out-of-step protection fundamentals2007/12/13  · december 13, 2007 introduction zthe aim of this...

70
Copyright © SEL 2007 Out-Of-Step Protection Fundamentals Demetrios Tziouvaras Schweitzer Engineering Laboratories, Inc. IEEE PES San Francisco Chapter December 13, 2007

Upload: others

Post on 25-Jan-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • Copyright © SEL 2007

    Out-Of-Step Protection Fundamentals

    Demetrios Tziouvaras

    Schweitzer Engineering Laboratories, Inc.

    IEEE PES San Francisco Chapter

    December 13, 2007

  • Introduction

    The aim of this presentation is to explainThe fundamentals of out-of-step (OOS) protection

    Discuss which relays and relay systems are prone to operate during power swingsShare experiences and lessons learnt from the past to avoid making the same mistakes

  • Introduction

    Interconnected systems experienced an increased number of large disturbances in the last 15 years

    Protective relay systems are often involved during major disturbances

    In many cases they prevent further propagation of the disturbance

    In some cases undesired relay operations have contributed to cascading blackouts

  • Outline

    Out of step (OOS) protection fundamentals

    Relay performance during OOS conditionsTransmission lines

    Generators

    System design and protection improvements

    Conclusions

  • What Is a Power Swing?

    Variation of power flow which occurs when generator rotor angles are advancing or retarding relative to each other in response to:

    System faults

    Line switching

    Major load switching

    Loss of large generation

    Major system disturbances

  • Stable and Unstable Power SwingsDefinitions

    A power swing is considered stable if the generators do not slip poles and the system reaches a new state of equilibrium, i.e. an acceptable operating conditionAn unstable power swing results in a generator or group of generators experiencing pole slipping or loss-of-synchronism for which some corrective action must be taken.

    Out-of-step is the same as an unstable power swing.

  • Power Swings can Cause Undesired Protective Relay Operation

    Power swings can cause undesired relay operation that may lead to:

    Undesired tripping of power system elements at undesired network locations

    Weakening of the power system

    Possible cascading outages and shutdown of major portions of the power system

    Damage of circuit breakers due to uncontrolled tripping

    Loss of human life

  • Unstable Power SwingsDamage System Integrity

    Pole slipping may damage generators and turbines

    Low voltage conditions experienced during unstable power swings may cause:

    Motor stalling

    Generator tripping

    Damage to voltage-sensitive loads

    Prolonged low voltages could cause instability of smaller areas within a utility’s system

  • Need for Out-of-Step Protection

    Generators operating asynchronously with the rest of the power system cannot regain stability as a result of any excitation or regulator actionAsynchronous power system areas must be separated in a controlled fashion to avoid:

    Equipment damageWidespread outages in the power system

  • Philosophy of Power-Swing Protection

    Detect both stable and unstable power swings

    Block tripping of relay elements prone to operate during power swings

    Differentiate between stable and unstable power swings

    Separate the system into islands during out-of-step conditions

  • Philosophy of Power-Swing Protection

    Separate the system at locations that provide good balance of load/generation in the resulting system islands

    Trip only at pre-selected network locations and block tripping at all other locations

    Trip only under controlled transient recovery voltages or with low current

  • Power System StabilityBrief Review

  • Power System StabilityDefinition

    The ability of the electric power system to regain a state of operating equilibrium after being subjected to disturbances such as faults, line switching, load rejection, loss-of-excitation, and loss of generation.

  • Power FlowTwo-Machine System

    1 2

    3 4

    Line 1VS VR

    Line 2X

    δ⋅

    = sinXVV

    P RSVS

    VRδ

  • Effect of Fault Type on Power Transfer

    δ

    P

    Three-Phase Fault

    Phase-Phase-Ground Fault

    Phase-Phase Fault

    Single-Line-Ground Fault

    Normal System

    1 2

    3 4

    VS VRLine 1

    Line 2

  • Transient Stability Concepts

    1 2

    3 4

    Prefault state (Both lines in service)

    Fault state

    Fault state with breaker 3 open

    Post-fault state (Line 2 out)

    VS VRLine 1

    Line 2

  • Equal-Area Criterion

    δ180°

    P0

    P

    Fault (one breaker open)Fault

    Prefault

    Post-Fault

    1

    0

    2

    34

    5

    6

    Area 2Area 1

    1 2

    3 4

    VS VRLine 1

    Line 2

  • Effect of Fault Clearing TimeUnstable System

    Fault

    Post-Fault

    δ

    PrefaultP

  • Stable and Unstable Power SwingsRotor Angle

    Stable System

    Unstable System

    t

    δ

    δ0

    δ1

  • Angular InstabilityDistinguishing Features

    Large voltage variations

    Large power oscillations

    Loss of synchronism

    Zero voltage at the electrical center

    Frequency excursions

  • Angular InstabilityLarge Voltage Variations

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

    -1

    0

    1

    Voltage MagnitudePe

    r uni

    t

    Seconds

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80

    0.5

    1

    1.5

    Per U

    nit

    Seconds

  • Angular InstabilityLarge Power Oscillations

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-1000

    -500

    0

    500

    Real and Reactive PowerM

    W

    Seconds

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-400-200

    0200400600

    MVa

    r

    Seconds

  • Angular InstabilityV1 and Angle of V1 / I1

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.90

    0.2

    0.4

    0.6

    Positive-Sequence Voltage MagnitudePe

    r Uni

    t

    Seconds

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9-200

    0

    200

    400Angle of (V1 / I1)

    Deg

    rees

    Seconds

  • Relay Elements Prone to OperateDuring Power Swings

  • Stable and Unstable Power SwingsImpedance Trajectories

    Stable Swing

    Unstable Swing

    R

    X

  • Relay Elements Prone to OperateDuring Power Swings

    Instantaneous phase overcurrentDirectional and non-directional

    UndervoltageShort time or instantaneous

    Zone 1 distance

    Zone 2 distance used in POTT scheme

  • Line Relays Prone to OperateDuring Angular Instability

    Zone 1 distance or overreaching distance elements applied in DCB or POTT schemes

    Potential reasons are:Lack of PSB function or improper settings of the PSB function

    Lack of frequency tracking and long memory polarizing voltage

    Phasor measurement errors due to large excursions of system frequency during islanding

  • Relay Systems Unresponsiveto Power Swings

    Phase comparison

    Line current differential

    Pilot-wire

  • Impedances Measuredby Distance Relays

    21

    V I

    ZS ZL ZR

    VS VR

    ( ) SRLSRS

    S ZZZZVV

    VIVZ −++−

    ==

  • Impedance Locus for k = ES / ER = 1.0

    δ

    ZL

    ZR

    X

    Rδ increases

    δ decreasesδ=180°

    ZS0.5ZT

    Z

    R

    S

    ST Z

    2cotj1

    2ZZ −⎟

    ⎠⎞

    ⎜⎝⎛ δ−=

    R

    S

    EEk =

  • Two-Machine System Impedance Locii

    RX

    S

    k > 1ES > ER

    Rk = 1

    k < 1ES < ER

  • Power-Swing ProtectionRelay Functions

  • Clarify the Terminology

    Unstable power swing

    Out of step (OOS)

    Out-of-step blocking (OSB)

    Power-swing blocking (PSB)

    Out-of-step tripping (OST)

    Pole-slip tripping

  • Power-Swing ProtectionRelay Functions

    Power-swing blocking (PSB)Detects both stable and unstable power swings

    Prevents operation of protection elements

    Out-of-step tripping (OST)Detects unstable power swings or OOS

    Separates system into islands with good generation / load balance

  • Conventional PSB Scheme

    Load Region

    X

    RA

    BZ1

    Inner ZElementDistance

    ElementOuter Z Element

  • Conventional OST Scheme

    Load Region

    X

    RA

    BZ1

    Inner ZElementDistance

    ElementOuter ZElement

  • Disadvantages ofConventional PSB Scheme

    Needs detailed system information

    Requires extensive system stability studies

    It is difficult to set for long lines with heavy loads

    May fail after severe disturbances on marginally stable systems

    May fail during swings with high slip frequency

  • Long Line With Heavy LoadZL => ZΣ

    A R

    ZR

    ZS

    Z2

    X

    B

    Swing LocusTrajectory ZL

  • Short Line With Light LoadZL

  • Unstable SwingAfter Severe Disturbance

    A R

    ZR

    ZS

    Z2

    X

    Swing LocusTrajectory

    B

    ZL

  • New Zero-Setting PSB Function

    Uses swing-center voltage (SCV)

    Has no user settings

    Does not need system parameters

    Does not require system stability studies

    Provides PSB during pole open

    Detects evolving faults during power swings

  • Swing-Center Voltage (SCV)

    ( ) ( ) ( )⎟⎠⎞

    ⎜⎝⎛ δ⋅⎟

    ⎠⎞

    ⎜⎝⎛ δ+ω=

    2tcos

    2ttsinE2tSCV

    o'

    o

    o"

    Z1S•I Z1L•I

    VS

    ERδ

    SCV

    Z1R•I

    ES

    VR

  • SCV During System OOS ConditionSwing-Center Voltage

    seconds

    volta

    ge (p

    u)SCV Amplitude

    0 0.05 0.1 0.15 0.2-1

    -0.5

    0

    0.5

    1

  • Local Estimate of SCV: Vcosϕ

    ϕ⋅≈ cos|V|SCV S

    o'Z1S•I Z1R•Iθ

    VSES ϕ

    SCV

    ER

    I

    Vcosϕ

    VR

    AnglepedanceImSystem:θ

  • Local Estimate of SCV: Vcosϕ

    ⎟⎠⎞

    ⎜⎝⎛ δ⋅=2

    cos1E1SCV

    ( )dtd

    2sin

    21E

    dt1SCVd δ

    ⎟⎠⎞

    ⎜⎝⎛ δ−=

  • Vcosϕ for 1-Rad/Sec OOS Condition

    0

    0 90 180 270 360

    E1

    E1/2d (SCV1) / dt

    δ

    SCV1

  • Benefits of SCV for PSB Application

    Independent of system source and line impedance

    Bounded:Lower limit: zero

    Upper limit: close to one per unit

    Relates directly to angle difference of two sources, δ

  • Transmission Line Relay PerformanceDuring Out-of-Step Conditions

  • 500 kV System

    Station CStation D

    Station E

    Line 1

    Line 3

    Line 2

    Unit 1

    Unit 2

    Lines 4, 5, and 6Intertie

    System B

    System A

  • Angular InstabilityZ1 Trajectory – Line 2 at Station C

    -10 -5 0 5 10-10

    -8

    -6

    -4

    -2

    0

    2

    4

    6

    8

    10

    23

    25

    27 29 31 33 35 37 3941

    43

    45

    Positive-Sequence Impedance (Z1) LocusIm

    (Z1)

    ohm

    Re(Z1) ohm

  • EHV System – Northern California

    Station CStation D

    Station E

    Line 1

    Line 3

    Line 2

    Unit 1

    Unit 2

    Lines 4, 5, and 6Intertie

    System B

    System A

  • Zone 1 Operation During OOS PSB Function not Enabled

  • Zone 1 Distance Is BlockedFirst Slip Cycle

  • Zone 1 Distance OperatesSecond Slip Cycle

  • Zone 1 Distance OperatesSecond Slip Cycle

    Fast slip frequency changeSetting fine-tuning could have prevented operation of Zone 1

    Concentric zone settingsSeparation between concentric zones

    PSB timer

    All of these settings are difficult to makeLong heavy loaded linesRequire large number of stability studies

  • Proper Blocking of Distance Elementsby Zero Setting PSB

    0 5 10 15 20-1

    -0.5

    0

    0.5

    1SCV1 (Solid), dSCV1/dt (Dash)

    (pu)

    ,(pu/

    cyc)

    0 5 10 15 20Cycle

    S

    PSBDPSB

    67QUB3PF ResetPSB Reset

    SLD SetStart-ZnSSD Set

  • Generator Relay PerformanceDuring Disturbances

  • Units 1 and 2 Operations

    Station CStation D

    Station E

    Line 1

    Line 3

    Line 2

    Unit 1

    Unit 2

    Lines 4, 5, and 6Intertie

    System B

    System A

  • One Unit Trips by Undervoltage

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

    -1

    -0.5

    0

    0.5

    1

    Station C VoltagePe

    r uni

    t

    Seconds

  • Unit 1: Three-Phase P and QDuring OOS

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-2000

    0

    2000Real Power

    MW

    Seconds

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-1000

    0

    1000Reactive Power

    MVa

    r

    Seconds

  • Units 1 and 2 TripInst. Dir. Phase OC Relay

    -20 -10 0 10 20-40

    -30

    -20

    -10

    0

    10

    1 3 5 7 9 1113

    15

    17

    19

    21

    23 2527 29

    Positive-Sequence Impedance (Z1) LocusIm

    (Z1)

    ohm

    Re(Z1) ohm

  • Protection Systemand Other System Improvements

    to Preserve System Stability

  • Proper System and Protection Design Preserve System Stability

    Prevent the occurrence of out-of-step conditions

    Install sufficient transmission capacity

    Maintain adequate reactive reserves

    Apply high-speed relaying systems and high-speed reclosing

    Apply single-phase tripping and reclosing

    Apply wide-area stability controls

  • Wide-Area Stability Controls or SIPSPreserve System Stability

    Wide-area stability controlsGenerator dropping

    Direct load dropping

    Fast valving

    Insertion of breaking resistors

    Series and shunt capacitor insertion

    Use FACTS devices

  • Protection Systemand Other Improvements

    Improvements in transient stabilityHigh speed fault clearing

    Single phase tripping and reclosing

    Apply local breaker failure protection on all EHV and critical HV substations

    Special protection systems

    Controlled system separation

    UVLS and UFLS

  • Protection System Improvements

    Apply dual pilot protection relay systems on all EHV and critical HV systems with

    PSB capability, or with systems that are immune to stable or unstable power swings

    Replace secondary non-pilot line relay systems in non-critical HV lines with:

    A relay system that has similar functionality with the main pilot protection systemConsider switching the communications channel to the secondary relay system when the Main 1 is out of service

  • Conclusions

    Utilities must take every action economically justifiable to preserve system stability

    Out-of-step tripping should be applied and operate only as a last resort to preserve system stability

    OST and PSB should be applied based on an inter-regional controlled system separation philosophy

  • Conclusions

    OOS tripping must separate the system at predetermined locations to minimize the effect of the disturbance

    OOS blocking compliments OOS tripping by blocking relay elements prone to operate and ensures a controlled system separation

    Controlled separation schemes provide a safety net to lessen the impacts of major disturbances

  • References

    Out-Of-Step Protection Fundamentals and Advancementshttp://www.selinc.com/techpprs/6163.pdf

    Zero-Setting Power-Swing Blocking Protectionhttp://www.selinc.com/techpprs/6172_ZeroSetting_20050302.pdf

    Relay Performance During Major System Disturbanceshttp://www.selinc.com/techpprs/6244_RelayPerformance_DT_20060914.pdf

    http://www.selinc.com/techpprs/6163.pdfhttp://www.selinc.com/techpprs/6172_ZeroSetting_20050302.pdfhttp://www.selinc.com/techpprs/6244_RelayPerformance_DT_20060914.pdf

  • Thank You

    Out-Of-Step Protection FundamentalsIntroductionIntroductionOutlineWhat Is a Power Swing?Stable and Unstable Power SwingsDefinitionsPower Swings can Cause Undesired Protective Relay OperationUnstable Power SwingsDamage System IntegrityNeed for Out-of-Step ProtectionPhilosophy of Power-Swing ProtectionPhilosophy of Power-Swing ProtectionPower System StabilityBrief ReviewPower System Stability DefinitionPower FlowTwo-Machine SystemEffect of Fault Type on Power TransferTransient Stability ConceptsEqual-Area CriterionEffect of Fault Clearing Time Unstable SystemStable and Unstable Power SwingsRotor AngleAngular InstabilityDistinguishing FeaturesAngular InstabilityLarge Voltage VariationsAngular InstabilityLarge Power OscillationsAngular InstabilityV1 and Angle of V1 / I1Relay Elements Prone to OperateDuring Power SwingsStable and Unstable Power SwingsImpedance TrajectoriesRelay Elements Prone to OperateDuring Power SwingsLine Relays Prone to OperateDuring Angular InstabilityRelay Systems Unresponsiveto Power SwingsImpedances Measuredby Distance RelaysImpedance Locus for k = ES / ER = 1.0Two-Machine System Impedance LociiPower-Swing ProtectionRelay FunctionsClarify the TerminologyPower-Swing ProtectionRelay FunctionsConventional PSB SchemeConventional OST SchemeDisadvantages ofConventional PSB SchemeLong Line With Heavy Load ZL => ZSShort Line With Light LoadZL