781-541-5060 www.pacerepresentatives.com Reference wall Basis of Design Package. Registered design professional in responsible charge to review prior to use. Page 1 of 1 Rev: 2015-12-31 Opaque Envelope Basis of Design Rainscreen Cladding w/ Dow THERMAX Wall System Rainscreen Cladding with Dow THERMAX Wall System and Metal Stud Backup Item Component Thickness Manufacturer Product 1 Interior Finish (vapor permeable) 0” - - 2 Interior Gypsum Board 5/8” - Type X 3 Metal Stud (18 GA. Min. @16” O.C.) 6” - - 3A 1 Stud Cavity Insulation (Optional) 2” Dow Styrofoam SPF CM-2045 4 1 Continuous Insulation 2” Dow Thermax XArmor 5 Flashing 60mils Dow LiquidArmor CM 6 Cladding Attachment System 1 1/2” Knight Wall CI System 7 1 Rainscreen Cladding - - NFPA 285 Compliant Total -” 1 Product recommendations are based on Type I-IV construction requiring NFPA 285 assembly acceptance criteria compliance per IBC 2015 Sections 1403.5 & 2603.5.5. Assembly Performance: (proposed assembly U-Factors are approximately 2%|25% better than code and have 91%|80% thermal effectiveness) Code Requirement (IECC 2015 – Metal Framed) Project Requirement (if different) Proposed Design R-Value: a R-13 + R-7.5ci N/A R-13ci | R-12.8 + R-13ci Total R-Value: N/A N/A R-17.09 | R-29.86 Effective R-Value: c N/A N/A R-15.56 | R-23.88 Design U-Factor: a, b U-0.064 N/A U-0.063 | U-0.048 Effective U-Factor: c N/A N/A U-0.064 | U-0.042 Assembly Air Permeability 0.04 cfm/ft 2 @75Pa N/A 0.01 cfm/ft 2 @75Pa a Wall assembly meets energy code and project thermal requirements without stud cavity insulation. b Assembly U-Factor is based on the stud size & spacing noted above and is calculated per IECC 2015 & ASHRAE 90.1-2013 Appendix A. c Effective assembly thermal performance is based on stud size & spacing above, manufacturer literature and industry studies on the thermal performance of façades. Attachments: Typical Clear Wall Detail Assembly Dew Point Calculation(s) Product Literature

Upload: phamanh

Post on 22-Apr-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

!

781-541-5060 www.pacerepresentatives.com Reference wall Basis of Design Package. Registered design professional in responsible charge to review prior to use.

Page 1 of 1 Rev: 2015-12-31

!

Opaque Envelope Basis of Design Rainscreen Cladding w/ Dow THERMAX Wall System

Rainscreen Cladding with Dow THERMAX Wall System and Metal Stud Backup

Item Component Thickness Manufacturer Product 1 Interior Finish (vapor permeable) 0” - -!2 Interior Gypsum Board 5/8” - Type X 3 Metal Stud (18 GA. Min. @16” O.C.) 6” - -!

3A1 Stud Cavity Insulation (Optional) 2” Dow Styrofoam SPF CM-2045

41 Continuous Insulation 2” Dow Thermax XArmor 5 Flashing 60mils Dow LiquidArmor CM 6 Cladding Attachment System 1 1/2” Knight Wall CI System 71 Rainscreen Cladding - - NFPA 285

Compliant Total -”

1 Product recommendations are based on Type I-IV construction requiring NFPA 285 assembly acceptance criteria compliance per IBC 2015 Sections 1403.5 & 2603.5.5.

Assembly Performance: (proposed assembly U-Factors are approximately 2%|25% better than code and have 91%|80% thermal effectiveness)

Code Requirement (IECC 2015 – Metal Framed)

Project Requirement (if different) Proposed

Design R-Value: a R-13 + R-7.5ci N/A R-13ci | R-12.8 + R-13ci Total R-Value: N/A N/A R-17.09 | R-29.86 Effective R-Value: c N/A N/A R-15.56 | R-23.88 Design U-Factor: a, b U-0.064 N/A! U-0.063 | U-0.048 Effective U-Factor: c N/A N/A! U-0.064 | U-0.042 Assembly Air Permeability 0.04 cfm/ft2 @75Pa N/A! 0.01 cfm/ft2 @75Pa a Wall assembly meets energy code and project thermal requirements without stud cavity insulation. b Assembly U-Factor is based on the stud size & spacing noted above and is calculated per IECC 2015 & ASHRAE 90.1-2013 Appendix A. c Effective assembly thermal performance is based on stud size & spacing above, manufacturer literature and industry studies on the thermal performance of façades.

Attachments: • Typical Clear Wall Detail • Assembly Dew Point Calculation(s) • Product Literature

Page 2: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible
Page 3: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible
Page 4: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible
Page 5: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

THERMAX™ Wall System Overview

Dow Building Solutions

The THERMAX™ Wall System is more than an insulated wall – it’s a systematic approach to achieving efficiency at every level: simplified design, streamlined construction and optimized energy consumption for a reduced carbon footprint. Dow’s four-in-one system with THERMAX XARMOR™ (ci) Exterior Insulation, LIQUIDARMOR™ - CM Fluid Applied Flashing and STYROFOAM™ CM Series Spray Polyurethane Foam, meets all applicable IBC and ASHRAE requirements for continuous insulation, moisture mitigation, air sealing, and vapor barriers. This complete system eliminates the need for exterior gypsum sheathing, applied air/vapor barrier membranes, and extensive site coordination, making it both cost effective and easy to install.

Steel transfers heat amazingly fast – up to 300 times faster than wood studs and reduces the effective R-value of metal stud wall designs by 40–60%. The ASHRAE prescriptive continuous insulation requirements for steel-framed, above-grade walls recognize this phenomenon, and in most climate zones, call for

See more case studies, details, and information at www.thermaxwallsystem.com

LIQUIDARMOR™- CMFluid Applied Flashing

Type I, Class 2, FiberReinforced Foam Core

THERMAX XARMOR™

Continuous Insulation

Ship-lapped Edge

4 mil Acrylic AluminumExterior Facer

1 mil Aluminum Interior Facer

Metal Stud Framing

STYROFOAM™ - CMSpray Polyurethane Foam

Page 6: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

NOTICE: No freedom from infringement of any patent owned by Dow or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other government enactments. The product shown in this literature may not be available for sale and/or available in all geographies where Dow is represented. The claims made may not have been approved for use in all countries. Dow assumes no obligation or liability for the information in this document. References to “Dow” or the “Company” mean the Dow legal entity selling the products to Customer unless otherwise expressly noted. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.

THERMAX™ products should be used only in strict accordance with product application instructions. THERMAX™ products, when used in a building containing combustible materials, may contribute to the spread of fire.

LIQUIDARMOR™ - CM bridges up to 1/4” gaps without the need of mesh or a backer rod. Larger gaps may need the addition of common backer rods. Read all instructions and (Material) Safety Data Sheets carefully be-fore use. It is recommended that spray applicators and those working in the spray area wear eye protection. Contact with exposed skin may cause skin discoloration and dryness. Gloves are recommended for prolonged exposure. Ensure adequate ventilation during spray applications. LIQUIDARMOR™ - CM is a combustible material. Ensure product application complies with local building codes.

Dow Polyurethane Foam Insulation and SealantsCAUTION: When cured, these products are combustible and will burn if exposed to open flame or sparks from high-energy sources. Do not expose to temperatures above 240ºF (116ºC). For more information, consult (Material) Safety Data Sheet ((M)SDS) call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400 in the U.S. or 1-519-339-3711 in Canada. When air sealing buildings, ensure that combustion appliances, such as furnaces, water heaters, wood burning stoves, gas stoves and gas dryers are properly vented to the outside. See website: http://www.epa.gov/iaq/homes/hip-ventilation.html. In Canada visit: http://archive.nrc-cnrc.gc.ca/eng/ibp/irc/bsi/83-house-ventilation.html.

STYROFOAM™ Brand Spray Polyurethane Foam contains isocyanate, hydrofluorocarbon blowing agent and polyol. Read all the instructions and (M)SDS carefully before use. Wear protective clothing (including long sleeves), gloves, goggles and proper respiratory protection. Supplied air or an approved air-purifying respirator equipped with an organic vapor sorbent and a P100 particulate filter is required to maintain exposure levels below ACGIH, OSHA, WEEL or other applicable limits.

Provide adequate ventilation. Contents under pressure. STYROFOAM™ Brand SPF should be installed by a trained SPF applicator.

Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mold formation. No material supplier including Dow can give assurance that mold will not develop in any specific system.

STYROFOAM™ Brand Extruded Polystyrene Foam InsulationCAUTION: This product is combustible. Protect from high heat sources. A protective barrier or thermal barrier may be required as specified in the appropriate building code. For more information, consult MSDS, call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400 in the U.S. or 1-519-339-3711 in Canada.

For more information, consult (Material) Safety Data Sheet ((M)SDS) and/or call Dow at 1-866-583-BLUE (2583). In an emergency, call 1-989-636-4400.

WARNING: Rigid foam insulation does not constitute a working walkable surface or qualify as a fall protection product.

Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mold formation. No material supplier including Dow can give assurance that mold will not develop in any specific system.

®™Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow Printed in U.S.A. Form No. 179-00041-0815 CDP

Learn more about making history with THERMAX XARMOR™ (ci) Exterior Insulation at www.dowbuildingsolutions.com

The Dow Chemical CompanyDow Building Solutions200 LarkinMidland, MI 48674

Technical Information: 1-866-583-BLUE (2583)Sales Information: 1-800-232-2436

Back up Applications Steel Stud

NFPA-285 Approval Passed (See Hughes Report)

ASTM E84,(Burning Characteristics)

THERMAX XARMOR™ (ci): Flames Spread: 25, Smoke: <450STYROFOAM™ CM Series SPF: Class A

UL Ratings V482, V499, V454, U425, U424

Intertek Fire Rating Listing FI 60-02, FI 60-01, FI 120-01

Joint Treatments LIQUIDARMOR™ - CM Flashing and Sealant orWEATHERMATE™ Flashing

Edge Treatment Square edge (5/8” & 1”)Ship-lapped (1.55” or greater)

Facer Technology 4 mil BLUE™ acrylic-coated aluminum facer1.25 mil embossed aluminum backing

Warranty

LEED Points

EA Credit: 1–19 pointsMR Credit 2: 1–2 pointsMR Credit 3.1 & 3.2: 1–2 pointsMR Credit 4.1 & 4.2: 1–2 pointsMR Credit 5.1 & 5.2: 1–2 pointsEQ Credit 2: 1 pointEQ Credit 7.1: 1 pointID Credit 1.1: 1 pointID Credit 1.2: 1 pointID Credit 1.3: 1 point

Thermal Layer

ASTM C518, R-value THERMAX XARMOR™ (ci): 6.5 R /in

STYROFOAM™ SPF (CM Series) CM 2030: 6.0 R / in CM 2045: 6.4 R / in

Water-Resistive Layer

ASTM E331: Pass – No water penetration during 2 hours of pressurized testing.

ASTM C209 Water Absorption, % by volume, max

THERMAX XARMOR™ (ci): 0.1

ASTM 2842 Water Absorption, 5% max volume STYROFOAM™ SPF (CM Series): Pass

Air Sealing Layer

ASTM E2357: @ 5/8” thick THERMAX XARMOR™ (ci) with 1.5” of STYROFOAM™ SPF

Code: 0.04 cfm / ft2 Tested: 0.01 cfm / ft2 Improvement over code: 250%

Vapor Retarding Layer

ASTM E96, perms <0.1= Class 1 Retarder (Vapor Impermeable)

a layer of continuous insulation (ci) to be added to the assembly to help stop the steel thermal shorts that can decrease the energy efficiency of the wall system.

To meet the continuous insulation code it’s critical to also account for condensation within the wall assembly. Even if a wall is adequately designed to prevent liquid water from entering the assembly, condensation can still occur as a result of the interior and exterior temperatures as well as relative humidity.

There are 4 control layers that make up a high performance wall assembly. They are: thermal, water, air, & vapor control layers. The THERMAX™ Wall System is designed to incorporate all of these control layers while simplifying the installation process and providing high effective R-value; all of the necessary components of a high-performing wall system.

Page 7: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

1. PRODUCT NAME STYROFOAM™ Brand Spray Polyurethane Foam (SPF) Insulation (CM Series)

2. MANUFACTURER The Dow Chemical Company Dow Building Solutions 200 Larkin Center, 1605 Joseph Drive Midland, MI 48674 1-866-583-BLUE (2583) Fax 1-989-832-1465

dowbuildingsolutions.com

3. PRODUCT DESCRIPTION STYROFOAM™ Brand SPF Insulation (CM Series) is a professionally applied two-component, polyurethane foam that creates a seamless, monolithic barrier for protection against water vapor and air on the interior of steel stud walls. This closed-cell, 2-pcf spray foam successfully incorporates an advanced blowing agent with zero ozone depleting potential.

STYROFOAM™ Brand SPF Insulation (CM Series) is available in two formulas: CM 2030 30°F – 70°F Ambient Processing 30°F – 60°F Substrate Processing

CM 2045 45°F – 95°F Ambient Processing 45°F – 100°F Substrate Processing

BASIC USE STYROFOAM™ Brand SPF Insulation (CM Series) is designed as a water vapor and air barrier for the THERMAX™ Wall System., STYROFOAM™ Brand SPF Insulation (CM Series) expands during installation to fill cavities, cracks and penetrations, preventing uncontrolled air leakage in steel stud cavity walls. The spray foam also also provides insulation to a wall system.

STYROFOAM™ Brand Spray Polyurethane Foam Insulation (CM Series)

SIZES

STYROFOAM™ Brand SPF Insulation (CM Series) is sold in sets of 55 gallon drums (one A isocyanate and one B polyol blend). Contact your Dow sales representative with questions.

4. TECHNICAL DATA Applicable Standards

Applicable test methods include:• ASTM C1029 – Standard Specification for Spray-Applied Rigid Cellular Polyurethane Thermal Insulation• ASTM C518 – Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus• ASTM D1621 – Standard Test Method for Compressive Properties of Rigid Cellular Plastics

• ASTM D1622 – Standard Test Method for Apparent Density of Rigid Cellular Plastics• ASTM D6226 – Standard Test Method for Open Cell Content of Rigid Cellular Plastics

Code Compliances STYROFOAM™ Brand SPF Insulation (CM Series) complies with the following codes:

• ICC ESR-2670• INTERTEK, Classified Class A (ASTM E84)• Southwest Research Institute (SWRI), Classified Class A (ASTM E84)• ICC ES AC377 Appendix X modified NFPA 286: Being exposed in attics and ceilings• ASTM E2178 Standard Test Method for Air Permeance for Building Materials• IBC/IRC requirements for foam plastic insulation

(1) Not to be considered sales specifications. (2) R means resistance to heat flow. The higher the R-value the greater the insulating value. (3) Pass AC377.(4) Flammability values for this or any other material are not intended to represent hazards that may be present under actual fire conditions.

Table 1: Typical Physical Properties(1) of STYROFOAM™ Brand SPF Insulation (CM Series)

Property and Test Method Value

CM 2030 CM 2045

Ambient (Substrate) Temperature Range, °F30-70 (30-60)

45-95 (45-100)

Core Density, ASTM D1622, lb/ft3 2.5 2.3

Compressive Strength, ASTM D1621, lb/in2, parallel 25 21.7

Closed-cell Content, ASTM D6226, Minimum 90% Pass Pass

Thermal Resistance, ASTM C518, 75°F mean temp., aged R-value(2)

ft2•h•°F/Btu, Aged Value @ 1” @ 4”

6.0 25

6.5 25

Water Vapor Permeability, ASTM E96, perm-inch 2.2 2.7

Water Absorption, ASTM D2842, 5% max. volume Pass Pass

Dimensional Stability, ASTM D2126, max. % linear change @ -20°F, ambient R.H., 7 days @ -40°F, ambient R.H., 7 days @ 158°F, ambient R.H., 7 days @ 158°F, 97% R.H., 7 days

-0.1 – -2.0

Pass(3)

– 0.2 0.1 Pass(3)

Surface Burning Characteristics(4), ASTM E84 Class A Class A

P R O D U C T I N F O R M A T I O N | United States | C O M M E R C I A L

Page 8: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

When used in conjunction withthe THERMAX™ Wall System,STYROFOAM™ Brand SPF Insulation (CM Series)complies with the following codes:

• NFPA 285-[06]: Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Components, Using the Intermediate-Scale, Multistory Test Apparatus• ASTM E331-[00]: Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors and Curtain Walls by Uniform Static Air Pressure Difference• ASTM E2357-[05]: Standard Test Method for Determining Air Leakage of Air Barrier Assemblies

Contact your Dow sales representative or local authorities for state and local building code requirements and related acceptances.

Physical Properties STYROFOAM™ Brand SPF Insulation (CM Series) exhibits typical physical properties indicated in Table 1 when tested as represented.

Environmental Data STYROFOAM™ Brand SPF Insulation (CM Series) is chloro fluorocarbon (CFC) free and uses the Enovate 3000 blowing agent from Honeywell, which is a zero-ozone depleting product.

Fire information STYROFOAM™ Brand SPF Insulation is combustible and may constitute a fire hazard. Do not expose foam to flame or temperatures above 240°F.

5. INSTALLATION

SAFETY AND CONDITIONS OF USE • STYROFOAM™ Brand SPF Insulation products are available to trained professional applicators only. Application certification is also recommended. • Read all instructions and (Material) Safety Data Sheets carefully before use. ((M)SDS) for STYROFOAM™ Brand SPF Insulation products are available at: www.dowbuildingsolutions.com/na. Visit www.spraypolyurethane.com for further details and supporting information covering a wide range of topics including an overview of SPF health and safety guidelines, suggested personal protective equipment (PPE), typical first-aid treatment, and regulations and information about “green” marketing.• STYROFOAM™ Brand SPF Insulation contains isocyanate, hydrofluorocarbon blowing agent and polyol. Do not breathe vapor or spray. Use only with a NIOSH-approved supplied air respirator (SAR) in accordance with your company’s respiratory protection program. Supplied air respirator or an approved air-purifying respirator

equipped with an organic vapor sorbent and a particle filter (P100) is required to maintain exposure levels below ACGIH, OSHA, WEEL or other applicable limits. For situations where the atmospheric levels may exceed the level for which an air-purifying respirator is effective, use a positive- pressure, air-supplying respirator (air line or self-contained breathing apparatus).• Provide cross ventilation in the spray zone during spraying at a minimum of 30 Air Changes per Hour (ACH) and for a minimum of 24 hours post-spray at a minimum of 3 ACH. Restrict access to the spray site to those with proper PPE, including respiratory protection, until at least 24 hours post-spray.• Isocyanate is irritating to the eyes, skin and respiratory system and may cause sensitization by inhalation or skin contact. Sensitization, or the development of asthma, can lead to permanent respiratory problems. • STYROFOAM™ Brand SPF Insulation will adhere to most surfaces and skin. Do not get foam on skin. When spraying polyurethane foam, wear MDI-resistant chemical gloves (e.g., nitrile) or fabric gloves coated in nitrile, neoprene, butyl or PVC. Spray applicators should wear chemically resistant coveralls or full body suits with hoods and Methylene diphenyl diisocyanate (MDI) resistant fitted boots or booties. Professional judgment is necessary to determine the appropriate PPE necessary for secondary activities such as cleaning and trimming of the cured foam. Cured foam must be mechanically removed or allowed to wear off in time.

Page 9: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

• The contents are under pressure. Ambient and substrate temperatures should be within the range stated in Table 1. Substrate must be at least 5 degrees above dew point, with best processing results when ambient humidity is below 80 percent. Substrate must also be free of moisture (dew or frost), grease, oil, solvents and other materials that would adversely affect the adhesion of the spray polyurethane foam.

Spray equipment must be capable of delivering the proper ratio (1:1 by vol-ume) of polymeric isocyanate and polyol blend at adequate temperatures and spray pressures. Primary and hose heaters should be set between 115°F and 130°F. Dynamic pressures should range between 800 psi and 1200 psi, and should not exceed a difference of 200 psi between the isocyanate and the polyol sides.

It is recommended that STYROFOAM™ Brand SPF Insulation (CM Series) be applied to the stud cavity once all insula-tion board and veneer fasteners have been installed. Apply spray polyurethane

foam in the stud cavity and the inside of the stud flanges to ensure that all fastener penetrations are covered. Apply in consecutive layers of no less than 1/2” and no more than 2”. If mul-tiple layers are used, allow foam to cool completely before applying successive layers.

6. AVAILABILITYSTYROFOAM™ Brand Spray SPF Insula-tion (CM Series) is distributed through an extensive network. For more information, call 1-800-232-2436.

7. WARRANTYSee THERMAX™ Wall System Limited Warranties for details.

8. MAINTENANCESTYROFOAM™ Brand SPF Insulation (CM Series) has a shelf life of six months when stored dry between 60°F and 90°F. Artificial warming of drums is not recom-mended. Caution should be exercised

when opening containers as pressure may be present when material has been exposed to elevated temperatures. Ensure drums are capped after use. Empty drums are nonreturnable and should be disposed of by using current industrial practices in accordance with federal, state or local regulations.

9. TECHNICAL SERVICESDow can provide technical information to help address questions when using STYROFOAM™ Brand SPF Insulation (CM Series). Technical personnel are available to assist with any insulation project. Call 1-866-583-BLUE (2583).

10. FILING SYSTEMS • www.thermaxwallsystem.com • www.dowbuildingsolutions.com

Page 10: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

®™Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. Form No. 179-04063-0615 CDPPrinted in U.S.A.

The Dow Chemical CompanyBuilding Solutions200 Larkin • Midland, MI 48674

NOTICE: No freedom from any infringement of patent owned by Dow or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other government enactments. The product shown in this literature may not be available for sale and/or available in all geographies where Dow is represented. The claims made may not have been approved for use in all countries or regions. Dow assumes no obligation or liability for the information in this document. References to “Dow” or the “Company” mean the Dow legal entity selling the products to Customer unless otherwise expressly noted. NO EXPRESS WARRANTIES ARE GIVEN EXCEPT FOR ANY APPLICABLE WRITTEN WARRANTIES SPECIFICALLY PROVIDED BY DOW. ALL IMPLIED WARRANTIES INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.Dow Polyurethane Foam Insulation and SealantsCAUTION: When cured, these products are combustible and will burn if exposed to open flame or sparks from high-energy sources. Do not expose to temperatures above 240ºF (116ºC). For more information, consult (Material) Safety Data Sheet ((M)SDS) call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400 in the U.S. or 1-519-339-3711 in Canada. When air sealing buildings, ensure that combustion appliances, such as furnaces, water heaters, wood burning stoves, gas stoves and gas dryers are properly vented to the outside. See website: http://www.epa.gov/iaq/homes/hip-ventilation.html. In Canada visit: http://archive.nrc-cnrc.gc.ca/eng/ibp/irc/bsi/83-house-ventilation.html. STYROFOAM™ Brand Spray Polyurethane Foam contains isocyanate, hydrofluorocarbon blowing agent and polyol. Read all the instructions and (M)SDS carefully before use. Wear protective clothing (including long sleeves), gloves, goggles and proper respiratory protection. Supplied air or an approved air-purifying respirator equipped with an organic vapor sorbent and a P100 particulate filter is required to maintain exposure levels below ACGIH, OSHA, WEEL or other applicable limits. Provide adequate ventilation. Contents under pressure. STYROFOAM™ Brand SPF should be installed by a trained SPF applicator.

Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mold formation. No material supplier including Dow can give assurance that mold will not develop in any specific system.

USTechnical Information: 1-866-583-BLUE (2583)Sales Information: 1-800-232-2436

dowbuildingsolutions.com thermaxwallsystem.com

Page 11: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

THERMAX XARMOR™ (ci) Exterior Insulation

1. PRODUCT NAMETHERMAX XARMOR™ (ci) Exterior Insulation

2. MANUFACTURERThe Dow Chemical Company Dow Building Solutions 200 Larkin Midland, MI 48674 1-866-583-BLUE (2583) Fax 1-989-832-1465

www.thermaxwallsystem.com

3. PRODUCT DESCRIPTIONTHERMAX XARMOR™ (ci) Exterior Insulation consists of a glass-fiber-reinforced polyisocyanurate foam core faced with nominal 4 mil embossed BLUE™ thermoset-coated aluminum on one side and 1.25 mil embossed aluminum on the other. When used as part of the THERMAX™ Wall System, the integral, durable thermoset-coated aluminum facer provides a drainage plane, water-resistive barrier and exterior sheathing; eliminating the extra steps of installing a membrane, building wrap and exterior gypsum. The foam core provides one of the highest R-values(2) available (R-6.5 at 1”) for immediate insulation and weather protection on the job site, as well as long-term thermal performance and water resistance. As a UV stable material, THERMAX XARMOR™ (ci) Exterior Insulation can remain uncovered up to six months. With its low perm rating and high insulating value, THERMAX XARMOR™ (ci) Exterior Insulation reduces the potential for condensation within the wall assembly resulting in long lasting performance.

With more than 30 years of proven performance, THERMAX™ products feature a distinct free-rise technology for better product consistency, durability and fire performance than generic polyisocyanurate insulations.

Basic Use THERMAX XARMOR™ (ci) Exterior Insulation is the core component of the THERMAX™ Wall System, which easily meets or exceeds ASHRAE 90.1-2013 prescriptive requirements for continuous insulation on exterior walls, as governed by building codes. The tough 4 mil BLUE™ embossed aluminum surface makes it a durable exterior insulated sheathing choice.

Sizes See Table 1 for sizes, R-values and edge treatment options.

4. TECHNICAL DATAApplicable Standards THERMAX XARMOR™ (ci) Exterior Insulation meets ASTM C1289 – Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board, Type I, Class 2. Applicable standards include:

Breaking Load and Flexural Properties of Block-Type Thermal Insulation

Cellulosic Fiber Insulating Board

State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus

Compressive Properties of Rigid Cellular Plastics

Response of Rigid Cellular Plastics to Thermal and Humid Aging

Vapor Transmission of Materials

and Tensile Adhesion Properties of Rigid Cellular Plastics

Physical PropertiesExterior Insulation exhibits the properties and characteristics indicated in Table 2 when tested as represented.

Fire ProtectionTHERMAX™ products should be used only in strict accordance with product application instructions. THERMAX™ products, when used in a building containing combustible materials, may contribute to the spread of fire. For more information, consult (Material) Safety Data Sheet ((M)SDS) and/or call Dow at 1-866-583-BLUE (2583). In an

P R O D U C T I N F O R M A T I O N | United States | C O M M E R C I A L

TABLE 1: Sizes(1), R-Values And Edge Treatments For THERMAX XARMOR™ (ci) Exterior Insulation

Nominal Board Thickness (in.) R-Value Board Size (ft.) Edge Treatment

0.625 4.1 4 x 8/4 x 12 Square Edge1.0 6.5 4 × 8/4 × 12 Square Edge1.55 10.1 4 × 8/4 × 12 Shiplap2.0 13.0 4 × 8/4 × 12 Shiplap

(1) Contact your Dow seller for information at different R-values and other sizes and lead time requirements. Not all product sizes are available in all regions.

(2)

by ASTM C518 using the aging process in ASTM C1289 (90 days @ 140°F).

Page 12: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

NOTICE: No freedom from infringement of any patent owned by Dow or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products nd the information in this document are appropriate for Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other government enactments. The product shown in this literature may not be vail-able for sale and/or available in all geographies where Dow is represented. The claims made may not have been approved for use in all countries. Dow assumes no obligation or liability for the information in this document. References to “Dow” or the “Company” mean the Dow legal entity selling the products to Customer unless otherwise expressly noted. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED

STYROFOAM™ Brand Extruded Polystyrene Foam Insulation CAUTION: This product is combustible. Protect from high heat sources. A protective barrier or thermal barrier may be required as specified in the appropriate building code. For more information, consult MSDS, call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400 in the U.S. or 1-519-339-3711 in Canada.

WARNING: Rigid foam insulation does not constitute a working walkable surface or qualify as a fall protection product.

Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mold formation. No material supplier including Dow can give assurance that mold will not develop in any specific system.

Printed in the U.S.A. ®TM Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow Form No. 179-00029-0815 CDP

dowbuildingsolutions.comFor Technical Information: 1-866-583-BLUE (2583) (English)1-800-363-6210 (French)

For Sales Information: 1-800-232-2436 (English)1-800-565-1255 (French)

In the United States The Dow Chemical Company Dow Building Solutions200 Larkin Center Midland, MI 48674

TABLE 2: Physical Properties of THERMAX XARMOR™ (ci) Exterior InsulationProperty and Test Method Value

Thermal Resistance(1) , ASTM C518, R-value 6.5

Compressive Strength(2) , ASTM D1621, psi 25.0

Flexural Strength, ASTM C203, psi 55.0Water Absorption, ASTM C209, % by volume, max. 0.1

Water Vapor Permeance, ASTM E96, perms ≤0.04

Maximum Use Temperature, °F 250

Surface Burning Characteristics(3) , ASTM E84Flame SpreadSmoke Developed

25<450

emergency, call 1-989-636-4400.

Code Compliances THERMAX XARMOR™ (ci) Exterior Insulation complies with the following codes:

Section 2603 – UL Classified; Class A UL 723 (ASTM

E84) Surface Burning Characteristics of Building Materials

– Fire Performance Evaluation approvals per NFPA 285, 2006 Edition (UBC 26.9, intermediate scale – multistory testing)

Spaces, compliant as an FM approved Class 1 Foil-faced Polyisocyanurate Insulation in Cavity Walls

Insulated Wall and Ceiling Panel ™ products are covered

under Underwriters Laboratories Inc. (UL) file R5622

wall rated assemblies as listed in the UL Fire Resistance Directory: U026, U326, U330, U354, U355, U424, U425, U460, U902, U904, U905, U906, U907, V454, V482, V499, W417

wall rated assemblies as listed in the Intertek Fire Rating Listing: FI 60-02, FI 60-01, FI 120-01

tested by ASTM E2357 and water barrier requirements as tested by ASTM E331 when THERMAX XARMOR™ (ci) Exterior Insulation is used as part of the THERMAX™ Wall System

Contact your Dow sales representative or local authorities for state and local building

(1)

ASTM C518 using the aging process in ASTM C1289 (90 days @ 140°F). (2) Vertical compressive strength is measured at 10 percent deformation or at yield, whichever occurs first. (3) Calculated flammability values for this or any other material are not intended to represent hazards that may be present under actual fire conditions.

code requirements and related acceptances.

5. INSTALLATIONBoards of THERMAX XARMOR™ (ci) Exterior Insulation are lightweight and can be sawed or cut with a knife. They install quickly and easily to walls with common building tools. Vertical joints should be staggered and butt joints must be installed over structural members. For optimum performance seal all joints between boards with LIQUIDARMOR-CM Sealant and Flashing.

6. AVAILABILITYTHERMAX XARMOR™ (ci) Exterior Insulation is distributed through an extensive network. For more information, call 1-800-232-2436.

7. WARRANTYFifteen-year limited Thermal warranty and Fifteen-year Water Resistive warranty may be applicable when used as a component in the THERMAX™ Wall System. See www.thermaxwallsystem.com for more details.

8. MAINTENANCENot applicable.

9. TECHNICAL SERVICESDow can provide technical information to help address questions when using THERMAX XARMOR™ (ci) Exterior Insulation. For technical assistance, call 1-866-583-BLUE (2583).

10. FILING SYSTEMSwww.thermaxwallsystem.comwww.dowbuildingsolutions.com

Page 13: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

1. PRODUCT NAME LIQUIDARMOR™ -CM Flashing and Sealant

2. MANUFACTURER The Dow Chemical Company Dow Building Solutions 200 Larkin Center, 1605 Joseph Drive Midland, MI 48674 1-866-583-BLUE (2583) Fax 1-989-832-1465

3. PRODUCT DESCRIPTION Basic Use LIQUIDARMOR™ -CM Flashing and Sealant is an innovative, patented liquid flashing solution designed to provide commercial buildings advanced moisture and air sealing protection. An innovative alternative to flashing tape, the elastomeric spray forms a tight, seamless barrier along the rough openings of windows and doors while helping to significantly reduce labor time. The liquid flashing solution offers an excellent alternative sealant solution to conventional flashing and sealing products for installation of THERMAX™ or the Ultra Air Barrier Wall Systems.

LIQUIDARMOR™ -CM Flashing and Sealant covers and seals hard-to-reach gaps up to a quarter inch wide and offers a reliable replacement to peel and stick flashing tapes commonly used on board joints of commercial buildings. The versatile, water-based coating works on a wide range of surfaces, including foam boards, steel studs, concrete masonry units, tapes, wood buck, and wraps. With sprayable, aqueous technology, it facilitates a consistent application using commonly available airless paint sprayers.

The liquid flashing solution seals around screws, veneer anchors and penetrating fasteners, resulting in a durable and resilient barrier suited to withstand job site variations and long term building performance. Once the LIQUIDARMOR™ -CM sealant sets to the final elastomeric solid, the treated area is protected and helps provide superior air leakage and moisture control as part of a joint treatment with Dow’s commercial wall assemblies.

Limitations Surface and ambient temperatures should be 35°F and rising and below 120°F during application. LIQUIDARMOR™ -CM Flashing and Sealant tolerates rain shortly after installation. However, do not apply to surfaces with standing water or frost.

4. TECHNICAL DATA Applicable Standards LIQUIDARMOR™ -CM Flashing and Sealant complies with the following standards listed in the codes:

Exterior Windows by Uniform Static Air

for Determining Air Leakage of Air

Contact your Dow sales representative or local authorities for state/provincial and local building code requirements and related acceptances.

Physical Properties LIQUIDARMOR™ -CM Flashing and Sealant exhibits typical properties and characteristics indicated in Table 1 when tested as represented.

Third-Party Tested:ASTM E331, “Water Penetration of Exterior Windows by Uniform Static Air Pressure Difference”: Passed with no leakage after 2 hours at 6.24 psf as part of Dow’s THERMAX™ Wall System and Ultra Air Barrier Wall system designs.ASTM E2357, “Standard Test Method for Determining Air Leakage of Air Barrier Assemblies”: Rated at 0.0810 and 0.0508 L/s-m2. as part of Dow’s THERMAX™ Wall System and Ultra Air Barrier Wall System designs, respectively.* Consult label and SDS carefully before use.

TABLE 1: LIQUID PROPERTIES

Form Grey-blue, sprayable sealant

Volatile Organic Compounds (VOC) 2.3 wt%

Density 11.4 lbs./gal.

Total Solids 75%

Shelf Life 1.5 years

LIQUIDARMOR™ – CM Flashing and Sealant

Application Environment

P R O D U C T I N F O R M A T I O N | United States | C O M M E R C I A L

TABLE 2: TYPICAL CURED PROPERTIES

Tensile Strength, ASTM D412 340 psi

Elongation at Break, ASTM D412 270%

Water Vapor Transmission, ASTM E96, Procedure B 4 perms

Accelerated Weathering AAMA714, Section 5.3 Passes

Nail Sealing Ability ASTM D1970/ AAMA714, Section 5.2 Passes

Elevated Temperature, AAMA 714, Section 5.4 Passes

Thermal Cycling/Freeze-Thaw, AAMA 714, Section 5.5 Passes

Page 14: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

5. INSTALLATION Preparation

of use before applying product.

surfaces free of contaminants.

with acrylic caulk.

Equipment

Titan Speedflow 1200 SF or Titan Impact 1140 or Graco GMAX II 5900 or Graco TexSpray Mark IV

– Motor: 2.2 hp

or Graco XHD325 – Use 500s series for wider spray widths and

200s or 300s series for narrower gaps, such as joints, as a general guidance. Refer to sprayer manufacturer for specific sprayer and tip details. Other sprayer models matching the equipment throughput and pressure range can be used.

Application Instructions

LIQUIDARMOR™ -CM Flashing and Sealant,

™ Window & Door Insulating Foam Sealant or acrylic caulk.

™ Window & Door Insulating Foam Sealant or acrylic caulk to skin over, then spray LIQUIDARMOR™ -CM Flashing and

on board joints. As window flashing, cover rough opening per flashing design details at 50 ±5 wet mils thick, and >any sheathing surface at transitions.

™ -CM Flashing and Sealant, ensure consistent film thickness of the coating and visually inspect for missed spots.

used to smooth the coating and fill any voids.™ -CM Flashing and

humidity, temperature, sun exposure and wind direction, minimum 1 to 4 hours or overnight may be needed.

instructions.

6. SAFETY AND CONDITIONS OF USE

safety practices.

and warnings.

carefully before use

and those working in the spray area wear eye protection such as safety glasses with side shields or googles.

discoloration and dryness.

exposures.

applications.

7. AVAILABILITY LIQUIDARMOR™ -CM Flashing and Sealant is available in 5-gallon pails at select locations.

For more information, call 1-800-232-2436.

8. WARRANTY When used per Dow’s recommended installation, Dow hereby warrants that the product will be free of defects in material and perform to Dow’s published physical property specifications at time of purchase so long

as product is within best-use date as stated on product label, and the product is applied per product literature. All recommendations or suggestions for use are made without guarantee. Dow recommends that customers inspect ambient and substrate conditions, and test product before use to determine content and suitability for their specific use. In no event shall Dow be liable for any other costs or damages, including labor costs.

LIMITATIONS THESE WARRANTIES ARE IN LIEU OF ALL OTHER GUARANTEES AND WARRANTIES,

WARRANTIES OF MERCHANTABILITY AND

SHALL NOT BE EXTENDED OR ALTERED

BY DOW AND THE OWNER. THERE ARE NO WARRANTIES OR GUARANTEES THAT

FORTH IN THESE WARRANTIES.

Dow does not warrant the compatibility of any other product (including but not limited to any roofing membrane or coatings) with the warranted products, and does not assume any liability for any incidental, consequential, exemplary, special or punitive damages, including (but not limited to) incremental heating, cooling or similar costs and any other harm to persons or property.

9. MAINTENANCE Not applicable.

10. TECHNICAL SERVICES Dow can provide technical information to help address questions when using LIQUIDARMOR™ -CM Flashing and Sealant. For technical assistance, call your local Dow Sales representative.

Notice: No freedom from infringement of any patent owned by Dow or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for Customer’s use and for ensuring that Customer’s workplace and disposal practices are in compliance with applicable laws and other government enactments. The product shown in this literature may not be available for sale and/or available in all geographies where Dow is represented. The claims made may not have been approved for use in all countries. Dow assumes no obligation or liability for the information in this document. References to “Dow” or the “Company” mean the Dow legal entity selling the products to Customer unless otherwise expressly noted. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.Dow Polyurethane Foam Insulation and SealantsCAUTION: When cured, these products are combustible and will burn if exposed to open flame or sparks from high-energy sources. Do not expose to temperatures above 240ºF (116ºC). For more information, consult MSDS, call Dow at 1-866-583-BLUE (2583) or contact your local building inspector. In an emergency, call 1-989-636-4400 in the U.S. or 1-519-339-3711 in Canada. When air sealing buildings, ensure that combustion appliances, such as furnaces, water heaters, wood burning stoves, gas stoves and gas dryers, are properly vented to the outside. See website: http://www.epa.gov/iaq/homes/hip-ventilation.html.GREAT STUFF PRO™ sealant and adhesive products contain isocyanate and a flammable blowing agent. Read the label and Safety Data Sheet carefully before use. Eliminate all sources of ignition before use. Wear long sleeves, gloves and safety glasses or goggles. Provide adequate ventilation or wear proper respiratory protection. Contents under pressure. Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mold formation. No material supplier, including Dow, can give assurance that mold will not develop in any specific system.®™Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow.Printed in U.S.A. Form No. 179-04682 1214 CDP

dowbuildingsolutions.comTechnical Information Contact your local Dow Sales representative Sales Information 1 800 232 2436

In the U.S. The Dow Chemical Company Dow Building Solutions200 Larkin, 1605 Joseph Drive Midland, MI 48674

Page 15: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

KNIGHT WALL SYSTEMS’ CI-SYSTEM RAIN SCREEN ATTACHMENT NOT ONLY PROVIDES OUTSTANDING THERMAL PERFORMANCE BY WAY OF TRUE CONTINUOUS INSULATION, IT WILL ALSO ACCOMMODATE NEARLY ANY FACADE OR CLADDING SYSTEM – FOR MAXIMUM VERSATILITY, EASE OF INSTALLATION AND A SIMPLE DESIGN.

DEVELOPED TO BE INSTALLED OVER EXTERIOR RIGID BOARD INSULATION – WITH ONLY THERMALLY ISOLATED FASTENERS PENETRATING THE THERMAL LAYER – KNIGHT’S CI-SYSTEM EASILY COMPLIES WITH THE NORTH AMERICAN ENERGY CODE REQUIREMENTS FOR CONTINUOUS INSULATION (ci)*.

KNIGHT CI-SYSTEM RAIN SCREEN ATTACHMENT: THE DEFINITION OF FAÇADE VERSATILITY – WITH ALL THE EXPECTED THERMAL PERFORMANCE

ADVANTAGES TO KNIGHT WALL SYSTEMS’ CI-SYSTEM RAIN SCREEN:¤ Easily attain code compliance with exterior insulation

¤ High corrosive-resistant 55 AL-ZN AZ50 coating for a long service life

¤ No trimming or manipulation of exterior insulation makes installation quick and simple

¤ All fasteners that penetrate the insulation are thermally isolated with preassembled washers

¤ Attach nearly any cladding with easy and efficient installation and detailing

¤ Excellent ventilation with a constant 3/4-inch, or optional 1 1/2-inch, continuous rain screen cavity

¤ Budget conscious assembly

¤ Pre-engineered, tested and warranted

EXTERIOR INSULATION EFFECTIVENESS AS COMPARED TO THE RATED R-VALUE+

...with Vertical Z-Girts: 43%-63% ...with Horizontal Z-Girts: 52%-71% ...with Aluminum Brackets: 60%-70% ...with the CI-SYSTEM: 95%-98%

* ASHRAE 90.1 prescriptive requirement for steel frame walls+ Effective percentages vary depending upon exact wall assembly, though 24” spacing was used in determining horizontal girts & bracket assembly percentages. Contact KWS for full thermal reports.

Page 16: Opaque Envelope Basis of Design - Pace Representatives, … BODs/Cladding w... · 781-541-5060 Reference wall Basis of Design Package. Registered design professional in responsible

CI-SIDINGRAIL RAIN SCREEN ATTACHMENT SYSTEM:The CI-SidingRail™ System enables the use of fiber-cement lap siding, horizontally oriented roll-formed metal siding and other horizontal siding. The system is comprised of continuous vertical members (CI-Girt) with a 2” fastening face for attaching various claddings.

CI-PANELTEK RAIN SCREEN ATTACHMENT SYSTEM:The CI-PanelTek™ System is a must for vertically oriented siding (i.e. roll formed metal sheets, etc.), exposed fastener—or face-fastened—panels and siding systems of all kinds. It’s comprised of continuous horizontal members (featuring a 2” or 3” fastening face) attaching to continuous vertical members (CI-Girt) that are attached to the substrate in a continous insulation fashion.

KNIGHTWALL SYSTEMS28308 N Cedar Road, Deer Park, WA 99006www.knightwallsystems.com1-855-597-9255 (KWS-WALL)509.262.0104

ACCOMMODATE NEARLY ANY PANEL OR CLADDING:Knight’s CI-System uses continuous vertical girts – called CI-Girts – that can be spaced up to 32” O.C. horizontally and support claddings that weigh over 15 PSF*. The system uses a unique thermal isolation washer at each penetrating fastener, creating one of the most thermally efficent rain screen attachments on the market today. This drop-in system is supplied with the correct wall anchors for attaching to the stud sub-structure with ThermaStop isolators pre-assembled on the fasteners, as well as associated rails and rail fasteners for a complete attachment solution.

CI-System is available in two configurations: CI-SidingRail™ & CI-PanelTek™.

CI, PanelTek, SidingRail, ThermaStop and PanelRail are trademarks of Knight Wall Systems

KNIGHT WALL CAN CONTRIBUTE TO THEFOLLOWING USGBC LEED CREDITS:¤ Energy & Atmosphere (EA) Prequisite and Credit 1¤ Materials & Resources (MR) Credits 4 and 5

ALL KNIGHT WALL SYSTEMS COMPONENTS ARE MANUFACTURED IN THE USA. (PATENT PENDING)

*Maximum allowable spacing & dead load is a function of live loads+dead load < allowable load of wall anchor. Contact KWS for more information.

DOW, DOW DIAMOND LOGO, THERMAX and STYROFOAM are trademarks of The Dow Chemical Company

NO EXPRESS WARRANTIES ARE GIVEN EXCEPT FOR ANY APPLICABLE WRITTEN WARRANTIES SPECIFICALLY PROVIDED BY KNIGHT WALL SYSTEMS. ALL IMPLIED WARRANTIES INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED. No freedom from any patent owned by Knight Wall Systems or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for Customer’s use.