® Job Name: Job Number: Model Numbers: Page SPECIFICATION SUBMITTAL 369369 Rev. B 1 06.02.11 Control Interfaces OMX-CI-NWK-E GRAFIK SystemsTM OMX-CI-NWK-E Control Interface Description • Integrates GRAFIK 5000TM, GRAFIK 6000®, GRAFIK 7000TM, Softswitch128®, and LCP128® systems with a touchscreen or other digital equipment that supports TCP/IP communication over Ethernet. • Provides monitoring commands that allow a touchscreen to query lighting systems to: – Determine which scene is selected. – Keep track of buttons pressed. • Provides control commands that allow a touchscreen or PC to operate lighting systems to: – Select or sequence lighting scenes. – Raise or Lower one or more zones. – Activate panic mode (lights go to full on). – Simulate button actions – Disable or Enable timeclock(s)

Upload: phungquynh

Post on 27-Jul-2018

220 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: OMX-CI-NWK-E Control Interface - Lutron Electronics Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page 369369 Rev. B 1 06.02.11 GRAFIK Systems TM OMX-CI-NWK-E Control Interfaces

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369369 Rev. B 1 06.02.11

Control InterfacesOMX-CI-NWK-EGRAFIK SystemsTM

OMX-CI-NWK-E Control Interface

Description

•IntegratesGRAFIK5000TM, GRAFIK 6000®, GRAFIK 7000TM, Softswitch128®, and LCP128® systems with a touchscreen or other digital equipment that supports TCP/IP communication over Ethernet.

•Providesmonitoringcommandsthatallowatouchscreen to query lighting systems to: – Determine which scene is selected. – Keep track of buttons pressed.

•Providescontrolcommandsthatallowa touchscreen or PC to operate lighting systems to: – Select or sequence lighting scenes. – Raise or Lower one or more zones. – Activate panic mode (lights go to full on).

– Simulate button actions – Disable or Enable timeclock(s)

Page 2: OMX-CI-NWK-E Control Interface - Lutron Electronics Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page 369369 Rev. B 1 06.02.11 GRAFIK Systems TM OMX-CI-NWK-E Control Interfaces

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369369 Rev. B 2 06.02.11

Control InterfacesOMX-CI-NWK-EGRAFIK SystemsTM

Power

•IECPELV/NEC® Class 2•OperatingVoltage:12V 125mA

24V 65mA

Uses OMX RS232 Command Set

•Monitoring:Sceneselectionandscenestatusupdates.•Control:Sceneselection,scenelockout,sequencing,zonelockout,zoneraise/lower.

System Communications and Capacity

•IECPELV/NEC® Class 2 wiring connects OMX-CI-NWK-E Interface to Processor Panel.•StandardCAT5cable,328ft(100m)maximum,connectsOMX-CI-NWK-EInterfacetoPCorother

Ethernet source.•SupportsMDI/MDIXauto-crossover(nocrossovercableneeded).•MultipleControlInterfacesmaybeusedinasinglesystem.

Environment

32 to 104 °F (0 to 40 °C). Relative humidity less than 90% non-condensing.

Specifications

Dip Switch Settings

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

ON

ON

ON

ON

1 2 3 4 5 6ON

7 8

1 2 3 4 5 6ON

7 8

AddressSwitch Settings

AddressSwitch Settings

AddressSwitch Settings

AddressSwitch Settings

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

1 2 3 4 5 6

ON

7 8

ON

ON

ON

ON

1 2 3 4 5 6ON

7 8

1 2 3 4 5 6ON

7 8

Up Down(On) (Off)

Addressing

Not used

Page 3: OMX-CI-NWK-E Control Interface - Lutron Electronics Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page 369369 Rev. B 1 06.02.11 GRAFIK Systems TM OMX-CI-NWK-E Control Interfaces

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369369 Rev. B 3 06.02.11

Control InterfacesOMX-CI-NWK-EGRAFIK SystemsTM

Dimensions 2.47 in(62.7 mm)

3.75in(95.3mm)

4.26 in(108.2 mm)

5.26in(133.6 mm)

1.06 in(26.9 mm)

Mounting Holes

Mounting

1. Mount the control interface directly on a wall, as shown in the Mounting Diagram, using screws (not included). When mounting, provide sufficient space for connecting cables.

The unit can also be placed in the LUT-19AV-1U AV rack using the screws provided with the unit. The LUT-19AV-1U will hold up to four units.

If conduit is desired for wiring, the LUT-5x10-ENC can be used to mount one unit.

2. Strip 4 in (10 mm) of insulation from wires. Each data link terminal will accept up to two 18 AWG (1.0 mm2) wires.

3. Connect wiring as shown in the Wiring Diagram (next page). LED 1 lights continuously (Power) and LED 7 blinks rapidly (Data Link RX) when the IEC PELV/NEC® Class 2 Data Link is installed correctly.

LUT-19AV-1U

Wire Strip Length

4 in (10 mm)

5.26

4.263.75

2.50

1.06

Control Interface

Wall

Mounting Diagram

LUT-5x10-ENC

0.25 (6.4)

0.34 (8.6) dia.

0.18 (4.6) dia.

0.18 (4.6) dia.

#6 or #8 (M3 or M4) screw recommended (not included)

Mounting Hole DetailDimensions: in (mm)

Page 4: OMX-CI-NWK-E Control Interface - Lutron Electronics Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page 369369 Rev. B 1 06.02.11 GRAFIK Systems TM OMX-CI-NWK-E Control Interfaces

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369369 Rev. B 4 06.02.11

Control InterfacesOMX-CI-NWK-EGRAFIK SystemsTM

Ethernet Link Wiring

•StandardCAT5cableconnectsOMX-CI-NWK-EInterfacetoPC,router,orotherEthernet source.

•Nocrossovercableneeded.•Mustbe328ft(100m)orless.•Ethernetnetworkandcableprovidedbyothers.

RJ45 jack: Ethernet Link (to PC or A/V equipment)

Ethernet link/ activity

Ethernet speed

Data Link (to Control Units, processors, and wallstations)

DIP Switches LED 1: PowerLED 2: Ethernet linkLED 3, 4, 5: UnusedLED 6: Data link TXLED 7: Data link RX

CAT5 Cable: maximum 328 ft

(100 m) To PC or AV Equipment. For Ethernet Link, use CAT5 cable provided to connect to auxiliary equipment. The Ethernet Link LED will light continuously when link is present and will flash when there is link activity. Additional Ethernet network equipment and cables provided by others.

12 or 24 V to outlet (with optional transformer). Do not wire terminal 2 on Data Link when using optional transformer. To power separately from the Data Link, order the following Lutron transformer model numbers: 120 V : T120-15DC-9-BL 240 V : TE240-15DC-9-BL 240 V (UK): TU240-15DC-9-BL

1 2 3 4 5 6 7

•Daisy-chaintheOMX-CI-NWK-EInterfacetotheIECPELV/NEC® Class 2 Wallstation Link that connects to the Processor Panel.

•Makedaisy-chainconnectionstotheIECPELV/NEC® Class 2 Data Link terminals on the front of OMX-CI-NWK-E Interface.

•DonotuseT-taps.Runallwiresinandoutofterminalblock.•Eachterminalacceptsuptotwo18AWG(1.0mm2) wires.•LED1lightswhentheIECPELV/NEC® Class 2 Data link is installed correctly.•ConsultProcessorPanelSpecificationSubmittalformoredetails.

IEC PELV/NEC® Class 2 Wiring

Page 5: OMX-CI-NWK-E Control Interface - Lutron Electronics Name: Job Number: Model Numbers: SPECIFICATION SUBMITTAL Page 369369 Rev. B 1 06.02.11 GRAFIK Systems TM OMX-CI-NWK-E Control Interfaces

®

Job Name:

Job Number:

Model Numbers:

PageSPECIFICATION SUBMITTAL

369369Rev.B506.02.11

Control InterfacesOMX-CI-NWK-EGRAFIK SystemsTM

•Two12AWG(2.5mm2)conductorsforcommon(terminal1)and24V (terminal 2). These will not fit in terminals. Connect as shown. Ensure that the terminal 2 connection is wired when not using optional transformer.

•Oneshielded,twistedpair18AWG(1.0mm2) for data link (terminals 3 and 4). •ConnectDrain/Shieldasshown.DonotconnecttoGround(Earth)orWallstation/Control

Interfaces. Connect the bare drain wires and cut off the outside shield.

IEC PELV/NEC® Class 2 Terminal Connections

4 3 2 1

IEC PELV/NEC® Class 2Power wiring:1: Common2: 24 V Power(2) 18 AWG (1.0 mm2) pigtails, 6 in (152 mm) maximum length

D: Drain/Shield

(2) 12 AWG (2.5 mm2)

(2) 12 AWG (2.5 mm2)

Data Link: (1) shielded, twisted pair 18 AWG (1.0 mm2)

4: MUX3: MUX

Note: 12 AWG (2.5 mm2) conductors for Common (terminal 1) and 24 V Power (terminal 2) will not fit in terminals; use 18 AWG (1.0 mm2) pigtails (< 6 in/152 mm).

Note: Do not connect Drain/Shield to Ground (Earth) or Wallstation/Control Interfaces. Connect the bare drain wires and cut off the outside shield.

Use Lutron Cable GRX-CBL-46L