© Electrical Safety Authority 2011 E-Tech marketing Forum Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1

Upload: truongthuy

Post on 07-Feb-2018

234 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Ontario Electrical Safety Code 25th Edition/ 2012

Ted Olechna

Director, Codes and Standard

Chief Engineer

1

Page 2: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

What I Will Cover

• ESA’s role is as the regulator

• Highlight of 2012 Code changes

• The Code and new Green technology

• Ontario differences

2

Page 3: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

For Your Safety

Electrical Safety Authority Bill 35, the Electricity Act, 1998

Section 113 (1) The Electrical Safety Authority, subject to the approval of the Lieutenant Governor in Council, may make regulations,

- prescribing the design, construction, installation, protection, use, maintenance, repair, extension, alteration, connection and disconnection of all works and matters used or to be used in the generation, transmission, distribution, retail or use of Electricity in Ontario;

Page 4: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

For Your Safety

Electrical Safety Authority

Mission and Vision

• Our Mission: To Improve electrical safety for the well

being of the people of Ontario.

• Long Term Vision: An Ontario free of electrical fatalities and

serious injury, damage or loss.

Page 5: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

For Your Safety

Regulations

• OESC is mandatory • The OESC is passed into law by

the Provincial Government

• Utility Regulations 2004

• Contractor Licensing 2005

• Product Safety 2007

Page 6: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Page 7: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

OESC 2012 Major changes

7

CEC CODE changes

273 proposals were submitted to the CSA

• 175 proposals

• 10 new interpretations

are approved and in the new edition

Ontario amendments

• 11* Ontario amendments are changed; plus

• Rule 2-005, An application for inspection not required is amended (to be finalized in Fall 2011)

Page 8: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Basic Exemption - proposed

The following are the changes under consideration:

• Modify the existing Rule to include owner occupied dwelling unit when the work is performed by a licensed electrical contractor;

• New amendment to allow unit owners to replace certain light fixtures & switches within an Owner-Occupied Single Dwelling;

• New amendment to permit wiring from approved class 2 extra low voltage power supply within an Owner-Occupied Dwelling Unit;

• New amendment to allow the replacement or connection of specific listed appliances by specific trades, in accordance to their designation, within an owner-occupied dwelling; and

• New amendment to allow the repair of utilization equipment by specific trades, in accordance to their designation, within an owner-occupied dwelling.

8

Page 9: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

OESC 2012 Major changes

9

General

• Cable Ampacity – Tables 1 to 4

• Temperature Limitations

• Overcurrent protection for No. 14, 12 and 10AWG conductors

• Grounding conductor size for AC systems

• Cablebus installation

• Tamper resistant receptacles

• Receptacle(s) on a roof top for equipment maintenance

• Receptacles exposed to the weather

Page 10: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

OESC 2012 Major changes

10

Green Energy Installations

• Renewable energy systems – New Section 64

• Solar photovoltaic systems – Section 50 changes

• Electric vehicle charging infrastructure

Page 11: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Electric Vehicle Charging

Systems Code Sections 2,8,26 and 86

11

Page 12: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Ontario Amendment Appendix B note to Rule 2-000(h)

• New Appendix B note to Rule 2-000(h)

For electrical vehicles;

This Code applies to electrical vehicle supply equipment and requires it to be approved and installed in accordance with applicable Code requirements.

This Code does not apply to the inlet or on-board charging equipment as defined by Rule 86-100 that does not provide bi-directional power feed, as specified by Rule 86-308.

12

Page 13: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Demand factors for EV equipment Rule 8-200(1)(a) and (3)

When determining the minimum ampacity of service or feeders conductors supplying:

• a single dwelling, any electric vehicle charging equipment loads shall be considered with a demand factor of 100%. – New Rule 8-200(1)(a)(vi)

• in apartment and similar building shall be added with a demand factor of 100% – New Rule 8-202(3)(d)

• As required by the Building Code

• The electric vehicle charging equipment loads shall not exceed 80% of the rating of the overcurrent device, Rule 8-104(5).

13

Page 14: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

A typical single family dwelling with 2000 ft² (186 m²) of living area:

14

Demand factors for EV equipment Rule 8-200(1)(a) and (3) Demand factors in a single dwelling

Page 15: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Electric vehicle systems Rule 86-306 Receptacles for charging equipment

• Amended Rule 86-306(1)(a)

(1) Each receptacle for the purpose of electric vehicle charging shall be labeled in a conspicuous, legible, and permanent manner identifying it as an electric vehicle charging receptacle and shall be

(a) a single receptacle of CSA configuration 5-20R supplied from a 125 V branch circuit rated not less than 20 A; or

(b) of the appropriate CSA configuration in accordance with Diagram 1 or 2 when supplied from a branch circuit rated at more than 125V or more than 20 A.

15

Page 16: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Electric vehicle systems Rule 86-400(3) EV charging sites in commercial garages

• New Rule 86-400(3) (similar to new Rule 86-308(4))

Charging equipment installed in commercial garages or on premises of flammable liquid and gas dispensing and service facilities described in Section 20 shall comply with Rule 20-114 and shall not be located in the hazardous area as described in Rule 20-102.

16

Page 17: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Electric vehicle systems Rule 86-404 Height of vehicle charging equipment

• New Rule 86-404

The height of the electric vehicle charging equipment shall be located at a height of not less than 450mm and not more than 1.2m above the floor level.

17

Page 18: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Solar Photovoltaic installations Section 50

18

Page 19: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Agenda

• Changes/additions to existing Rules

– Marking

– PV source and output circuit voltage

– PV circuit current rating

– Overcurrent protection

– Wiring methods

– Attachment plug

19

Page 20: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Agenda

• New Rules and requirements:

– Voltage drop

– AFCI protection for DC circuits

– Grounding

– Inverter

20

Page 21: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Rule 50-014

Photovoltaic dc arc-fault circuit protection

It is the direction in Ontario that DC AFCI will not be required until May 1st, 2013

21

Page 22: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Rule 50-018 – Wiring methods (Amended)

Newly developed Solar cables type RPV & RPVU – in Part II Standard

A new standard CSA C22.2 No. 271 (published May 2011), Photovoltaic Cables specifies the requirements for photovoltaic single-conductor and multi-conductor thermoset-insulated wires and cables rated 600 V, 1000 V and 2000 V.

The standard applies to conductors installed between

22

solar panels and from solar panels to the inverter or combiner box or from combiner box to inverter.

Page 23: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

New cables type RPV and RPVU are also recognized in Tables 6, 10B and 19

23

Rule 50-018 – Wiring methods (Amended)

Newly developed Solar cables type RPV & RPVU – Part I Standard tables

Page 24: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Rule 50-020 – Attachment Plugs (Amended)

• Used to be 50-016, renumbered to fit.

• New Subrule (2) added to require the attachment plugs to be of a type that requires the use of a tool to open, when:

• Readily accessible; and

• Used in circuits operating at over 30V

24

Page 25: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Only inverters and AC modules approved and identified as interactive shall be permitted in interactive systems.

25

Rule 50-028 – Power Conditioning Unit (New rule) – Utility Interactive systems, Inverters approved for the purpose

This is existing direction in Ontario as per current Bulletin 84-1-*

64-108 Connection to other sources

Page 26: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

64-112 Unbalanced interconnection

1) Single-phase inverters and AC modules in interactive renewable energy systems shall not be connected to 3-phase systems, unless the interconnected system:

26

a) Is designed to provide balanced 3-phase output;

b) Complies with Rules 84-008 and 84-018; and

c) Complies with the supply authority requirements

Rule 50-028 – Power Conditioning Unit (New rule) – Multiple 1-phase inverters form 3-phase interactive system

This is existing direction in Ontario as per current Bulletin 84-1-*

Page 27: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Renewable energy systems Code Sections 64

Page 28: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Special terminology

Rule 64-002

• Renewable Energy.

• energy derived from resources that are naturally replenished, such as sunlight, wind, water, tides, and geothermal heat.

Page 29: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Special terminology. Rule 64-002

Renewable Energy System

• a complete system enabling a renewable energy source to be connected to a utilization load.

Page 30: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Small wind systems Rule 64-002 Special Terminology

• Small wind system. A system consisting of one or more wind turbines with a rated output up to and including 100 kW.

Page 31: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Large wind systems Rule 64-002 Special

Terminology

• a system consisting of one or more wind turbines with rated power output exceeding 100 KW rated power output.

Page 32: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Stationary Fuel Cell

Page 33: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

MICRO-HYDROPOWER SYSTEMS

33

Page 34: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Hydrokinetic system • a system operating as an interconnected or stand-alone

system and consisting of one or more hydrokinetic turbines that convert the kinetic energy of flowing water into electrical energy with a rated output of up to and including100 kW.

Page 35: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

STORAGE BATTERIES RULE 64-700 – 64-714

35

Page 36: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

General

Rule 64-010 Overcurrent protection

• Where a circuit breaker is backfed (“LOAD” to “LINE” rather than “LINE” to “LOAD”) it shall be approved for the purpose.

• Circuit breakers labelled “LINE” and “LOAD” are not approved to be backfed.

Page 37: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

General

Page 38: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

General Rule 64-028 Interconnections to other circuits Where the renewable energy system is not intended to be interconnected with the supply authority the system shall be designed so that it is impossible to have both systems connected at the same time.

Page 39: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

General Rule 64-030 Interconnected system connections (1) The output from a utility-interactive inverter or power

conditioner shall be connected to the line side of the service disconnecting means in accordance with Section 84, except as permitted in Subrule (3).

Page 40: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

General Rule 64-030 Interconnected system

connections Cont’d

Page 41: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

General

Rule 64-034 Systems in access of 750 V dc Where the maximum system voltage of a renewable energy source exceeds 750 V dc it shall comply with the requirements of Section 36 and any other requirements applicable to these installations.

Page 42: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Other Code changes

42

Page 43: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Receptacles “General”

26-700 Tamper resistant requirements

New Subrule 26-700 (12)

Tamper resistant receptacles now required in “child care facilities”

Page 44: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Rule 26-702 is amended to require 15A and 20A (125V and 240V) receptacles exposed to weather to be provided with cover plates suitable for “wet locations” that will provide shielding with and without a plug inserted into the receptacle.

Receptacles “General”

26-702 Receptacles exposed to weather

Page 45: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Rule 26-702 (1) & (2)

Receptacles “General”

26-702 Receptacles exposed to weather

As per Rule 26-702(2) Requires to be marked “WET Locations” whether or not a plug is inserted into it.

As per Rule 26-702(1) Requires to be marked “Wet Location Only When Cover Closed”

Page 46: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Installation of lighting equipment

30-308 Circuit connections Amended Subrule 30-308(4)

Fluorescent luminaire disconnect means.

(4) The connection of branch circuit conductors exceeding 150 volts-to-ground to the conductors of each fluorescent luminaire utilizing double-ended lamps shall be made by one of the following ways;

Page 47: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Administrative Rule 2-022(3) Approval of LED luminaires

• New Rule 2-022(3)(c)(ii)

Luminaires with LED lamps supplied from a class 2 powers supply are required to be approved.

47

Page 48: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Administrative Rule 2-022 Approval of LED luminaries

• New Appendix B note to Rule 2-022(3)(c)

Decorative light strings, signs or displays with LED lamps other than LED luminaries that are connected to approved class 2 power supplies are not required to be approved.

48

Page 49: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

Wiring methods Rule 32-102(1) Use of rigid non-metallic conduit in fire alarm systems

• Amended Rule 32-102(1)

Conductors of a fire alarm systems are now permitted to be installed in rigid non-metallic conduit without being embedded in 50mm of masonry (as per current ESA Bulletin 32-3-*)

49

Page 50: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

• Amended Rule 46-108(1)

Conductors described in Rule 46-108 (Life Safety, Emergency etc.) are now permitted to be installed in rigid non-metallic conduit without being embedded in 50mm of masonry (as per current ESA Bulletin 46-4-*).

50

Wiring methods Rule 46-108(1) Use of rigid non-metallic conduit in life safety systems

Page 51: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

New Cable types in Tables 11, 12 and 19 Table 19, Armoured cable types ACG & ACGWU

• ACG90— a 14 AWG to 6 AWG multi-conductor aluminum interlocked armoured cable with aluminum bonding conductor in intimate contact with armour designed for applications permitting the use of the armour as a means of equipment bonding.

• ACGWU90 — Same construction as the ACG90 with the addition of the overall jacket.

Page 52: Ontario Electrical Safety Code - · PDF fileOntario Electrical Safety Code 25th Edition/ 2012 Ted Olechna Director, Codes and Standard ... protection, use, maintenance, repair, extension,

© Electrical Safety Authority 2011 E-Tech marketing Forum

New Cable types in Tables 11, 12 and 19 Table 19, Cable Type ACG & ACGWU

The construction of ACG & ACGWU cables incorporates a full size aluminum bond conductor in direct intimate contact with the interlocked armour.