Outdoor Air Processing UnitFXMQ-MFVJU
EDUS39-900B-F10202103
Engineering Data
60 Hz
1
FXMQ-MFVJU EDUS39-900B-F10
Table of Contents
1. FeaturesandBenefits ................................................................................22. Specifications .............................................................................................33. Dimensions .................................................................................................54. CenterofGravity ........................................................................................75. Piping Diagrams .........................................................................................86. Wiring Diagrams .........................................................................................97. Electric Characteristics ............................................................................. 118. CapacityTables ........................................................................................129. OperationLimit .........................................................................................1510.FanPerformances ....................................................................................1811.SoundLevels(ReferenceData) ...............................................................21
11.1 Overall .............................................................................................2111.2 OctaveBandLevel ..........................................................................22
12.Accessories ..............................................................................................2312.1OptionalAccessories(forUnit) .......................................................23
2
FXMQ-MFVJU EDUS39-900B-F10
1. Features and Benefits
Concealed, Powerful, Fresh Air IntegrationThe100%outsideairprocessingunitprovidesazoned,decentralizedapproachtoconditioningoutsideair.Thishelpstoreduceductworkandinstallationtimewhileincreasingefficiencyandflexibility.Bothoutsideairtreatmentandspaceconditioningcanbeprovidedfromonecompact,flexible,andefficientVRVsystem.VRVindoorunitsandoutdoorairprocessingunitcanbeconnectedtothesamerefrigerantline,enablingenhanceddesignflexibility.
� Designflexibilitywithacapacityrangeupto96MBH � Thenominalairflowratesare635,988,and1,236CFM � ImprovedductworkandfiltrationflexibilitywithESPcapabilityofupto1.03”W.G � Lowprofiledesignoflessthan19”hightoreducerequiredinstallationspace � IndoorAirQualityoptionsincludeMERV8and13filtersandfilterboxes � SeamlesslyintegrateswithNorthAmericanDaikinVRVsystemsandcontrollers
Outside air processing unit VRV outdoor unit
for outside air supply
VRV indoor unit
for air-conditioning
3
FXMQ-MFVJU EDUS39-900B-F10
2. Specifications
Model FXMQ48MFVJU FXMQ72MFVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230VH1,H3Coolingcapacity Btu/h 48,000 72,000H2,H3Heatingcapacity Btu/h 30,000 47,000Casing/Color Galvanizedsteelplate GalvanizedsteelplateDimensions:(H×W×D) in. 18-1/2×29-1/4×43-5/16 18-1/2×54-3/8×43-5/16Coil(crossfincoil)
Rows×Stages×Finpitch 3×26×13 3×26×13Face area ft² 3.01 7.00
Fan
Model D13/4G2DA1 D13/4G2DA1Type Siroccofan SiroccofanMotoroutput×Numberofunits W 380×1 380×1
Airflowrate cfm 635 988Externalstaticpressure in.H2O 0.88 0.96
Drive Directdrive DirectdriveTemperaturecontrol Microprocessorthermostatforcoolingandheating MicroprocessorthermostatforcoolingandheatingSoundabsorbingthermalinsulationmaterial Glassfiber Glassfiber
Airfilter H4 H4H6Soundpressurelevel(referencedata) dBA 43 48
Weight lbs 190 271
Piping connections
Liquidpipes in. ɸ3/8(flareconnection) ɸ3/8(flareconnection)Gaspipes in. ɸ5/8(flareconnection) ɸ3/4(brazingconnection)Drain pipe in. PS1B PS1B
Safetydevices Fuse,Thermalprotectorforfanmotor Fuse,ThermalprotectorforfanmotorRefrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveH5Connectableoutdoorunits R410AVRV series R410AVRV series
Standardaccessories Operationmanual,Installationmanual,Sealingpads,Screws,Clamps
Operationmanual,Installationmanual,Sealingpads,Screws,Clamps,Connectionpipes
Note:H1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Outdoortemperature:91°FDB,82°FWB(68%RH) Dischargesettemperature:64°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
H2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Outdoortemperature:32°FDB,27°FWB(50%RH) Dischargesettemperature:77°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
H3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.H4. Airfilterisnotstandardaccessory,butpleasemountitintheductsystemofthesuctionside.
Selectitsductcollectionefficiency(gravitymethod)50%ormore.H5. Withintherangethatthetotalcapacityofindoorunitsis50to100%,itispossibletoconnecttotheoutdoorunit.H6. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,thesevaluesmaybehigherasaresultof
installationconditions.
C:3D065463
4
FXMQ-MFVJU EDUS39-900B-F10
Model FXMQ96MFVJUPowersupply 1phase,60Hz,208/230VH1,H3Coolingcapacity Btu/h 96,000H2,H3Heatingcapacity Btu/h 59,000Casing/Color GalvanizedsteelplateDimensions:(H×W×D) in. 18-1/2×54-3/8×43-5/16Coil(crossfincoil)
Rows×Stages×Finpitch 3×26×13Face area ft² 7.00
Fan
Model D13/4G2DA1Type SiroccofanMotoroutput×Numberofunits W 380×1
Airflowrate cfm 1,235Externalstaticpressure in.H2O 1.03
Drive DirectdriveTemperaturecontrol MicroprocessorthermostatforcoolingandheatingSoundabsorbingthermalinsulationmaterial Glassfiber
Airfilter H4H6Soundpressurelevel(referencedata) dBA 48
Weight lbs 271
Piping connections
Liquidpipes in. ɸ3/8(flareconnection)Gaspipes in. ɸ7/8(brazingconnection)Drain pipe in. PS1B
Safetydevices Fuse,ThermalprotectorforfanmotorRefrigerantcontrol ElectronicexpansionvalveH5Connectableoutdoorunits R410AVRV seriesStandardaccessories Operationmanual,Installationmanual,Sealingpads,Screws,Clamps,Connectionpipes
Note:H1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Outdoortemperature:91°FDB,82°FWB(68%RH) Dischargesettemperature:64°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
H2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Outdoortemperature:32°FDB,27°FWB(50%RH) Dischargesettemperature:77°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
H3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.H4. Airfilterisnotstandardaccessory,butpleasemountitintheductsystemofthesuctionside.
Selectitsductcollectionefficiency(gravitymethod)50%ormore.H5. Withintherangethatthetotalcapacityofindoorunitsis50to100%,itispossibletoconnecttotheoutdoorunit.H6. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,thesevaluesmaybehigherasaresultof
installationconditions.
C:3D065463
5
FXMQ-MFVJU EDUS39-900B-F10
3. Dimensions
FXMQ48MFVJU
3D06
5452
A
Uni
t: in
.
6
FXMQ-MFVJU EDUS39-900B-F10
FXMQ72-96MFVJU
3D06
5453
A
Uni
t: in
.
7
FXMQ-MFVJU EDUS39-900B-F10
4. Center of Gravity
FXMQ48-96MFVJU
Unit: in.
4D065444
Model
FXMQ48MFVJU
FXMQ72MFVJU
FXMQ96MFVJU
ProductMass
190Lbs
271Lbs
271Lbs
AA
30-11/16
54-5/16
54-9/16
AB
27-3/8
51
51
AC
23-5/8
22-7/16
22-7/16
AD
9-13/16
9-13/16
9-13/16
AE
13
23-5/8
23-5/8
8
FXMQ-MFVJU EDUS39-900B-F10
5. Piping Diagrams
FXMQ48-96MFVJU
Unit:in.Model Gas Liquid
FXMQ48MFVJU ɸ5/8ɸ3/8FXMQ72MFVJU ɸ3/4
FXMQ96MFVJU ɸ7/8
4D018650D
9
FXMQ-MFVJU EDUS39-900B-F10
6. Wiring Diagrams
FXMQ48-96MFVJU
C: 3
D06
5426
D
NO
TES)
1.
: T
ERM
INAL
BLO
CK,
,
: C
ON
NEC
TOR
,
:
TER
MIN
AL,
: S
HO
RT
CIR
CU
IT C
ON
NEC
TOR
,
: FIE
LD W
IRIN
G.
2. IN
CAS
E U
SIN
G C
ENTR
AL R
EMO
TE C
ON
TRO
LLER
, CO
NN
ECT
IT T
O T
HE
UN
IT IN
AC
CO
RD
ANC
E W
ITH
TH
E AT
TAC
HED
INST
RU
CTI
ON
MAN
UAL
.3.
IN C
ASE
CO
NN
ECTI
NG
TH
E IN
PUT
WIR
ES F
RO
M O
UTS
IDE,
FO
RC
ED O
FF O
R O
N/O
FF C
ON
TRO
L O
PER
ATIO
N C
AN B
E SE
LEC
TED
BY
REM
OTE
CO
NTR
OLL
ER.
IN
DET
AILS
, REF
ER T
O T
HE
INST
ALLA
TIO
N M
ANU
AL A
TTAC
HED
TO
TH
E U
NIT
.4.
DO
NO
T R
EMO
VE S
HO
RT
CIR
CU
IT C
ON
NEC
TOR
OF
X9A.
5. S
YMBO
LS S
HO
W A
S FO
LLO
WS:
RED
: RED
BLK
: BLA
CK
WH
T: W
HIT
E Y
LW: Y
ELLO
W P
PL: P
UR
PLE
GR
Y: G
RAY
BLU
: BLU
E P
NK:
PIN
K O
RG
: OR
ANG
E
GR
N: G
REE
N
6. C
LASS
2 W
IRE
10
FXMQ-MFVJU EDUS39-900B-F10
FXMQ48-96MFVJU
ELECTRICALCOMPONENTSANDWIRINGCONNECTORSFORINDOORUNITA1P PRINTEDCIRCUITBOARDC1·C2 CAPACITOR(M1F)F1U FUSE( B ,5A,250V)(A1P)HAP LIGHTEMITTINGDIODE(SERVICEMONITOR-GREEN)K1M MAGNETICRELAY(M1F)K1R MAGNETICRELAY(M1F)KPR MAGNETICRELAY(M1P)KSR MAGNETICRELAY(Y1S)M1F MOTOR(FAN)Q1M THERMALPROTECTOR(M1FEMBEDDED135°C)R1T THERMISTOR(SUCTIONAIR)R2T THERMISTOR(COIL,LIQUID)R3T THERMISTOR(COIL,GAS)R4T THERMISTOR(DISCHARGEAIR)T1R TRANSFORMAR(208V/230V25VA)X1M TERMINALBLOCK(POWER)X2M TERMINALBLOCK(CONTROL)X3M TERMINALBLOCKX51A,X52A CONNECTORY1E ELECTRICEXPANSIONVALVEY1S SOLENOIDVALVE(HOTGAS)CONNECTORFOROPTIONALPARTSX18A CONNECTOR(WIRINGADAPTORFORELECTRICALAPPENDICES)
C:3D065426D
11
FXMQ-MFVJU EDUS39-900B-F10
7. Electric Characteristics
FXMQ48-96MFVJU
ModelPowersupply IFM Input(W)
SCCRHz Volts Voltagerange MCA MOP KW FLA Cooling Heating
FXMQ48MFVJU60 208/230V Max.253V
Min.187V
2.1 15 0.380 1.7 359 359 SCCRkArms,Symmetrical
@600VMAX:5FXMQ72MFVJU 3.6 15 0.380 2.9 548 548FXMQ96MFVJU 4.1 15 0.380 3.3 638 638
Symbol:MCA: Min.CircuitAmps(A)MOP: Max.OvercurrentProtectiveDevice(A)KW: FanMotorRatedOutput(kW)FLA: FullLoadAmps(A)IFM: IndoorFanMotorSCCR:Short-CircuitCurrentRating
Note:1.Voltagerange Unitsaresuitableforuseonelectricalsystemswherevoltagesuppliedtounitterminalsisnotbeloworabovelistedrangelimits.
2.Maximumallowablevoltageunbalancebetweenphaseis2%.3.MCA/MOP MCA=1.25×FLA MOP≤4×FLA (Nextlowerstandardfuseraring.Min.15A)
4.SelectwiresizebasedontheMCA.
C:4D065596
12
FXMQ-MFVJU EDUS39-900B-F10
8. Capacity Tables
FXMQ48MFVJU
Cooling
Outdoorairtemperature °FWB
°FDB62 66 70 74 78 82 86 90
CapacityMBh MBh MBh MBh MBh MBh MBh MBh
67 13000 1590071 13000 15900 1830075 13000 15900 18300 2330079 15900 18300 2290083 18300 22900 3770087 17900 22600 37300 4830091 17900 22200 37000 48000 5620095 21900 36600 47600 55800 59600
Heating
Outdoorairtemperature °FWB
°FDB19 23 27 31 35 39 43 51 55
CapacityMBh MBh MBh MBh MBh MBh MBh MBh MBh
22 32600 32600 - - - - - - -32 - - 30000 - - - - - -37 - - 26600 26600 26600 - - - -42 - - - - 21500 21500 21500 - -52 - - - - - 16800 16800 16800 -57 - - - - - - 12100 12100 12100
Note:1.Theabovecapacitiesarebasedonthefollowingconditions: Airdischargetemperaturesetting:64°Fforcoolingoperation, 77°Fforheating(factorysetting). Equivalentpipinglength:25ft. Leveldifference:0ft.2.Theabovecapacitiesvaluesaregeneralaveragevalueswhichcanbegeneratedbyeachcompressoroperationlevel.3.Avalueenclosedin meansratedcapacity.
13
FXMQ-MFVJU EDUS39-900B-F10
FXMQ72MFVJU
Cooling
Outdoorairtemperature °FWB
°FDB62 66 70 74 78 82 86 90
CapacityMBh MBh MBh MBh MBh MBh MBh MBh
67 19600 24000 - - - - - -71 19600 24000 27600 - - - - -75 19600 24000 27600 34700 - - - -79 - 24000 27300 34400 - - - -83 - - 27300 34000 56500 - - -87 - - 27000 33700 55900 72600 - -91 - - 27000 33100 55600 72000 84200 -95 - - - 32700 54900 71300 83800 89300
Heating
Outdoorairtemperature °FWB
°FDB19 23 27 31 35 39 43 51 55
CapacityMBh MBh MBh MBh MBh MBh MBh MBh MBh
22 50700 50700 - - - - - - -32 - - 47000 - - - - - -37 - - 41200 41200 41200 - - - -42 - - - - 33800 33800 33800 - -52 - - - - - 26300 26300 26300 -57 - - - - - - 18900 18900 18900
Note:1.Theabovecapacitiesarebasedonthefollowingconditions: Airdischargetemperaturesetting:64°Fforcoolingoperation, 77°Fforheating(factorysetting). Equivalentpipinglength:25ft. Leveldifference:0ft.2.Theabovecapacitiesvaluesaregeneralaveragevalueswhichcanbegeneratedbyeachcompressoroperationlevel.3.Avalueenclosedin meansratedcapacity.
14
FXMQ-MFVJU EDUS39-900B-F10
FXMQ96MFVJU
Cooling
Outdoorairtemperature °FWB
°FDB62 66 70 74 78 82 86 90
CapacityMBh MBh MBh MBh MBh MBh MBh MBh
67 26000 3180071 26000 31800 3670075 26000 31800 36700 4620079 31800 36300 4590083 36300 45600 7540087 36000 44900 74700 9660091 36000 44200 74000 96000 11240095 43800 73300 95300 111700 119300
Heating
Outdoorairtemperature °FWB
°FDB19 23 27 31 35 39 43 51 55
CapacityMBh MBh MBh MBh MBh MBh MBh MBh MBh
22 63700 63700
32 59000
37 51800 51800 51800
42 42300 42300 42300
52 33200 33200 33200
57 23700 23700 23700
Note:1.Theabovecapacitiesarebasedonthefollowingconditions: Airdischargetemperaturesetting:64°Fforcoolingoperation, 77°Fforheating(factorysetting). Equivalentpipinglength:25ft. Leveldifference:0ft.2.Theabovecapacitiesvaluesaregeneralaveragevalueswhichcanbegeneratedbyeachcompressoroperationlevel.3.Avalueenclosedin meansratedcapacity.
15
FXMQ-MFVJU EDUS39-900B-F10
9. Operation Limit
FXMQ48MFVJU
C: 3
D04
6312
Ope
ratio
nlim
it(c
oolin
g)
Ope
ratio
n lim
it(h
eatin
g)
Fan o
nlyop
erati
on
Outdoor air te
mp. (°F WB)
Out
door
air
tem
p. (°
F D
B)23
3242
.859
66.2
84.2
(92.
3)10
6.7
109.
4
2)
:The
dis
char
ge a
ir te
mpe
ratu
re
may
not
mat
ch th
e te
mpe
ratu
re
setti
ng fo
r too
larg
e ou
tdoo
r-air
proc
essi
ng c
apac
ity.
Ther
mos
tat O
FF m
ay b
e ca
rried
out
.
NO
TE1)
The
se fi
gure
s as
sum
e th
e fo
llow
ing
oper
atin
g co
nditi
ons.
(Indo
or a
nd o
utdo
or u
nits
)Eq
uiva
lent
pip
e le
ngth
: 25
ft.Le
vel d
iffer
ence
: 0 ft
.
3)
:
The
dis
char
ge a
ir te
mpe
ratu
re
may
not
mat
ch th
e te
mpe
ratu
re
setti
ng fo
r too
sm
all o
utdo
or-a
ir pr
oces
sing
cap
acity
.
4) T
he s
yste
m w
ill no
t ope
rate
in fa
n m
ode
whe
n th
e ou
tdoo
r-air
tem
pera
ture
is 4
1°F
or b
elow
.
89.6
16
FXMQ-MFVJU EDUS39-900B-F10
FXMQ72MFVJU
C: 3
D04
7750
Ope
ratio
nlim
it(c
oolin
g)
Ope
ratio
n lim
it(h
eatin
g)
Fan
only
oper
atio
n
Outdoor air te
mp. (°F WB)
Out
door
air
tem
p. (°
F D
B)23
3259
66.2
86(9
2.3)
106.
710
9.4
2)
:The
dis
char
ge a
ir te
mpe
ratu
re
may
not
mat
ch th
e te
mpe
ratu
re
setti
ng fo
r too
larg
e ou
tdoo
r-air
proc
essi
ng c
apac
ity.
Ther
mos
tat O
FF m
ay b
e ca
rried
out
.
NO
TE1)
The
se fi
gure
s as
sum
e th
e fo
llow
ing
oper
atin
g co
nditi
ons.
(Indo
or a
nd o
utdo
or u
nits
)Eq
uiva
lent
pip
e le
ngth
: 25
ft.Le
vel d
iffer
ence
: 0 ft
.
3)
:
The
dis
char
ge a
ir te
mpe
ratu
re
may
not
mat
ch th
e te
mpe
ratu
re
setti
ng fo
r too
sm
all o
utdo
or-a
ir pr
oces
sing
cap
acity
.
4) T
he s
yste
m w
ill no
t ope
rate
in fa
n m
ode
whe
n th
e ou
tdoo
r-air
tem
pera
ture
is 4
1°F
or b
elow
.
89.6
17
FXMQ-MFVJU EDUS39-900B-F10
FXMQ96MFVJU
C: 3
D04
6313
Ope
ratio
nlim
it(c
oolin
g)
Ope
ratio
n lim
it(h
eatin
g)
Fan
only
oper
atio
nOutdoor a
ir temp. (°
F WB)
Out
door
air
tem
p. (°
F D
B)23
3259
66.2
84.2
(92.
3)10
6.7
109.
42)
:The
dis
char
ge a
ir te
mpe
ratu
re
may
not
mat
ch th
e te
mpe
ratu
re
setti
ng fo
r too
larg
e ou
tdoo
r-air
proc
essi
ng c
apac
ity.
Ther
mos
tat O
FF m
ay b
e ca
rried
out
.
NO
TE1)
The
se fi
gure
s as
sum
e th
e fo
llow
ing
oper
atin
g co
nditi
ons.
(Indo
or a
nd o
utdo
or u
nits
)Eq
uiva
lent
pip
e le
ngth
: 25
ft.Le
vel d
iffer
ence
: 0 ft
.
3)
:
The
dis
char
ge a
ir te
mpe
ratu
re
may
not
mat
ch th
e te
mpe
ratu
re
setti
ng fo
r too
sm
all o
utdo
or-a
ir pr
oces
sing
cap
acity
.
4) T
he s
yste
m w
ill no
t ope
rate
in
fan
mod
e w
hen
the
outd
oor-a
ir te
mpe
ratu
re is
41
°F o
r bel
ow.
89.6
18
FXMQ-MFVJU EDUS39-900B-F10
10. Fan Performances
FXMQ48MFVJU
3D06
5649
B
19
FXMQ-MFVJU EDUS39-900B-F10
FXMQ72MFVJU
3D06
5650
B
20
FXMQ-MFVJU EDUS39-900B-F10
FXMQ96MFVJU
3D06
5651
B
21
FXMQ-MFVJU EDUS39-900B-F10
11. Sound Levels (Reference Data)11.1 Overall
n Location of microphone
6.6 ft4.
9 ft
DUCTDISCHARGE SUCTION
MICROPHONE
DUCT
3.3 ft
Note:1.Operationnoisedifferswithoperationandambientconditions.
dBAModel 208/230V,60Hz
FXMQ48MFVJU 43FXMQ72MFVJU 48FXMQ96MFVJU 48
22
FXMQ-MFVJU EDUS39-900B-F10
11.2 Octave Band Level
208/230V,60Hz
FXMQ48MFVJU FXMQ72MFVJU
C: 4D068575 C: 4D068576
FXMQ96MFVJU
C: 4D068577
23
FXMQ-MFVJU EDUS39-900B-F10
12. Accessories12.1 Optional Accessories (for Unit)
Option FXMQ48MFVJU FXMQ72MFVJU FXMQ96MFVJUDrainpumpkit KDU30L250VE
Highefficiencyfilter65% KAF372M140 KAF372M28090% KAF373M140 KAF373M280
FilterchamberH1 KDJ3705L140 KDJ3705L280Longlifereplacementfilter KAF371M140 KAF371M280
C:3D065445Note:H1.Filterchamberhasasuction-typeflange.(Mainunitdoesnothave.) ·Dimensionsandweightoftheequipmentmayvarydependingontheoptionsused. ·Someoptionsmaynotbeusableduetotheequipmentinstallationconditions,sopleaseconfirmpriortoordering. ·Someoptionsmaynotbeusedincombination. ·Operatingsoundmayincreasesomewhatdependingontheoptionsused.
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
©All rights reserved 03/21 FS
●Specifications, designs and other content appearing in this brochure are current as of March 2021 but subject to change without notice.