operation of different types of circuit breaker

Upload: mrgrumpy13

Post on 04-Jun-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Operation of different types of Circuit Breaker

    1/13

    Circuit Breaker OperationIn addition to the events that cause a trip, a circuit breaker for switchgear

    applications must also be selected for the method by which it opens when

    tripped. This is important, because when contacts are opened quickly at

    high voltage levels, a conductive metallic vapor can form that allows

    current to continue to travel between the open contacts. This phenomenon,

    known as arcing, creates the greatest obstacle to circuit interruption.

    As a result, medium- and high-voltage circuit breakers employ one of four

    different arc interrupting technologies. All take advantage of the fact that

    even the most powerful AC overcurrent cycles pass the ero-current level

    twice in one cycle. !y reducing the amount of conductive gas between the

    contacts, the arc cannot be sustained when it passes through a current ero.

    "ince the current in #C circuits

    does not follow a sine-wave

    pattern, circuit interruption is very

    difficult. This makes the #C

    interrupting rating for most

    breakers much lower than the

    interrupting rating for AC circuits.

    Air magnetic breakersuse the arc

    to generate a magnetic field that

    forces the arc into arc chutes, which lengthen and cool the arc, allowing it

    to be e$tinguished at a current ero.

    Oil breakersare of several types,

    including bulk oil, but they all work in a

    relatively similar way. %ere, the contacts

    are immersed in a container of non-

    conductive oil. &hen an overcurrent

    occurs, the arc heats the surrounding oil

    forcing it to flow violently. The rapidly

    flowing oil displaces the arcing gases and breaks the arc path.

  • 8/13/2019 Operation of different types of Circuit Breaker

    2/13

    'il breakers always carry the haards of handling and disposing of spent oil,

    and the potential for oil fire. In (urope, however, special minimum-oil

    designs have been developed to reduce these drawbacks, and some

    minimum oil breakers have even been approved for limited indoor use.

    #ifferent oil breakers are designed for different power levels, with the

    highest rated for )*+ k to + k.

    Sulfur hexafluoride (SF6)is an

    insulating gas used in circuit breakers

    in two ways. In puffer designs, it/s

    blown across contacts as they open to

    displace the arcing gas. In blast

    designs, it/s used at high pressures to

    open contacts as it simultaneously e$tinguishes the arc. "01breakers are

    rated for the highest voltage of all breaker designs.

    Vacuum breakersenclose the contacts

    within a vacuum chamber, so when the

    arc of metallic vapor forms it is

    magnetically controlled and thereby

    e$tinguished at current ero. acuum breakers are rated up to )*.+ k.

    AS! Classes Of "ela#sThere are many types of protective relays. The revision of A2"I )3.4,

    5elays and 5elay "ystems Associated with (lectric 6ower Apparatus listsand defines five classes of relays7

    8. Auxiliar# rela#- one that operates in response to the opening orclosing of its operating circuit to assist another relay or device inperforming a function.

    9. $rotecti%e rela#- one whose function is to detect defective lines,apparatus, or other dangerous or undesired conditions, and to initiateor permit suitable switching, or to give adequate warning.

    ). "egulating rela#- one that operates because of a departure of a

    parameter from predetermined limits and that functions through

  • 8/13/2019 Operation of different types of Circuit Breaker

    3/13

    supplementary equipment to restore the quantity to within theselimits.

    *. &onitoring rela#- one whose function is to verify that system orcontrol circuit conditions con form to prescribed limits.

    +. $rogramming rela#- one whose function is to establish or detect

    electrical sequences.

    "ome +8 different types of relays and 9* kinds of protection are listed and

    defined in the "tandard. The types of relays include alarm, differential,

    distance, directional power, timing, voltage, etc., while the kinds are7

    differential protection, directional over-current protection, ground

    protection, pilot wire protection, etc.

    The "tandard defines high speed as a qualifying term applied to a relay,

    indicating that the time of its operation usually does not e$ceed l:9th of a

    second ;) cycles on 1 cycle base

  • 8/13/2019 Operation of different types of Circuit Breaker

    4/13

  • 8/13/2019 Operation of different types of Circuit Breaker

    5/13

    'verloads, if continued, cause conductor circuit or motor overheating. They

    may not require immediate disconnect from the system only before the

    operating temperatures become too high. The overcurrent protective device

    used for overloads should have a time-overcurrent characteristic. A short-

    circuit should be removed from the system immediately however, a small

    amount of time may be allowed to permit selective operation of the device

    closest to the short-circuit location.

    Arcing ;and other< ground faults may be smaller than the normal full load

    current. Therefore, a different scheme must be used if the system is to be

    protected from this type of fault. This ground fault current may cause

    serious damage at the location of the fault, but still may be too small to trip

    the overcurrent device. This ground-fault sensing and protection concepts

    are discussed elsewhere in this manual. They involve au$iliary trip devices

    operated by e$ternal sensors. The 2(C ;9)-4+< requires that ground fault

    protection be provided on certain services rated 8,A or more, where at

    least 8,9A of ground fault current might flow. These systems need to be

    coordinated with the downstream overload protection devices, to prevent

    shutting down the entire system in the event of a down-stream ground fault.

    $oints ,o Consider !n ,ransformer SelectionThere are several points to consider when selecting a transformer.

    -. kVA "ating

    The kA rating must be sufficient to handle the load. Consideration should

    also be given to possible future load growth. "ome companies handle growth

    using a large number of various sie transformers, installing them with a

    rating close to the actual load requirements, and then changing the bank

    when the load grows. &hile this is the way electric utilities do it, most

    industrial plants do not have the necessary stock of spares to operate in this

    manner, and the practice does not lend itself to the use of substations. 'f

    course, transformer ratings can be increased by forced cooling.

    The transformer kA, impedance, and voltage rating determine the short-

    circuit current interruption requirements for the protective device.

  • 8/13/2019 Operation of different types of Circuit Breaker

    6/13

    5emember that replacing a transformer with a larger unit to handle a larger

    connected load also impacts the interrupting requirements.

    /. Voltage "atings and "atios

    The transformer should be selected to give the proper voltage at the load

    terminals. This voltage is the system voltage desired, not the equipment

    utiliation voltage. 0or instance, if motors are rated for *1 olts, the

    transformer no-load voltage should be *B olts. This permits a voltage drop

    in the feeders to the point of use.

    0. Voltage ,aps

    ost modern transformers have taps in the windings that make it possible to

    slightly change the turns ratio. These taps do not materially affect the

    voltage drop through the transformer they merely change the voltage level.

    The standard for the taps in transformers used in industrial systems is two 9-

    8:9= taps both above and below rated voltage. Tap changing must be

    carried out with the transformer disconnected from the circuit. %owever,

    load tap changing transformers are available at additional cost.

    Taps are intended to ad@ust the transformer to the primary voltage level

    actually present. Therefore, if the input voltage is 9-8:9= above the

    nominal system voltage, the tap should be set to provide 9-8:9= more

    primary turns in order to keep the secondary voltage at the design level

    during operation. Taps are not intended to be used to raise or lower the

    secondary voltage from the design or rated values.

    "ome transformers are supplied with several taps on the secondary

    windings. These permit the choice of any one of the secondary terminal

    voltages appropriate to that particular tap. %owever, this is not what is

    referred to as changing the taps on a transformer. "ome auto transformers

    are designed to provide continuous ad@ustment of the secondary voltage by

    using wires wound around a toroidal core and providing a sliding contact to

    bared regions on these secondary turns. This is equivalent to having a

    secondary tap for every turn.

    1. ,#pes of Construction

  • 8/13/2019 Operation of different types of Circuit Breaker

    7/13

    >iquid-filled transformers may be filled with either transformer oil or an

    insulating liquid specifically designed for transformers. These liquids

    perform two functions, serving as heat transfer mediums and as insulation.

    #ry-type transformers are available in either ventilated or sealed

    enclosures.

    The physical location of the transformer is of primary importance in

    determining the type of transformer to be used for a particular application.

    The characteristics of a given location may preclude the use of certain types

    or may make one type more desirable than another. In general, liquid-filled

    and sealed dry-type transformers are suitable for indoor and outdoor

    locations. 'il-filled transformers are suitable only for outdoor locations, and

    may not be used indoors because of the flammability of the oil ;unless

    located in a suitable fireproof vault

  • 8/13/2019 Operation of different types of Circuit Breaker

    8/13

    Transformers may be sub@ect to overvoltages from lightning or switching

    surges and should be appropriately protected. These surge handling

    capabilities are described by the impulse level the amount of a momentary

    voltage surge which the insulation can withstand. #ry-type transformers

    with their basic insulation being air, have appro$imately one-half the

    impulse level handling capability of similar kA liquid-filled transformers.

    Therefore, more thought must be given to dry-type transformer situations.

    6ole-top distribution transformers are frequently e$posed to these voltage

    surges. That is why these transformers have the insulation on their windings

    strengthened to withstand lightning ;and other< surges. The strength of this

    insulation is given by the !asic Impulse >evel ;!I>< number. Enits with high

    !I> numbers can be obtained at a cost premium. As an e$ample, typical

    pole-top insulators for 4-8) k would have a !I> of 889 k since that is their

    flash-over voltage. The transformer used on such a line should have a !I>

    greater than this value.

    Another insulation parameter is the insulation between primary and

    secondary windings. This is essential in the application of instrument

    transformers, and in applications which require isolation between circuits

    ;such as the filament transformers for high-voltage F-5ay tubesow-voltage transformers are generally designed to conform with the

    impedance/s as shown in the T5A2"0'5(5 I6(#A2C( Table in the

    Appendi$. These values are sub@ect to standard tolerances of plus-or-minus

    3 percent of the nominal impedance values listed. anufacturers will design

    transformers to meet other impedance requirements if the standard values

    are not adequate, but this naturally adds to the cost.

    Transformers with lower impedance have lower voltage drop, but will also

    allow higher available fault currents. "ome devices, such as welders and arc

    furnaces, use transformers that are specifically designed to have relatively

  • 8/13/2019 Operation of different types of Circuit Breaker

    9/13

    high percent impedance/s. This is done to reduce the disturbances on the

    primary power system when these devices are operating.

    3. Single+$hase or ,hree+$hase ,ransformers

    The recent trend is to use three-phase transformers rather than three

    single-phase transformers to make up a three-phase bank. Three-phase

    transformers have an e$cellent service record, cost less to install, and

    require less space. If three single-phase transformers connected delta-delta

    are used, the bank can still operate three-phases in the event one

    transformer fails. %owever, the capacity is reduced to about +3 percent of

    the original capacity and the voltages are unbalanced. Transformer failures

    are rare, and the e$tra space and labor needed to connect a bank of three

    instead of one three-phase unit may not be @ustified.

    4. 5#e+*elta Arrangements

    Another consideration when ordering transformers is the manner in which

    they are connected to the system. 0or e$ample, when using three-phase

    transformers, specify how the primary and secondary windings are to be

    connected, whether they are to be delta or wye, and the polarity.

    . !nterrupting "ating

    Today/s utility transformers are capable of delivering very large currents to

    a building. "hort circuits can cause high currents and electrical arcs that

    generate tremendous heat and large mechanical forces in a building, which

    in turn could seriously damage or destroy apparatus and conductors in a

    very short time if they are not promptly interrupted. This increased short

    circuit potential over the values assumed to be adequate a few years ago

    should be considered whenever any transformer is changed out for a larger

    one.

    "ela# ,#pesThis course is not intended to make relay engineers out of youG The

    discussion is limited to naming some basic operating principles, and

    discussing some of the common relay applications.

  • 8/13/2019 Operation of different types of Circuit Breaker

    10/13

    All relays provide an output signal which can be used to initiate some

    action. This output signal is often used to close one or more set of contacts,

    operate a circuit breaker, or a switch. "ome electronic relays provide an

    output current or a voltage signal, the more elaborate programmable

    controllers send digital signals which can be read by other devices. The

    basic electromechanical relays, however, simply operate to close a set of

    contacts when moved by either7

    8. (lectromagnetic attraction, or9. (lectromagnetic induction ;turn like a motor

  • 8/13/2019 Operation of different types of Circuit Breaker

    11/13

    connections, @oints, and connections to @oints are insulated, and the

    stationary structures consist of self-supporting steel frames.

    etal-clad switchgear should not be confused with metal enclosed

    switchgear where the individual components are not isolated from each

    other even though enclosed in a protective metal cabinet.

    Single $hase $oer(5atts7 Volt+Amperes and VA"s)

    'hm/s law for alternating-current circuits uses the quantity called

    impedance, ;represented by the letter H

  • 8/13/2019 Operation of different types of Circuit Breaker

    12/13

    This is called the reactive power ;or magnetiing power< and is measured

    in olt-Amperes-5eactive ;A5s

  • 8/13/2019 Operation of different types of Circuit Breaker

    13/13

    Home9 Index9 FAQs9 Appendix

    http://redding.apogee.net/pd/home.asphttp://redding.apogee.net/pd/index_a.asphttp://redding.apogee.net/pd/faqs.asphttp://redding.apogee.net/pd/appendix.asphttp://redding.apogee.net/pd/home.asphttp://redding.apogee.net/pd/index_a.asphttp://redding.apogee.net/pd/faqs.asphttp://redding.apogee.net/pd/appendix.asp