Overview of MEA Power
Distribution System
Dr. Asawin RajakromConstruction Department, Metropolitan electricity Authority
Presentation Outline
• Thailand power system
• MEA organization overview
• MEA Power system overview
• MEA Power system loss
• MEA Power system reliability
• MEA success story
2
14/01/58
2
3
Thailand Utility Highlight
4
Description EGAT PEA MEA
Area (km2) 513,115 509,923 3,192
Population 64,456,695 56,421,160 8,035,535
Customer 16,599,507 3,194,167
Employee 22,460 28,060 8,121
Demand (MW) 26,121.1 16,748.8 8,383
14/01/58
3
Thailand Network Facilities
5
DescriptionEGAT PEA MEA
Line1) Sub2) TR3) Line Sub TR Line Sub TR
500kV 3,721.95 10 15,850
230kV 13,393.05 68 44,560 49.54 3 2,400
132kV 8.71 133
115kV 13,279.73 130 14,574 9,214* 463 695.32 233** 20,896
69kV 18.8 870.23
MV(11, 12, 22, 24, 33kV)
296,245 16,058.68 16,980
LV 457,959 25,509.97
300kV (HVDC) 22.99 388
Total 30,639.75 208 75,505 763,418 463 72,110 43,183.74 236 40,276
* All HV transmission lines** 69 & 115 kV
1) cct-km2) No. of substation3) MVA
Thailand Utility Performance
6
DescriptionEGAT PEA MEA
2011 2012 2011 2012 2011 2012Total assets 15,777 16,956 9,645 9,814 4,401 4,700
Total liabilities 6,183 6,613 6,277 6,246 2,409 2,544
Equity 9,594 10,343 3,368 3,567 1,992 2,157
Total revenues 13,284 16,285 10,310 12,323 4,745 5,664
Total expenses 11,634 14,460 9,915 11,848 4,569 5,365
Net profit 1,087 1,339 395 475 176 299
14/01/58
4
Electricity Consumption by Sector
7
Thailand Generation Installed Capacity
8
Source: EGAT 2011
14/01/58
5
Thailand Generation Fuel Mix
9
Source: EGAT 2011
MEA Organization Chart
10
14/01/58
6
MEA Organization Overview
11
Wat
LiabKlongToei
Yan Nawa
Samsen
Bang Khen
LatPhrao
Bang
Kapi
Samut Prakarn
Bang Plee
Min Buri
Lat Krabang
Prawet
Thon Buri
Rat Burana
Bang
Khunthian
Nonta Buri
Bang Yai
Bang Buathong
Metropolitan Electricity Authority District
MEA System Performance
12
Description Unit 2011 2012 2013Population (Thailand) 64,076,033 64,456695 64,785,909
Population (MEA) 8,000,693 8,035,535 8,084,133
Customers 3,115,695 3,194,167 3,281,574
Employees 7,926 8,121
Customer/employee 393 393
Energy Purchase GWh 45,774 49,997 49,627
Energy Sale GWh 44,197 48,244 47,951
Maximum Power MW 7,858 8,383 8,590
Energy Loss % 3.44 3.51 3.31
Load Factor % 66.47 68.92 64.27
14/01/58
7
MEA Financial Performance
13
Description 2011 2012 2013Total assets 138,641 148,060 165,127
Total liabilities 75,898 80,126 92,228
Equity 62,744 67,935 72,899
Total revenues 149,471 178,412 192,152
Total expenses 143,934 169,005 180,921
Net profit 5,537 9,408 11,234
Unit in Million THB
MEA Power System
14
230/500 kV
Terminal Station
Substation69/115 kV Customer
Power Plant
12/24 kV Customer
12/24 kV
220/380 V Customer
69/115 kV
220/380 V
14/01/58
8
MEA Power System
15220/380 V
CUSTOMER
GENERATORGENERATOR
69/115 kV
CUSTOMER
12/24 kV
CUSTOMER
1313..8 8 kVkV1313..8 8 kVkV 6969//115 115 kVkV6969//115 115 kVkV 1212//24 24 kVkV1212//24 24 kVkV 220220//380 380 VV220220//380 380 VV230 230 kVkV230 230 kVkV
Tra
nsm
issi
on
Tra
nsm
issi
on
Line
Line
Sub
sta
tion
Sub
sta
tion
Sub
tra
nsm
issi
on
Sub
tra
nsm
issi
on
Line
Line
Term
ina
l S
tatio
nTe
rmin
al
Sta
tion
Dis
trib
utio
n Li
neD
istr
ibut
ion
Line
Se
cond
ary
Se
cond
ary
EGATEGATMEAMEA
MEA Power System
16
MEA MEA MEA MEA 69 69 69 69 kV T/SkV T/SkV T/SkV T/S
MEA MEA MEA MEA 115 115 115 115 kV T/SkV T/SkV T/SkV T/S
MEA MEA MEA MEA 69 69 69 69 & & & & 115 115 115 115 kV T/SkV T/SkV T/SkV T/S
MEA MEA MEA MEA 230 230 230 230 kV T/SkV T/SkV T/SkV T/S
EGAT EGAT EGAT EGAT 500 500 500 500 kV Transmission LineskV Transmission LineskV Transmission LineskV Transmission Lines
EGAT EGAT EGAT EGAT 230 230 230 230 kV Transmission LineskV Transmission LineskV Transmission LineskV Transmission Lines
MEA MEA MEA MEA 230 230 230 230 kV Transmission LineskV Transmission LineskV Transmission LineskV Transmission Lines
EGAT EGAT EGAT EGAT 500 500 500 500 kV StationkV StationkV StationkV Station
South Bangkok
Bangplee
On-nuj
Teparak
Klong Rangsit
Thanontok
Chidlom
Vibhavadi
Klongdan
(Future)
Nongjok
SainoiJangwattana
North Bangkok
South Thonburi
Bangkoknoi
Ratchadapisek
Lardprao
Bangkapi
Sainoi
Nongjok
14/01/58
9
MEA Power System
17
Description No Capacity (MVA)
Terminal Station 17 18,306
Substation 131 17,690
Switching Station 1 80
Small Power Producer 1 105.88
69, 115kV Customer 84 3,285
Distribution transformer 17,350
MEA Power System
18
Description Length (Circuit km)
230kV Transmission Line 49.54
115kV Sub-transmission Line 746.14
69kV Sub-transmission Line 900.93
12, 24kV Distribution Line 17,478.15
220/380V Low Voltage Line 27,656.33
14/01/58
10
Power System Losses
19
4.34.19
3.963.82
3.25 3.23
3.41
3.6
3.14
3.46 3.39 3.44 3.51
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
1998 2000 2002 2004 2006 2008 2010 2012 2014
Loss Reduction Program
20
0
5
10
15
20
25
1958 1963 1968 1973 1978 1983 1988 1993 1998 2003
Year
% MEA's total energy losses
1. Conversion from 110 to 220 Volts (1962 – 1970)
4.3 Conversion from 12 kV Primary to 24 kV primary (1977-present)
4.4 Conversion from 69 kV Primary to 115 kV primary (1990-present)
3. Non-technical loss reduction (1963-present)
4.2 Conversion from 220 V, 3-phase 3 wire to 220 / 380 V, 3-phase 4 wire
(1977- 1988)
4.1 Capacitor installation (1964-present)
4. Distribution system improvement program
2. Engineering standard (1963-present)
14/01/58
11
Power System Reliability
21
Reliability Indices
SAIFI (System Average Interruption Frequency Index)
SAIFI = Σ Total number of Customers Interrupted
Total number of Customers Served
SAIDI (System Average Interruption Duration Index)
SAIDI = Σ Customer Interruption Duration
Total number of Customer Served
MAIFI (Momentary Average Interruption Duration Index)
MAIFI = Σ Total number of Customers Interrupted less than defined time
Total number of Customers Served
Reliability Service Standard
22
Service Area SAIFI (times/cust/year)
SAIDI (minutes/cust/year)
City/Business 2.46 54.86
Industrial 2.63 54.23
Suburb 4.32 100.37
Overall MEA 2.79 62.07
14/01/58
12
MEA SAIFI
23
2.0191.931
1.869
1.699
2.3882.299
1.865
1.715
1.837
1.831
0
0.5
1
1.5
2
2.5
3
2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013
MEA SAIDI
24
42.174 42.136
37.101
59.652
50.645
47.055
46.919
58.798
49.448
0
10
20
30
40
50
60
70
2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013
14/01/58
13
Reliability Improvement Measures
25
Stage ActivitiesPlanning construct of additional subtransmission line
conversion of overhead line to underground cable
Design open loop tap-tied configuration
Install line LBS
Maintenance Tree Pruning/Cutting
Line patrol with Thermo-scan or binocular
Clean live line insulation by pressurized water spray
provide outage restoration crews on standby
for 24 hour service
Su
bS
ub
--tra
nsm
issio
n L
ine
str
an
sm
issio
n L
ine
s
Reliability Improvement Measures
26
Stage ActivitiesPlanning Build new substations
Replace metal-clad air insulated switchgears with SF6 gas insulated ones
Install fibre optic network which is far more reliable and accurate than radio signal for SCADA
Design Design double bus for 69 KV& 115 KV GIS and single bus tie for 12 KV & 24 KV GIS
OLTC with oil filter
partition power transformer bank and install fire extinguish system
Maintenance Do periodic test of protection relay and alarm system
power transformer oil filtration
Clean OLTC contact
Measure contact resistance and closing time of circuit breaker of medium voltage switchgear
Su
bsta
tio
ns
14/01/58
14
Reliability Improvement Measures
27
Stage ActivitiesPlanning Replace bare conductor or partial insulated cable with aerial
spaced cable.
Convert from overhead line to underground cable
Install distribution automation system (DAS)
Design multi-dividing multi-connecting configuration
reduce the length of line
Replace pin type insulator (ANSI class 56-1) with pin-post type
(TISI class 56/57-2)
Maintenance Prune the trees
Line patrol with Thermo-scan Or binocular
Measure transformer load current
Provide outage restoration crews on 24 hour standby services
Insulate live parts to prevent interruption caused by animals. Dis
trib
uti
on
Lin
es
MEA Success Story:
Distribution System Performance
28
With the SAIFI of 1.831 and SAIDI of 49.448 in 2011,
MEA steps towards leading utility of South East Asia.
2.019 1.9311.869
1.699
2.388 2.299
1.865
1.715
1.8371.831
0
0.5
1
1.5
2
2.5
3
2002 2004 2006 2008 2010 2012 2014
42.17442.136
37.101
59.652
50.64547.055
46.919
58.798
49.448
0
10
20
30
40
50
60
70
2002 2004 2006 2008 2010 2012 2014
14/01/58
15
MEA Success Story: Loss Minimization
With 3.51% system loss in 2011, MEA stands at level
of the lowest loss utility.
29
4.3 4.193.96 3.82
3.25 3.23
3.41
3.6
3.14
3.46 3.39 3.44 3.51
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
1998 2000 2002 2004 2006 2008 2010 2012 2014
MEA Success Story:
Underground System Implementation
With 5 decades experience of
planning, design, installation, operation and maintenance of
underground cable, MEA has excellent knowledge of large
city underground power system implementation.
30
6
5 4
3
2 1
R =0.912 m
Angle = 90 Deg. R =9.12 m
Angle = 15 Deg.
R =18.24 m
Angle = 15 Deg.
50.8 M.
63.5 M.
14/01/58
16
MEA Success Story:
Gas Insulated Switchgear: GIS
To meet the performance requirement, maintenance costs
and land use minimization, MEA has standardized its HV/MV
switchgear to the GIS.
31
MEA Success Story: SCADA EMS/DMS
With 5 dispatching centers and 18 district control centers, MEA can remotely control and monitor almost every CB, DS in substations and major switches in distribution lines.
32
HV customerHV customerHV customerHV customer
MV customerMV customerMV customerMV customeror MV / LV transformeror MV / LV transformeror MV / LV transformeror MV / LV transformer
EHV customerEHV customerEHV customerEHV customer
Transmission networkTransmission networkTransmission networkTransmission network
SubSubSubSub----transmission networktransmission networktransmission networktransmission network
Primary Primary Primary Primary distribution distribution distribution distribution
systemsystemsystemsystemEMSEMSEMSEMS
DMSDMSDMSDMS
14/01/58
17
MEA Success Story:
Geographical Information System: GISMore than ten years of GIS implementation, MEA not only provides data and tools for their staff to deal with power system management and its customer services , but also benefits from selling GIS services to external public and private sector.
33
MEA Success Story:1130 Call Center
Anything concerning with ELECTICITY, 1130 can TELL you.
Services are available 24 hours a day, 7 days a week.
34
14/01/58
18
MEA Success Story:
Consulting and Training Services
• Private sector electrical training
• IPP consultancy services
• Industrial customer reliability improvement
program
• International training programs both in-
house and oversea
• Consultancy services for oversea utilities35
Oversea Utility Takeover Program
• Enugu Electricity Distribution Company, Nigeria
36
14/01/58
19
MEA Success Story: More…..
• Robust communication infrastructure
• Concrete pole factory
• ISO 9001:2000
• TIS/OHSAS 18001
• ERP
• And many more ……
37
“T“Thank you!”hank you!”