H7.00A
& SYSTEM SUMMARY
CONTROL SCHEMATIC
RF
F
AI
EA
MA
MOD
AO MOD
AO
MOD
AO
M
ASD
SD
BI
RA
OA
BOS
S
SCAO RBI
TYPICAL ASD CONTROL/MONITORING POINTS
AS
D
M
R AOM
SYSTEM
FIRE ALARM
WIRE TO
COM BACnet / MSTP
AV: SPEED (RPM)
AV: POWER (KW)
P
AI
AIR
OUTSIDE
AIR
RETURN
T
AI
SETPOINT
AV
N.C.
N.O.
N.C.
RA
AOM
SYSTEM
ALARM
TO FIRE
SF
M
ASD
F
AI
P
BI
TO FAN CIRCUIT
P
BI
TO FAN CIRCUIT
P
BI
TO FAN CIRCUIT
P
BI
TO FAN CIRCUIT
T
AI
T
AI
RH
AI
F
AI
MANUFACTURER
STATION BY UNIT
FAN INLET AIRFLOW
T
AISETPOINT
AV
C
PH
T
AI
AO
N.O.
COIL
PREHEAT
C
C
T
AI
COIL VALVE
PREHEAT
BANK
FILTERRETURN & OUTSIDE AIR DAMPER BY UNIT MANUFACTURER
RBI
SSBO
COMPRESSOR
DIGITAL SCROLL
COIL
COOLING
DXSP
REFER TO PLANS
SETPOINT
AVAI
AIRSUPPLY
FAN INLET AIRFLOW STATION
RH
AI
SETPOINT
AV
AIR
RELIEF
1AHU-1 CONTROL SCHEMATIC AND SYSTEM SUMMARY
NTS
SEQUENCE OF OPERATION
AS NOTED
POINT SCHEDULE
AIR HANDLING UNIT AHU-1 SYSTEM
HARDWARE POINTS SOFTWARE POINTS
GRAPHIC
SHOWN ONNOTES
BI BO AI AO AV BV SCH TRENDALARM
BACS EMCS DESCRIPTION
STEAM LOAD SHED X (6) BINARY NETWORK INPUTS FROM EMCS
CHILLED WATER LOAD SHED X (4) BINARY NETWORK INPUTS FROM EMCS
OUTSIDE AIR FLOW X X X EITHER MINIMUM OR TOTAL
OUTSIDE AIR DAMPER POSITION COMMAND X X
RELIEF AIR DAMPER POSITION COMMAND X X
OUTSIDE AIR TEMPERATURE X X X AVERAGING SENSOR
OUTSIDE AIR DEWPOINT X X X
MIXED AIR TEMPERATURE X X X X +/- 4 DEG F FROM SETPOINT X AVERAGING SENSOR
MIXED AIR TEMPERATURE SETPOINT X X X
FILTER RACK DIFFERENTIAL PRESSURE X X X X HIGH LIMIT X MAGNEHELIC INDICATING TRANSMITTER
PREHEAT COIL VALVE POSITION COMMAND X X X X F DELTA T ACROSS COIL WITH VALVE COMMANDED CLOSEDo
5 X NORMALLY OPEN
PRE-HEAT COIL DISCHARGE AIR TEMPERATURE X X X AVERAGING SENSOR
COOLING COIL COMPRESSOR START/STOP X X X
COOLING COIL COMPRESSOR STATUS X X X FAILURE X
COOLING COIL DISCHARGE AIR TEMPERATURE X X X AVERAGING SENSOR
SUPPLY FAN LOW SUCTION PRESSURE SWITCH STATUS X X X LOW LIMIT X
SUPPLY FAN START/STOP X X X INTERLOCK WITH FA SYSTEM, IF REQUIRED
SUPPLY FAN SPEED COMMAND X X X
SUPPLY FAN STATUS X X X FAILURE X VIA CONTACT ON DRIVE
SUPPLY FAN POWER (KW) X X X BACnet MSTP NETWORK POINT
SUPPLY FAN SPEED (RPM) X X X BACnet MSTP NETWORK POINT
SUPPLY AIRFLOW X X X INSTALL IN INLET CONE
SUPPLY FAN HIGH DISCHARGE PRESSURE SWITCH STATUS X X X HIGH LIMIT X
AHU DISCHARGE AIR TEMPERATURE X X X X DEVIATION FROM SETPOINT X SINGLE POINT SENSOR
AHU DISCHARGE AIR TEMPERATURE SETPOINT X X X
SUPPLY FAN DOWNSTREAM STATIC PRESSURE X X X X 10% DEVIATION FROM SETPOINT X
SUPPLY FAN DOWNSTREAM STATIC PRESSURE SETPOINT X X X
RETURN DUCT SMOKE DETECTOR STATUS X X
RETURN FAN LOW SUCTION PRESSURE SWITCH STATUS X X X LOW LIMIT X
RETURN FAN AIRFLOW X X X INSTALL IN INLET CONE
RETURN FAN MOTOR START/STOP X X X X INTERLOCK WITH FA SYSTEM
RETURN FAN SPEED COMMAND X X X
RETURN FAN STATUS X X X FAILURE X VIA CONTACT ON DRIVE
RETURN FAN POWER (kW) X X X BACnet MSTP NETWORK POINT
RETURN FAN SPEED (RPM) X X X BACnet MSTP NETWORK POINT
RETURN FAN HIGH DISCHARGE PRESSURE SWITCH STATUS X X X HIGH LIMIT X
RETURN AIR TEMPERATURE X X X
RETURN AIR RELATIVE HUMIDITY X X X
DIVISION 23
STATION BY
OUTSIDE AIRFLOW
SYSTEM DESCRIPTION
RECIRCULATING AIR HANDLING UNIT
SUPPLY AIR FAN
RETURN AIR FAN
GLYCOL PREHEAT COIL
DX COOLING COIL
GENERAL
CONTROL SYSTEM (BACS)
SYSTEM SHALL BE CONTROLLED THROUGH THE BUILDING AUTOMATION AND
ALL SETPOINTS SHALL BE ADJUSTABLE
SEVEN DIFFERENT DAILY SCHEDULES PER WEEK.
THE BACS SHALL BE CAPABLE OF STARTING AND STOPPING THE SYSTEM FOR
SETTING DURING A LOSS OF POWER FOR AT LEAST TEN HOURS.
THE BACS SHALL BE CAPABLE OF RETAINING ITS PROGRAMMING AND TIME
AND SHALL REQUIRE MANUAL RESET.
ALL SAFTIES SHALL BE HARD WIRED INTO THE FAN MOTOR POWER CIRCUIT
SETPOINTS
AHU DISCHARGE AIR TEMPERATURE (DAT): SEE RESET SCHEDULE
MINIMUM OUTSIDE AIRFLOW RATE (BASE BID): 510 CFM
MINIMUM OUTSIDE AIRFLOW RATE (ADD ALT 1): 730 CFM
FILTER DIFFERENTIAL PRESSURE HIGH LIMIT = 1.0" W.C.
SUPPLY DOWNSTREAM STATIC PRESSURE = 1.0" W.C.
SUPPLY FAN DISCHARGE HIGH STATIC PRESSURE LIMIT: 6.0" W.C.
SUPPLY FAN SUCTION LOW STATIC PRESSURE LIMIT: - 6.0" W.C.
RETURN FAN DISCHARGE HIGH STATIC PRESSURE LIMIT: 6.0" W.C.
RETURN FAN SUCTION LOW STATIC PRESSURE LIMIT: - 6.0" W.C.
RETURN AIRFLOW RATE:
AIRFLOW SETPOINT MINUS 300 CFM.
BASE BID: THE RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO THE SUPPLY
AIRFLOW SETPOINT MINUS 730 CFM.
ADD ALT 1: THE RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO THE SUPPLY
MODULATED ECONOMIZER MIXED AIR TEMPERATURE: 5
OWNER)
SYSTEM OCCUPANCY SCHEDULE: 6 AM TO 8 PM, MON-FRI (COORDINATE WITH
START/STOP
OCCUPANCY.
TEMPERATURE AND THE AMOUNT OF TIME PRIOR TO THE SCHEDULED
MINIMUM, BE A FUNCTION OF THE DIFFERENCE BETWEEN SPACE
OPTIMUM START CONTROL ALGORITHM. THE ALGORITHM SHALL AS A
AND OPERATE CONTINUOUSLY BASED ON THE TIME OF DAY SCHEDULE AND AN
OCCUPIED: SUPPLY AIR FAN AND ASSOCIATED RETURN AIR FAN SHALL START
OPERATE FOR A PERIOD OF UP TO 2 HOURS.
SWITCHES INDICATE OCCUPANCY; IN WHICH CASE THE SYSTEM SHALL
SHALL BE INDEXED TO START WHENEVER ANY OF THE MANUAL OVERRIDE
SWITCHES ARE PROVIDED IN LIEU OF OCCUPANCY SENSORS, THE SENSOR
OCCUPANCY IS NOT SENSED FOR A PERIOD OF 30 MINUTES. IF OVERRIDE
SYSTEM SHALL STOP AND INDEX BACK TO UNOCCUPIED MODE WHEN
SYSTEM IS OCCUPIED, AS DETERMINED VIA SPACE OCCUPANCY SENSORS. THE
SHALL BE INDEXED TO START WHENEVER ANY SPACE ASSOCIATED WITH THE
UNOCCUPIED: DURING THE SCHEDULED UNOCCUPIED PERIOD, THE SYSTEM
ADD ALTERNATE 1: SYSTEM SHALL BE ENABLED AT ALL TIMES
SHUTOFF DAMPER CONTROL
SHALL BE CLOSED. THE MIXED AIR DAMPER SHALL BE OPEN.
WHEN THE SYSTEM FANS ARE OFF, THE OUTSIDE AIR AND RELIEF AIR DAMPERS
SAFETIES
THE HIGH FAN DISCHARGE STATIC PRESSURE SWITCH.
OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE UPON ACTIVATION OF
HIGH FAN STATIC: THE SUPPLY AND RETURN AIR FANS SHALL SHUT DOWN, THE
THE LOW FAN SUCTION STATIC PRESSURE SWITCH.
OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE UPON ACTIVATION OF
LOW FAN STATIC: THE SUPPLY AND RETURN AIR FANS SHALL SHUT DOWN, THE
FAN SPEED CONTROL
MAINTAIN THE CRITICAL ZONE DAMPER POSITION AT 95% OPEN.
DOWNSTREAM STATIC PRESSURE SETPOINT SHALL BE RESET AS NEEDED TO
REQUIRED TO MAINTAIN THE DOWNSTREAM STATIC PRESSURE SETPOINT. THE
THE SUPPLY AIR FAN SHALL MODULATE VIA VARIABLE FREQUENCY DRIVE AS
REQUIRED TO MAINTAIN THE RETURN AIRFLOW SETPOINT.
THE RETURN AIR FAN SHALL MODULATE VIA VARIABLE FREQUENCY DRIVE AS
AIRFLOW SETPOINT MINUS 300 CFM.
BASE BID: THE RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO THE SUPPLY
AIRFLOW SETPOINT MINUS 730 CFM.
ADD ALT 1: THE RETURN AIRFLOW SETPOINT SHALL BE EQUAL TO THE SUPPLY
SUPPLY AIR TEMPERATURE CONTROL
SCHEDULE:
TEMPERATURE SHALL BE ALLOWED TO RESET BASED ON THE FOLLOWING
DISCHARGE AIR TEMPERATURE RESET: THE AHU DISCHARGE AIR
OAT = 75F & --- DAT = 5
DAT = 6---OAT = 55F &
SETPOINT.
PREHEAT COIL CONTROL VALVE SHALL MODULATE AS REQUIRED TO MAINTAIN
SETPOINT, THE SCROLL COMPRESSOR SHALL BE INDEXED TO OFF AND THE
HEATING MODE: WHEN THE AHU DISCHARGE AIR TEMPERATURE FALLS BELOW
PACKAGED CONTROLS.
COMPRESSOR SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFTIES AND
REQUIRED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. THE
SCROLL COMPRESSOR SHALL MODULATE, VIA PACKAGED CONTROLS, AS
SETPOINT, THE PREHEAT COIL CONTROL VALVE SHALL BE CLOSED AND THE
COOLING MODE: WHEN THE AHU DISCHARGE AIR TEMPEARTURE RISES ABOVE
UNOCCUPIED TEMPERATURE CONTROL
THE ZONE SETPOINT IS SATISFIED.
CONTROL VALVE SHALL MODULATE AND THE SYSTEM SHALL OPERATE UNTIL
SHALL BE CLOSED, THE RETURN AIR DAMPER SHALL BE OPEN, THE PREHEAT
START AND RUN AT 30% AIRFLOW, THE RELIEF AND OUTSIDE AIR DAMPERS
UNOCCUPIED HEATING TEMPERATURE SETPOINT, THE SUPPLY FAN SHALL
IF ANY ZONE TEMPERATURES ASSOCIATED WITH AHU FALL BELOW
THE ZONE SETPOINT IS SATISFIED.
COMPRESSOR SHALL BE INDEXED ON AND THE SYSTEM SHALL OPERATE UNTIL
SHALL BE CLOSED, THE RETURN AIR DAMPER SHALL BE OPEN, THE SCROLL
START AND RUN AT 100% AIRFLOW, THE RELIEF AND OUTSIDE AIR DAMPERS
UNOCCUPIED COOLING TEMPERATURE SETPOINT, THE SUPPLY FAN SHALL
IF ANY ZONE TEMPERATURE ASSOCIATED WITH THE AHU RISE ABOVE THE
MINIMUM VENTILATION CONTROL
DAMPER SHALL BE CLOSED AND THE RETURN AIR DAMPER SHALL BE OPEN.
WHEN THE UNIT IS NOT OPERATING, THE OUTSIDE AIR DAMPER AND RELIEF AIR
SETPOINT.
MODULATE, WITH THE RETURN AIR DAMPER, AS NEEDED TO MAINTAIN
THE OUTSIDE AIR DAMPER SHALL OPEN TO MINIMUM POSITION AND THEN
WHEN THE UNIT IS OPERATING AND ECONOMIZER CONTROL IS NOT INITIATED,
MODULATED ECONOMIZER MODE (MAT CONTROL)
ECONOMIZER MODE (MAT CONTROL) SHALL BE INITIATED.
AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN 55F, MODU
WHEN THE RETURN AIR TEMPERATURE RISES ABOVE THE COOLING SETPOINT,
MIXED AIR TEMPERATURE SETPOINT OF 55î
RETURN AIR AND RELIEF AIR DAMPERS SHALL MODULATE TO MAINTAIN THE
THE MINIMUM OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE OUTSIDE AIR,
BE INITIATED.
AIR DAMPER SHALL INDEX TO MAXIMUM POSITION AND HEATING MODE SHALL
OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL INDEX TO MINIMUM, THE RETURN
LOW LIMIT: WHEN THE MIXED AIR TEMPERATURE FALLS BELOW SETPOINT, THE
SHALL BE INITIATED.
RETURN AIR DAMPER SHALL CLOSE AND INTEGRATED ECONOMIZER MODE
OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL INDEX TO FULL OPEN AND THE
HIGH LIMIT: WHEN THE MIXED AIR TEMPERATURE RISES ABOVE SETPOINT, THE
INTEGRATED ECONOMIZER MODE
REQUIRED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT.
CLOSED, THE CHILLED WATER CONTROL VALVE SHALL MODULATE AS
RELIEF AIR DAMPERS SHALL OPEN AND THE RETURN AIR DAMPER SHALL BE
55F, INTEGRATED ECONOMIZER MODE SHALL BE INITIATED. THE OUTSID
TEMPERATURE AND THE OUTDOOR AIR DEWPOINT TEMPERATURE IS BELOW
WHEN THE RETURN AIR TEMPERATURE IS ABOVE THE OUTDOOR AIR
OUTSIDE AIR TEMPERATURE FALLS BELOW 55
DISABLED, THE MODULATED ECONOMIZER MODE SHALL BE INTIATED WHEN THE
LOW LIMIT SHUTOFF: INTEGRATED ECONOMIZER CONTROL SHALL BE
INITIATED
CLOSED, MINIMUM VENTILATION CONTROL AND COOLING MODE SHALL BE
TEMPERATURE. THE OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL INDEX
DISABLED WHEN THE OUTDOOR AIR TEMPERATURE EXCEEDS THE RETURN AIR
HIGH LIMIT SHUTOFF: INTEGRATED ECONOMIZER CONTROL SHALL BE
DEWPOINT
AV
INTEGRAL SPEED DRIVE
KEY PLAN:
COLLEGE OF AGRICULTURE AND LIFE
CORNELL UNIVERSITY
SCIENCES (CALS)
ARCHITECT:
Mitchell Giurgola Architects LLP
630 Ninth Avenue, Suite 711
New York, New York 10036
212 663 4000
PROJECT NO:
PHASE:
DATE:
SCALE:
COPYRIGHT c 2018 MITCHELL GIURGOLA ARCHITECTS LLP
NO.
ISSUE/REVISION:
DATE COMMENTS
PROJECT: DRAWING TITLE:MEP ENGINEER
M/E Engineering, P.C.
300 Trolly Boulevard
Rochester, NY 14606
585 288 5590
607 272 6477
SITE | CIVIL ENGINEER:
T.G. Miller, P.C.
203 North Aurora Street
Ithaca, NY 14850
212 750 9000
STRUCTURAL ENGINEER:
LERA Consulting Structural Engineers
40 Wall Street, 23rd Floor
New York, NY 10005
M/E Engineering, P.C.
300 Trolly Boulevard
Rochester, NY 14606
585 288 5590
LEED CONSULTANT:
716 206 5100
HAZMAT CONSULTANT:
Watts Architecture & Engineering
95 Perry Street, Suite 300
Buffalo, NY 14203
716 823 0006
COST ESTIMATING:
4588 South Park Avenue
Trophy Point, L.L.C.
Blasdell, NY 14219
191900
WITH WORK.
ALL DIMENSIONS & EXISTING CONDITIONS SHALL BE CHECKED & VERIFIED BY CONTRACTOR BEFORE PROCEEDING
SUCF #: 161027
GREENHOUSES
RENOVATE CALS
- PHASE 1
BID DOCUMENTS
4-7-2020
SEAL: