optimize efficiency with thermal iq and advanced …...optimize efficiency with thermal iq™ and...
TRANSCRIPT
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS
Wyatt Culler Jayson Perdue John Parker
TABLE OF CONTENTS
Abstract ......................................................................................................................................................................................... 2
Description of site issue ................................................................................................................................................................ 3
Troubleshooting and analysis ....................................................................................................................................................... 5
Conclusions ................................................................................................................................................................................... 8
Appendix. Siegert Combustion. Efficiency versus Thermal Efficiency .......................................................................................... 9
1
OPTIMZIE 2
ABSTRACT
This whitepaper shows how Thermal IQ™ and advanced analytics can be used to troubleshoot equipment and optimize efficiency. One of the plant heating boilers at the Honeywell Thermal Solutions campus in Muncie, Indiana had persistent issues with short-cycling. The short-cycling caused additional wear via thermal fatigue stress and excessive valve actuation, as well as reductions in efficiency. Thermal IQ allowed a number of potential causes of the short-cycling to be narrowed to a single root cause that could be addressed. Addressing the root cause reduced the short-cycling of the boiler and resulted in an efficiency gain of about 5%. Note that the techniques and sensors used to optimize this small heating boiler are also applicable to larger process steam boilers where they could result in larger savings.
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 3
Description of site issue
The manufacturing facility for Honeywell Thermal Solutions in Muncie, Indiana utilizes a natural gas fired boiler, pictured in Fig. 1, for plant heating. This is used as a low-pressure boiler with a nominal pressure setpoint around 10 PSI. Throughout 2019 and into 2020 this boiler would frequently short-cycle, as shown in Fig. 2. The time traces in Fig. 2 show (from top to bottom) the commanded firing rate, fuel flow, stack O2 percentage, and boiler pressure. All traces exhibit sinusoidal variations with period around 4 minutes. This unstable operation is not conducive for boiler efficiency or longevity. Some potential causes for the rapid cycling are identified in the list below. However, without adequate instrumentation it was not possible to isolate these potential root causes into an actual root cause.
1.1 Potential Root Causes
• Low condensate return
o A low condensate return could be caused by a leaky steam trap or a hole in a heat exchanger.
o Symptoms:
▪ Frequent boiler filling
▪ Frequent cycling of makeup water
▪ Temperature swings in feedwater
o Potential root causes:
▪ Frequent cycling of city water valve
▪ Steam leak necessitating frequent feedwater top offs
• Excessive feedwater flow
o Introducing too much feedwater too quickly can reduce the boiler pressure. The burner control compensates by quickly ramping up the throttle.
o Symptoms:
▪ Rapid cycling of burner throttle
▪ Rapid cycling of feedwater pumps
▪ Rapid changes in boiler pressure
o Potential root causes:
▪ Oversized feedwater pumps
▪ Faulty on/off floats
1
Figure 1. Muncie Boiler
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 4
Figure 2. Data traces showing boiler short cycling
1.2 Instrumentation and Control Upgrades
The boiler controls were upgraded to Honeywell SLATE in 2015, but the
upgrade was limited to adding the burner control system, new actuators, and
limited fuel, air, and pressure metering. The SLATE upgrade confirmed the
severity of the short-cycling issues.
In January 2020, the boiler was upgraded with additional sensors to measure
feedwater flow, freshwater flow, feedwater temperature, and combustion air
temperature.
Figure 3. SLATE Control Panel
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 5
Troubleshooting and analysis
Data collection with the new sensors was started by January 25th, 2020. Figure
4 shows representative time-series data from the new sensors. Very little
makeup water was added to the boiler (5th plot from top), indicating the rapid
cycling was not caused by a low condensate return. Additionally, the feedwater
temperature (7th plot from the top) does not appear to be low or to oscillate
significantly. However, the feedwater flow (6th plot from top) shows frequent,
high amplitude oscillations that lead the oscillations in the firing rate and fuel
flow plots (top and second from the top plots). This indicates that that
excessive feedwater flow is the root cause of the rapid oscillations in the firing
rate because it happens before the firing rate and fuel flow oscillations. The
root cause was addressed by reducing the maximum feedwater flow using a
gate valve, as the installed feedwater pumps had no adjustment on pump
pressure. The transition for the flow decrease is shown by the red region on Fig.
3. After the adjustment period the rapid oscillations in boiler firing rate were
greatly diminished. Additionally, the boiler pressure setpoint was much better
maintained after the feedwater flow adjustment.
Figure 4. Data traces before and after feedwater flow adjustment
The savings benefit of the feedwater flow adjustment is quantified by
comparing the boiler thermal efficiency both before and after the
adjustment. Note that calculating the actual thermal efficiency using
2
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 6
estimated steam flows1 is more accurate than using a Sievert combustion
efficiency calculation2. Figure 5 shows the thermal efficiency of the
boiler, where the amount of steam generated is inferred from the
feedwater flow. A time series of the daily average thermal efficiency in
black overlaid on the firing rate in red is shown in Fig. 5, while Fig. 5b
shows a histogram distribution of the daily thermal efficiencies. Before
the feedwater flowrate adjustment, the daily efficiency was around 75%
and the boiler rapidly cycled from high fire to low fire as indicated by the
nearly solid-looking red trace firing rate trace in Fig. 5. After the
feedwater flow was decreased, the thermal efficiency increased to above
80 percent. This efficiency gain translates to about a 5% savings in fuel
per year.
Figure 5. Comparison of efficiency before and after feedwater flow adjustment
Figure 6 shows a summary plot of the daily fuel cost of running the
boiler, assuming a natural gas price of $0.80 per therm. Figure 6a shows
the daily fuel cost of the boiler in black on top of the plotted firing rate in
1 It was not possible to install a steam flow meter, so steam flow was inferred using a mass balance on the feedwater flow. 2 Elaborated in the Appendix
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 7
red. Fig. 6b shows a histogram of the daily costs. It is important to note
that the daily cost depends on both boiler demand and boiler efficiency.
Although the daily fuel cost increased after the boiler feedwater flow
was optimized, Fig. 5 indicates this increase was due to increased
demand rather than lower efficiency. Assuming an average daily cost of
$300, the roughly 5% efficiency gain translates to an annual savings of
more than $5,000 per boiler.
Figure 6. Comparison of daily cost before and after feedwater flow adjustment
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 8
Conclusions
This case study has demonstrated how advanced sensors and the
capability of Thermal IQ can be used to optimize an industrial boiler.
The additional instrumentation allowed the root cause of the short-
cycling of the boiler to be identified as excessive feedwater flow, and to
be quickly remedied.
The instrumentation also allowed the thermal efficiency to be calculated,
showing how this adjustment resulted in about a 5% efficiency gain.
Finally, this case study has shown how Thermal IQ coupled with fuel flow
sensing can be used to both track the daily fuel cost on a per-asset basis
and to quantify gains in terms of dollars saved. Even greater cost savings
can be possible when applying these techniques to larger process steam
boilers.
3
OPTIMIZE EFFICIENCY WITH THERMAL IQ™ AND ADVANCED ANALYTICS 9
Appendix: Siegert Combustion Efficiency versus Thermal Efficiency
Siegert Combustion Efficiency versus Thermal Efficiency
Efficiency in indirect heating applications such as boilers is sometimes
modeled using the Siegert equation (also known as the combustion
efficiency equation or similar variants). This semi-empirical equation
takes the form of equation 1, using the assumptions of equation 2,
where A and B are constants that vary by fuel. For natural gas, A is taken
as 0.66 and B is 0.009. This equation only models the stack heat loss and
assumes that all other heat losses (such as radiation) are negligible.
𝜂 = 100% − 𝑄𝑆𝑡𝑎𝑐𝑘(%)
𝑆𝑡𝑎𝑐𝑘𝐿𝑜𝑠𝑠 = (𝑇𝑆𝑡𝑎𝑐𝑘 − 𝑇𝐶𝑜𝑚𝑏𝑢𝑠𝑡𝑖𝑜𝑛𝐴𝑖𝑟) (𝐴
21 −%𝑂2+ 𝐵)
Figure A.1. shows the combustion efficiency of the Muncie boiler
calculated using equation 2. This equation yields an efficiency around
90%. This is significantly higher than the thermal efficiency shown in Fig.
4 and the efficiency estimates provided by the boiler manufacturer.
Thus, the Siegert method of calculating combustion efficiency over-
predicts the actual thermal efficiency of a boiler.
Figure A.1. Comparison of efficiency before and after flow adjustment
4
References [1] Ministry of Fuel and Power. The Efficient Use of Fuel. H.M. Stationery Office. 1944. [2] TSI Incorporated. Combustion Analysis Basics. Tech. Rep. P/N 2980175, Rev. B, TSI. 2004.
For More Information
www.ThermalSolutions.Honeywell.com
Honeywell Process Solutions
Honeywell Thermal Solutions 2101 City West Blvd
Houston TX 77042
WP-20-03-ENG I 03/20
© 2020 Honeywell International Inc.