Page 1 April 2010 Building Technologies
Product Presentation
SINORIXTM CDT
Page 2 April 2010 Building Technologies
Characteristic of nitrogen (N2)
Agent: clean
Extinguishing principle: displacement of Oxygen
Extinguishing concentration: min 30%
< 14.5% O2
Storage stage: as expended gas
Effect on people: harmless
(due to not having medical
effect on blood supply)
Room ambient After extinguishing
Oxygen
21%
Nitrogen
79 %
Nitrogen
89%
Approx.
Oxygen 10-12%
Nitrogen (N2) extinguishing agent
Page 3 April 2010 Building Technologies
Inert Gas ExtinguishingInert Gas Extinguishing
Inert gas systems aim to drop the O2 to between 10% and
14%. Ideally inert gas systems aim for ca. 12.5% O2
Page 4 April 2010 Building Technologies
• Nitrogen: Main component of air, inert and odourless
• Extinguishing agent which works by reducing the oxygen level
(< 14%)
• Ecologically clean
ODP = 0 (Ozone Depletion Potential)
GWP = 0 (Global Warming Potential)
• Does not create breakdown products in contact with a naked flame
•Siemens was the first to have the idea of using nitrogen as an extinguishing agent
SINORIX CDT 300 bar regulated
Page 5 April 2010 Building Technologies
• 60 second discharge with extinguishing before the end of the discharge.
• Pipework pressure < 100 bar
• Centralised system with optional directional valves
• Modular system for protection of small enclosures
• Using 40.3% of nitrogen reduces oxygen level to 12.5%, which equates to air breathed at an altitude of 3,500 m.
SINORIX CDT 300 bar regulated
Page 6 April 2010 Building Technologies
Sinorix CDT: The best solution compared with gas blends
Unlimited access to natural gases
Not dependent on specialist suppliers- Natural gas blends are available from only a limited number of
suppliers
No extra costs for an inert gas without extinguishing benefits- No patent costs for N2, Ar and CO2
- The price of a gas blend is about 5 times that of a single gas
No CO2 in SINORIX CDT(Unlike IG-541, which contain CO2)
Page 7 April 2010 Building Technologies
• Excellent extinguishing performance for Class A, B and C fires
- best solutions for rapidly spreading fires
- excellent performance on liquid and gas fires
• Electrically non-conductive
- safe for electronic risk
• Excellent performance on deep-seated fires with a retention time of 20 minutes
- suitable for archives
• Using inert gas
- no residues after a discharge
SINORIX CDT 300 bar regulated – Key points
Page 8 April 2010 Building Technologies
SINORIX CDT Stability of nitrogen after discharge
Oxygen Concentration after Discharge
10.0
11.0
12.0
13.0
14.0
0 60 120 180 240 300 360 420 480 540 600 660 720 780 840 900
Time [s]
Oxy
gen
Co
nce
ntr
atio
n [
Vo
l%]
O2% on 90% room height
O2% on 50% room height
O2% on 10% room height
max. O2 level after CEA 4008
110 m3 room/60 seconds discharge time
Page 9 April 2010 Building Technologies
What does CDT mean?
Constant
Discharge
Technology
New constant (or regulated) flow technology:
Discharge pressure is almost constant, whatever the container pressure.
Technology developed in house by Siemens SAS and manufactured by Production Extinction Siemens SAS.
All the accessories too (e.g.: Pressure switch, Manual actuator, ….)
SINORIX CDT 300 bar regulated
Page 10 April 2010 Building Technologies
SINORIX CDT
Removable pressure gauge
and pressure switch
Pressure Gauge 0-400 bar
Pressure Switch 270 bar
Removable under pressure
PRESCODEM 400/270
Equipped cylinders
80L / 130 Kg 300 bar working pressure
Cône DIN 477
Transportatino without accesories
TPED
BOUT80-CDT
Constant Discharge Valve
VFR 300SQuick connection
Page 11 April 2010 Building Technologies
VFR 300 S
Gas
Pressure at 15°C
Outlet pressure
Specifications
Nitrogen or Argon
300 bar
60 bar to 40 bar(60s discharge time)
No perforation disc (OPEF).
Soft opening of the valve
Outlet positioning left or right
No difference between master and slave valve
SINORIX CDT
Safety valve 95bars included
Page 12 April 2010 Building Technologies
VFR 300 SInterfaces
Accessories removable under pressure
1/8NPT port for pneumatic driving
Standard outlet connection(3/4’’ BSP) / FR16-type
Using of existing actuators (COPIST, DEPYM, POUSSAX…)
SINORIX CDT
Page 14 April 2010 Building Technologies
Comparison mass flow rate standard/CDT
Time
Flo
w r
ate
Comparison standard technology to CDT
Flow rate CDT
Flow rate Std
VFR 300 SResults
Page 17 April 2010 Building Technologies
Type of system No. of
80 litre containers
Total venting area
(in m2)
Service pressure upstream
Restrictors/sector valves
(in bar)
Nitrogen system (Standard)
200 bar 15 0.89 PN220
Nitrogen system (Standard)
300 bar 10 0.89 PN360
Nitrogen system (CDT)
300 bar regulated 10 0.31 PN100
Benefits of the SINORIX CDT 300 bar regulated systemBenefits of the SINORIX CDT 300 bar regulated system
Comparison for a protected volume of 450mComparison for a protected volume of 450m3 3 and 3 mbar acceptable overpressureand 3 mbar acceptable overpressure
SINORIX CDT 300 bar regulated
Page 18 April 2010 Building Technologies
Benefits of the SINORIX CDT regulated nitrogen system
SINORIX CDT regulated nitrogen
at least one third fewer containers compared with a 200 bar system.
More than 50% less overpressure venting area compared with an unregulated system.
pressure downstream of the valve VFR300-S less than 100 bar.
SINORIX CDT 300 bar regulated
Page 19 April 2010 Building Technologies
SINORIX CDT: A modular system
As well as centralised systems, SINORIX CDT also allows you the option of modular systems
The benefits are:
• No pipework
• No nozzle orifice drilling calculation
• Installation in existing premises without disturbing the user
• Cost
Page 20 April 2010 Building Technologies
Examples of applications of the CDT system:
• Computer room
• Anechoic chamber
• Electrical rooms
• Solvent storage
• Cold rooms
• Deep-seated fires
• etc…
SINORIX CDT 300 bar regulated
Page 21 April 2010 Building Technologies
SINORIX CDT International Approvals
Nitrogen is recognised by the following organisations:
- Authorities and Laboratories:VdS, LPC, FM, UL, CNPP, HK-FSD, etcAgreement by the French Ministry of Health to the use of nitrogen as an extinguishing agent in the presence of people
- Standards:CEA 4007&4008/NFPA 2001/UL 2127/ISO & CEN 14520
Siemens introduced nitrogen
as an extinguishing agent on the international stage for 4 years
Page 22 April 2010 Building Technologies
SINORIX CDT - Approvals
The IEAG APSAD Gas Committee issued a favourable opinion on Nitrogen 300 bar systems since December 2004
More than 10000 bottles installed since 02/2005
VdS approved S-number + G-numbers
Page 23 April 2010 Building Technologies
All extinguishing systems using an inert agent need an overpressure vent to avoid damage to the protected enclosure. Even though the SINORIX CDT system uses a new constant flow technology, reducing the venting area required by 70%, you must still provide overpressure venting.
Siemens FR has developed its own overpressure vent
1 hour fire resistant
SINORIX CDT 300 bar regulated
EVENT0,1
GRIFEU0,1
GRIPRO0,1