olar p tandard electrical plans: microinverter mc …

6
SCOPE: Use this plan ONLY for systems using ulity-interacve Micro-inverters or AC Modules (ACM) not exceeding a combined system AC inverter output rang of 10 kW, with a maximum of 3 branch circuits, one PV module per inverter and with PV module ISC maximum of 10-A DC, installed on a roof of a one- or two-family dwelling or accessory structure. The photovoltaic system must interconnect to a single-phase AC service panel of 120/240 Vac with service panel bus bar rang of 225 A or less. This plan is not intended for bipolar systems, hybrid systems or systems that ulize storage baeries, charge controllers or trackers. Systems must be in compliance with current California Building Standards Codes and local amendments of the authority having jurisdicon (AHJ). Other arcles of the California Electrical Code (CEC) shall apply as specified in secon 690.3. MANUFACTURER’S SPECIFICATION SHEETS MUST BE PROVIDED for proposed inverters, modules, combiner/juncon boxes and racking systems. Installaon instrucons for bonding and grounding equipment shall be provided and local AHJs may require addional details. Listed and labeled equipment shall be installed and used in accordance with any instrucons included in the lisng or labeling (CEC 110.3). Equipment intended for use with PV system shall be idened and listed for the applicaon CEC 690.4(D). Applicant and Site Informaon Job Address: ___________________________________________ Permit #: __________________________ Contractor/Engineer Name: _______________________________ License # and Class: __________________ Signature: ___________________________ Date: _____________ Phone Number: _____________________ 1. General Requirements and System Informaon Microinverter AC Module (ACM) Number of PV modules installed: __________ Number of ACMs installed: __________ Number of Microinverters installed: __________ Note: Listed Alternang-Current Module (ACM) is defined CEC 690.2 and installed per CEC 690.6 1.1 Number of Branch Circuits, 1, 2 or 3: __________ 1.2 Actual number of Microinverters or ACMs per branch circuit: 1 ________ 2.________ 3._______ 1.3 Total AC system power rang = (Total Number of Microinverters or ACMs) * (AC inverter power output) = __________ Was 1.4 Lowest expected ambient temperature for this plan in Table 1: For -1° to -5° C use 1.12 or for -6° to -10° C use 1.14 correcon factors. 1.5 Average ambient high temperature for this plan: = +47° C Note: For lower expected ambient or higher average ambient high temperatures, use Comprehensive Standard Plan. 2. Microinverter or ACM Informaon and Rangs Microinverters with ungrounded DC inputs shall be installed in accordance with CEC 690.35. Microinverter or ACM Manufacturer: _____________________________ Model: ______________________________________________________ 2.1 Rated (connuous) AC output power: __________ Was WEST HOLLYWOOD 8300 Santa Monica Boulevard West Holl ywood, CA 90069-6216 Solar PV Standard Electrical Plan: Microinverter & AMC Page 1 of 6 Building & Safety Division tel 323 848.6475 fax 323.848.6569 Solar PV Standard Electrical Plan: Microinverter & AMC Systems SOLAR PV STANDARD ELECTRICAL PLANS: MICROINVERTER & AMC SYSTEMS

Upload: others

Post on 13-Feb-2022

5 views

Category:

Documents


0 download

TRANSCRIPT

SCOPE: Use this plan ONLY for systems using utility-interactive Micro-inverters or AC Modules (ACM) not exceeding a combined system AC inverter output rating of 10 kW, with a maximum of 3 branch circuits, one PV module per inverter and with PV module ISC maximum of 10-A DC, installed on a roof of a one- or two-family dwelling or accessory structure. The photovoltaic system must interconnect to a single-phase AC service panel of 120/240 Vac with service panel bus bar rating of 225 A or less. This plan is not intended for bipolar systems, hybrid systems or systems that utilize storage batteries, charge controllers or trackers. Systems must be in compliance with current California Building Standards Codes and local amendments of the authority having jurisdiction (AHJ). Other articles of the California Electrical Code (CEC) shall apply as specified in section 690.3.

MANUFACTURER’S SPECIFICATION SHEETS MUST BE PROVIDED for proposed inverters, modules, combiner/junction boxes and racking systems. Installation instructions for bonding and grounding equipment shall be provided and local AHJs may require additional details. Listed and labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling (CEC 110.3). Equipment intended for use with PV system shall be identified and listed for the application CEC 690.4(D).

Applicant and Site Information

Job Address: ___________________________________________ Permit #: __________________________

Contractor/Engineer Name: _______________________________ License # and Class: __________________

Signature: ___________________________ Date: _____________ Phone Number: _____________________

1. General Requirements and System Information

Microinverter AC Module (ACM)Number of PV modules installed: __________ Number of ACMs installed: __________Number of Microinverters installed: __________ Note: Listed Alternating-Current Module (ACM) is defined

CEC 690.2 and installed per CEC 690.6

1.1 Number of Branch Circuits, 1, 2 or 3: __________

1.2 Actual number of Microinverters or ACMs per branch circuit: 1 ________ 2.________ 3._______

1.3 Total AC system power rating = (Total Number of Microinverters or ACMs) * (AC inverter power output) = __________ Watts

1.4 Lowest expected ambient temperature for this plan in Table 1: For -1° to -5° C use 1.12 or for -6° to -10° C use 1.14 correction factors.

1.5 Average ambient high temperature for this plan: = +47° C Note: For lower expected ambient or higher average ambient high temperatures, use Comprehensive Standard Plan.

2. Microinverter or ACM Information and Ratings

Microinverters with ungrounded DC inputs shall be installed in accordance with CEC 690.35.

Microinverter or ACM Manufacturer: _____________________________

Model: ______________________________________________________

2.1 Rated (continuous) AC output power: __________ Watts

WEST HOLLYWOOD 8300 Santa Monica Boulevard West Hollywood, CA 90069-6216

Solar PV Standard Electrical Plan: Microinverter & AMC Page 1 of 6

Building & Safety Division tel 323 848.6475 fax 323.848.6569

Solar PV Standard Electrical Plan: M

icroinverter & A

MC

Systems

SOLAR PV STANDARD ELECTRICAL PLANS: MICROINVERTER & AMC SYSTEMS

2.2 Nominal AC voltage rating: __________ Volts

2.3 Rated (continuous) AC output current: __________ Amps

If installing ACMs, skip [STEPS 2.4]

2.4 Maximum DC input voltage rating: __________ Volts (limited to 79 V, otherwise use the Comprehensive Standard Plan)

2.5 Maximum AC output overcurrent protection device (OCPD) ___________ Amps

2.6 Maximum number of microinverters or ACMs per branch circuit: ___________

3. PV Module Information

(If installing ACMs, skip to [STEP 4])

PV Module Manufacturer: _______________________________________________

Model: _______________________________________________________________

Module DC output power under standard test conditions (STC) = __________ Watts

3.1 Module VOC at STC (from module nameplate): __________ Volts

3.2 Module ISC at STC (from module nameplate): ___________ Amps

3.3 Adjusted PV Module DC voltage at minimum temperature = [Table 1] ________ [cannot exceed Step 2.4]

Table 1. Module VOC at STC Based on Inverter Maximum DC Input Voltage Derived from CEC 690.7

Microinverter Max. DC Input [STEP 2.4] (Volts) 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79

Max. Module VOC @ STC, 1.12 (-1° to -5° C) Correction

Factor (Volts)30.4 33.0 35.7 38.4 41.1 43.8 46.4 49.1 51.8 54.5 57.1 59.8 62.5 65.2 67.9 70.5

Max. Module VOC @ STC, 1.14 (-6° to -10° C) Correction

Factor (Volts)29.8 32.5 35.1 37.7 40.4 43.0 45.6 48.2 50.9 53.5 56.1 58.8 61.4 64.0 66.7 69.3

4. Branch Circuit Output Information

Fill in [Table 3] to describe the branch circuit inverter output conductor and OCPD size. Use [Table 2] for determining the OCPD and Minimum Conductor size.

Table 2. Branch Circuit OCPD and Minimum Conductor Size*

Circuit Current (Amps) OCPD (Amps) Minimum Conductor Size (AWG)

Minimum Metal Conduit Size for 6 Current Carrying

Conductors

12 2880 15 12 ¾”

16 3840 20 10 ¾”

20 4800 25 8 1”

24 5760 30 8 1”

*CEC 690.8 and 210.19 (A)(1) factored in Table 2, conductors are copper, insulation must be 90° C wet-rated. Table 2 values are based on maximum ambient temperature of 69° C, which includes 22° C adder, exposed to direct sunlight, mounted > 0.5 inches above rooftop, ≤ 6 current carrying conductors (3 circuits) in a circular raceway. Otherwise use Comprehensive Standard Plan.

WEST HOLLYWOOD 8300 Santa Monica Boulevard West Hollywood, CA 90069-6216

Solar PV Standard Electircal Plan: Microinverter & AMC Page 2 of 6

Building & Safety Division tel 323 848.6475 fax 323.848.6569

Solar PV Standard Electrical Plan: M

icroinverter & A

MC

Systems

SOLAR PV STANDARD ELECTRICAL PLANS: MICROINVERTER & AMC S YSTEMS

Table 3. PV Array Configuration Summary

Branch 1 Branch 2 Branch 3

Number of Microinverters or ACMs [Step 1]

Selected Conductor Size [Table 2] (AWG)

Selected Branch and Inverter Output OCPD [Table 2]

5. Solar Load Center (if used)

5.1 Solar Load Center is to have a bus bar rating not less than 100 Amps. Otherwise use ComprehensiveStandard Plan.

5.2 Circuit Power see [STEP 1] =___________ Watts

5.3 Circuit Current = (Circuit Power) / (AC voltage) = __________ Amps

Table 4. Solar Load Center and Total Inverter Output OCPD and Conductor Size**

Circuit Current (Amps) OCPD (Amps) Minimum Conductor Size (AWG)

Minimum Metal Conduit Size

24 5760 30 10 ½”

28 6720 35 8 ¾”

32 7680 40 8 ¾”

36 8640 45 8 ¾”

40 9600 50 8 ¾”

41.6 ≤ 10000 60 6 ¾”

**CEC 690.8 and 210.19 (A)(1) factored in Table 4, conductors are copper, insulation must be 90° C wet-rated. Table 4 values are based on maximum ambient temperature of 47° C (no rooftop temperature adder in this calculation), ≤ 3 current carrying conductors in a circular raceway. Otherwise use Comprehensive Standard Plan.

6. Point of Connection to Utility:

6.1 Load Side Connection only! Otherwise use the Comprehensive Standard Plan.

6.2 Is the PV OCPD positioned at the opposite end from input feeder location or main OCPD location? Yes No (If No, then use 100% row in Table 5)

6.3 Per 705.12(D)(2): (Combined inverter output OCPD size + Main OCPD size) ≤ [bus bar size × (100% or 120%)]

Table 5. Maximum Combined Inverter Output CIrcuit OCPD

Bus Bar Size (Amps) 100 125 125 200 200 200 225 225 225

Main OCPD (Amps) 100 100 125 150 175 200 175 200 225

Maximum Combined Inverter OCPD with 120% of bus bar rating (Amps)

20 50 25 60† 60† 40 60† 60† 45

Maximum Combined Inverter OCPD with 100% of bus bar rating (Amps)

0 25 0 50 25 0 50 25 0

†This plan limits the maximum system size to less than 10 kW, therefore the OCPD size is limited to 60 A. Reduction of Main Breaker is not permitted with this plan.

WEST HOLLYWOOD 8300 Santa Monica Boulevard West Hollywood, CA 90069-6216

Solar PV Standard Electrical Plan: Microinverter & AMC Page 3 of 6

Building & Safety Division tel 323 848.6475 fax 323.848.6569

Solar PV Standard Electrical Plan: M

icroinverter & A

MC

Systems

SOLAR PV STANDARD ELECTRICAL PLANS: MICROINVERTER & AMC SYSTEMS

WES

TH

OLL

YWO

OD

Bui

ldin

g &

Saf

ety

Div

isio

n83

00 S

anta

Mon

ica

Bou

leva

rd W

est H

olly

woo

d, C

A 90

069-

6216

tel 3

23.8

48.6

475

fax

323.

848.

6569

Sola

r PV

Stan

dard

Pla

n:C

entr

al/S

trin

g In

vert

er

Pag

e 5

of 6

7. Grounding and Bonding

Check one of the boxes for whether system is grounded or ungrounded: Grounded Ungrounded

For Microinverters with a grounded DC input, systems must follow the requirements of GEC (CEC 690.47) and EGC (CEC 690.43).

For ACM systems and Microinverters with ungrounded a DC input follow the EGC requirements of (CEC 690.43).

8. Markings

Informational note: ANSI Z535.4 provides guidelines for the design of safety signs and labels for application to products. A phenolic plaque with contrasting colors between the text and background would meet the intent of the code for permanency. No type size is specified, but 20 point (3/8”) should be considered the minimum.

M

NOTE: CEC 705.10 requires a permanent plaque or directory denoting all electric power sources on or in the premesis.

CEC 690.54

CEC 690.54 & CEC 705.12(D)(4)

WARNINGDUAL POWER SOURCES

SECOND SOURCE IS PHOTOVOLTAIC SYSTEMRATED AC OUTPUT CURRENT ______ AMPS ACNORMAL OPERATING VOLTAGE ______ VOLTS

WARNINGINVERTER OUTPUT CONNECTION

DO NOT RELOCATE THISOVERCURRENT DEVICE

AC

DC

PV

AC

DC

PV

AC

DC

PV

AC

DC

PV

Optional AC Disconnect per AHJ PV SYSTEM AC DISCONNECTSECOND SOURCE IS PHOTOVOLTAIC SYSTEMRATED AC OUTPUT CURRENT ______ AMPS ACNORMAL OPERATING VOLTAGE ______ VOLTS

Optional Solar Load Center

AC

DC

PV

AC

DC

PV

AC

DC

PV

AC

DC

PV

AC

...

CEC 705.12 (D)(7)

WEST HOLLYWOOD 8300 Santa Monica Boulevard West Hollywood, CA 90069-6216

Solar PV Standard Electrical Plan: Microinverter & AMC Page 4 of 6

Building & Safety Division tel 323 848.6475 fax 323.848.6569

Solar PV Standard Electrical Plan: M

icroinverter & A

MC

Systems

SOLAR PV STANDARD ELECTRICAL PLANS: MICROINVERTER & AMC SYSTEMS

Sola

r PV

Stan

dard

Pla

n —

Sim

pli�

edCe

ntra

l/Str

ing

Inve

rter

Sys

tem

s fo

r One

- and

Tw

o-Fa

mily

Dw

ellin

gs

9.Si

ngle

-Inve

rter

Lin

e D

iagr

am

PV

DC

-> A

C

PV

DC

-> A

C

PV

DC

-> A

C

Sol

ar P

V M

odul

e or

AC

M:

DE

SC

RIP

TIO

N: (

Pro

vide

mod

el #

if p

rovi

ded)

Mic

roin

verte

r (if

not A

CM

):Ju

nctio

n B

ox (e

s):

Sol

ar L

oad

Cen

ter,

Yes

/ N

o:P

erfo

rman

ce M

eter

Yes

/ N

o:*U

tility

Ext

erna

l Dis

conn

ect S

witc

h Y

es /

No:

TAG

1 2 3 4 5 6

1

Sing

le-L

ine

Dia

gram

for M

icro

inve

rter

s or

AC

Ms

A

B

GM

M

45

67

2

Mai

n O

CP

D s

ize:

(tab

le 5

) ___

____

____

____

____

____

_ C

ombi

ned

Inve

rter O

utpu

t OC

PD

: (Ta

ble

4)__

____

____

_ M

ain

Ser

vice

Pan

el B

usba

r: (T

able

5) _

____

____

____

__

Equi

pmen

t Sch

edul

e

Bra

nch

Circ

uit O

CPD

s (T

able

3)

Mai

n Se

rvic

e Pa

nel O

CPD

sD

C G

EC

,W

hen

Req

uire

d

3

Bra

nch

1 O

CP

D s

ize

____

__B

ranc

h 2

OC

PD

siz

e __

____

Bra

nch

3 O

CP

D s

ize

____

__S

olar

Loa

d C

ente

r B

usba

r(S

ectio

n 5)

___

____

_

Che

ck a

box

for d

c sy

stem

gro

undi

ng: □

Gro

unde

d, □

Ung

roun

ded

For u

ngro

unde

d dc

pow

er s

yste

ms,

EG

C is

requ

ired

For g

roun

ded

dc p

ower

sys

tem

s, G

EC

& E

GC

are

requ

ired

Ref

er to

CE

C 2

50.1

20 fo

r EG

C in

stal

latio

n &

Tab

le 2

50.1

22 fo

r siz

ing

Des

crip

tion

and

Con

duct

or T

ype:

(Tab

le 3

)

Cur

rent

-Car

ryin

g C

ondu

ctor

s: (f

or e

ach

bran

ch c

ircui

t)

TAG

A

Con

duct

orS

ize

Con

duit/

Con

duct

or/

Cab

le T

ype

Con

duit

Siz

e

EG

C:

Con

duct

or, C

able

and

Con

duit

Sche

dule

mm

b

GE

C (w

hen

requ

ired)

:C

urre

nt-C

arry

ing

Con

duct

ors:

BE

GC

:G

EC

(whe

n re

quire

d):

Num

ber o

f C

ondu

ctor

s

* C

onsu

lt w

ith y

our l

ocal

AH

J an

d /o

r Util

ity7

Mai

n E

lect

rical

Ser

vice

Pan

el

9.Si

ngle

-Inve

rter

Lin

e Di

agra

m

WES

TH

OLL

YWO

OD

Bui

ldin

g &

Saf

ety

Div

isio

n83

00 S

anta

Mon

ica

Bou

leva

rd W

est H

olly

woo

d, C

A 90

069-

6216

tel 3

23.8

48.6

475

fax

323.

848.

6569

Sola

r PV

Stan

dard

Ele

ctric

al P

lan:

C

entr

al/S

trin

g In

vert

er

Pag

e 5

of 6

SOLA

R P

V ST

AN

DA

RD

PLA

N —

SIM

PLIF

IED

Mic

roin

vert

er a

nd A

CM

Sys

tem

s fo

r One

- and

Tw

o-Fa

mily

Dw

ellin

gs

PLO

T PL

AN

AN

D R

OO

F LA

YOU

T PL

AN

Item

s re

quire

d: P

rope

rty

line

loca

tions

, dim

ensi

ons

from

ex

terio

r wal

ls to

pro

pert

y lin

es, r

oof l

ayou

t of a

ll pa

nels

, m

odul

es, c

lear

acc

ess

path

way

s an

d ap

prox

imat

e lo

catio

ns o

f el

ectr

ical

dis

conn

ectin

g m

eans

and

roof

acc

ess

poin

ts.

Sola

r PV

Stan

dard

Ele

ctric

al P

lan:

C

entr

al/S

trin

g In

vert

er

Pag

e 6

of 6