operation of different types of circuit breaker
TRANSCRIPT
-
8/13/2019 Operation of different types of Circuit Breaker
1/13
Circuit Breaker OperationIn addition to the events that cause a trip, a circuit breaker for switchgear
applications must also be selected for the method by which it opens when
tripped. This is important, because when contacts are opened quickly at
high voltage levels, a conductive metallic vapor can form that allows
current to continue to travel between the open contacts. This phenomenon,
known as arcing, creates the greatest obstacle to circuit interruption.
As a result, medium- and high-voltage circuit breakers employ one of four
different arc interrupting technologies. All take advantage of the fact that
even the most powerful AC overcurrent cycles pass the ero-current level
twice in one cycle. !y reducing the amount of conductive gas between the
contacts, the arc cannot be sustained when it passes through a current ero.
"ince the current in #C circuits
does not follow a sine-wave
pattern, circuit interruption is very
difficult. This makes the #C
interrupting rating for most
breakers much lower than the
interrupting rating for AC circuits.
Air magnetic breakersuse the arc
to generate a magnetic field that
forces the arc into arc chutes, which lengthen and cool the arc, allowing it
to be e$tinguished at a current ero.
Oil breakersare of several types,
including bulk oil, but they all work in a
relatively similar way. %ere, the contacts
are immersed in a container of non-
conductive oil. &hen an overcurrent
occurs, the arc heats the surrounding oil
forcing it to flow violently. The rapidly
flowing oil displaces the arcing gases and breaks the arc path.
-
8/13/2019 Operation of different types of Circuit Breaker
2/13
'il breakers always carry the haards of handling and disposing of spent oil,
and the potential for oil fire. In (urope, however, special minimum-oil
designs have been developed to reduce these drawbacks, and some
minimum oil breakers have even been approved for limited indoor use.
#ifferent oil breakers are designed for different power levels, with the
highest rated for )*+ k to + k.
Sulfur hexafluoride (SF6)is an
insulating gas used in circuit breakers
in two ways. In puffer designs, it/s
blown across contacts as they open to
displace the arcing gas. In blast
designs, it/s used at high pressures to
open contacts as it simultaneously e$tinguishes the arc. "01breakers are
rated for the highest voltage of all breaker designs.
Vacuum breakersenclose the contacts
within a vacuum chamber, so when the
arc of metallic vapor forms it is
magnetically controlled and thereby
e$tinguished at current ero. acuum breakers are rated up to )*.+ k.
AS! Classes Of "ela#sThere are many types of protective relays. The revision of A2"I )3.4,
5elays and 5elay "ystems Associated with (lectric 6ower Apparatus listsand defines five classes of relays7
8. Auxiliar# rela#- one that operates in response to the opening orclosing of its operating circuit to assist another relay or device inperforming a function.
9. $rotecti%e rela#- one whose function is to detect defective lines,apparatus, or other dangerous or undesired conditions, and to initiateor permit suitable switching, or to give adequate warning.
). "egulating rela#- one that operates because of a departure of a
parameter from predetermined limits and that functions through
-
8/13/2019 Operation of different types of Circuit Breaker
3/13
supplementary equipment to restore the quantity to within theselimits.
*. &onitoring rela#- one whose function is to verify that system orcontrol circuit conditions con form to prescribed limits.
+. $rogramming rela#- one whose function is to establish or detect
electrical sequences.
"ome +8 different types of relays and 9* kinds of protection are listed and
defined in the "tandard. The types of relays include alarm, differential,
distance, directional power, timing, voltage, etc., while the kinds are7
differential protection, directional over-current protection, ground
protection, pilot wire protection, etc.
The "tandard defines high speed as a qualifying term applied to a relay,
indicating that the time of its operation usually does not e$ceed l:9th of a
second ;) cycles on 1 cycle base
-
8/13/2019 Operation of different types of Circuit Breaker
4/13
-
8/13/2019 Operation of different types of Circuit Breaker
5/13
'verloads, if continued, cause conductor circuit or motor overheating. They
may not require immediate disconnect from the system only before the
operating temperatures become too high. The overcurrent protective device
used for overloads should have a time-overcurrent characteristic. A short-
circuit should be removed from the system immediately however, a small
amount of time may be allowed to permit selective operation of the device
closest to the short-circuit location.
Arcing ;and other< ground faults may be smaller than the normal full load
current. Therefore, a different scheme must be used if the system is to be
protected from this type of fault. This ground fault current may cause
serious damage at the location of the fault, but still may be too small to trip
the overcurrent device. This ground-fault sensing and protection concepts
are discussed elsewhere in this manual. They involve au$iliary trip devices
operated by e$ternal sensors. The 2(C ;9)-4+< requires that ground fault
protection be provided on certain services rated 8,A or more, where at
least 8,9A of ground fault current might flow. These systems need to be
coordinated with the downstream overload protection devices, to prevent
shutting down the entire system in the event of a down-stream ground fault.
$oints ,o Consider !n ,ransformer SelectionThere are several points to consider when selecting a transformer.
-. kVA "ating
The kA rating must be sufficient to handle the load. Consideration should
also be given to possible future load growth. "ome companies handle growth
using a large number of various sie transformers, installing them with a
rating close to the actual load requirements, and then changing the bank
when the load grows. &hile this is the way electric utilities do it, most
industrial plants do not have the necessary stock of spares to operate in this
manner, and the practice does not lend itself to the use of substations. 'f
course, transformer ratings can be increased by forced cooling.
The transformer kA, impedance, and voltage rating determine the short-
circuit current interruption requirements for the protective device.
-
8/13/2019 Operation of different types of Circuit Breaker
6/13
5emember that replacing a transformer with a larger unit to handle a larger
connected load also impacts the interrupting requirements.
/. Voltage "atings and "atios
The transformer should be selected to give the proper voltage at the load
terminals. This voltage is the system voltage desired, not the equipment
utiliation voltage. 0or instance, if motors are rated for *1 olts, the
transformer no-load voltage should be *B olts. This permits a voltage drop
in the feeders to the point of use.
0. Voltage ,aps
ost modern transformers have taps in the windings that make it possible to
slightly change the turns ratio. These taps do not materially affect the
voltage drop through the transformer they merely change the voltage level.
The standard for the taps in transformers used in industrial systems is two 9-
8:9= taps both above and below rated voltage. Tap changing must be
carried out with the transformer disconnected from the circuit. %owever,
load tap changing transformers are available at additional cost.
Taps are intended to ad@ust the transformer to the primary voltage level
actually present. Therefore, if the input voltage is 9-8:9= above the
nominal system voltage, the tap should be set to provide 9-8:9= more
primary turns in order to keep the secondary voltage at the design level
during operation. Taps are not intended to be used to raise or lower the
secondary voltage from the design or rated values.
"ome transformers are supplied with several taps on the secondary
windings. These permit the choice of any one of the secondary terminal
voltages appropriate to that particular tap. %owever, this is not what is
referred to as changing the taps on a transformer. "ome auto transformers
are designed to provide continuous ad@ustment of the secondary voltage by
using wires wound around a toroidal core and providing a sliding contact to
bared regions on these secondary turns. This is equivalent to having a
secondary tap for every turn.
1. ,#pes of Construction
-
8/13/2019 Operation of different types of Circuit Breaker
7/13
>iquid-filled transformers may be filled with either transformer oil or an
insulating liquid specifically designed for transformers. These liquids
perform two functions, serving as heat transfer mediums and as insulation.
#ry-type transformers are available in either ventilated or sealed
enclosures.
The physical location of the transformer is of primary importance in
determining the type of transformer to be used for a particular application.
The characteristics of a given location may preclude the use of certain types
or may make one type more desirable than another. In general, liquid-filled
and sealed dry-type transformers are suitable for indoor and outdoor
locations. 'il-filled transformers are suitable only for outdoor locations, and
may not be used indoors because of the flammability of the oil ;unless
located in a suitable fireproof vault
-
8/13/2019 Operation of different types of Circuit Breaker
8/13
Transformers may be sub@ect to overvoltages from lightning or switching
surges and should be appropriately protected. These surge handling
capabilities are described by the impulse level the amount of a momentary
voltage surge which the insulation can withstand. #ry-type transformers
with their basic insulation being air, have appro$imately one-half the
impulse level handling capability of similar kA liquid-filled transformers.
Therefore, more thought must be given to dry-type transformer situations.
6ole-top distribution transformers are frequently e$posed to these voltage
surges. That is why these transformers have the insulation on their windings
strengthened to withstand lightning ;and other< surges. The strength of this
insulation is given by the !asic Impulse >evel ;!I>< number. Enits with high
!I> numbers can be obtained at a cost premium. As an e$ample, typical
pole-top insulators for 4-8) k would have a !I> of 889 k since that is their
flash-over voltage. The transformer used on such a line should have a !I>
greater than this value.
Another insulation parameter is the insulation between primary and
secondary windings. This is essential in the application of instrument
transformers, and in applications which require isolation between circuits
;such as the filament transformers for high-voltage F-5ay tubesow-voltage transformers are generally designed to conform with the
impedance/s as shown in the T5A2"0'5(5 I6(#A2C( Table in the
Appendi$. These values are sub@ect to standard tolerances of plus-or-minus
3 percent of the nominal impedance values listed. anufacturers will design
transformers to meet other impedance requirements if the standard values
are not adequate, but this naturally adds to the cost.
Transformers with lower impedance have lower voltage drop, but will also
allow higher available fault currents. "ome devices, such as welders and arc
furnaces, use transformers that are specifically designed to have relatively
-
8/13/2019 Operation of different types of Circuit Breaker
9/13
high percent impedance/s. This is done to reduce the disturbances on the
primary power system when these devices are operating.
3. Single+$hase or ,hree+$hase ,ransformers
The recent trend is to use three-phase transformers rather than three
single-phase transformers to make up a three-phase bank. Three-phase
transformers have an e$cellent service record, cost less to install, and
require less space. If three single-phase transformers connected delta-delta
are used, the bank can still operate three-phases in the event one
transformer fails. %owever, the capacity is reduced to about +3 percent of
the original capacity and the voltages are unbalanced. Transformer failures
are rare, and the e$tra space and labor needed to connect a bank of three
instead of one three-phase unit may not be @ustified.
4. 5#e+*elta Arrangements
Another consideration when ordering transformers is the manner in which
they are connected to the system. 0or e$ample, when using three-phase
transformers, specify how the primary and secondary windings are to be
connected, whether they are to be delta or wye, and the polarity.
. !nterrupting "ating
Today/s utility transformers are capable of delivering very large currents to
a building. "hort circuits can cause high currents and electrical arcs that
generate tremendous heat and large mechanical forces in a building, which
in turn could seriously damage or destroy apparatus and conductors in a
very short time if they are not promptly interrupted. This increased short
circuit potential over the values assumed to be adequate a few years ago
should be considered whenever any transformer is changed out for a larger
one.
"ela# ,#pesThis course is not intended to make relay engineers out of youG The
discussion is limited to naming some basic operating principles, and
discussing some of the common relay applications.
-
8/13/2019 Operation of different types of Circuit Breaker
10/13
All relays provide an output signal which can be used to initiate some
action. This output signal is often used to close one or more set of contacts,
operate a circuit breaker, or a switch. "ome electronic relays provide an
output current or a voltage signal, the more elaborate programmable
controllers send digital signals which can be read by other devices. The
basic electromechanical relays, however, simply operate to close a set of
contacts when moved by either7
8. (lectromagnetic attraction, or9. (lectromagnetic induction ;turn like a motor
-
8/13/2019 Operation of different types of Circuit Breaker
11/13
connections, @oints, and connections to @oints are insulated, and the
stationary structures consist of self-supporting steel frames.
etal-clad switchgear should not be confused with metal enclosed
switchgear where the individual components are not isolated from each
other even though enclosed in a protective metal cabinet.
Single $hase $oer(5atts7 Volt+Amperes and VA"s)
'hm/s law for alternating-current circuits uses the quantity called
impedance, ;represented by the letter H
-
8/13/2019 Operation of different types of Circuit Breaker
12/13
This is called the reactive power ;or magnetiing power< and is measured
in olt-Amperes-5eactive ;A5s
-
8/13/2019 Operation of different types of Circuit Breaker
13/13
Home9 Index9 FAQs9 Appendix
http://redding.apogee.net/pd/home.asphttp://redding.apogee.net/pd/index_a.asphttp://redding.apogee.net/pd/faqs.asphttp://redding.apogee.net/pd/appendix.asphttp://redding.apogee.net/pd/home.asphttp://redding.apogee.net/pd/index_a.asphttp://redding.apogee.net/pd/faqs.asphttp://redding.apogee.net/pd/appendix.asp