Cryogenics Test Laboratory Kennedy Space Center June 29, 2015 2015 Cryogenic Engineering Conference 1 OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH GLASS BUBBLES INSULATION J. P. Sass 1 , G. Carmouche 2 , R. Hunter 3 , B. Meneghelli 1 , R. E. Obregon 2 , and J. E. Fesmire 1 1 NASA Kennedy Space Center 2 NASA Stennis Space Center 3 3M Energy and Advanced Materials Division Cryogenic Engineering Conference Tucson

Upload: others

Post on 25-May-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

June 29, 2015

2015 Cryogenic Engineering Conference

1

OPERATIONAL HISTORY OF

LIQUID HYDROGEN TANK WITH GLASS BUBBLES INSULATION

J. P. Sass1, G. Carmouche2, R. Hunter3, B. Meneghelli1,

R. E. Obregon2, and J. E. Fesmire1

1NASA Kennedy Space Center

2NASA Stennis Space Center

33M Energy and Advanced Materials Division

Cryogenic Engineering Conference

Tucson

Page 2: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Timeline History

1972 Accidental production of first glass bubbles at 3M plant in Guin, AL.

1975 Cryogenic research testing by G.R. Cunnington and C.L. Tien.

2003 Proposal to Rocket Propulsion Technology Development Board, Stennis Space

Center

2003 OSF NASA IR&D solicitation, November 2003 and Proposal, New Materials &

Technologies for Cost-Efficient Cryogenic Storage & Transfer

2003 SBIR Phase I, Cryogenic Propellant Insulation Project, Technology Applications Inc.

2004 Cost-Efficient Storage and Transfer (CESAT) proposal accepted in April, start of

project.

2004 SBIR Phase II, Cryogenic Propellant Insulation Project, Technology Applications Inc.

2005 Field demonstration of 6000 gallon LN2 tank insulation at Acme Cryogenics in

Allentown, PA (TAI, SBIR).

2007 Completion of CESAT project and presentation of six papers at the Cryogenic

Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic

Engineering.

2008 Field demonstration of 50,000 gallon LH2 tank insulation at Stennis in September

2009 Paper presented at Cryogenic Engineering Conference, Tucson, AZ on the field

demonstration at SSC and the one year boiloff performance results.

2011 Vibration/mechanical impact testing and experimentation with bulk fill materials.

2013 Paper presented at Cryogenic Engineering Conference, Spokane on the vibration

test results for glass bubbles in comparison with perlite powder and aerogel beads.

June 29, 2015

2015 Cryogenic Engineering Conference

2

Page 3: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

3

Overview

To bridge the gap between lab scale testing and massive storage tanks, a full-scale field application of glass bubbles insulation was executed using a 218,000 L liquid hydrogen storage tank at Stennis Space Center, MS

NASA/Industry shared costs under NASA HQ Innovative Partnership Project

NASA

Kennedy Space Center

Stennis Space Center

Industry

3M Energy and Advanced Materials Division

Technology Applications, Inc.

Field Demonstration

June 29, 2015

2015 Cryogenic Engineering Conference

Page 4: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Outline

Introduction

The Cryogenic Tank

Perlite Removal

Vacuum Manifold

Installation of Glass Bubbles

Bulk Delivery and Installation

Dust Collection System

Evacuation of Tank Annulus

Performance Test (2 cryo cycles)

Conclusions

4

June 29, 2015

2015 Cryogenic Engineering Conference

Page 5: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Introduction

LARGE CRYOGENIC STORAGE TANKS

~200,000 liters and up

TRADITIONAL INSULATION SYSTEM

Double-wall tank with perlite powder insulation filling the annular space

For LH2 tanks, annular space evacuated to a high vacuum level

INSULATION SYSTEM ALTERNATIVE

Glass bubbles

Mechanical characterization

System studies

1000 L tank demonstration testing

Reduced liquid hydrogen boiloff by 34%

46% reduction for degraded vacuum (100 millitorr)

5

June 29, 2015

2015 Cryogenic Engineering Conference

Page 6: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

July 19, 2007

2007 Cryogenic Engineering Conference

6

Page 7: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

7

Why Glass Bubbles?

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

0.01 0.1 1 10 100 1000

Cold Vacuum Pressure (millitorr)

Ab

solu

te k

-va

lue (

mW

/m-K

) .

A102 3M Glass Bubbles 65

A103 Perlite Powder 132

Better Thermal Performance

June 29, 2015

2015 Cryogenic Engineering Conference

Page 8: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

The Cryogenic Tank

Constructed in early 1960’s

Spherical double wall tank

Evacuated perlite annulus

Internal sphere supported by

rods near the equator

Outside sphere = 9.3 m

Inner sphere is 7.3 m

Insulation thickness = 0.90 m

Internal volume = 218,000 L

Annulus volume = 200 m3

8

June 29, 2015

2015 Cryogenic Engineering Conference

Page 9: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Perlite Removal and Inspections

Original 45 year old perlite insulation was in pristine condition

No signs of deterioration or compaction

Free-flowing

Majority of it was easily removed from the tank using vacuum trucks

connect to ports on the bottom of the tank

Technicians entered annulus to suction out small amounts of

residual perlite that was left on top of the inner sphere and in

structural catch points

Annular space was fully inspected and found to be in excellent

condition

Internal tank support structure

Internal piping

Vacuum manifold

9

June 29, 2015

2015 Cryogenic Engineering Conference

Page 10: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Installation of Glass Bubbles

10

4 Trailers

offloaded

Each offloaded

in about 1 to

1.5 hours

Could be a

continuous

operation until

nearly full

June 29, 2015

2015 Cryogenic Engineering Conference

Page 11: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Evacuation of Tank Annulus

Vacuum pump down operation lasted about two months

12 hours of pumping time over first three days to reach 13 kPa (100 torr)

After 1 month, vacuum levels were 27-67 Pa (200-500 millitorr)

After 2 months, vacuum levels were 13-40 Pa (100-300 millitorr)

Significant amounts of moisture were removed during the process

Between 13 – 0.13 kPa (100 – 1 torr)

Necessitated regular pump oil changes over the course of about 1 month

Not uncommon, no equipment damage, however used a lot of pump oil

11

0

200

400

600

800

9/24/08 12:00 9/25/08 12:00 9/26/08 12:00

Annu

lus

Pre

ssure

(to

rr)

Date and Time

Bottom

1

10

100

1,000

10,000

100,000

1,000,000

0 10 20 30 40 50

Anulu

s P

ress

ure

(10

-3to

rr)

Days

Top

Bottom

Liquid Hydrogen

Loading

June 29, 2015

2015 Cryogenic Engineering Conference

Page 12: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

2009 Performance Test

Tank filled with liquid hydrogen to 80% full

After nearly six months, the liquid level was at 66% full

Boiloff reduced by 44% compared to baseline perlite data

Stable vacuum at 1.3 Pa (10 millitorr)

12

Baseline

Perlite

Glass

Bubbles

Normal Evaporation Rate

(NER) 0.18 %/day 0.10 %/day

44 %

Reduction

Boiloff Rate 386 L/day 216 L/day

Vacuum Pressure 4.5 Pa

(34 millitorr)

1.3 Pa

(10 millitorr)

June 29, 2015

2015 Cryogenic Engineering Conference

Page 13: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

2008 – 2011 and 2013 – 2015 Performance Tests

Starting tank level for 2nd cryo cycle higher than 1st cryo cycle

Boiloff data within 2 gallons per day difference

Both cycles vacuum stable

Data collected using controls system (stores data up to 14 days)

Each data file 501 samples

Data file for second cryo cycle consistent at 4.5 days files

13

1st Cryo Cycle 2nd Cryo Cycle

Normal Evaporation Rate

(NER) 0.10 %/day 0.10 %/day

Boiloff Rate 208 L/day 201 L/day

June 29, 2015

2015 Cryogenic Engineering Conference

Page 14: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Conclusions

Full-scale glass bubbles field application completed

Logistical aspects on this scale were straightforward to execute

No special facility requirements necessary

The boiloff rate was reduced by 44% compared to perlite

Glass bubbles are an excellent high performance insulation choice

for future large storage tanks and for perlite retrofits

Glass bubbles insulation is ready to be adopted in spherical tanks

Further demonstration tests are suggested to answer questions for

more demanding tank geometries such as horizontal cylindrical

tanks

14

June 29, 2015

2015 Cryogenic Engineering Conference

Page 15: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

Potential Applications

KSC Launch Complex 39 850,000 gallon Storage Spheres

SSC LH2 barges and maybe LOX barges

Glass bubbles research for the ultimate in VJ bulk-fill insulation

systems (beating out MLI in some cases).

Glass bubbles insulation systems deployment in the world’s first LH2

tanker ship (two 240,000 gal tanks) by Kawasaki in Japan.

June 29, 2015

2015 Cryogenic Engineering Conference

15

Page 16: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

16

Acknowledgements

This work was supported by corporate and NASA funding

through the Innovative Partnerships Program administered by

NASA Headquarters

We thank Randy Galloway, Bartt Hebert, and Stan Gill of Stennis

Space Center for their vision, cooperation, and support in

bringing this full-scale field application of a laboratory

technology to fruition

We also wish to thank all of the engineers and technicians at the

E-1 Test Complex for their dedication to making this project a

success

June 29, 2015

2015 Cryogenic Engineering Conference

Page 17: OPERATIONAL HISTORY OF LIQUID HYDROGEN TANK WITH … · Engineering Conference in Chattanooga, TN for publication in Advances in Cryogenic Engineering. 2008 Field demonstration of

Cryogenics Test Laboratory

Kennedy Space Center

17

Questions?

June 29, 2015

2015 Cryogenic Engineering Conference