Over Current & Earth Fault RelayS8-200
TRIP
51
50
D/I 3
Pickup Current Setting
Curve Selection
Time Multiplier
Instantaneous Setting
A
%
R E
Trip Record
SetEnter
Parameters Setting51G/N
50G/N
D/I 2
D/I 4 Test Trip
D/I 1
Relays Setting
RS485 Setting
D/I Setting
K
TAIK
O v e r c u r r e n t & E a r t h - F a u l t Re lay
S8-200
S8-200
S8-200
S8-200
200
S8-
Overcurrent and Earth-Fault Relay S8-200
Rated current input
Overload capability
Input burden
Rated frequency
Measuring range
Pickup current setting range
Inverse time multipier range
Definite time range
Instantaneous setting range
Time delay
Minimum acting time
1A or 5A
2 x rated continuously
50 x rated 2sec.
0.2VA per phase
50HZ or 60HZ
0 ~ 2000%
4 ~ 200%(1% step)
0.1 ~ 20.0 (0.1 step)
0.0 ~ 600.0sec.(0.1 sec. step)
4 ~ 2000% (1% step)
0.01 ~ 2.00sec.(0.01 sec. step)
40msec. Typical
Overcurrent unit
Earth-Fault unit
Rated current input
Overload capability
Input burden
Rated frequency
Measuring range
Pickup current setting range
Inverse time multipier range
Definite time range
Instantaneous setting range
Time delay
Minimum acting time
0.6A or 3A
2 x rated continuously
50 x rated 2sec.
0.2VA
50HZ or 60HZ
0 ~ 500%
2.0 ~ 50.0% (0.1% step)
0.1 ~ 20.0 (0.1 step)
0.0 ~ 600.0sec. (0.1 sec. step)
2 ~ 500% (1% step)
0.00 ~ 2.00se c. (0.01 sec. step)
40msec. Typical
IEC/BS142, ANSI, IAC(selection)
Nomal inverse
Very inverse
Extremely inverse
Short time inverse
Moderately inverse
Cmply with standards
Inverse time curve
Time/Current Characteristic at Inverse Mode
SPECICATION
Display
Definite time mode
Accuracy
± 0.5% full scal
± 2% of set value or ± 20ms
<
=
Nominal voltage
Burden
Power supply
AC/DC 85~265 V
or DC 20~60 V
AC 6VA,DC 7W<= <=
Type
Digital format
0.56"H, red LED
1 row of 4 digits
Display
SPDT
SPSTx2
AC 250V 5A
DC 30V 5A
5 type
Latch or pulse
Trip relay
Auxiliary relay
Contact capacity
Trip status
Energized mode
Output
Digital Input
Contact made
Type
Dry contact
4 programmable input
Communication
Interface
Protocal
Baud rate
Address range
Data format
Number of meter
RS485
MODBUS, RTU framing
1200 ~ 38400 programmable
1 ~ 255 programmable
N.8.1/ N.8.2/ O.8.1/ E.8.1 programmable
up to 32
256 (option)
Frame
IP50Degree
4 records
EEPROM
IEC 688, AC 2.3KV/1 minute between terminals
AC 3KV/1 minute between all terminals/case
Trip record
Setup memory
Dielectric strength
Operating temperatur
Storage temperature
Max.humidity
General
0 ~ 60 ºC
-10 ~ 70 ºC
90%
IEC 61000-4-5 (IEC 255-5)
IEC 61000-4-4 (IEC 255-22-4)
IEC 61000-4-2
IEC 61000-4-11
IEC 255-22-1,CLASS III
IEC 255-22-3,CLASS III
IEC 255-21-2,CLASS I
IEC 255-5
Withstanding impulse voltage
Electrical transient in burst
Electrostatic discharge
Voltage disps and short interuptions
1MHZ interference
Radio interfrence
Shock test
Insulation test
Immunity Test
S8-200
Model
Input current
1: 1A
5: 5A
0: Option
Power supply
1: AC/DC 85 ~ 265 V
2: DC 20 ~ 60 V
0: Option
RS485 output
Y: Yes
N: No
ORDERING INFORMATION
CONNECTION DIAGRAM
Overcurrent and Earth-Fault Relay S8-200
)(OUTSIDE DIMENSION Unit:mm
Panel Cut-Out
138 +1- 0
138 +1- 0
144
868
137.4
Max. 25
RS 485 or
(RS 232)
144
144
T1
P1P2
A+B-O 2G2a1G1aO2V+O1V+
2A 3C 3A1A 2CR1R2S2 S1T1E1 T2E2 1B 1C
T3T2
Current Input Ry1 Ry2 Ry3 Power Supply
- +
D/I1D/I2D/I3D/I4
Digital Input