© 2020 Johnson Controls, Inc. 1 of 2 Specifications subject to change. Form No. DFS-12PHP2-2020 Effective Date 7/31 P Series SUBMITTAL DATA SHEET DHP12NWB21S/DHP12CSB21S 12,000 BTU/H Wall Mounted Heat Pump System Job Name: Location: Purchaser: Order No.: Engineer: Submitted To: For: Ref: Approval: Construction: Submitted By: Date: Unit Designation: Schedule No.: Model No.: DHP12NWB21S DHP12CSB21S System Rating Heat Pump Rated Cooling Capacity 12,000 Cooling Capacity (Min-Max) 3,753-12,500 Rated Heating Capacity 13,000 Heating Capacity (Min-Max) 3,924-14,000 9.25 16 9 Rated Voltage 208/230-1-60 Rated Cooling Current 5.8 Rated Heating Current 5.6 MCA 9 MOCP 15 Max. Total Piping Length Max. Piping Height Piping Connection - Liquid (O.D.) 1/4 Piping Connection - Gas (O.D.) 3/8 DHP12NWB21S Set Temperature Range 6186 (16 30) Airflow High to Low 400/318/241/194 SoundPressureLevel High to Low 43/39/35/29 Unit Dimension (WxDxH) 33.26×11.37×8.22 (845×289×209) Net Weight / Gross Weight Operation Range - Cool/Heat 23.14/28.55(10.5/13.1) DHP12CSB21S 0~115 0~115 (-18~46)/-4~75 (-20~24) R410A Refrigerant Charge 30 (0.85) Unit Dimension (WxDxH) 30.55x21.26x12.59(776x540x320) Net Weight / Gross Weight 67.24/72.75 (30.5/33) Sound Pressure Level dB(A) 53 Ԭ (Ԩ) CFM lbs (kg) dB(A) Outdoor Model number Ԭ (Ԩ) Refrigerant oz (kg) in. (mm) dB(A) in. (mm) lbs (kg) V-PH-Hz Amps Amps Amps Amps in. (m) in. (m) in. in. Indoor Model number SystemType Btu/h Btu/h Btu/h Btu/h EER SEER HSPF ft. ft. 33 (10) 65.5 (20) FEAT URES Compact and Quiet Design High Efficiency DC Inverter Technology Wireless Remote with LCD Display Low Ambient Cool to 0 deg F Vertical Swing Louver DRCPX CS532AH (Standard) (Optional) ACCESSORIES Wired Controller DWCPX2 Wired Controller DWUNI Wi-Fi Module CS532AH DWUNI (Optional) DWCPX2 (Optional)

Upload: others

Post on 31-May-2022

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: P Series SUBMITTAL DATA SHEET

© 2020 Johnson Controls, Inc. 1 of 2 Specifications subject to change.

Form No. DFS-12PHP2-2020 Effective Date 7/31 P Series

SUBMITTAL DATA SHEET

DHP12NWB21S/DHP12CSB21S 12,000 BTU/H Wall Mounted Heat Pump System

Job Name: Location: Purchaser: Order No.:Engineer: Submitted To: For: Ref: Approval: Construction: Submitted By: Date: Unit Designation: Schedule No.: Model No.:

DHP12NWB21S

DHP12CSB21S

System RatingHeat Pump

Rated Cooling Capacity 12,000

Cooling Capacity (Min-Max) 3,753-12,500

Rated Heating Capacity 13,000

Heating Capacity (Min-Max) 3,924-14,000

9.25

16

9

Rated Voltage 208/230-1-60

Rated Cooling Current 5.8

Rated Heating Current 5.6

MCA 9

MOCP 15

Max. Total Piping Length

Max. Piping Height

Piping Connection - Liquid (O.D.) 1/4

Piping Connection - Gas (O.D.) 3/8

DHP12NWB21S Set Temperature Range 61 86 (16 30)

Airflow High to Low 400/318/241/194

SoundPressureLevel High to Low 43/39/35/29

Unit Dimension (Wx DxH) 33.26×11.37×8.22 (845×289×209)

Net Weight / Gross Weight

Operation Range - Cool/Heat

23.14/28.55(10.5/13.1)

DHP12CSB21S 0~115 0~115 (-18~46)/-4~75 (-20~24)

R410A

Refrigerant Charge 30 (0.85)

Unit Dimension (Wx DxH) 30.55x21.26x12.59(776x540x320)Net Weight / Gross Weight 67.24/72.75 (30.5/33)

Sound Pressure Level dB(A) 53

( )

CFM

lbs (kg)

dB(A)

Outdoor Model number ( )

Refrigerant

oz (kg)

in. (mm)

dB(A)

in. (mm)

lbs (kg)

V-PH-Hz

Amps

Amps

Amps

Amps

in. (m)

in. (m)

in.in.

Indoor Model number

SystemType

Btu/h

Btu/h

Btu/h

Btu/h

EER

SEER

HSPF

ft.ft. 33 (10)

65.5 (20)

FEAT URES • Compact and Quiet Design

• High Efficiency DC Inverter Technology

• Wireless Remote with LCD Display

• Low Ambient Cool to 0 deg F

• Vertical Swing Louver

DRCPX CS532AH (Standard) (Optional)

ACCESSORIES • Wired Controller DWCPX2

• Wired Controller DWUNI

• Wi-Fi Module CS532AH

DWUNI(Optional)

DWCPX2(Optional)

Page 2: P Series SUBMITTAL DATA SHEET

© 2020 Johnson Controls, Inc. 2 of 2 Specifications subject to change

DHP12NWB21S/DHP12CSB21S

Indoor Unit Dimensions

Outdoor Unit Dimensions

Drain Connector 5/8-in OD

Unit: inch

Unit: inch

W 33 1/4H 11 3/8D 8 1/4

Dimensions

Notes:

1. Recommended cable type between Outdoor and Indoor Unit,14-4 AWG Stranded Copper THHN 600V Wire2. Power wiring cable size must comply with applicable national and local codes3. Test conditions are based on AHRI 210/240