page 1 mcquay digital scroll system unit & piping selection
TRANSCRIPT
Page 1
MCQUAY DIGITAL SCROLL SYSTEM
Unit & Piping Selection
Page 2
Sample of InstallationSample of Installation
Page 3
Main Factors to consider during Piping Selection• Location of equipment
• Indoor Unit• Outdoor Unit• Refnet & Distributor Joint
Unit & Piping SelectionUnit & Piping Selection
These item will influence the piping layout and length of the design
Page 4
Some other factors to consider during Piping Selection• Equivalent Piping Length
• Type of Joint for branches
• Outdoor capacity factor
• Piping length & height factor
• Refrigerant Pipe Specification
Unit & Piping SelectionUnit & Piping Selection
Page 5
Equivalent length is the converted length and includes parts such as elbow, which has pressure losses in the pipe. The formula is as follow:
Equivalent length= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap
Equivalent Piping CalculationEquivalent Piping Calculation
Elbow Oil Trap9.52 0.18 1.30
12.70 0.20 1.5015.88 0.25 2.0019.05 0.35 2.4022.02 0.40 3.0025.40 0.45 3.4028.58 0.50 3.7031.80 0.55 4.00
Diameter of Pipe
Equivalent Length
Page 6
Restriction of Piping LengthRestriction of Piping Length
3~5 Hp 6 Hp 8~10 Hp 12~30 Hp100 125 250 350
Actual piping length 50 70 125 150Equivalent length 60 80 150 200
25 30
Outdoor above 20 30Indoor above 20 30
Length (m)
Piping
Height
Maximum equivalent length from first branch to furthers unit
Maximum height between indoor unit
Maximum length of longest branch
Between further indoor and outdoor
Total equivalanet length
15
40
5040
Page 7
Important Factor to ConsiderImportant Factor to Consider
Example:Outdoor Model : MDS100BRPipe Diameter : 28.6 mmMain Pipe : 80mBranch Length: 20mElbows: 10 unitsOil traps: 3 units
Elbow Oil Trap9.52 0.18 1.30
12.70 0.20 1.5015.88 0.25 2.0019.05 0.35 2.4022.02 0.40 3.0025.40 0.45 3.4028.58 0.50 3.7031.80 0.55 4.00
Diameter of Pipe
Equivalent Length
Equivalent Length
= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap= (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m
Page 8
When the equivalent length is over 90% of the maximal real length the diameter of the main tubing (from the outdoor unit to the first branch joint) should be one size bigger than normal.
Important CriteriaImportant Criteria
After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. The formula is as follow:
Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch
Criteria 1
Criteria 2
Page 9
Important Factor to ConsiderImportant Factor to Consider
3~5 Hp 6 Hp 8~10 Hp 12~30 Hp100 125 250 350
Actual piping length 50 70 125 150Equivalent length 60 80 150 200
25 30
Outdoor above 20 30Indoor above 20 30
Length (m)
Piping
Height
Maximum equivalent length from first branch to furthers unit
Maximum height between indoor unit
Maximum length of longest branch
Between further indoor and outdoor
Total equivalanet length
15
40
5040
Maximum allow actual length for 10Hp is 125mCalculated Equivalent Length is 116.1mRatio of Equivalent Length over Maximum allow Actual Length= 92.88%
Equivalent length is over 90% of the maximal real length the diameter of the main tubing. Hence the gas Pipe of MDS100BR need to change.
Example:
Page 10
Refrigerant Copper Pipe Specification : MDS-B
Unit & Piping SelectionUnit & Piping Selection
Page 11
Important Factor to ConsiderImportant Factor to Consider
Example:
Hence the gas Pipe of MDS100BR need to change from 28.6 mm to 34.9 mmAfter expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate.
Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch
Main Pipe : 80mBranch Length: 20mElbows: 10 unitsOil traps: 3 units
Equivalent Length
= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap= (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m
Expanded Equivalent Length = [80 + (10 X 0.5) + (3 X 3.7)] X 0.5 + 20
Expanded Equivalent Length = 68.05 m
Page 12
• Type of Joint for branchesInfluence the piping layout design
• Outdoor capacity factorInfluence by the design ambient temperature and
indoor temperature• Piping length & height factor
Influence by the location of outdoor and the total piping length
• Refrigerant Pipe SpecificationUse to determine the branches diameter
Unit & Piping SelectionUnit & Piping Selection
Page 13
Selection of branch joint / distributors for MDS
Unit & Piping SelectionUnit & Piping Selection
ModelMDS-Y1MDS-Y2MDS-Y3MDS-Y4MDS-Y6MDS-Y7MDS-C1MDS-C2MDS-C3
Refnet Joint (2 Branches)
Distributors Header (4 Branches)
Page 14
MDS-Y1~Y4 dimensional drawing
Unit & Piping SelectionUnit & Piping Selection
A B C D E
(outer diameter)
F G H I
(outer diameter)
J K L M N
(outer diameter)
O P Q R
MDS-Y1 553 172 293 120 28.6 28.9 25.7 22.5 28.6 28.9 25.7 22.5 19.3 22.2 19.3 16.1 12.9 9.7MDS-Y2 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 12.7 12.9 9.7 6.5MDS-Y3 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 15.88 16.1 12.9 9.7MDS-Y4 493 142 223 80 22.2 22.5 19.3 16.1 19.1 19.3 16.1 12.9 9.7 19.1 19.3 16.1 12.9
Diameter (mm)Refnet model
Length(mm) Diameter (mm) Diameter (mm)
Page 15
MDS-Y6 dimensional drawing
Unit & Piping SelectionUnit & Piping Selection
Page 16
MDS-Y7 dimensional drawing
Unit & Piping SelectionUnit & Piping Selection
Page 17
MDS-C1 dimensional drawing
Unit & Piping SelectionUnit & Piping Selection
Page 18
MDS-C2~C3 dimensional drawing
Unit & Piping SelectionUnit & Piping Selection
Page 19
Unit & Piping SelectionUnit & Piping Selection
Using Distribution Header may lead to imbalance refrigerant flow.
Page 20
Connection Type of Refnet Joint/Distributors
Unit & Piping SelectionUnit & Piping Selection
Refnet Joint
Page 21
Unit & Piping SelectionUnit & Piping Selection
Connection Type of Refnet Joint/Distributor
Distributor
Page 22
Unit & Piping SelectionUnit & Piping Selection
Connection Type of Refnet Joint/Distributors
Refnet Joint Distributor
Page 23
Unit & Piping SelectionUnit & Piping Selection
Connection Type of Refnet Joint/Distributors
Refnet Joint Distributor
Page 24
Unit & Piping SelectionUnit & Piping Selection
Cooling Capacity Correction Factor
Page 25
Unit & Piping SelectionUnit & Piping Selection
Heating Capacity Correction Factor
Page 26
Cooling cap. factor
Unit & Piping SelectionUnit & Piping Selection
Cooling Capacity Correction Factor
Page 27
Unit & Piping SelectionUnit & Piping Selection
Heating Capacity Correction Factor
Page 28
Refrigerant Pipe Specification : MDS-A
Unit & Piping SelectionUnit & Piping Selection
Page 29
Refrigerant Pipe Specification : MDS-B
Unit & Piping SelectionUnit & Piping Selection
Page 30
Unit & Piping SelectionUnit & Piping Selection
Example
C
A B
D
E
F
Building Type: Building Type: BungalowBungalow
Page 31
ExampleRequirement• Cooling only model• Ambient temperature : 35.0 °C• Indoor temperature : 22.0 °C
Other Information• Piping length : 40m• Height between I/O : 4m• Outdoor Unit located below indoors
Unit - AWall
Mounted
Unit - BWall
Mounted
Unit - CWall
Mounted
Unit - DWall
Mounted
Unit - ECeiling
Cassette
Unit - FCeiling
Concealed
1.8 2.0 2.2 4.0 5.0 5.8
Required Cooling Capacity
(kW)
Unit & Piping SelectionUnit & Piping Selection
Page 32
Unit & Piping SelectionUnit & Piping Selection
Indoor RequirementWall Mounted
MWMD 010GR MWMD 015GR MWMD 020GR MWMD 025GRBtu/h 9500 12000 19000 23500
W 2780 3520 5569 6887Btu/h 9500 12000 19500 24000
W 2780 3520 5715 7034MWMD 010G MWMD 015G MWMD 020G MWMD 025G
Btu/h 9500 12000 19000 24000W 2780 3520 5569 7034
Ceiling CassetteMCKD 010C MCKD 015C MCKD 020AR MCKD 025AR MCKD 030AR MCKD 040AR MCKD 050AR
Btu/h 9500 12000 19000 23500 30000 39500 48000W 2780 3520 5569 6887 8792 11569 14067
Btu/h 9500 12000 19500 24000 31000 41000 50000W 2780 3520 5715 7034 9085 12016 14654
MCKD 010C MCKD 015C MCKD 020A MCKD 025A MCKD 030A MCKD 040A MCKD 050ABtu/h 9500 12000 19000 24000 29000 39500 48500
W 2780 3520 5569 7034 8793 11570 14200
Ceiling ConcealedMCCD 010CR MCCD 015CR MCCD 020CR MCCD 025CR MCCD 028CR MCCD 030DR MCCD 038CR MCCD 040DR MCCD 050DR
Btu/h 9500 12000 19000 23500 28000 30000 37000 39500 48000W 2780 3520 5569 6887 8210 8792 10844 11569 14067
Btu/h 9500 12000 19500 24000 28500 31000 38000 41000 50000W 2780 3520 5715 7034 8353 9085 11137 12016 14654
MCCD 010C MCCD 015C MCCD 020C MCCD 025C MCCD 028C MCCD 030D MCCD 038C MCCD 040D MCCD 050DBtu/h 9500 12000 19000 24000 28000 29000 37000 39500 48500
W 2780 3520 5569 7034 8210 8793 10844 11570 14200
NOMINAL HEATING CAPACITY
COOLING ONLY MODEL
NOMINAL CAPACITY
HEATPUMP MODEL
NOMINAL COOLING CAPACITY
NOMINAL CAPACITY
NOMINAL CAPACITY
HEATPUMP MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
COOLING ONLY MODEL
HEATPUMP MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
COOLING ONLY MODEL
Unit - A Wall Mounted 1.8Unit - B Wall Mounted 2.0Unit - C Wall Mounted 2.2Unit - D Wall Mounted 4.0Unit - E Ceiling Cassette 5.0Unit - F Ceiling Concealed 5.8
Required Cooling Capacity(kW)
Page 33
Example
A B C D E F
Capacity, kW 1.8 2.0 2.2 4.0 5.0 5.8
Model 010 010 010 020 020 025
HP of indoor unit 2.78 2.78 2.78 5.59 5.59 7.03
Total Indoor capacity is 26.55 kW
Unit & Piping SelectionUnit & Piping Selection
Page 34
Example
Selection Criteria Indoor cap. should between 50% ~ 120% of the outdoor
cap. We recommend that the outdoor capacity equals to the
indoor capacity or a little larger than the indoor capacity
Unit & Piping SelectionUnit & Piping Selection
Page 35
Example
Selected Outdoor : MDS100B
Cooling Capacity : 28.0kW
%7.94
%10028
55.26
%100
/
CapacityOutdoorCapacityIndoorTotal
RatioOI
Comply to selection criteria
Unit & Piping SelectionUnit & Piping Selection
kW kWMDS080 24.5 26.0MDS100 28.0 30.0MDS120 32.5 3.0MDS150 40.0 43.0MDS180 47.5 50.0MDS200 50.0 53.0MDS220 55.0 58.0MDS240 65.0 68.0MDS260 70.0 75.0MDS280 75.0 80.0MDS300 80.0 85.0
ModelCooling Capacity
Heating Capacity
Page 36
Example Selected Outdoor and Indoor Model
Outdoor Model MDS100B 28.0 kW
Indoor A MWMD 010G 2.78 kW
Indoor B MWMD 010G 2.78 kW
Indoor C MWMD 010G 2.78 kW
Indoor D MWMD 020G 5.59 kW
Indoor E MCKD 020A 5.59 kW
Indoor F MCCD 025C 7.03 kW
Unit & Piping SelectionUnit & Piping Selection
Page 37
ExampleOutdoor Capacity factor• Cooling only model• Ambient temperature : 35.0 °C• Indoor temperature : 22.0 °C
1.08
Unit & Piping SelectionUnit & Piping Selection
Page 38
Example Piping length & height factor• Piping length : 40m• Height between I/O : 4m• Outdoor Unit located below indoors
97%
Unit & Piping SelectionUnit & Piping Selection
Page 39
Example
Total Capacity
= Outdoor Capacity X Outdoor Capacity Factor
X Piping length & height Factor
= 28.0 kW X 1.08 X 97%
= 29.3 kW
Unit & Piping SelectionUnit & Piping Selection
Page 40
Unit & Piping SelectionUnit & Piping Selection
Example
C
A B
D
E
F
Building Type: BungalowBuilding Type: Bungalow
Page 41
Example 1.1. Selection pipe diameterSelection pipe diameter
A B C
D E
MDS100B
MCCD 025C MWMD 010G MWMD 010G
MWMD 020GMCKD 020A MWMD 010G
7.03 kW2.78 kW 2.78 kW
5.59 kW5.59 kW
2.78 kW
Unit & Piping SelectionUnit & Piping Selection
Page 42
Refrigerant Pipe Specification : MDS-B
Unit & Piping SelectionUnit & Piping Selection
Page 43
A B C
D E
MDS100B
MCCD 25C MWMD 10G MWMD 10G
MWMD 20GMCKD 20A MWMD 10G
7.03 kW2.78 kW 2.78 kW
5.59 kW5.59 kW 2.78 kW
Example
Main pipeMain pipe diameter : diameter : ø ø 12.712.7mm / ø mm / ø 28.628.6mmmm
Calculate the downstream capacityCalculate the downstream capacity
Point APoint A
A-B-C : 12.59 kWA-B-C : 12.59 kW
A-D-E : 13.96 kWA-D-E : 13.96 kW
Point BPoint B
B-C : 5.59 kWB-C : 5.59 kW
D-E : 8.37 kWD-E : 8.37 kW
Unit & Piping SelectionUnit & Piping Selection
Page 44
Refrigerant Pipe Specification : MDS-B
Unit & Piping SelectionUnit & Piping Selection
Point APoint A
A-B-C : 12.59 kWA-B-C : 12.59 kW
A-D-E : 13.96 kWA-D-E : 13.96 kW
Page 45
A B C
D E
MDS100B
MCCD 25C MWMD 10G MWMD 10G
MWMD 20GMCKD 20A MWMD 10G
7.03 kW2.78 kW 2.78 kW
5.59 kW5.59 kW 2.78 kW
Example
Main pipeMain pipe diameter : diameter : ø ø 12.712.7mm / ø mm / ø 28.628.6mmmm
Unit & Piping SelectionUnit & Piping Selection
A-B diameter : A-B diameter : ø ø 9.529.52mm / ø mm / ø 19.0519.05mmmm
A-D diameter : ø 9.52mm / ø 19.05mm
Page 46
A B C
D E
MDS100B
MCCD 25C MWMD 10G MWMD 10G
MWMD 20GMCKD 20A MWMD 10G
7.03 kW2.78 kW 2.78 kW
5.59 kW5.59 kW 2.78 kW
Example
Unit & Piping SelectionUnit & Piping Selection
Point BPoint B
B-C : 5.56 kWB-C : 5.56 kW
B-MCCD25C : 7.03 kWB-MCCD25C : 7.03 kW
Page 47
Refrigerant Pipe Specification : MDS-B
Unit & Piping SelectionUnit & Piping Selection
Point BPoint B
B-C : 5.56 kWB-C : 5.56 kW
B-MCCD25C : 7.03 kWB-MCCD25C : 7.03 kW
Page 48
A B C
D E
MDS100B
MCCD 25C MWMD 10G MWMD 10G
MWMD 20GMCKD 20A MWMD 10G
7.03 kW2.78 kW 2.78 kW
5.59 kW5.59 kW 2.78 kW
Example
Main pipeMain pipe diameter : diameter : ø ø 12.712.7 / ø / ø 28.628.6
Unit & Piping SelectionUnit & Piping Selection
A-B: A-B: ø ø 9.529.52
/ ø / ø 19.0519.05
A-D: ø 9.52
/ ø 19.05
B-MCCD25C: B-MCCD25C: ø 9.52 / ø1ø 9.52 / ø15.885.88
B-C: B-C: ø 9.52 / ø1ø 9.52 / ø15.885.88
All unit in mm
Page 49
Example
Location Capacity (kW)
Liquid pipe (ø,mm) Gas pipe (ø,mm)
Inlet Outlet Inlet Outlet
A-B 13.20 12.70 9.52 28.60 19.05
A-D 14.70 12.70 9.52 28.60 19.05
B-C 5.86 9.52 9.52 19.05 15.88
D-E 8.79 9.52 9.52 19.05 15.88
Unit & Piping SelectionUnit & Piping Selection
Page 50
Example
A B C
D E
MDS100B
MCCD 25C MWMD 10G MWMD 10G
MWMD 20GMCKD 20A MWMD 10G
A-B diameter : A-B diameter : ø ø 9.529.52mm / ø mm / ø 19.0519.05mmmm
B-C diameter : B-C diameter : ø 9.52mm / ø1ø 9.52mm / ø15.885.88mmmm
A-D diameter : A-D diameter : ø 9.52mm / ø 19.05mmø 9.52mm / ø 19.05mm D-E diameter : D-E diameter :
ø 9.52mm / ø15.88mmø 9.52mm / ø15.88mm
Main pipeMain pipe diameter : diameter : ø ø 12.712.7mm / ø mm / ø 28.628.6mmmm
Unit & Piping SelectionUnit & Piping Selection
Page 51
Example 2.2. Selection of branchSelection of branch
Select the refnet joint of point ASelect the refnet joint of point A
A (liquid) A (liquid) : MDS-: MDS-Y2Y2
A (gas) A (gas) : MDS-: MDS-Y1Y1
Unit & Piping SelectionUnit & Piping Selection
A B C D E
(outer diameter)
F G H I
(outer diameter)
J K L M N
(outer diameter)
O P Q R
MDS-Y1 553 172 293 120 28.6 28.9 25.7 22.5 28.6 28.9 25.7 22.5 19.3 22.2 19.3 16.1 12.9 9.7MDS-Y2 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 12.7 12.9 9.7 6.5MDS-Y3 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 15.88 16.1 12.9 9.7MDS-Y4 493 142 223 80 22.2 22.5 19.3 16.1 19.1 19.3 16.1 12.9 9.7 19.1 19.3 16.1 12.9
Diameter (mm)Refnet model
Length(mm) Diameter (mm) Diameter (mm)
A-D diameter : A-D diameter : ø 9.52 / ø 19.05ø 9.52 / ø 19.05
Main pipe diameter : Main pipe diameter : ø 12.7 / ø 28.6ø 12.7 / ø 28.6
A-B diameter : A-B diameter : ø 9.52 / ø 19.05ø 9.52 / ø 19.05
All unit in mm
AA
Page 52
Example
AB C
D E
MDS100B
MCCD 25C MWMD 10G MWMD 10G
MWMD 20GMCKD 20A MWMD 10G
A-B: A-B: ø ø 9.529.52 / / ø ø 19.0519.05
B-C: B-C: ø 9.52 / ø 9.52 / ø1ø15.885.88
A-D: A-D: ø 9.52 / ø 9.52 / ø 19.05ø 19.05
D-E: D-E: ø 9.52 / ø 9.52 / ø15.88ø15.88
Main pipeMain pipe diameter : diameter : ø ø 12.712.7 / ø / ø 28.628.6
Unit & Piping SelectionUnit & Piping Selection
Liquid GasMWMD 010G 6.35 9.52MCCD 025C 9.52 15.88MWMD 010G 6.35 9.52MCKD 020A 6.35 15.88MWMD 020G 6.35 15.88MWMD 010G 6.35 9.52
ModelIndoor Valve Size (Ø, mm)
All unit in mm
Page 53
Example
2.2. Selection of branchSelection of branch
Select the refnet joint of point
A (liquid): MDS-Y2 A (gas) : MDS-Y1
B (liquid): MDS-Y3 B (gas) : MDS-Y4
C (liquid): MDS-Y2 C (gas) : MDS-Y2
D (liquid): MDS-Y2 D (gas) : MDS-Y4
E (liquid): MDS-Y2 E (gas) : MDS-Y4
Unit & Piping SelectionUnit & Piping Selection
Page 54
Example
Formula:
G = ∑ Li* Gi
Using liquid tube length to calculate required refrigerant → Add in refrigerant
G : Refrigerant charge amountLi : The each section of liquid tube length in all (m)Gi : Charge amount per length ( g/m)
Unit & Piping SelectionUnit & Piping Selection
Page 55
Example
5m (9.52mm)
5m (9.52mm)
2m (6.35mm)
15m (9.52mm)
5m (6.35mm)
2m (6.35mm)
3m (9.52mm)
1m (6.35mm)
1m (9.52mm) 1m
(6.35mm)
A B C
D E
MDS100B
MCCD 25C MWMD 10G
MCKD 20A
1m (12.70mm)
Unit & Piping SelectionUnit & Piping Selection
MWMD 10G
MWMD 10GMWMD 20G
Total Piping Length12.7mm – 1m9.52mm – 29m6.35mm – 11m
Page 56
Example
Additional charge amount :
= ∑ Li* Gi
= (Piping Length for 15.88mm X Refrigerant Charge Amount)
+ (Piping Length for 12.7mm X Refrigerant Charge Amount)
+ (Piping Length for 9.52mm X Refrigerant Charge Amount)
+ (Piping Length for 6.35mm X Refrigerant Charge Amount)
= (0 X 180) + (1 x 120) + (29 x 80) + (11 x 50)
= 2990 g
Unit & Piping SelectionUnit & Piping Selection
Liquid tube diameter (mm) 6.35 9.52 12.7 15.88
Refrigerant charge amount (g/m)
50 80 120 180
Total Piping Length12.7mm – 1m 9.52mm – 29m 6.35mm – 11m
Page 57
EXV BoxEXV BoxEXV BoxEXV Box
Unit & Piping SelectionUnit & Piping SelectionElectronic Expansion Valve
Page 58
Indoor Unit EXV Box ModelMCCD 010/15MCKD 010/15MWMD 010/15 MEX-14-2SA-B
MWMD 020 MEX-18-2SA-BMCCD 020/25MCKD 020/25
MWMD 025 MEX-18-3SA-BMCCD 030/40/50/60
MCKD 030/40MCKD 050 MEX-30-3SA-A
MEX-14-2SA-A
MEX-18-3SA-A
MEX-24-3SA-A
Unit & Piping SelectionUnit & Piping SelectionElectronic Expansion Valve
3 units
1 unit
2 units
Page 59
Unit & Piping SelectionUnit & Piping Selection
Page 60
Software Demo
Page 61
Thank YouThank You