nuts or butt connectors and heat shrink tubing.  The splices must be waterproof!  Splices that are not waterproof may cause a malfunction of the controls if water should leak into the splice box. 

 

Connect the Control Panel 

10.   Connect the wires coming from floats to the terminals in the control panel.  Refer to the panel wiring diagram for the correct terminal connections. 

11.   Connect the wires coming from the pump(s) to the pump terminals.   Refer to the panel wiring diagram for the correct terminal connections. 

12.   Connect the incoming power to the panel.  Power to the panel must be appropriate to the control panel and pump motor (i.e. 120 VAC, single phase for a 120 VAC motor, 240 VAC single phase for a 240 VAC motor, etc.)  Insure that the panel is properly grounded and that the fuse or breaker and wire size, from the main power panel and to the control panel, are sized correctly.  Separate circuits for the pump controls and each of the pump motors is recommended.  Note:  Voltage for the controls in the panel is always 120 VAC, although the pump voltage may be 120 VAC or 240 VAC. 

13.   Use 60° minimum CU conductors only. Torque the terminal blocks to 15 LB‐IN and the ground lugs to 45 LB‐IN. Torque the circuit breakers to 20 LB‐IN for 14‐10 AWG wire, 25 LB‐IN for 8 AWG wire, and 27 LB‐IN for 6‐4 AWG wire. 

14.  When power is applied to the control panel, the wires to the pump may be energized. Do not service the pump or any electrical wiring in the pump vault without disconnecting the power at the circuit breaker and the fuse.  The pump vault area is a hazardous area and may contain explosive gases.  Take appropriate precautions before working in the pump vault. 

15.   If you have any questions please contact GEOFLOW. 

Figure 1.  Recommended Breaker & Wire Size 

Pump Motor Size  Breaker Size  Wire Size  Max Distance* 

120VAC   1/2hp  20 amp  10 AWG  105 ft 

240VAC 1/2hp  15 amp  14 AWG  161 ft 

240VAC 3/4hp  20 amp  14 AWG  130 ft 

240VAC 1hp  20 amp  12 AWG  172 ft 

240VAC 1‐1/2hp  20 amp  12 AWG  126 ft 

 

* This is the maximum distance from this subpanel to the pump motor for the recommended wire size.  Distance is based on 3% maximum voltage drop from subpanel to load at maximum recognized pump 

motor amps at 75° C.

Page 8: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 4   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

3 Panel Wiring Diagram 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 9: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 5 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 10: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 6   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 11: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 7 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 12: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 8   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

4 Panel Operation   

Your control panel can perform the float functions listed below.  Depending on the number of 

floats for your application, some functions may be omitted or combined. 

High Level Alarm (Float 4):  This float activates the alarm light and audible alarm when lifted.  

The audible alarm may be silenced by pressing the illuminated PUSH TO SILENCE button on the 

front of the control panel.  The alarm light will remain on until the float is lowered. 

Secondary Timer On & Off (Float 3): This float activates the Secondary Timer function when 

lifted. The timer will cycle the pump based on the values programmed in the Secondary Timer 

block, both the “On” and “Off” time may be different from those for the Primary Timer.  The 

secondary timer function will remain active until the Secondary Timer On & Off float lowers.  

When the Secondary Timer function has been completed, normal Primary timer operation will 

resume. 

Primary Timer On & Off (Float 2):  This float activates the Primary Timer and cycles the pump 

on and off based on the values in the Primary Timer block.  The timer will control the pump 

cycle, beginning with the off cycle. 

Redundant Off & Low‐Level Alarm (Float 1):  This float turns off the pump when lowered.  This 

float is a secondary off float which will operate if the Primary Timer On & Off float fails.  

Pumping will be disabled if in the automatic mode.  This float also activates the alarm light and 

audible alarm in a pulse/flashing manor (field adjustable).  The audible alarm may be silenced 

by pressing the illuminated PUSH TO SILENCE button on the front of the control panel.  The 

alarm light will remain on until the float is lifted. 

Pump & Valve Operation: The pump dosing cycles will be controlled by the Primary Timer 

(Float 2). During high flow conditions, the pump dosing cycles will be controlled by the 

Secondary Timer (Float 3). The Filter Flush valve will open for 15 seconds (field adjustable) at 

the beginning of the pump dosing cycle to allow for filter flushing. When the filter flush is 

complete the pump will remain activated for the duration of the current zone timer.  After the 

pump is deactivated the field flush valve and filter flush valve will remain activated for 5 

minutes (field adjustable) to allow for drainage.  After 10 dosing cycles (field adjustable), the 

field flush valve will be activated at the end of each zone’s dose cycle allowing the zone to be 

flushed for 5 minutes (field adjustable).  This operation will also occur after a power outage. 

 

Page 13: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 9 

5 Connecting Via WiFi  The GEO line of control panels includes an easy‐to‐use programmable logic unit that incorporates many time and logic functions.  The units have built in WiFi Modules which allow wireless connection via a smart phone, tablet, PC or other WiFi capable device giving easier access to system data screens and settings. 

Connecting with Smart Phone or PC Computer: 

Step 1: To connect to the WiFi network ensure 

you are within range of the Panel (WiFi 

range is typically up to 100’, however 

obstructions, walls, device hardware etc. 

may effect range). 

Step 2: Open the WiFi Settings of the device that 

is to be connected.  Find the WiFi 

network “GEOFLOW” and connect.    

 

 

 

 

Step 3: When prompted the password to the 

network is “geoflow2018”.  Once 

connected your device may indicate 

there is no Internet Access, this is 

normal the Geo Panel is a local network 

only.    

Note: If your Smart Phone device is having a 

difficult time connecting to the network, it may 

be necessary to turn off cell data while 

attempting to connect. 

 

 

Page 14: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 10   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

Step 4: Once connected, open the internet 

browser (Safari, Firefox, Chrome etc.).  In 

the address bar, type “192.168.1.4”.  

 

 

 

 

 

 

 

 

 

Step 5: When the login page has loaded select 

the default language as “English” and 

enter the password “geo”, select the box 

Keep me logged on and then select Log 

On.  

 

 

 

 

 

 

 

 

 

 

Page 15: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 11 

Step 6: Once logged in select the dropdown in 

the upper right‐hand corner and select 

SmartRelay TD, then click Done.   

Warning: Do not adjust settings in any other 

dropdown screen or menu.  Doing so 

may permanently alter the panel 

programming, which cannot be 

restored without the use of a MicroSD 

card. 

Step 7: This will bring up the Home Page for the 

WiFi access screen.  For instructions on 

adjusting settings and navigating the 

screens see “WiFi Connected Navigation 

& Settings”.   

                   

Page 16: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 12   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

6 Setting Instructions ‐ WiFi Connected While wirelessly connected to the Geo line of control panels, the connection will grant access to the following system data screens and settings. 

System Data Screens:  Description 

1. Home Screen  System status overview, including device status 

2. Total Power Cycles  Displays total number of power cycles 

3. Pump Run Time  Pump run time meter in Hours 

4. Pump Starts Count  Pump cycle counter 

5. Level Override Count  Override cycle counter 

6. High Level Count  High level alarm counter 

7. Hand Starts  Number of times the pump has been started in Hand 

8. Current Zone & Timer  Displays current active value for zone timer or off timer 

9. Secondary Timer  Number of Zones, individual zone timers and float 3 off time 

10.  Primary Timer  Number of Zones, individual zone timers and float 2 off time 

11.  Field Flush  Field Flush Settings  

12.  Filter Flush   Filter Flush Settings 

13.  Drain Down   Filter & Field Drain Down Settings 

14.  Low Level Fault Blink  Low Level Fault Blink Intervals 

 

Home Screen – Informational Screen Only 

 

 

 

 

 

Only the Up and Down arrows are used when navigating and changing screens.  The Fuction(F), ESC and OK buttons are not incorporated. 

 

Screens #2 ‐ #7 – Informational Screens Only 

 

 

 

 

Use the Up and Down arrows 

navigate through the System Screens. 

Indicates the status of device. 

Description of the current counter or 

timer being displayed. 

Current counter or timer value of the 

named device. 

Page 17: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 13 

Float 2 & 3 Screens – Adjustment & Informational Screens 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Flush Screen – Adjustment & Informational Screen 

 

 

 

 

 

 

 

 

 

 

 

 

 

Block Names  Description  Factory Default  Range 

Zone= X  System Zone Counter  1 zone  1‐6        *Model dependent* 

ZX=   Individual Zone Timer  Z1= Zone 1, Z2= Zone 2 etc. 

Float 2 = 5 min Float 3 = 5 min 

Minutes 

Off Time  System off Timer  Float 2 = 115 min Float 3 = 55 min 

Minutes 

Block Names  Description  Factory Default  Range 

Cycle B4 Flush  Field Flush Counter  10 cycles   

Flush Time 1 & 2  Field Flush Timer   

Float 2 = 5 min Float 3 = 5 min 

Minutes 

Adjustable number of Zones the 

system is configured to operate.  

*Panel model dependent. 

Adjustable run time for each zone in 

minutes. Z1= Zone 1, Z2= Zone 2 etc.   

Adjustable off time for the displayed 

float in minutes. Float 2 & Float 3 Screens are very similar.  

This number indicates which Float screen is 

currently being viewed. 

Adjustable Field Flush Counter is the 

number of cycles that will occur 

before a field flush is triggered. 

Adjustable Flush Time 1 & 2 are the 

timers for the field flush in minutes. 

Current flush valve status. 

Current cycle counter value. 

Page 18: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 14   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

Filter Flush Screen – Adjustment & Informational Screen 

 

 

 

 

 

 

 

 

 

Drain Down Screen – Adjustment & Informational Screen 

 

 

 

 

 

 

 

 

Low Level Fault Blink Interval Screen – Adjustment & Informational Screen 

 

 

 

 

 

 

 

Block Names  Description  Factory Default  Range 

Filter Flush Duration 

Filter Flush Duration Timer  15 seconds  MM:SS 

Block Names  Description  Factory Default  Range 

Drain Down Timer  Filter & Field Drain Down Timer  5 minutes  MM:SS 

Block Names  Description  Factory Default  Range 

Low Lvl Blink On  Alarm Light & Buzzer On Timer  2 seconds  Seconds 

Low Lvl Blink Off  Alarm Light & Buzzer Off Timer  30 seconds  Seconds 

Adjustable Flush Duration Timer in 

MM:SS. 

Current flush duration timer value. 

Current filter flush valve status. 

Adjustable Drain Down Timer in 

MM:SS. 

Current flush duration timer value. 

Adjustable on timer for Low Level 

alarm light and buzzer activation in 

seconds. 

Adjustable off timer for Low Level 

alarm light and buzzer activation in 

seconds. 

Page 19: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 15 

Changing Adjustable Parameter Blocks: 

Step 1: Press   or   to view the system screen 

of the parameter to be adjusted.  In this 

example, “Primary Timer Float 2” is 

being viewed.  

 

Step 2: The blue values indicate the ability to 

change the setting/value.  Click on the 

value to be changed, this will bring up a 

Modify Parameter popup.  Enter the 

desired value in the New Value box. 

Warning: From some screens the timer base 

units can be adjusted from this screen.  

Pay close attention to keep current unit 

(s, m, h) unless you’ve referred to 

Default Settings Instructions for 

detailed explanation of individual 

timing units.  At any time, pressing 

popup will close without adjusting the 

value. 

Step 3: When the desired value has been 

entered, press the “OK” key.  The new 

time value will now be in effect. In this 

example, the set value has been 

changed from 5 minutes to 7 minutes.  

 

 

 

 

 

Page 20: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 16   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

7 Setting Instructions – PLC Interface The GEO line of control panels includes an easy‐to‐use programmable logic unit that incorporates many time and logic functions.  The units have built in screens which show the time and date and input/output status.  Additionally, the following system data screens have been included in your panel: System Data Screens:  Description 1. Power Cycle Count  Total number of power cycle counter 2. Pump Run Time  Pump run time meter in Hours 3. Pump Starts Count  Pump cycle counter 4.  Level Override Count  Override cycle counter 5.  High Level Count  High level alarm counter 6. Hand Starts Count  Pump hand starts counter 7. Current Zone Timing  Displays current active value for zone timer or off timer 

 

 

 

 

Input and Output Screens: The unit will activate various inputs and outputs as it operates (please refer to the LCD Display screens shown below).  Knowing what conditions cause the inputs and outputs to activate can be a helpful installation and troubleshooting tool.  The following inputs and outputs have been used with your control panel: 

 

 

 

 

Input Functions:  Activation Conditions: 

1. Run Return (ETM & CT Signal)  Contactor is engaged 

2. Redundant Off & Low‐Level Alarm Float 1  Float is in up position 

3.  Primary Timer On & Off Float 2  Float is in up position 

4.  Secondary Timer On & Off Float 3  Float is in up position 

5.  High Level Alarm Float 4  Float is in up position 

7.  Pump Auto     Pump HOA is in the Auto position 

Output Functions:  Conditions for Activation: 

1. Pump   Pump is on 

2. General Alarm  Alarm condition exists 

3. Filter Flush Valve  Filter flush valve is activated 

4. Field Flush Valve  Field flush valve is activated 

System Data Screen

System Data Screen

Time & DateDigital Inputs 

(#1‐24)

Digital Outputs   (#1‐20)

Analog Inputs (#1‐5)

Analog Inputs (#6‐8)

Analog Outputs   (#1‐5)

Analog Outputs   (#6‐8)

Memory      (#1‐49)

Memory    (#50‐64)

ESC+C

Inputs 1‐9 

Inputs 10‐19 

Outputs 1‐9 

Inputs 20‐24 

Outputs 10‐16 

Activated 

Input/Output 

 

Page 21: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 17 

The unit uses block names to identify the various parameters (please refer to the Liquid Crystal 

Display screen shown in Step #3). The following block types have been used with your control 

panel: 

Timer blocks different time base units that can be used; s = seconds, m = minutes, h = hours. If an h appears after the timer setting, then the time will be HH:MM (e.g. 01:55h = 1 hour and 55 minutes). If an m appears after the timer setting then the time will be MM:SS (e.g. 05:00m = 5 minutes and 0 seconds). If an s appears after the timer setting then the time will be SS.ss (e.g. 25:13s = 25.13 seconds).  All adjustable parameters DO NOT use the same type of blocks, check the block types above to determine which steps apply to your application.  Data Register timing units are not labeled within the LCD screen, to determine the timing units refer to chart above.    

Changing Adjustable Parameter Blocks: 

Step 1: Press   repeatedly until the display 

does not change.  To begin the 

configuration process, press the “ESC” 

key. 

Block Names  Description  Factory Default  Range  Block Type 

Zone Counter  System Zone Counter  1 zone  1‐6        *Model dependent* 

Counter 

Zone 1 Timer  Zone 1 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Zone 2 Timer  Zone 2 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Zone 3 Timer  Zone 3 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Zone 4 Timer  Zone 4 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Zone 5 Timer  Zone 5 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Zone 6 Timer  Zone 6 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Off Timer  Float 2 & Float 3 Timer Off  (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 115 min V2 = 55 min 

Minutes  Data Register 

FltrFlsh Tmr  Filter Flush Timer  15 seconds  MM:SS  Timer 

Fld Flsh Tmr  Field Flush Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min V2 = 5 min 

Minutes  Data Register 

Fld Flsh Cnt  Field Flush Counter  10 cycles    Counter 

Drain Timer  Filter & Field Drain Timer  5 minutes  MM:SS  Timer 

Lvl Blnk On  Low Level Alarm/Buzzer Blink ON timer 

2 seconds  Seconds  Data Register 

Lvl Blnk Off  Low Level Alarm/Buzzer Blink OFF timer 

30 seconds  Seconds  Data Register 

Not Named  Background program functions  Do not change  n/a  n/a 

Page 22: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 18   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

Step 2: Press   on the unit to select “Program”.  

Then press the “OK” key. 

 

Warning: Do not select “Stop”.  Doing so may 

erase the panel programming, which cannot be 

restored without the use of a MicroSD card, 

which is not included with the panel.  If this is 

selected by accident, a confirmation screen will 

come up.  Select “No” and press the “OK” key 

immediately. 

 

Step 3: Using the arrow keys highlight “Set 

Parameter” and press the “OK” key.  

This will bring up a list of program 

parameter blocks that can be edited. For 

editing specific parameter blocks see 

specific instructions below. 

 

 

Changing Adjustable Parameter Timer Blocks: 

Step 4: Press   or   to view the parameter 

values.  In this example, “FltrFlsh Tmr” is 

being viewed.  

 

 

Step 5: The first line indicates the set value for 

the parameter.  In this example, it’s the 

on time for Filter Flush and is set to 15 

seconds, “T =00:15m”.  To change the 

value for the parameter, press the “OK” 

key.  

Page 23: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 19 

  The second line indicates, in real time, 

the current timer value. The current 

value in this example is 0, “Ta = 00:00”, 

because the Filter Flush timer is not 

currently active. This value is meant to 

be informational only and should not be 

adjusted. 

Step 6: The cursor will appear in the set value.  

To select the digit to be changed, press  

 or  .  To change the value of the 

digit, press   or  .  In this example, 

the set value has been changed from 15 

seconds to 18 seconds.  

Step 7: When the desired time value has been 

entered, press the “OK” key.  The new 

time value will now be in effect. 

 

 

 

Step 8: To exit parameter mode, press the “ESC” 

key four times. 

 

 

 

 

Changing Adjustable Parameter Counter Blocks: 

Step 4: Press   or   to view the parameter 

values.  In this example, “Fld Flsh Cnt” is 

being viewed.  

 

 

Page 24: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 20   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

Step 5: The value listed after the “On =” parameter is the set point for the counter. In this example, the setting is 10, “On = 10.” To change the value for the parameter, press the “OK” key.   

 The next line, starting with “Off =” is not used. This value must remain set to zero, “Off = 0.”    The third line indicates, in real time, how many counts have occurred for this process. The current value in this example is 3, “Cnt = 3.” This value is meant to be informational only and should not adjusted.    The parameter “STV =” is not used. This value must remain set to zero, “STV = 0”.  

 

Step 6: The cursor will appear in the set value.  

To select the digit to be changed, press  

 or  .  To change the value of the 

digit, press   or  .  In this example, 

the set value has been changed from 10 

to 20.  

Step 7: When the desired time value has been 

entered, press the “OK” key.  The new 

time value will now be in effect. 

 

Step 8: To exit parameter mode, press the “ESC” 

key four times. 

 

Page 25: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 21 

Changing Adjustable Data Register Blocks: 

Step 4: Press   or   to view the parameter 

values.  In this example, “Zone 1 Timer” 

is being viewed.  

 

 

Step 5: The value listed after the “V1 =” parameter is the On Timer for Zone 1 when Float 2 is active, “V2 =” parameter is the On Timer for Zone 1 when Float 3 is active. In this example, both timers are set to 5 minutes. To change the value for the parameter, press the “OK” key.   

 The following “V3 & V4” lines, are not used. These values must remain set to zero, “Off = 0.”    The fifth line indicates, in real time, what current time value is active (based on which float/timer is active). The current value in this example is 5, “AQ =+5.” This value is meant to be informational only and should not be adjusted.    

Step 6: The cursor will appear in the set value.  

To select the digit to be changed, press  

 or  .  To change the value of the 

digit, press   or  .  In this example, 

the set value has been changed from 5 

to 10.  

 

Page 26: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 22   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

 

Step 7: When the desired time value has been 

entered, press the “OK” key.  The new 

time value will now be in effect. 

 

 

 

Step 8: To exit parameter mode, press the “ESC” 

key four times. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 27: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 23 

8 Time‐Date & Contrast Settings  The GEO line of control panels includes an easy‐to‐use programmable logic unit that incorporates many timing and logic functions. The unit has been programmed at the factory for all control functions, however these values should be field adjusted for the individual the unit is installed to operate.  Setting the date and time is not necessary, however, if desired, the time and date can be set by following these instructions.  To set the time and date, use the four arrow keys located on the face of the unit (up, down, left, and right), along with the “ESC” key and the “OK” key.  Follow the three easy steps below.  

Changing Settings: 

Step 1: Press   repeatedly until the display 

does not change.  To begin the 

configuration process, press the “ESC” 

key. 

 

Step 2: Press   on the unit to select “Setup”.  

Then press the “OK” key. 

 

Warning: Do not select “Stop”.  Doing so may 

erase the panel programming, which cannot be 

restored without the use of a MicroSD card, 

which is not included with the panel.  If this is 

selected by accident, a confirmation screen will 

come up.  Select “No” and press the “OK” key 

immediately. 

If adjusting contrast, continue with the steps 

below.  If adjusting time & date, skip to “Setting 

Time and Date:” on the following pages. 

    

Page 28: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 24   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

Adjusting Contrast: 

Step 3: Press   or   to select “LCD” and press 

the “OK” key. 

    

Step 4: Press   or   to select “Contrast” and 

press the “OK” key. 

      

Step 5: Using   or   select the desired 

contrast and the press the “OK” key.   

      

Step 8: To exit, press the “ESC” key three times. 

             

Page 29: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Geoflow Subsurface Drip Systems – 1‐800‐828‐3388      Page 25 

Setting Time and Date: 

Step 3: Press   or   to select “Clock” and 

press the “OK” key. 

    

Step 4: Press   or   to select “Set Clock” and 

press the “OK” key. 

      

Step 5: Use the   or   keys to the desired 

position. 

Step 6: Change the value by pressing   or  .    

    

Step 7: To confirm your entries press the “OK” 

key once.  Then press the “ESC” key 

three times. 

          

Page 30: O&M - Geo1 SIM-AUTO- 95% - Geoflow

Page 26   Geoflow Subsurface Drip Systems – 1‐800‐828‐3388 

9 PLC Alarm Troubleshooting Guide The GEO line of control panels include built in saftey functions designed to protect the system and pump from operating in unsafe/undesirable conditions.    

 

 

 

 

 

 

High Level Alarm:  This alarm is triggered when the High 

Level float (Float 4) is no longer in the hanging 

position.  Activates the alarm light and audible 

alarm when lifted.  The alarm will remain on 

until the float is lowered. 

 

Low‐Level Alarm:  This alarm is triggered when the Low 

Level float (Float 1) is in the hanging position.  

The alarm will remain on until the float is lifted. 

 

 

 

Run Return Alarm:  This alarm is triggered if the PLC has 

called for the pump to start and there is not run 

return signal from the contactor indicating it 

has energized the motor.  

   

Floats Fault:  This alarm is triggered if the float inputs of 

the PLC react in an unanticipated manor, i.e. if 

float 1 is indicating it’s hanging and float 2 is 

indicating it’s floating.    

Indicates which device(s) are 

associated with the alarm 

Displays the specific alarm condition 

that is active. 

Describes the alarm. 

Page 31: O&M - Geo1 SIM-AUTO- 95% - Geoflow

1‐800‐828‐3388 

WiFi Quick Reference Guide ‐ PREC‐GEO1‐SIM‐AUT 

System Data Screens: Once connected via WiFi, press the up and down arrow keys to navigate system screens. The following screens have been used.

When viewing the screens from a WiFi connected device the blue values 

indicate the ability to change the setting/value.  Click or touch the value to be 

changed, this will bring up a Modify Parameter popup.  Enter the desired value 

in the New Value box.  When the desired value has been entered, press the 

“OK” key.  The new setting value will now be in effect. Warning: From some screens the timer base units can be adjusted.  Pay close attention to keep 

current unit (s, m, h) unless you’ve referred to Operation Instructions for detailed explanation of 

individual timing units.  At any time, pressing Cancel while in the Modify Parameter popup will close 

without adjusting the value. 

 

WiFi Connection & Remote Access Wi‐Fi Hotspot/SSID  GEOFLOW Wi‐Fi Password  geoflow2018 

PLC Web Address/URL  192.168.1.4 PLC Login User Password  geo 

System Data Screens:  Description 

1. Home Screen  System status overview, including device status 

2. Total Power Cycles  Displays total number of power cycles 

3. Pump Run Time  Pump run time meter in Hours 

4. Pump Starts Count  Pump cycle counter 

5. Level Override Count  Override cycle counter 

6. High Level Count  High level alarm counter 

7. Hand Starts  Number of times the pump has been started in Hand 

8. Current Zone & Timer  Displays current active value for zone timer or off timer 

9. Float 3 Settings  Number of Zones, individual zone timers and float 3 off time 

10. Float 2 Settings  Number of Zones, individual zone timers and float 2 off time 

11. Field Flush  Field Flush Settings  

12. Filter Flush   Filter Flush Settings 

13. Drain Down   Filter & Field Drain Down Settings 

14. Low Level Fault Blink  Low Level Fault Blink Intervals 

Block Names  Description  Factory Default  Range 

Zone= X  System Zone Counter  1 zone  1‐6 *Model dependent* 

ZX=  Individual Zone Timer  Z1= Zone 1, Z2= Zone 2 etc. 

Float 2 = 5 min Float 3 = 5 min 

Minutes 

Off Time  System off Timer  Float 2 = 115 min Float 3 = 55 min 

Minutes 

Cycle B4 Flush  Field Flush Counter  10 cycles   

Flush Time 1 & 2  Field Flush Duration Timer  Float 2 = 5 min Float 3 = 5 min 

Minutes 

Filter Flush Duration  Filter Flush Duration Timer  15 seconds  MM:SS 

Drain Down  Filter & Field Drain Down Timer  5 minutes  MM:SS 

Low Lvl Blink On  Alarm Light & Buzzer On Timer  2 seconds  Seconds 

Low Lvl Blink Off  Alarm Light & Buzzer Off Timer  30 seconds  Seconds 

Page 32: O&M - Geo1 SIM-AUTO- 95% - Geoflow

1‐800‐828‐3388 

Quick Reference Guide ‐ PREC‐GEO1‐SIM‐AUT 

Built-in Screens: Built in screens are time & date, digital inputs, digital outputs, analog inputs, analog outputs, memory flag, and ESC+cursor key status. To view these screens, press the down arrow repeatedly until a built-in screen appears, then use the left and right arrow keys to change between screens. System Data Screens: To change between screens, press the up and down arrow keys. The following screens have been used with your panel. System Data Screens:  Description 

1. Power Cycle Count  Total number of power cycle counter 

2. Pump Run Time  Pump run time meter in Hours 

3. Pump Starts Count  Pump cycle counter 

4.  Level Override Count  Override cycle counter 

5.  High Level Count  High level alarm counter 

6. Hand Starts Count  Pump hand starts counter 

7. Current Zone Timing  Displays current active value for zone timer or off timer 

  

Input Functions:  Activation Conditions: 

1. Run Return (ETM & CT Signal)  Contactor is engaged 

2. Redundant Off & Low‐Level Alarm Float  Float is in up position 

3.   Primary Timer On & Off Float  Float is in up position 

4.  Secondary Timer On & Off Float  Float is in up position 

5.  High Level Alarm Float  Float is in up position 

7.  Pump Auto  Pump HOA is in the Auto position 

Output Functions:  Conditions for Activation: 

1. Pump   Pump is on 

2. General Alarm  Alarm condition exists 

3. Filter Flush Valve  Filter flush valve is activated 

4. Field Flush Valve  Field flush valve is activated 

Block Names  Description  Factory Default  Range  Block Type 

Zone Counter 

System Zone Counter  1 zone  1‐6 *Model dependent* 

Counter 

Zone 1 Timer  Zone 1 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Zone 2 Timer  Zone 2 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Zone 3 Timer  Zone 3 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Zone 4 Timer  Zone 4 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Zone 5 Timer  Zone 5 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Zone 6 Timer  Zone 6 Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Off Timer  Float 2 & Float 3 Timer Off (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 115 min / V2 = 55 min  Minutes  Data Register 

FltrFlsh Tmr  Filter Flush Timer  15 seconds  MM:SS  Timer 

Fld Flsh Tmr  Field Flush Timer (Floats 2 & 3) (V1= Float 2 Timer, V2= Float 3 Timer) 

V1 = 5 min / V2 = 5 min  Minutes  Data Register 

Fld Flsh Cnt  Field Flush Counter  10 cycles    Counter 

DrainTmr  Filter & Field Drain Timer  5 minutes  Minutes  Data Register 

Not Named  Background program functions  Do not change  n/a  n/a