orrfire product catalogue - orrcon steel · when orrfire® hot dipped galvanised pipe is roll...

16
we’ll see it through ORRFIRE ® Product Catalogue Sprinkler & Hydrant Pipe

Upload: lamtuyen

Post on 17-Apr-2018

239 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

we’ll see it through

ORRFIRE® Product CatalogueSprinkler & Hydrant Pipe

Page 2: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

Orrcon Steel is a leading Australian distributor and manufacturer of Steel, Tube and Pipe.

We have distribution centres in five Australian states and a number of branches, stockists and resellers nation-wide.

Orrcon Steel adheres to principles of quality, innovation, flexibility and dedication. These principles are achieved by going the extra mile in everything we do and working in partnership with our customers and suppliers.

At Orrcon Steel – we’ll see it through.

ORRFIRE® Pipe is a leading product specifically designed

for pressure reticulation in commercial and industrial fire

protection applications.

All Orrcon Steel ORRFIRE® products offered to the fire

protection market have ActivFire® Scheme* approval and are

listed under the register of fire protection equipment.

Orrcon Steel ORRFIRE® products cover a diverse range of

wall thicknesses and diameters from extra light through

to medium wall and 25NB through to 300NB. A variety of

surface finishes are available for use in the fire protection

industry, from sprinkler systems through to hydrants.

*ActivFire® Scheme is a registered trademark of CSIRO - MSE

2 | ORRFIRE® Product Catalogue

Page 3: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

we’ll see it through

ORRFIRE® PIPEORRFIRE® Pipe is available as sprinkler and hydrant pipe. All sprinkler and hydrant pipe products are designed to comply with AS 4118.2.1 and AS 2419.ORRFIRE® finishes include:• SMARTCOTE® (painted in Red Gum finish)• ALLGAL® inline zinc coating• Hot Dipped Galvanised.

SMARTCOTE® SPRInklER PIPESMARTCOTE® painted sprinkler pipe is a leading Australian made product designed for pressure reticulation in commercial and industrial fire protection applications. SMARTCOTE® is a water based acrylic primer applied to a nominal 20 micron thickness. A Red Gum* coloured primer is applied to the external surface of the steel using Orrcon Steel’s SMARTCOTE® technology. ORRFIRE® SMARTCOTE® is designed for use in “closed systems” only, such as fire sprinkler assemblies. SMARTCOTE® painted firepipe is easy to weld and as a keyed primer can be readily painted over if necessary. SMARTCOTE® painted pipe is approved by the ActivFire® Scheme for use in fire protection systems and is covered by afp 1510, 1511, 1641 and 2481 certificates of conformity.

SMARTCOTE® – VOC Specification SMARTCOTE® painted pipe is a finished product that has zero Volatile Organic Compounds (VOC’s) with respect to the ‘Green Star’ building rating as it arrives onsite pre-primed. SMARTCOTE® complies with Australian Standards on paint formulation and as such does not contain any of the following:• Glycol Ethers• Prohibited, restricted or carcinogenic substances• Heavy metals• Ozone depleting substances

*The manufactured colour of the SMARTCOTE® pipe is Red Gum. The colour of the SMARTCOTE® pipe shown in this brochure can vary due to the post painting application of Fire Red carried out on specified projects.

AllGAl® SPRInklER PIPE

ORRFIRE® ALLGAL® is an Australian made sprinkler pipe product that is manufactured using an inline zinc-coated steel feed strip.

ALLGAL® is easy to weld and can be either ‘touched up’ in weld areas with zinc paint and installed as supplied or painted if necessary.

It is approved by the ActivFire® Scheme for use in fire protection systems and is covered by afp 1508, 1509, 1528 and 1640 certificates of conformity.

HOT DIPPED GAlVAnISED SPRInklER & HYDRAnT PIPE

ORRFIRE® Hot Dipped Galvanised Pipe is an Australian made product specifically manufactured for the Fire and Industrial Plumbing Industries.

It undergoes a hot dipped galvanising process prior to being made available for use in the fire protection (sprinkler and hydrant) and other associated reticulation industries.

ORRFIRE® Hot Dipped Galvanised Pipe is zinc galvanised on both the internal and external surfaces with a minimum coating weight of 300g/m2 applied in accordance with AS 4792.

The latest galvanising technology is applied to the product and it is designed for use in ‘open reticulation systems’ where oxygenated water is transported.

ORRFIRE® Hot Dipped Galvanised Pipe is approved by the ActivFire® Scheme for use in fire protection and hydrant systems and is covered by afp 1529 and 1530 certificates of conformity.

Note: The availability of Hot Dipped Galvanised Sprinkler & Hydrant

Pipe is subject to availability. Please contact your local Orrcon Steel

Representative for more information.

3we’ll see it through

Page 4: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

EquIPMEnT lISTInG SCHEME

All Orrcon Steel products offered to the fire protection market have ActivFire® Scheme approval and are listed under the register of fire protection equipment. ActivFire® Scheme is your assurance that Orrcon Steel products have met the stringent requirements of CSIRO’s accreditation process. All Orrcon Steel ActivFire® certified products are deemed to comply with the following standards:

• AS 2419.1 - Fire Hydrant Installations

• AS 4118.2.1 - Fire Sprinkler Systems - Piping - General

• AS 1074 - Steel tubes and tubulars for ordinary services

The CSIRO ActivFire® Scheme for certification and listing of ActivFire® protection equipment includes the following objectives:1

• To verify the conformity (compliance) of equipment through physical testing and appraisal to relevant and endorsed standards and specifications (reference criteria).

• To verify and recognise approvals and certifications by other national and International bodies.

• To provide an effective and transparent mechanism for appraisal, testing, certification and listing of emerging and new technologies in the field of active fire protection equipment and systems.

• To provide reference documentation and information which supports the various building regulation and authority requirements for “evidence of suitability” for equipment used in building construction.

• To maintain a continuing process that provides means by which the conformity of changes to products can be submitted and verified.

• To maintain a Register of Fire Protection Equipment to publicly list and promote products which meet established reference criteria for listing.

Procedures and mechanisms for monitoring compliance and performance can vary. Listed products are identified in the Register of Fire Protection Equipment. This resource exists primarily as an on-line database accessed through the website www.activfire.gov.au. Information is also provided online such as product listing data sheets published for many of ActivFire’s® registered listings and technical specifications.

1 Reference: CSIRO ActivFire® protection – product certification viewed 23/07/12, http://activfire.gov.au.

4 | ORRFIRE® Product Catalogue

Page 5: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

Product Designation ActivFire® Scheme Approval Listing Number

ORRFIRE® SMARTCOTE® Painted Red Gum Extra Light pipe afp 1641

ORRFIRE® SMARTCOTE® Painted Red Gum Light pipe afp 1510

ORRFIRE® SMARTCOTE® Painted Red Gum Medium pipe afp 1511

ORRFIRE® SMARTCOTE® Painted Red Gum Sprinkler & Hydrant pipe - Extra Light and Light afp 2481

ORRFIRE® ALLGAL® Zinc Coated Extra Light pipe afp 1640

ORRFIRE® ALLGAL® Zinc Coated Extra Light pipe - 100NB and above afp 1528

ORRFIRE® ALLGAL® Zinc Coated Light pipe afp 1508

ORRFIRE® ALLGAL® Zinc Coated Medium pipe afp 1509

ORRFIRE® Hot Dipped Galvanised Sprinkler & Hydrant pipe - Extra Light and Light afp 1529

ORRFIRE® Hot Dipped Galvanised Sprinkler & Hydrant pipe - Medium afp 1530

Current ActivFire® Scheme approvals are listed below. Copies of ActivFire® Scheme certificates are available from www.orrconsteel.com.au/downloads

5we’ll see it through

Page 6: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

MAnuFACTuRInG

Leak tightness is in accordance with AS1074 using inline eddy current testing. This is equivalent to a hydrostatic pressure of 500kPa.

The internal weld bead of the pipe is not removed, however the external weld bead is scalped flush with the outer surface of the pipe prior to painting or zinc repair.

The standard end finish is plain end. A range of optional end treatments are available subject to enquiry, including roll grooved ends and threaded one end (refer to page 8 for specifications).

The standard stock length available is 6.5 metres. Non standard lengths up to 12 metres are available ex rollings subject to enquiry.

MAnuFACTuRInG TOlERAnCES

Tolerances applicable to ORRFIRE® Sprinkler Pipe are:

localised Wall Thickness: Not less than 10% of nominal wall thickness.

Linear Mass: - 4.0% to +10% for any length.

Straightness: Deviation from straight line = stock length (6.5m) / 250.

Length: Standard stock length tolerance is +50mm, - 0mm, on nominal length supplied. Special cut lengths + 6mm to 0mm tolerance is subject to enquiry.

PIPE MARkInG

Each straight length of pipe is permanently marked once per length with information on the manufacturer, size, wall thickness and grade. The minimum height of the lettering is 15mm.

SMARTCOTE® SPRInklER PIPE - APPlICATIOnS AnD RECOMMEnDED uSE

Applications:

• Fire sprinkler system applications for all “closed” oxygenated systems.

• Hydraulic installations and compressed air services.

• Heating, ventilation and air conditioning systems with “closed” pipe work systems.

Recommended Use:

• Extra light and light wall SMARTCOTE® is suitable for use with all reputable roll grooved coupling systems.

• Medium wall SMARTCOTE® can be used with threaded or roll grooved jointing systems.

AllGAl® SPRInklER PIPE - APPlICATIOnS AnD RECOMMEnDED uSE

Applications:

• Fire sprinkler applications for all “closed” non-oxygenated systems.

• Hydraulic installations and compressed air services.

• Heating, ventilation and air conditioning with “closed” pipe work systems.

Recommended Use:

• Extra light and light wall ALLGAL® pipe is suitable for use with all reputable roll grooved coupling systems.

• Medium wall ALLGAL® pipe can be used with threaded or roll grooved jointing systems.

6 | ORRFIRE® Product Catalogue

Page 7: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

ORRFIRE® HOT DIPPED GAlVAnISED PIPE - APPlICATIOnS AnD RECOMMEnDED uSE

Applications:

• Fire system applications for all “open” oxygenated systems.

• Industrial plumbing and mechanical services.

• Hydraulic installations and compressed air services.

• Mining air / water services.

• Building services and heating, Ventilation and Air Conditioning (H.V.A.C).

• Process plant pipelines.

Recommended Use:

• Substitution of light wall spiral welded, plastic ductile iron and copper pipes in reticulation applications.

HOT DIPPED GAlVAnISED PIPE - MECHAnICAl JOInTInG SYSTEMS

• All pipe wall thicknesses listed in the ORRFIRE® pipe range table are suitable for use with all approved roll grooved or shouldered couplings.

• Where threaded systems are used, only medium and heavy wall pipe is acceptable.

•Hot Dipped Galvanised pipe is approved for use in underground applications when used with ActivFire® Scheme UL or FM approved coupling systems. Hot Dipped Galvanised Pipe is approved for underground applications in accordance with AS 4118.2.1 and AS 2419.1 provided that suitable external pipe corrosion protection is provided.

HOT DIPPED GAlVAnISED PIPE -CORROSIOn PROTECTIOn

Buried Service

Orrcon Steel ORRFIRE® Hot Dipped Galvanised Pipe, when buried underground, must be further protected from external corrosion by:

• Coating with a high density polyethylene plastic jacket or wrapped with a polyethylene tape of minimum thickness 1.0mm applied in accordance with Australian Standard AS1518; Or

• Wrapping in a reputable proprietary petrolatum based tape (eg. Denso) with a minimum of 1.3mm thickness which is over-wrapped with a self-adhesive polyethylene tape with minimum thickness of 225 microns, applied as per manufacturers guidelines.

Mechanical fittings and couplings must also be similarly prepared when installed in buried applications.

Coating Repairs

Damaged coating must be repaired to ensure the integrity of internal and external corrosion resistance. The damaged area should be cleaned with a wire brush and have a quality zinc rich paint (e.g ALLGAL® paint) applied to a minimum thickness in accordance with the paint manufacturers recommendations.

When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired by this method. Refer to Australian Standard AS1650 Appendix F -1989 Hot Dipped Galvanised Coatings on Ferrous Articles for further details.

7we’ll see it through

Page 8: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

ORRFIRE® PIPE SPECIFICATIOnS

DIAMETER TOlERAnCE – ORRFIRE® PIPEDiameter Range (mm)

Nominal Bore Diameter (NB) 20 25 32 40 50 65 80 100 125 150 - 200 250 300

Outside Diameter (OD) 26.9 33.7 42.4 48.3 60.3 76.1 88.9 114.3 139.7 165.1 168.3 219.1 273.1 323.9

Minimum OD 26.63 33.36 41.98 47.82 59.70 75.34 88.01 113.16 138.30 163.45 166.62 216.91 270.37 320.66Maximum OD 27.17 34.04 42.82 48.78 60.90 76.86 89.79 115.44 141.10 166.75 169.98 221.29 275.83 327.14

NOTE: • Outside diameter is fixed for all wall thicknesses.

MECHAnICAl PROPERTIES – ORRFIRE® PIPE

Pipe Dimensions Minimum Yield Strength

Minimum Tensile Strength

Minimum Elongation as a proportion of

gauge length

light Wall Pipe20 TO 150 nB

(3/4 TO 6 INCH)350 MPa 430 MPa 20%

Medium Wall Pipe20 TO 150 nB

(3/4 TO 6 INCH)250 MPa 350 MPa 22%

Schedule200 TO 300 nB (8 TO 12 INCH)

350 MPa 430 MPa 20%

THREADInG SPECIFICATIOnS - ORRFIRE® PIPE

End Treatment Min Diameter (mm) Max Diameter (mm) Min Thickness (mm) Max Thickness (mm)

Threading 25NB 50NB 3.2 4.5

ROll GROOVInG SPECIFICATIOnS - ORRFIRE® PIPE

End Treatment Diameter (mm) Min Thickness* (mm) Max Thickness (mm)

Roll Grooving

50NB 2.3 3.6

65NB 2.3 3.6

80NB 2.6 4.0

100NB 2.5 4.5

125NB 3.0

150NB 3.0

200NB 4.8

250NB 4.8 NOTE: • * Contact your Orrcon Steel Representative for minimum thicknesses outside the listed range.

• Contact your Orrcon Steel Representative for maximum thicknesses which are not listed for the specified diameter pipe.

8 | ORRFIRE® Product Catalogue

Page 9: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

ORRFIRE® PIPE RAnGE

Section: ORRFIRE® Pipe - Sprinkler and Hydrant PipeStandard: AS 4118.2.1 / AS 2419.1 / ActivFire® SchemeSurface Finish: SMARTCOTE® / ALLGAL® /Hot Dipped Galvanised*

OD(mm)

nB(mm)

Nominal Thickness

(mm)

DesignationSurface Finish Nominal

Linear Mass (Kg/m)

Nominal Metres /

Tonne(m/t)

Lengths / Pack

Lengths / MiniPakSMARTCOTE® ALLGAL®

6500mm Lengths Standard26.7 20 2.0 XLight ü ü 1.23 814 127 6126.7 20 2.3 Light ü ü 1.40 717 127 6126.7 20 2.6 Medium ü ü 1.56 642 127 6133.4 25 2.0 XLight ü ü 1.56 639 91 3733.4 25 2.6 Light ü ü 1.99 501 91 3733.4 25 3.2 Medium ü ü 2.41 415 91 3742.2 32 2.0 XLight ü ü 1.99 501 61 3742.2 32 2.6 Light ü ü 2.55 392 61 3742.2 32 3.2 Medium ü ü 3.09 323 61 3748.3 40 2.3 XLight ü ü 2.61 383 61 3748.3 40 2.9 Light ü ü 3.25 308 61 3748.3 40 3.2 Medium ü ü 3.56 280 61 3760.3 50 2.3 XLight ü ü 3.29 304 37 1960.3 50 2.9 Light ü ü 4.11 244 37 1960.3 50 3.6 Medium ü ü 5.03 199 37 1976.1 65 2.3 XLight ü ü 4.19 239 37 1976.1 65 3.2 Light ü ü 5.75 174 37 1976.1 65 3.6 Medium ü ü 6.44 155 37 1988.9 80 2.6 XLight ü ü 5.53 181 - -88.9 80 3.2 Light ü ü 6.76 148 - -88.9 80 4.0 Medium ü ü 8.38 119 - -

114.3 100 2.5 - ü ü 6.89 145 - -114.3 100 3.2 XLight ü ü 8.76 114 - -114.3 100 3.6 Light ü ü 9.83 102 - -114.3 100 4.5 Medium ü ü 12.20 82 - -139.7 125 3.0 XLight ü ü 10.11 99 - -139.7 125 3.5 Light ü ü 11.08 85 - -139.7 125 5.0 Medium ü ü 16.60 60 - -165.1 150 3.0 XLight ü ü 11.99 83 - -165.1 150 3.5 Light ü ü 13.90 72 - -165.1 150 5.0 Medium ü ü 19.70 51 - -

Refer Notes Page 10

Table Continues Over Page

9we’ll see it through

Page 10: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

ORRFIRE® PIPE RAnGE COnT...

Section: ORRFIRE® Pipe - Sprinkler and Hydrant PipeStandard: AS 4118.2.1 / AS 2419.1 / ActivFire® SchemeSurface Finish: SMARTCOTE® / ALLGAL® /Hot Dipped Galvanised*

OD(mm)

nB(mm)

Nominal Thickness

(mm)

DesignationSurface Finish Nominal

Linear Mass (Kg/m)

Nominal Metres /

Tonne(m/t)

Lengths / Pack

Lengths / MiniPakSMARTCOTE® ALLGAL®

165.1 150 5.4 Heavy ü ü 21.30 47 - -12000mm Lengths Standard

168.3 - 4.8 - 19.35 52 - -168.3 - 6.4 - 25.55 39 - -219.1 200 4.8 - 25.37 39 - -219.1 200 6.4 - 33.57 30 - -273.1 250 4.8 - 31.76 31 - -273.1 250 6.4 - 42.09 24 - -323.9 300 4.8 - 37.77 26 - -355.6 350 4.8 - 41.53 24 - -

NOTES: • Recommended maximum test pressure is 5000 kPa / 725 Psi.• The pipe must be supported to avoid all external loads and free to accommodate thermal expansion.• Refer to page 8 for the mechanical properties of ORRFIRE® Pipe.• These tables are applicable for services where pipe contents temperature does not exceed 250 C̊.• Pipe 20NB up to 150NB is painted in Red Gum acrylic primer.• Pipe 200NB and above is painted in black acrylic primer.• Hot Dipped Galvanised pipe is available subject to enquiry.• Non standard sizes, surface finishes and lengths available, subject to enquiry. Minimum order quantities (MOQ’s) apply.

10 | ORRFIRE® Product Catalogue

Page 11: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

PRESSuRE DROP & FlOW RATES

The development of lighter wall, higher grade steel pipe for use with mechanical jointing / coupling has offered reduced costs for the industry in both material and labour costs. A further extension of this development is the opportunity to vary pipe design sizes and the type of pipe product used in a project by incorporating the reduced pressure-drop offered by light wall steel pipes.

The tables on the following pages are intended to assist pipe fabrication designers in optimising the use of mechanically jointed light wall steel pipes in either SMARTCOTE®, ALLGAL® or Hot Dipped Galvanised Pipes.

11we’ll see it through

Page 12: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

4 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 5

00

5

10

15

25

20

30

40 60 120 160

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

20 N OMIN A L P IP E S IZE D I ME N S IO N S

20 N OM IN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 26.90 26.90 19.01 26.75 Norm Thick (mm) = 2.60 2.00 1.02 1.55 Norm Mean I.D. (mm) = 21.70 22.90 16.97 23.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

5

10

15

20

50 100 200150 250

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

2 5 N O MI N A L P IP E S IZ E D I M E N S I O N S

2 5 N O MI N A L S IZ E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 33.70 33.70 25.35 33.55 Norm Thick (mm) = 3.20 2.00 1.22 1.90 Norm Mean I.D. (mm) = 27.30 29.40 22.91 29.75 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

32 N O MIN A L P IP E S IZE D IME N S IO N S

32 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 42.40 42.40 31.70 42.25 Norm Thick (mm) = 3.20 2.00 1.22 2.40 Norm Mean I.D. (mm) = 36.00 38.20 29.26 37.45 Surface roughness K = 4.50 4.50 1.50 1.50

00

4

8

12

16

100 200 400300 500

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min0

0

4

2

8

6

10

12

14

100 200 400300 600500 700PR

ESSU

RE

DR

OP

kPa/

mFLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

40 N OMIN A L P I P E S IZE D IME N S ION S

40 N OMIN A L S I ZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 48.30 48.30 38.50 48.25 Norm Thick (mm) = 3.20 2.30 1.22 2.75 Norm Mean I.D. (mm) = 41.90 43.70 35.61 42.75 Surface roughness K = 4.50 4.50 1.50 1.50

PRESSuRE DROP & FlOW RATES

4 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 5

00

5

10

15

25

20

30

40 60 120 160

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

20 N OMIN A L P IP E S IZE D I ME N S IO N S

20 N OM IN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 26.90 26.90 19.01 26.75 Norm Thick (mm) = 2.60 2.00 1.02 1.55 Norm Mean I.D. (mm) = 21.70 22.90 16.97 23.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

5

10

15

20

50 100 200150 250

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

2 5 N O MI N A L P IP E S IZ E D I M E N S I O N S

2 5 N O MI N A L S IZ E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 33.70 33.70 25.35 33.55 Norm Thick (mm) = 3.20 2.00 1.22 1.90 Norm Mean I.D. (mm) = 27.30 29.40 22.91 29.75 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

32 N O MIN A L P IP E S IZE D IME N S IO N S

32 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 42.40 42.40 31.70 42.25 Norm Thick (mm) = 3.20 2.00 1.22 2.40 Norm Mean I.D. (mm) = 36.00 38.20 29.26 37.45 Surface roughness K = 4.50 4.50 1.50 1.50

00

4

8

12

16

100 200 400300 500

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min0

0

4

2

8

6

10

12

14

100 200 400300 600500 700

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

40 N OMIN A L P I P E S IZE D IME N S ION S

40 N OMIN A L S I ZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 48.30 48.30 38.50 48.25 Norm Thick (mm) = 3.20 2.30 1.22 2.75 Norm Mean I.D. (mm) = 41.90 43.70 35.61 42.75 Surface roughness K = 4.50 4.50 1.50 1.50

20 NOMiNal BOre PiPe Size

20 NOMiNal BOre PiPe Size DiMeNSiONS

4 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 5

00

5

10

15

25

20

30

40 60 120 160

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

20 N OMIN A L P IP E S IZE D I ME N S IO N S

20 N OM IN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 26.90 26.90 19.01 26.75 Norm Thick (mm) = 2.60 2.00 1.02 1.55 Norm Mean I.D. (mm) = 21.70 22.90 16.97 23.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

5

10

15

20

50 100 200150 250

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

2 5 N O MI N A L P IP E S I Z E D I M E N S I O N S

2 5 N O M I N A L S IZ E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 33.70 33.70 25.35 33.55 Norm Thick (mm) = 3.20 2.00 1.22 1.90 Norm Mean I.D. (mm) = 27.30 29.40 22.91 29.75 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

32 N O MIN A L P IP E S IZE D IME N S I O N S

32 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 42.40 42.40 31.70 42.25 Norm Thick (mm) = 3.20 2.00 1.22 2.40 Norm Mean I.D. (mm) = 36.00 38.20 29.26 37.45 Surface roughness K = 4.50 4.50 1.50 1.50

00

4

8

12

16

100 200 400300 500

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min0

0

4

2

8

6

10

12

14

100 200 400300 600500 700

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

40 N OMIN A L P I P E S IZE D IME N S ION S

40 N OMIN A L S I ZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 48.30 48.30 38.50 48.25 Norm Thick (mm) = 3.20 2.30 1.22 2.75 Norm Mean I.D. (mm) = 41.90 43.70 35.61 42.75 Surface roughness K = 4.50 4.50 1.50 1.50

25 NOMiNal BOre PiPe Size

25 NOMiNal BOre PiPe Size DiMeNSiONS

12 | ORRFIRE® Product Catalogue

Page 13: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

6 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 7

00

4

2

8

6

10

100 200 400300 600500 700 800 900 1000

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

5 0 N OMI N A L P IP E S IZE D I ME N S I O N S

50 N O MIN A L S IZE P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 60.30 60.30 50.74 60.35 Norm Thick (mm) = 3.60 2.30 1.22 3.35 Norm Mean I.D. (mm) = 53.10 55.70 48.30 53.65 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

65 N OMIN A L P IP E S IZE D IME N S I O N S

65 N OMIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 76.10 76.10 63.43 75.35 Norm Thick (mm) = 3.60 2.30 1.22 4.20 Norm Mean I.D. (mm) = 68.90 71.50 60.99 66.95 Surface roughness K = 4.50 4.50 1.50 1.50

00

2

1

3

5

7

4

6

8

200 400 800 1000 1200 1400 1600600 1800

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

00

2

1

4

3

5

6

7

200 400 800600 12001000 1400 1600 1800 2000 2200 2400

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

8 0 N OM I N A L P I P E S I Z E D I M E N S I O N S

8 0 N OM I N A L S I Z E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 88.90 88.90 76.11 88.90 Norm Thick (mm) = 4.00 2.60 1.53 4.95 Norm Mean I.D. (mm) = 80.90 83.70 72.85 79.00 Surface roughness K = 4.50 4.50 1.60 1.50

00

2

1

4

3

5

500 1000 20001500 30002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

9 0 N O M I N A L P I P E S IZ E D I ME N S I O N S

9 0 N O M I N A L S I ZE P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 101.60 101.60 88.80 101.50 Norm Thick (mm) = 4.00 2.60 1.63 5.55 Norm Mean I.D. (mm) = 93.60 96.40 85.54 90.40 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

4 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 5

00

5

10

15

25

20

30

40 60 120 160

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

20 N OMIN A L P IP E S IZE D I ME N S IO N S

20 N OM IN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 26.90 26.90 19.01 26.75 Norm Thick (mm) = 2.60 2.00 1.02 1.55 Norm Mean I.D. (mm) = 21.70 22.90 16.97 23.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

5

10

15

20

50 100 200150 250

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

2 5 N O MI N A L P IP E S IZ E D I M E N S I O N S

2 5 N O MI N A L S IZ E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 33.70 33.70 25.35 33.55 Norm Thick (mm) = 3.20 2.00 1.22 1.90 Norm Mean I.D. (mm) = 27.30 29.40 22.91 29.75 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

32 N O MIN A L P IP E S IZE D IME N S IO N S

32 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 42.40 42.40 31.70 42.25 Norm Thick (mm) = 3.20 2.00 1.22 2.40 Norm Mean I.D. (mm) = 36.00 38.20 29.26 37.45 Surface roughness K = 4.50 4.50 1.50 1.50

00

4

8

12

16

100 200 400300 500

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min0

0

4

2

8

6

10

12

14

100 200 400300 600500 700

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

40 N OMIN A L P I P E S IZE D IME N S ION S

40 N OMIN A L S I ZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 48.30 48.30 38.50 48.25 Norm Thick (mm) = 3.20 2.30 1.22 2.75 Norm Mean I.D. (mm) = 41.90 43.70 35.61 42.75 Surface roughness K = 4.50 4.50 1.50 1.50

PRESSuRE DROP & FlOW RATES

40 NOMiNal BOre PiPe Size

50 NOMiNal BOre PiPe Size

65 NOMiNal BOre PiPe Size

40 NOMiNal BOre PiPe Size DiMeNSiONS

50 NOMiNal BOre PiPe Size DiMeNSiONS

65 NOMiNal BOre PiPe Size DiMeNSiONS

4 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 5

00

5

10

15

25

20

30

40 60 120 160

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

20 N OMIN A L P IP E S IZE D I M E N S IO N S

20 N OM IN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 26.90 26.90 19.01 26.75 Norm Thick (mm) = 2.60 2.00 1.02 1.55 Norm Mean I.D. (mm) = 21.70 22.90 16.97 23.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

5

10

15

20

50 100 200150 250

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

2 5 N O MI N A L P IP E S IZ E D I M E N S I O N S

2 5 N O MI N A L S IZ E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 33.70 33.70 25.35 33.55 Norm Thick (mm) = 3.20 2.00 1.22 1.90 Norm Mean I.D. (mm) = 27.30 29.40 22.91 29.75 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

32 N O MIN A L P IP E S IZE D IME N S I O N S

32 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 42.40 42.40 31.70 42.25 Norm Thick (mm) = 3.20 2.00 1.22 2.40 Norm Mean I.D. (mm) = 36.00 38.20 29.26 37.45 Surface roughness K = 4.50 4.50 1.50 1.50

00

4

8

12

16

100 200 400300 500

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min0

0

4

2

8

6

10

12

14

100 200 400300 600500 700

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

40 N OMIN A L P I P E S IZE D IME N S ION S

40 N OMIN A L S I ZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 48.30 48.30 38.50 48.25 Norm Thick (mm) = 3.20 2.30 1.22 2.75 Norm Mean I.D. (mm) = 41.90 43.70 35.61 42.75 Surface roughness K = 4.50 4.50 1.50 1.50

32 NOMiNal BOre PiPe Size DiMeNSiONS

32 NOMiNal BOre PiPe Size

13we’ll see it through

Page 14: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

8 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 9

00

2

1

4

3

5

500 1000 20001500 3000 3500 40002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 00 N O MI N A L P IP E S IZ E D IM E N S ION S

1 0 0 N O MIN A L S IZ E P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 114.30 114.30 101.48 114.30 Norm Thick (mm) = 4.50 2.50 1.63 6.30 Norm Mean I.D. (mm) = 105.30 109.30 95.22 101.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

00

1

0.5

2

1.5

2.5

3

3.5

1000 2000 40003000 60005000 7000 8000 9000

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 5 0 N O M IN A L P I P E S I ZE D I M E N S I O N S

1 5 0 N O M IN A L S I Z E P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 165.10 165.10 152.25 160.25 Norm Thick (mm) = 5.00 3.00 2.03 8.80 Norm Mean I.D. (mm) = 155.10 159.10 148.19 142.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

2

2.5

0.5

1

1.5

4

3

3.5

4.5

500 1000 20001500 30002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

12 5 N OM IN A L P IP E S IZE D IM E N S I O N S

1 25 N O MI N A L S I ZE P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 139.70 139.70 126.88 140.20 Norm Thick (mm) = 5.00 3.00 1.63 7.65 Norm Mean I.D. (mm) = 129.70 133.70 123.62 124.90 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min0

0

1

0.5

2

1.5

2.5

3000 6000 9000 12000 15000PR

ESSU

RE

DR

OP

kPa/

m

ASTM A 53 SCHEDULE 40AS 1432 COPPER (Grade B)

200 N OMI N A L P IP E S IZE D IME N S I ON S

200 N OMI N A L S IZE P IP E

ORRFIRE® LIGHTAS 1477 CPVC (Class 12)

ASTM A 53 ORRFIRE® AS1432 Copper AS1477 CPVC Sch 40 Light (Grade B) (Class 12) Mean O.D. (mm) = 219.10 219.10 203.00 225.30 Norm Thick (mm) = 7.11 4.80 2.03 12.30 Norm Mean I.D. (mm) = 204.88 209.50 198.94 200.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

8 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 9

00

2

1

4

3

5

500 1000 20001500 3000 3500 40002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 00 N O MI N A L P IP E S IZ E D IM E N S ION S

1 0 0 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 114.30 114.30 101.48 114.30 Norm Thick (mm) = 4.50 2.50 1.63 6.30 Norm Mean I.D. (mm) = 105.30 109.30 95.22 101.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

00

1

0.5

2

1.5

2.5

3

3.5

1000 2000 40003000 60005000 7000 8000 9000

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 5 0 N O M IN A L P I P E S I ZE D I M E N S I O N S

1 5 0 N O M IN A L S I Z E P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 165.10 165.10 152.25 160.25 Norm Thick (mm) = 5.00 3.00 2.03 8.80 Norm Mean I.D. (mm) = 155.10 159.10 148.19 142.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

2

2.5

0.5

1

1.5

4

3

3.5

4.5

500 1000 20001500 30002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

12 5 N OM I N A L P I P E S I Z E D IM E N S I ON S

1 25 N O M I N A L S I Z E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 139.70 139.70 126.88 140.20 Norm Thick (mm) = 5.00 3.00 1.63 7.65 Norm Mean I.D. (mm) = 129.70 133.70 123.62 124.90 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min0

0

1

0.5

2

1.5

2.5

3000 6000 9000 12000 15000

PRES

SUR

E D

RO

P kP

a/m

ASTM A 53 SCHEDULE 40AS 1432 COPPER (Grade B)

200 N OMI N A L P IP E S IZE D IME N S I ON S

200 N OMI N A L S IZE P IP E

ORRFIRE® LIGHTAS 1477 CPVC (Class 12)

ASTM A 53 ORRFIRE® AS1432 Copper AS1477 CPVC Sch 40 Light (Grade B) (Class 12) Mean O.D. (mm) = 219.10 219.10 203.00 225.30 Norm Thick (mm) = 7.11 4.80 2.03 12.30 Norm Mean I.D. (mm) = 204.88 209.50 198.94 200.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

6 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 7

00

4

2

8

6

10

100 200 400300 600500 700 800 900 1000

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

5 0 N OMI N A L P IP E S IZE D I ME N S IO N S

50 N O MIN A L S IZE P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 60.30 60.30 50.74 60.35 Norm Thick (mm) = 3.60 2.30 1.22 3.35 Norm Mean I.D. (mm) = 53.10 55.70 48.30 53.65 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

65 N OMIN A L P IP E S IZE D IME N S IO N S

65 N OMIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 76.10 76.10 63.43 75.35 Norm Thick (mm) = 3.60 2.30 1.22 4.20 Norm Mean I.D. (mm) = 68.90 71.50 60.99 66.95 Surface roughness K = 4.50 4.50 1.50 1.50

00

2

1

3

5

7

4

6

8

200 400 800 1000 1200 1400 1600600 1800

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

00

2

1

4

3

5

6

7

200 400 800600 12001000 1400 1600 1800 2000 2200 2400

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

8 0 N OM I N A L P I P E S I Z E D I M E N S I O N S

8 0 N OM I N A L S I Z E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 88.90 88.90 76.11 88.90 Norm Thick (mm) = 4.00 2.60 1.53 4.95 Norm Mean I.D. (mm) = 80.90 83.70 72.85 79.00 Surface roughness K = 4.50 4.50 1.60 1.50

00

2

1

4

3

5

500 1000 20001500 30002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

9 0 N OM I N A L P I P E S IZ E D I M E N S I O N S

9 0 N OM I N A L S I ZE P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 101.60 101.60 88.80 101.50 Norm Thick (mm) = 4.00 2.60 1.63 5.55 Norm Mean I.D. (mm) = 93.60 96.40 85.54 90.40 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

80 NOMiNal BOre PiPe Size

90 NOMiNal BOre PiPe Size

100 NOMiNal BOre PiPe Size

125 NOMiNal BOre PiPe Size

80 NOMiNal BOre PiPe Size DiMeNSiONS

90 NOMiNal BOre PiPe Size DiMeNSiONS

100 NOMiNal BOre PiPe Size DiMeNSiONS

125 NOMiNal BOre PiPe Size DiMeNSiONS

PRESSuRE DROP & FlOW RATES

14 | ORRFIRE® Product Catalogue

Page 15: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

10 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 11

00

1

0.5

2

1.5

5000 19000 15000 20000 25000

PRES

SUR

E D

RO

P kP

a/m

ASTM A 53 SCHEDULE 40

250 N OM IN A L P IP E S IZE D I ME N S IO N S

2 50 N O MIN A L S IZE P I P E

ORRFIRE® LIGHT AS 1477 CPVC (Class 12)

ASTM A 53 ORRFIRE® AS1432 Copper AS1477 CPVC Sch 40 Light (Grade B) (Class 12) Mean O.D. (mm) = 273.10 273.10 0.00 280.40 Norm Thick (mm) = 9.27 4.80 0.00 15.35 Norm Mean I.D. (mm) = 254.56 263.50 0.00 249.70 Surface roughness K = 4.50 4.50 0.00 1.50

FLOW RATE Litres /Min

00

1

0.4

0.6

0.8

0.2

1.6

1.4

1.2

4000 8000 1600012000 24000 2800020000 32000

PRES

SUR

E D

ROP

kPa/

m

ASTM A 53 SCHEDULE 40

300 N OMIN A L P IP E S IZ E D IME N S ION S

300 N OMIN A L S IZ E P I P E

ORRFIRE® LIGHT AS 1477 CPVC (Class 12)

ASTM A 53 ORRFIRE® AS1432 Copper AS1477 CPVC Sch 40 Light (Grade B) (Class 12) Mean O.D. (mm) = 323.90 323.90 0.00 315.45 Norm Thick (mm) = 10.31 6.40 0.00 17.20 Norm Mean I.D. (mm) = 303.28 311.10 0.00 281.05 Surface roughness K = 4.50 4.50 0.00 1.50

FLOW RATE Litres /Min

Need more information? Get the complete suite of Orrcon ORRFIRE brochures.

ORRCON “ORRFIRE” RANGE OF FIRE PROTECTION PIPE

COMPLIANCE WITH AUSTRALIAN STANDARDS

NOMINAL SIZE DN MM WALL THICKNESS MM COMPLIANCE WITH AS 4118 PART 2.1 FIRE SPRINKLERS

COMPLIANCE WITH AS 2419 HYDRANTS

S.S.L. APPROVAL LISTING NO’S

APPROVED FINISH ALLGAL, SMARTCOTE, H.D.G.

HOT DIP GALV. ONLY afp

25 2.0 Y - 1529 1640 1641

2.6 Y - 1510 1508

3.2 Y - 1530 1509 1511

32 2.0 Y - 1529 1640 1641

2.6 Y - 1510 1508

3.2 Y - 1530 1509 1511

40 2.3 Y - 1529 1640 1641

2.9 Y - 1510 1508

3.2 Y - 1530 1509 1511

50 2.3 Y - 1529 1640 1641

2.9 Y - 1510 1508

3.6 Y - 1530 1509 1511

65 2.3 Y - 1529 1640 1641

3.04 min. Y Y 1529

3.2 Y Y 1510 1508

3.6 Y Y 1530 1509 1511

80 2.6 Y - 1529 1640 1641

3.04 min. Y Y 1529

3.2 Y Y 1510 1508

4.0 Y Y 1530 1509 1511

100 2.3 Y - 1529

2.5 Y - 1529 1528

3.04 min. Y Y 1529 1528

3.2 Y Y 1640 1641

3.6 Y Y 1510 1508

4.5 Y Y 1530 1509 1511

5.4 Y Y 1530

125 3.0 Y - 1640 1641

3.5 min. Y Y 1510

5.0 Y Y 1530 1509 1511

150 2.77 Y - 1529

3.00 Y - 1529 1528

3.5 min. Y Y 1529 1640 1641 1508

5.0 Y Y 1530 1509 1511

5.4 Y Y 1530

200 4.8 Y Y 1529 1510

250 4.8 Y Y 1529 1510

������������������������������

����������������������������

�������������������������

������������������������ �����������������

���������������������

�����������������������

����������

���������������������������

�����������������

��������������

������������������� �

������������

����������������������

�����������������

�������������������������

������������������������� ���������

����������������������� �

������ �

�������������������������

���������������

������������������

��������������������������������

�������������������������

�����������������������

������������������

����������������������

�����������������

���������������������������������

���������������������������������

���������������������������������

���������

�������������������������� ������������

������������������������� �����������������

�������������������

������������������������

���������������������

�����������������������

��������������������

��������������������������

������������������

��������������

�����������������

ORRFIRE

SMARTCOTE PAINTED PIPE

ORRFIRE

ALLGAL ELECTRO-GALVANISED SPRINKLER PIPE

ORRFIRE

HOT DIP GALVANISED PLUMBING & HYDRANT PIPE

8 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 9

00

2

1

4

3

5

500 1000 20001500 3000 3500 40002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 00 N O MI N A L P IP E S IZ E D IM E N S ION S

1 0 0 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 114.30 114.30 101.48 114.30 Norm Thick (mm) = 4.50 2.50 1.63 6.30 Norm Mean I.D. (mm) = 105.30 109.30 95.22 101.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

00

1

0.5

2

1.5

2.5

3

3.5

1000 2000 40003000 60005000 7000 8000 9000

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 5 0 N O M I N A L P I P E S I ZE D I M E N S I O N S

1 5 0 N O M IN A L S I Z E P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 165.10 165.10 152.25 160.25 Norm Thick (mm) = 5.00 3.00 2.03 8.80 Norm Mean I.D. (mm) = 155.10 159.10 148.19 142.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

2

2.5

0.5

1

1.5

4

3

3.5

4.5

500 1000 20001500 30002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

12 5 N OM I N A L P I P E S I Z E D IM E N S I O N S

1 25 N O M I N A L S I Z E P I P E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 139.70 139.70 126.88 140.20 Norm Thick (mm) = 5.00 3.00 1.63 7.65 Norm Mean I.D. (mm) = 129.70 133.70 123.62 124.90 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min0

0

1

0.5

2

1.5

2.5

3000 6000 9000 12000 15000

PRES

SUR

E D

RO

P kP

a/m

ASTM A 53 SCHEDULE 40AS 1432 COPPER (Grade B)

200 N OMI N A L P IP E S IZE D IME N S I O N S

200 N OMI N A L S IZE P IP E

ORRFIRE® LIGHTAS 1477 CPVC (Class 12)

ASTM A 53 ORRFIRE® AS1432 Copper AS1477 CPVC Sch 40 Light (Grade B) (Class 12) Mean O.D. (mm) = 219.10 219.10 203.00 225.30 Norm Thick (mm) = 7.11 4.80 2.03 12.30 Norm Mean I.D. (mm) = 204.88 209.50 198.94 200.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

150 NOMiNal BOre PiPe Size

200 NOMiNal BOre PiPe Size 300 NOMiNal BOre PiPe Size

250 NOMiNal BOre PiPe Size

150 NOMiNal BOre PiPe Size DiMeNSiONS

200 NOMiNal BOre PiPe Size DiMeNSiONS

250 NOMiNal BOre PiPe Size DiMeNSiONS

300 NOMiNal BOre PiPe Size DiMeNSiONS

8 | Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 Orrcon Orrfire Pressure Drop & Flow Rates Version 1 Mar 2005 | 9

00

2

1

4

3

5

500 1000 20001500 3000 3500 40002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 00 N O MI N A L P IP E S IZ E D IM E N S ION S

1 0 0 N O MIN A L S IZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 114.30 114.30 101.48 114.30 Norm Thick (mm) = 4.50 2.50 1.63 6.30 Norm Mean I.D. (mm) = 105.30 109.30 95.22 101.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

00

1

0.5

2

1.5

2.5

3

3.5

1000 2000 40003000 60005000 7000 8000 9000

PRES

SUR

E D

RO

P kP

a/m

FLOW RATE Litres /Min

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

1 5 0 N O M I N A L P I P E S I ZE D I M E N S I O N S

1 5 0 N O M I N A L S I Z E P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 165.10 165.10 152.25 160.25 Norm Thick (mm) = 5.00 3.00 2.03 8.80 Norm Mean I.D. (mm) = 155.10 159.10 148.19 142.65 Surface roughness K = 4.50 4.50 1.50 1.50

00

2

2.5

0.5

1

1.5

4

3

3.5

4.5

500 1000 20001500 30002500

PRES

SUR

E D

RO

P kP

a/m

AS 1074 MEDIUMAS 1432 COPPER (Grade B)

12 5 N OM IN A L P IP E S IZE D IM E N S I ON S

1 25 N O MI N A L S I ZE P IP E

ORRFIRE® EXTRA LIGHTAS 1477 CPVC (Class 12)

AS 1074 ORRFIRE® AS1432 Copper AS1477 CPVC Medium Extra Light (Grade B) (Class 12) Mean O.D. (mm) = 139.70 139.70 126.88 140.20 Norm Thick (mm) = 5.00 3.00 1.63 7.65 Norm Mean I.D. (mm) = 129.70 133.70 123.62 124.90 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min0

0

1

0.5

2

1.5

2.5

3000 6000 9000 12000 15000

PRES

SUR

E D

RO

P kP

a/m

ASTM A 53 SCHEDULE 40AS 1432 COPPER (Grade B)

200 N O MI N A L P IP E S IZ E D IME N S I O N S

200 N O MI N A L S IZ E P IP E

ORRFIRE® LIGHTAS 1477 CPVC (Class 12)

ASTM A 53 ORRFIRE® AS1432 Copper AS1477 CPVC Sch 40 Light (Grade B) (Class 12) Mean O.D. (mm) = 219.10 219.10 203.00 225.30 Norm Thick (mm) = 7.11 4.80 2.03 12.30 Norm Mean I.D. (mm) = 204.88 209.50 198.94 200.70 Surface roughness K = 4.50 4.50 1.50 1.50

FLOW RATE Litres /Min

PRESSuRE DROP & FlOW RATES

15we’ll see it through

Page 16: ORRFIRE Product Catalogue - Orrcon Steel · When ORRFIRE® Hot Dipped Galvanised Pipe is roll grooved after galvanising, any flaked area of the internal galvanising should be repaired

although all care has been taken in the preparation of information in this brochure,

Orrcon Operations Pty ltd cannot accept liability for errors or omissions, or for the use

of this brochure. You should always satisfy yourself as to the accuracy of the information and

applicability to your circumstances.

OrrFire® Product Catalogue Orr0011 Printed September 2012

Quality ISO 9001

we’ll see it through

ORRFIRE® Product Catalogue

images are for illustration purposes only.

Orrcon Operations Pty ltd aBN 92 094 103 090Head Office - 121 evans road, Salisbury, QlD 4107Telephone (07) 3274 0500 Facsimile (07) 3274 0517For your nearest stockist call 1300 650 303Orrcon Steel 1300 OrrCON (1300 677 266)email [email protected] Website www.orrconsteel.com.au

Distributed by