pcs-931 my instruction manual en general x r1.00 (en xlbh5104.0060.1101)

Upload: mac-david

Post on 07-Jul-2018

237 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    1/229

     

    PCS-931_MY

    Line Differential Relay

    Instruction Manual

    Nanjing Nari-Relays Electric Co., Ltd.

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    2/229

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    3/229

      PCS-931 Line Differential Relay  

    NANJING NARI-RELAYS ELECTRIC CO., LTD i

    Preface

    Introduction

    This guide and the relevant operating or service manual documentation for the equipment provide

    full information on safe handling, commissioning and testing of this equipment.

    Documentation for equipment ordered from NARI-RELAYS is dispatched separately from

    manufactured goods and may not be received at the same time. Therefore, this guide is provided

    to ensure that printed information normally present on equipment is fully understood by the

    recipient.

    Before carrying out any work on the equipment, the user should be familiar with the contents ofthis manual, and read relevant chapter carefully.

    This chapter describes the safety precautions recommended when using the equipment. Before

    installing and using the equipment, this chapter must be thoroughly read and understood.

    Health and Safety

    The information in this chapter of the equipment documentation is intended to ensure that

    equipment is properly installed and handled in order to maintain it in a safe condition.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of

    the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger

    personnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling,

    proper storage, installation and commissioning, and on careful operation, maintenance and

    servicing. For this reason, only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who:

      Are familiar with the installation, commissioning, and operation of the equipment and of the

    system to which it is being connected;

      Are able to safely perform switching operations in accordance with accepted safety

    engineering practices and are authorized to energize and de-energize equipment and to

    isolate, ground, and label it;

      Are trained in the care and use of safety apparatus in accordance with safety engineering

    practices;

      Are trained in emergency procedures (first aid).

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    4/229

    PCS-931 Line Differential Relay

    NANJING NARI-RELAYS ELECTRIC CO., LTDii

    Instructions and Warnings

    The following indicators and standard definitions are used:

    DANGER! 

    It means that death, severe personal injury, or considerable equipment damage will occur if safety

    precautions are disregarded.

    WARNING!

    It means that death, severe personal, or considerable equipment damage could occur if safety

    precautions are disregarded.

    CAUTION!

    It means that light personal injury or equipment damage may occur if safety precautions are

    disregarded. This particularly applies to damage to the device and to resulting damage of the

    protected equipment.

    WARNING! 

    The firmware may be upgraded to add new features or enhance/modify existing features, please

    make sure that the version of this manual is compatible with the product in your hand.

    WARNING! 

    During operation of electrical equipment, certain parts of these devices are under high voltage.

    Severe personal injury or significant equipment damage could result from improper behavior.

    Only qualified personnel should work on this equipment or in the vicinity of this equipment. These

    personnel must be familiar with all warnings and service procedures described in this manual, as

    well as safety regulations.

    In particular, the general facility and safety regulations for work with high-voltage equipment must

    be observed. Noncompliance may result in death, injury, or significant equipment damage.

    DANGER! 

    Never allow the current transformer (CT) secondary circuit connected to this equipment to be

    opened while the primary system is live. Opening the CT circuit will produce a dangerously high

    voltage.

    WARNING! 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    5/229

      PCS-931 Line Differential Relay  

    NANJING NARI-RELAYS ELECTRIC CO., LTD iii

      Exposed terminals

    Do not touch the exposed terminals of this equipment while the power is on, as the high voltage

    generated is dangerous

      Residual voltage

    Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It

    takes a few seconds for the voltage to discharge.

    CAUTION!

      Earth

    The earthing terminal of the equipment must be securely earthed

      Operating environment

    The equipment must only be used within the range of ambient environment detailed in the

    specification and in an environment free of abnormal vibration.

      Ratings

    Before applying AC voltage and current or the DC power supply to the equipment, check that they

    conform to the equipment ratings.

      Printed circuit board

    Do not attach and remove printed circuit boards when DC power to the equipment is on, as this

    may cause the equipment to malfunction.

      External circuit

    When connecting the output contacts of the equipment to an external circuit, carefully check the

    supply voltage used in order to prevent the connected circuit from overheating.

      Connection cable

    Carefully handle the connection cable without applying excessive force. 

    Copyright 

    Manual: V1.00

    P/N: EN_XLBH5104.0060.1101  

    Copyright © NR 2009. All rights reserved

    We reserve all rights to this document and to the information

    contained herein. Improper use in particular reproduction and

    dissemination to third parties is strictly forbidden except where

    expressly authorized.

    The information in this manual is carefully checked periodically,

    and necessary corrections will be included in future editions. If

    nevertheless any errors are detected, suggestions for correction or

    improvement are greatly appreciated.We reserve the rights to make technical improvements without

    notice. 

    NANJING NARI-RELAYS ELECTRIC CO., LTD.

    69 SuYuan. Avenue, Nanjing 211102,China

    Tel: 86-25-87178185, Fax: 86-25-87178208

    Website: www.nari-relays.com

    Email: [email protected]

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    6/229

    PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTDiv

    Table of Contents

    Preface ....................................................................................................................................... i 

    Introduction ........................................................................................................................ i 

    Health and Safety .............................................................................................................. i 

    Instructions and Warnings ...............................................................................................ii 

    Table of Contents .....................................................................................................................iv 

    Chapter 1 Introduction .............................................................................................................1 

    1.1 Application ...................................................................................................................1 

    1.2 Function .......................................................................................................................2 

    1.3 Features ........................................................................................................................3 

    Chapter 2 Technical Data .........................................................................................................5 

    2.1 Electrical Specifications .............................................................................................5 

    2.1.1 Analog Input Ratings .........................................................................................5 

    2.1.2 Power Supply .....................................................................................................5 

    2.1.3 Binary Input .......................................................................................................6 

    2.1.4 Binary Output.....................................................................................................6 

    2.1.5 Power Supply Output for Opto-coupler ...........................................................6 

    2.2 Mechanical Specifications ..........................................................................................6 

    2.3 Ambient Temperature and Humidity Range ..............................................................7 

    2.4 Communication Port ...................................................................................................7 

    2.4.1 Communication Port for RTU/SCADA .............................................................7 

    2.4.2 Communication Port for Print ..........................................................................8 

    2.4.3 RS-485 for Clock Synchronization ...................................................................8 

    2.5 Type Tests ....................................................................................................................8 

    2.5.1 Environmental Tests ..........................................................................................8 

    2.5.2 Mechanical Tests ...............................................................................................8 

    2.5.3 Electrical Tests ..................................................................................................8 

    2.5.4 Electromagnetic Compatibility .........................................................................9 

    2.6 Certifications ..............................................................................................................10 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    7/229

      PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTD v

    2.7 Protective Functions .................................................................................................10 

    2.7.1 Optical Interface ..............................................................................................10 

    2.7.2 Fault Detector ..................................................................................................10 

    2.7.3 Current Differential Protection ....................................................................... 11 

    2.7.4 DPFC Distance Protection .............................................................................. 11 

    2.7.5 Distance Protection ......................................................................................... 11 

    2.7.6 Directional Zero-sequence Overcurrent Protection ..................................... 11 

    2.7.7 Directional Phase Overcurrent Protection .................................................... 11 

    2.7.8 Inverse-time Zero-sequence Overcurrent Protection ................................... 11 

    2.7.9 Breaker Failure Protection ..............................................................................12 

    2.7.10 Transient Overreach ......................................................................................12 

    2.7.11 Fault Locator ..................................................................................................12 

    2.7.12 Auto-Reclosing ..............................................................................................12 

    Chapter 3 Protection Description ..........................................................................................13 

    3.1 General Description ..................................................................................................13 

    3.2 General Fault Detector Element (GFD) ....................................................................13 

    3.2.1 DPFC Overcurrent Element ............................................................................13 

    3.2.2 Zero-sequence Overcurrent Element .............................................................14 

    3.2.3 Auxiliary Voltage Element ...............................................................................14 

    3.2.4 Transfer Trip Element ......................................................................................15 

    3.3 Protective Fault Detector Element (PFD) .................................................................15 

    3.4 DPFC Distance Protection ........................................................................................15 

    3.5 Current Differential Protection .................................................................................16 

    3.5.1 Application .......................................................................................................16 

    3.5.2 Function Description .......................................................................................17 

    3.5.3 Logic Scheme ..................................................................................................28 

    3.6 Overcurrent Protection .............................................................................................35 

    3.6.1 Application .......................................................................................................35 

    3.6.2 Directional Zero-sequence Overcurrent Protection .....................................35 

    3.6.3 Directional Phase Overcurrent Protection ....................................................37 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    8/229

    PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTDvi

    3.6.4 Inverse-time zero-sequence overcurrent protection ....................................38 

    3.6.5 Overcurrent Protection when VT Circuit Failure...........................................40  

    3.7 Distance Protection ...................................................................................................40 

    3.7.1 Distance Element with Memorized Polarization ............................................41 

    3.7.2 Phase-to-ground Distance Element ...............................................................43 

    3.7.3 Phase-to-phase distance element ..................................................................46 

    3.7.4 Reversal Distance Element .............................................................................46 

    3.7.5 Blinder Scheme ...............................................................................................47 

    3.7.6 Power Swing Blocking Releasing (PSBR) .....................................................47 

    3.7.7 Scheme Logic ..................................................................................................49 

    3.8 Breaker Failure Protection ........................................................................................51 

    3.8.1 Overview ..........................................................................................................51 

    3.8.2 Function Description .......................................................................................51 

    3.8.3 Logic Scheme ..................................................................................................51 

    3.9 Switch onto Fault Protection ....................................................................................52 

    3.9.1 Zero-sequence SOTF Protection ....................................................................53 

    3.9.2 Distance SOTF Protection ..............................................................................54 

    3.10 Fault Phase Selection (FPS) ...................................................................................54 

    3.10.1 FPS Based on Deviation of Operation Voltage ...........................................54 

    3.10.2 FPS Based on Differential Current ...............................................................55 

    3.10.3 FPS Based on Phase Difference between I0 and I2A  ...................................55 

    3.11 Pole Disagreement ..................................................................................................56 

    3.11.1 PD State by Single-phase Trip ......................................................................56 

    3.11.2 PD State by Three-phase Trip .......................................................................57 

    3.12 Trip Scheme .............................................................................................................57 

    3.13 Synchronism Check ................................................................................................63 

    3.13.1 Overview ........................................................................................................63 

    3.13.2 Function Description .....................................................................................63 

    3.13.3 Logic Scheme ................................................................................................64 

    3.14 Automatic Reclosure ...............................................................................................65 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    9/229

      PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTD vii

    3.14.1 Overview ........................................................................................................65 

    3.14.2 Function Description .....................................................................................66 

    3.15 Transfer Trip And Transfer Signal ..........................................................................69 

    3.15.1 Transfer Trip ...................................................................................................70 

    3.15.2 Transfer signal ...............................................................................................70 

    Chapter 4 Automatic Supervision .........................................................................................71 

    4.1 General Description ..................................................................................................71 

    4.2 Understand the Alarms ..............................................................................................71 

    4.3 Relay Self-supervision ..............................................................................................74 

    4.3.1 Fault Detection Check .....................................................................................74 

    4.3.2 Trip Output Circuit Check ...............................................................................74 

    4.3.3 Settings Check.................................................................................................74 

    4.4 AC Input Monitoring ..................................................................................................74 

    4.4.1 Voltage and Current Drift Auto Regulation ....................................................74 

    4.4.2 DSP Sampling Monitoring ...............................................................................75 

    4.5 Secondary Circuit Monitoring ..................................................................................75 

    4.5.1 Opto-coupler Power Supervision ...................................................................75 

    4.5.2 Circuit Breaker Supervision ...........................................................................75 

    4.5.3 Bus VT Circuit Supervision ............................................................................75 

    4.5.4 Line VT Circuit Supervision ............................................................................76 

    4.5.5 CT Circuit Supervision ....................................................................................76 

    4.5.6 Binary Input Supervision ................................................................................77 

    Chapter 5 Metering and Recording .......................................................................................79 

    5.1 Metering ......................................................................................................................79 

    5.2 Event & Fault Record ................................................................................................81 

    5.2.1 General Description ........................................................................................81 

    5.2.2 Event Recorder ................................................................................................81 

    5.2.3 Disturbance Recorder .....................................................................................82 

    5.2.4 Present Recording ...........................................................................................83 

    Chapter 6 Hardware Description ...........................................................................................85 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    10/229

    PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTDviii

    6.1 General Description ..................................................................................................85 

    6.2 Typical Wiring ............................................................................................................86 

    6.3 Plug-in Modules .........................................................................................................89 

    6.3.1 MON Module ....................................................................................................89 

    6.3.2 DSP Module (Protection Function Calculation) ............................................91 

    6.3.3 DSP Module (Fault Detector Logic Calculation) ...........................................91 

    6.3.4 AI Module .........................................................................................................92 

    6.3.5 GOOSE Module ................................................................................................94 

    6.3.6 BI Module .........................................................................................................98 

    6.3.7 BO Module .....................................................................................................105 

    6.3.8 BO Module .....................................................................................................106 

    6.3.9 BO Module .....................................................................................................108 

    6.3.10 BO Module ................................................................................................... 110 

    6.3.11 BO Module .................................................................................................... 111 

    6.3.12 PWR Module................................................................................................. 112 

    6.4 Display Panel ........................................................................................................... 114 

    Chapter 7 Configurable Function ........................................................................................ 115 

    7.1 General Description ................................................................................................ 115 

    7.2 Introduction on PCS-PC software .......................................................................... 115 

    7.3 Protective Device Configuration ............................................................................ 115 

    7.3.1 Configuration of LED Indicators .................................................................. 115 

    7.3.2 Configuration of Binary Input ....................................................................... 116 

    7.3.3 Configuration of Binary Output .................................................................... 117 

    Chapter 8 Settings ................................................................................................................ 119 

    8.1 Equipment Parameters ............................................................................................ 119 

    8.2 System Parameters .................................................................................................121 

    8.3 Protection Settings ..................................................................................................122 

    8.4 Logic Settings ..........................................................................................................136 

    8.5 Equipment VEBI Settings ........................................................................................143 

    8.6 GOOSE VEBI Settings .............................................................................................143 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    11/229

      PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTD ix

    Chapter 9 Human Machine Interface ...................................................................................145 

    9.1 Overview ...................................................................................................................145 

    9.1.1 Keypad Operation ..........................................................................................146 

    9.1.2 LED Indications .............................................................................................146 

    9.1.3 Communication Port .....................................................................................148 

    9.1.4 Communication .............................................................................................148 

    9.2 Understand the HMI Menu Tree ..............................................................................149 

    9.2.1 Overview ........................................................................................................149 

    9.2.2 VALUES ..........................................................................................................152 

    9.2.3 REPORT .........................................................................................................152 

    9.2.4 PRINT ..............................................................................................................153 

    9.2.5 SETTINGS ......................................................................................................154 

    9.2.6 LOCAL CONTROL .........................................................................................154 

    9.2.7 CLOCK ............................................................................................................155 

    9.2.8 VERSION ........................................................................................................155 

    9.2.9 TEST_MODE ..................................................................................................155 

    9.2.10 INTERFACE ..................................................................................................156 

    9.3 Understand the LCD Display ..................................................................................156 

    9.3.1 Overview ........................................................................................................156 

    9.3.2 Normal Status Display ...................................................................................156 

    9.3.3 Display Fault Report ......................................................................................157 

    9.3.4 Display Self-supervision Report ..................................................................159 

    9.3.5 Display Binary Input Change Report ...........................................................160 

    9.3.6 Display Control Report .................................................................................164 

    9.4 Keypad Operation ....................................................................................................164 

    9.4.1 View Device Status ........................................................................................164 

    9.4.2 View Device Report .......................................................................................164 

    9.4.3 View Module Information ..............................................................................165 

    9.4.4 Print Device Report .......................................................................................165 

    9.4.5 View Device Setting .......................................................................................166 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    12/229

    PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTDx

    9.4.6 Modify Device Setting ...................................................................................167 

    9.4.7 Copy Device Setting ......................................................................................169 

    9.4.8 Switch Setting Group ....................................................................................169 

    9.4.9 Delete Device Message .................................................................................170 

    9.4.10 Modify Device Clock ....................................................................................170 

    9.4.11 Check Software Version ..............................................................................170 

    9.4.12 Communication Test ...................................................................................171 

    Chapter 10 Communications ...............................................................................................173 

    10.1 General Description...............................................................................................173 

    10.2 Rear Communication Port Information ................................................................173 

    10.2.1 RS-485 Interface ..........................................................................................173 

    10.2.2 Ethernet Interface ........................................................................................175 

    10.2.3 IEC60870-5-103 Communication ................................................................176 

    10.3 IEC60870-5-103 Interface over Serial Port ...........................................................176 

    10.3.1 Physical Connection and Link Layer .........................................................176 

    10.3.2 Initialization ..................................................................................................176 

    10.3.3 Time Synchronization .................................................................................177 

    10.3.4 Spontaneous Events ...................................................................................177 

    10.3.5 General Interrogation ..................................................................................177 

    10.3.6 General Service ...........................................................................................177 

    10.3.7 Disturbance Records ..................................................................................178 

    10.4 IEC60870-5-103 Interface over Ethernet ..............................................................178 

    10.5 Messages Description for IEC61850 Protocol .....................................................178 

    10.5.1 Overview ......................................................................................................178 

    10.5.2 Communication profiles .............................................................................179 

    10.5.3 Server data organization .............................................................................180 

    10.5.4 Server features and configuration .............................................................182 

    10.5.5 ACSI Conformance ......................................................................................184 

    10.5.6 Logical Nodes ..............................................................................................188 

    10.6 GOOSE Service ......................................................................................................191 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    13/229

      PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTD xi

    10.6.1 GOOSE Introduction ...................................................................................191 

    10.6.2 GOOSE Function .........................................................................................191 

    Chapter 11 Installation and Commissioning ......................................................................193 

    11.1 Introduction ............................................................................................................193 

    11.2 Safety Information .................................................................................................193 

    11.3 Overview ................................................................................................................. 195 

    11.4 Unpacking And Checking The Protection Equipment ........................................195 

    11.5 Installing The Protective Device ...........................................................................196 

    11.5.1 Overview .......................................................................................................196 

    11.5.2 Dimensions ..................................................................................................197 

    11.5.3 Grounding Guidelines .................................................................................197 

    11.5.4 Cubicle Grounding ......................................................................................198 

    11.5.5 Ground Connection on the Device .............................................................199 

    11.5.6 Grounding Strips and their Installation......................................................199 

    11.5.7 Making the electrical connections .............................................................200 

    11.6 Check the External Circuit ....................................................................................201 

    11.7 Energizing The Protective Device ........................................................................202 

    11.8 Setting The Protective Device ..............................................................................203 

    11.9 Establishing Connection And Verifying Communication ...................................204 

    11.10 Verifying Settings by Secondary Injection ........................................................204 

    11.10.1 Insulation Test (if required) .......................................................................205 

    11.10.2 AC Measurement Check ............................................................................205 

    11.10.3 Print Fault Report ......................................................................................206 

    11.10.4 On-load Checks .........................................................................................206 

    11.11 Final Check ...........................................................................................................207 

    Chapter 12 Maintenance ......................................................................................................209 

    12.1 Appearance Check ................................................................................................209 

    12.2 Failure Tracing And Repair ...................................................................................209 

    12.3 Replace Failed Modules ........................................................................................210 

    12.4 Replace Button Battery ......................................................................................... 211 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    14/229

    PCS-931 Line Differential Relay 

    NANJING NARI-RELAYS ELECTRIC CO., LTDxii

    12.5 Cleaning ................................................................................................................. 211 

    12.6 Storage ................................................................................................................... 211 

    Chapter 13 Decommissioning and Disposal ......................................................................213 

    13.1 Decommissioning ..................................................................................................213 

    13.2 Disposal ..................................................................................................................213 

    Chapter 14 Manual Version History .....................................................................................215 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    15/229

      Chapter 1 Introduction  

    NANJING NARI-RELAYS ELECTRIC CO., LTD 1

    Chapter 1 Introduction

    1.1 Application

    The PCS-931 is a digital EHV line differential relay with the main and back-up protection functions,

    which mainly is designed for transmission line of 220KV and above.

    PCS-931 Optical fibre channel PCS-931

     

    Figure 1.1-1 Typical application of PCS-931

    The main protection of PCS-931 comprises of current differential protection, which can clear the

    fault immediately for the whole line. DPFC distance protection can reach to extremely fast speed

    for the fault near the busbar.

    The back-up protection of PCS-931 comprises of distance protection, directional zero-sequence

    overcurrent protection, inverse-time zero-sequence overcurrent protection, directional phase

    overcurrent protection and breaker failure protection. Specially, one zone reversal distance

    protection is also available in PCS-931. In addition, as a substitution, phase/zero-sequence

    overcurrent protections are put into service automatically when VT circuit is failure.

    Figure 1.1-2 Functional diagram of PCS-931

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    16/229

    Chapter 1 Introduction 

    NANJING NARI-RELAYS ELECTRIC CO., LTD2

    PCS-931 can implement single-phase or three-phase trip and configurable auto-reclosing that can

    implement 1-pole AR, 3-poles AR and 1/3-pole AR.

    1.2 Function

    1. Main protection

      Current differential protection (87)

      DPFC current differential element

      Steady-state current differential element

      Zero-sequence current differential element

      DPFC distance protection (21D)

    2. Backup protection

      Phase-to-phase distance protection (21P)

      Phase-to-ground distance protection (21G)

      Reversal distance protection (21R)

      Directional zero-sequence overcurrent protection (67G)

      Instantaneous zero-sequence overcurrent protection (50G)

      Definite-time zero-sequence overcurrent protection (51G)

      Directional phase overcurrent protection (67P)

      Definite-time phase overcurrent protection (51P)

      Inverse-time phase overcurrent protection (IDMT)

      Inverse-time zero-sequence overcurrent protection (IDMT)

      Breaker failure protection (50BF)

      Phase overcurrent protection when VT circuit failure (51PVT)

      Zero-sequence overcurrent protection when VT circuit failure (51GVT)

      Switch onto fault (SOTF)

      Distance protection for SOTF

      Directional zero-sequence overcurrent protection for SOTF

    3. Additional function

      Power swing blocking releasing (PSBR)

       Auto-reclosing (79)

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    17/229

      Chapter 1 Introduction  

    NANJING NARI-RELAYS ELECTRIC CO., LTD 3

      Synchronism check (25)

      VT circuit supervision (VTS)

      CT circuit supervision (CTS)

      Line VT circuit supervision (LVTS)

      Self diagnostic test

      Voltage and current drift auto regulation

      Fault location (FL)

      Fault phase selection (FPS)

    Note!

    DPFC is the abbreviation of “Deviation of Power Frequency Component”. In case of a fault

    in the power system, the fault current consists of three parts: the power frequency

    components before the fault, the power frequency variables during the fault and the

    transient variables during the fault. DPFC is the power frequency variables during the fault.

    1.3 Features

    1. Protection and Control

      It adopts the new UAPC hardware platform of NR, and its AC inputs can support the electric

    instrument transformer and conventional instrument transformer.

      It adopts the high performance MCU and DSP processors, high-speed inner bus and

    intelligent I/O interfaces. The modularization design of the hardware and software makes this

    device be configured to meet the demands of different practical application, and it is very

    convenient for maintenance.

      High precision 16 bits A/D converter is adopted in this protection device.

      This protection device can communicate with SAS or RTU, optional communication protocol:

    IEC60870-5-103 or IEC61850

      Quickly clearing the internal fault for whole line, the time is less than 10 ms for fault where is

    near the busbar, is less than 15ms for fault where is in the center of line and is less than 25ms

    for fault where is in the remote end.

      Plug connectors from the relay rear panel to the terminal blocks on the rack or cabinet, which

    makes the on-site commissioning and replacement much easier than what you do the

    commissioning using the traditional screw terminals on the rear panel.

      Two independent data acquisition paths, one for fault detector element and another for

    protections and logic functions, to prevent any undesired trip.

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    18/229

    Chapter 1 Introduction 

    NANJING NARI-RELAYS ELECTRIC CO., LTD4

      The unique DPFC distance element is integrated in the protective device, which can clear the

    internal fault quickly with high sensitivity and high speed and is not affected by power swing.

      Self-adaptive floating threshold which only reflects deviation of power frequency component

    can defend system imbalance and system disturbance. Hence, it is both rather reliable and

    very fast, and it is very sensitive but does not pickup frequently.

      Main protection adopts integral transform to ensure high-speed; Back-up protection adopts

    Fourier transform, which has an excellent filtering result, to ensure accuracy.

      24 samples per cycle, all task including data measurement, protection calculation, logic

    discrimination, event recording and protection logic calculation could be done within one

    sampling period.

      GPS clock synchronization – PPS (pulse per second), PPM (pulse per minute) and IRIG-B

    synchronization

      High-speed 2048kbit/s multiplex channel or dedicated channel

    2. Communication

      2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol

      1 RS-485 communication rear ports for clock synchronization

      2~4 optional Ethernet ports, IEC 61850, or IEC 60870-5-103 over TCP/IP

      2 optional Ethernet port via optic fiber (ST interface or SC interface)

    3. Monitoring and Metering

      Event Recorder including 1024 tripping report, 1024 binary input change reports, 1024

    self-supervision reports and 1024 control reports.

      Disturbance recorder including 64 fault reports with waveforms (The file format of disturbance

    recorder is compatible with international COMTRADE file.)

      Self diagnostic test

    4. User Interface

      Friendly HMI interface with 320×240-dot LCD and 9-button keypad on the front panel.

      1 RS-232 communication rear ports for printer

      Multi-language - English, Chinese, Russian option

       Auxiliary software - PCSPC

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    19/229

      Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 5

    Chapter 2 Technical Data

    2.1 Electrical Specifications

    2.1.1 Analog Input Ratings

    1. Analog current

    Standard IEC 60255-27:2005

    Phase rotation ABC

    Nominal frequency 50±5Hz, 60±5Hz

    Rated Current  1A  5A 

    Linear to  0.05In~40In  0.05In~40In 

    Thermal withstand

    -continuously

    -for 10s

    -for 1s

    -for half a cycle 

    4In

    30In

    100In

    250In 

    4In

    30In

    100In

    250In 

    Burden  < 0.2VA/phase @In  < 0.25VA/phase @In 

    2. Analog voltage

    Standard  IEC 60255-6:1988 

    Rated Voltage (Un)  100V, 110V  200V

    Linear to  0.01Un~1.7Un  0.01Un~1.7Un

    Thermal withstand

    -continuously

    -10s

    -1s 

    2Un

    2.6Un

    3Un

    1.1Un

    1.9Un

    2.1Un

    Burden at rated  < 0.25VA/phase @Un 

    2.1.2 Power Supply

    Standard  IEC 60255-11:2008 Rated Voltage  110V/125V, 220V/250V 

    Variation  80%Un~120%Un 

    Permissible AC ripple

    voltage ≤15% of the nominal auxiliary voltage 

    Voltage short

    interruptions 100ms for interruption without de-energizing 

    Voltage dips Up to 10s for dips 40%Un without reset

    Burden

    Quiescent condition

    Operating condition

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    20/229

    Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD6

    2.1.3 Binary Input

    Rated Voltage (Un)  24V, 48V, 110V, 125V, 220V, 250V 

    Maximal pickup

    voltage 70%Un

    Minimum dropout

    voltage 55%Un

    Maximum permissible

    voltage 120%Un 

    Withstand  2000VAC, 3000VDC

    Resolving time for

    logic input

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    21/229

      Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 7

    Display language English

    Housing material Aluminum

    Location of terminal Rear panel of the device

    Protection class

    Standard IEC 60225-1:2007Front side IP40, up to IP51 (Flush mounted)

    Other sides IP30

    Rear side, connection

    terminalsIP20

    2.3 Ambient Temperature and Humidity Range

    Standard IEC 60225-1:2007

    Operatingtemperature

    -25°C to +55°C

    Transport and storage

    temperature range-40°C to +70°C

    Permissible humidity 5%-95%, condensation not permissible

    2.4 Communication Port

    2.4.1 Communication Port for RTU/SCADA

    RS-485

    (EIA)

    Electrical

    Port number   2 

    Baud rate  4800,9600,19200,38400,57600,115200

    Transmission distance 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    22/229

    Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD8

    Transmission standard  100Base-TX

    Transmission distance 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    23/229

      Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 9

    Dielectric tests Test voltage 2kV, 50Hz, 1min

    Standard IEC 60255-5:2000

    Impulse voltage tests Test voltage 5kV 

    Insulation resistance

    measurements

    Isolation resistance >100M@500VDC 

    2.5.4 Electromagnetic Compatibility

    1MHz burst

    disturbance test

    Per IEC 60255-22-1:2007 

    Common mode: class III 2.5KV 

    Differential mode: class III 1.0KV 

    Electrostatic

    discharge test

    Per IEC60255-22-2:2008 class IV 

    For contact discharge: 8kV 

    For air discharge: 15kV 

    Radio frequency

    interference tests

    Per IEC 60255-22-3:2007 class III 

    Frequency sweep

    Radiated amplitude-modulated

    10V/m (rms), f=80…1000MHz 

    Spot frequency

    Radiated amplitude-modulated

    10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

    Radiated pulse-modulated

    10V/m (rms), f=900MHz 

    Fast transient

    disturbance tests

    Per IEC 60255-22-4:2008 

    Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns 

    Communication terminals: class IV, 2kV, 5kHz, 5/50ns

    Surge immunity test Per IEC 60255-22-5:2008 

    Power supply, AC input, I/O port: class IV, 1.2/50us

    Common mode: 2kV

    Differential mode: 1kV

    Conducted RF

    Electromagnetic

    Disturbance

    Per IEC 60255-22-6:2001

    Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150

    kHz~80MHz

    Power FrequencyMagnetic Field

    Immunity

    Per IEC 61000-4-8:2001

    class V, 100A/m for 1min, 1000A/m for 3s

    Pulse Magnetic Field

    Immunity

    Per IEC 61000-4-9:2001

    class V, 6.4/16μs, 1000A/m for 3s

    Damped oscillatory

    magnetic field

    immunity

    IEC 61000-4-10:2001

    class V, 100kHz & 1MHz–100A/m

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    24/229

    Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD10

    2.6 Certifications

      ISO9001: 2000

      ISO14001:2004

      OHSAS18001: 1999

      ISO10012:2003

      CMMI L3

      EMC: 89/336/EEC, EN50263:2000

      Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950: 2002

    2.7 Protective Functions

    2.7.1 Optical Interface

    Using multiplex channel or dedicated channel and transmission distance is smaller than 40kM,

    PCS-931 is equipped with 1310nm laser emitter.

    FO type: Single mode, CCITT Rec.G652, 1310nm

    Send power: -14.0±2.0 dBm

    Receive sensitivity: -35 dBm

    Maximum transmission distance: -8 dBm

    Using dedicated channel and transmission distance is greater than 40kM, PCS-931 is equipped

    with 1550nm laser emitter.

    FO type: Single mode, CCITT Rec.G652, 1550nm

    Send power: -14.0±2.0 dBm

    Receive sensitivity: -35 dBm

    Maximum transmission distance: -8 dBm

    2.7.2 Fault Detector

    2.7.2.1 DPFC Overcurrent Element

    Setting range: 0.1In~0.5In

     Accuracy: ≤2.5% or 0.02In whichever is greater

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    25/229

      Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 11

    2.7.2.2 Zero-sequence Overcurrent Element

    Setting range: 0.1In~0.5In

     Accuracy: ≤2.5% or 0.02In whichever is greater

    2.7.3 Current Differential Protection

    Current setting accuracy: ≤5% or 0.04In whichever is greater

    Time delay accuracy:

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    26/229

    Chapter 2 Technical Data 

    NANJING NARI-RELAYS ELECTRIC CO., LTD12

     Accuracy: ≤  5% of reference (calculated) value +2%current tolerance, respectively 40ms

    2.7.9 Breaker Failure Protection

    Time delay: 0.01s~10s

     Accuracy: ≤1%Setting+40ms

    2.7.10 Transient Overreach

    Tolerance for all high-speed protection: ≤2% 

    2.7.11 Fault Locator

     Accuracy for multi-phase faults with one end source: < ±2.5%

    Tolerance will be higher in case of single-phase fault with high ground resistance. 

    2.7.12 Auto-Reclosing

    Item Range Accuracy

    Frequency difference 0.01~1.00 Hz ±0.01 Hz

    Phase difference 0~89 deg ±2.0 deg

    Voltage difference 0.02~0.8Un ±1.0% Un

    Item Range Accuracy

    Reclosing time 0.01~50

    ±0.5%±10ms

    Reclosing pulse length 0.01~50Time of circuit breaker in closed state before AR ready 0.01~250

    Maximal waiting time of the synchronism check 0.01~250

    Check time of AR unsuccessful 0.01~250

    Reset time 0.01~250

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    27/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 13

    Chapter 3 Protection Description

    3.1 General Description

    Designing hardware platform of PCS-931 based on the dual processor (DSP and CPU), two

    independent fault detector elements are provided for each protection logic, i.e. GFD (general fault

    detector element) and PFD (protective fault detector element).

    GFD is used to control the output circuit of the protective device. PFD is used to trigger the

    calculation of protective elements. Under the normal condition, the positive pole of DC power

    supplied to tripping outputs is continually supervised by GFD, and the output circuit will be

    switched on for tripping or reclosing only when GFD operates. It means that the relay will have the

    capability to output a final tripping or reclosing signal while both GFD and PFD operate.

    3.2 General Fault Detector Element (GFD)

    Main part of GFD is DPFC overcurrent fault detector element that reflects the deviation of

    phase-to-phase power frequency current, and zero-sequence overcurrent fault detector element

    that reflects total current is taken as supplementary.

    The GFD comprise of the following elements:

      DPFC overcurrent element

      Zero-sequence overcurrent element

       Auxiliary voltage element

      Transfer trip element

    If any of the above fault detector elements operates, the GFD will operate to provide DC power

    supply to the output relays to enable the output circuit.

    3.2.1 DPFC Overcurrent Element

    This element adopts adaptive floating threshold which consists of unbalanced output of deviation.

    The adaptive floating threshold is kept higher than the unbalanced output all along, which makes it

    not pick up frequently and have an extremely high sensitivity and reliability. By using adaptive

    floating threshold, the unbalanced output value is small under normal condition, so this element

    has extremely high sensitivity. When power swing occurs, the adaptive floating threshold

    increases while the sensitivity decreases automatically, so it is not influenced by power swing

    condition and need not be controlled by power swing blocking element.

    Its criterion:

    ΔIΦΦMAX>1.25ΔITh+ΔISet  (Equation 3.2-1)

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    28/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD14

    Where:

    ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current

    ΔISet: The fixed threshold value (i.e. the setting [I_DPFC_OC_FD])

    ΔITh: The floating threshold value

    If operating condition is met, DPFC overcurrent element will operate to provide DC power supply

    for output relay, and pickup signal will be kept 7 seconds after DPFC overcurrent element drops

    out.

    3.2.2 Zero-sequence Overcurrent Element

    This element will operate when both 3I0 and 3I0Cal are greater than the setting [I_ROC_FD].

    Where:

    3I0: zero-sequence current derived at the neutral current circuit from three-phase currents 

    3I0Cal: zero-sequence current calculated depending on the summation of I A, IB  and IC  (i.e.

    3I0Cal=I A+IB+IC)

    If operating condition is met, zero-sequence overcurrent element will operate to provide DC power

    supply for output relay, and pickup signal will be kept 7 seconds after zero-sequence overcurrent

    element drops out.

    When CT circuit failure is detected, this element will be disabled and an alarm [Alm_CTS] will be

    issued.

    Note!

    The zero-sequence current should be connected to the protective device; otherwise all

    protection elements corresponding with zero-sequence current will be blocked.

    3.2.3 Auxiliary Voltage Element

    Because DPFC overcurrent element and zero-sequence overcurrent element might not operate in

    some special cases, in order to ensure protection device pick up in following three conditions,

    PCS-931 provides auxiliary voltage element.

    1. Internal fault associated with high fault resistance

    2. In the case of weak infeed, internal unearthing fault

    3. In the case of VT circuit failure or no VT connection, internal unearthing fault

    The auxiliary voltage element will operate to provide DC power supply for output relay and pickup

    signal will be kept 7 seconds after auxiliary voltage element drops out.

    Note!

    Here UN  is the rated secondary phase voltage of VT. UNN  is the rated secondary

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    29/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 15

    phase-to-phase voltage of VT. (UN  means phase voltage; UNN  means phase-to-phase

    voltage)

    3.2.4 Transfer Trip Element

    If the logic setting [En_FD_Ctrl_TT] is set as “0” and the transfer trip signal received from opposite

    end of line, the transfer trip element will operate to provide DC power supply for output relay and

    pickup signal will be kept 500ms after transfer trip element drops out. 

    3.3 Protective Fault Detector Element (PFD)

    The protective fault detection element is the same as the general fault detection element.

    3.4 DPFC Distance Protection

    The power system is normally treated as a balanced symmetrical three-phase network. When a

    fault occurs in the power system, by applying the principle of superposition, the load currents and

    voltage can be calculated in the system prior to the fault and the pure fault component can be

    calculated by whole fault current or voltage subtracted by load current or voltage. DPFC distance

    protection reflects deviation of power frequency, therefore, only pure fault current and voltage is

    useful to DPFC distance protection which is not influenced by load current and voltage.

      For forward direction fault

    ZZDZK

    ZS+ZK

    -ZS

    R

     jX

     

    Figure 3.4-1 Operation characteristic for forward fault

    ZZD: The setting of distance protection

    ZS: Total impedance between local system and protective device location

    ZK: Measurement impedance

    Figure 3.4-1 shows the operation characteristic of the DPFC distance element on R-X plane when

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    30/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD16

    a fault occurs in forward direction, which is the circle with the –Zs as the center and the│Zs+Zzd│ 

    as the radius. When measured impedance Zk is in the circle, the DPFC distance element will

    operate. The DPFC distance element has a large capability of enduring fault resistance. When

    there is infeed current from power source at the other end in the fault resistance, the phase of ΔINis the same as

    ΔI and the phase of voltage of fault resistance is same as

    ΔI, so the fault resistance

    appears resistive and is in parallel with R axes. The overreaching problem that results from infeed

    current can be prevented.

      For reverse direction fault

    Figure 3.4-2 Operation characteristic for reverse fault

    Z'S:Total impedance between remote system and protective device location

    Figure 3.4-2 shows the operation characteristic of the DPFC distance element on R-X plane when

    a fault occurs in reverse direction, which is the circle with the Z's as the center and the │Z's-Zzd│

    as the radius. The region of operation is in the quadrant 1 but the measured impedance –Zk is

    always in the quadrant 3, so the DPFC distance element will not operate and have the definite

    directionality.

    Note!

    The DPFC distance protection can be enabled or disabled by corresponding logic setting

    and binary input. Please refer to section 8.4.

    3.5 Current Differential Protection

    3.5.1 Application

    Current differential protection can be used as main protection of EHV and HV overhead line or

    cable. It includes phase-segregated current differential protection and zero-sequence current

    differential protection.

    Current differential protection exchanges information among ends by optical fibre channel. The

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    31/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 17

    protection device can flexibly select dedicated optical fibre channel or multiplex channel. The

    protection device can calculate channel delay in real time, and adjust sample instant to ensure

    synchronism sampling of each end based on channel delay. The channel delay is calculated on

    the premise that the routine of both directions (receiving and sending) shall be same to each other.

    The communication rate used by protection device is 2048kbit/s. The maximum one-way channel

    propagation delay is 20ms. A transfer trip and two transfer signals can be transmitted to the

    remote end to fulfill some auxiliary functions via a communication channel.

    Through capacitive current compensation, the sensitivity of current differential protection is

    improved. Because capacitive current compensation depends on voltage, capacitive current

    compensation will be disabled automatically if no voltage is input or VT circuit fails.

    3.5.2 Function Description

    Based on channel supervision function, the protection device can automatically record temporal

    channel status if the channel fails which will block current differential protection automatically. The

    detailed channel status, including channel delay, current from the remote end and differential

    current, can be display on the LCD.

    Current differential protection comprises three elements:

      DPFC current differential element

      Steady-state current differential element

      Zero-sequence differential element

    3.5.2.1 DPFC Current Differential Element (Stage 1)

    Operation criteria:

    ⎩⎨⎧

    >

    ×>

    HDiff Φ

    BiasΦDiff Φ

    IΔIΔI0.75ΔI

      Equation 3.5-1

    Where:

    Diff ΦΔI : The DPFC differential current ( NΦMΦDiff Φ IΔIΔΔI   &&   += )

    BiasΦΔI : The DPFC restraint current ( NΦMΦBiasΦ   ΔIΔIΔI   += )

    HI : Max(1.5×[I_Diff],C1L

    N

    X

    1.5U)

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    32/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD18

     

    Figure 3.5-1 Operation characteristic of DPFC current differential element (stage 1)

    3.5.2.2 DPFC Current Differential Element (Stage 2)

    Operation criteria:

    ⎩⎨⎧

    >

    ×>

    QDiff Φ

    BiasΦDiff Φ

    IΔIΔI0.75ΔI

      Equation 3.5-2

    Where:

    QI : Max([I_Diff],C1L

    N

    X

    1.25U)

    Diff ΦΔI and BiasΦΔI   are the same as those mentioned above.

    IQ

    k=0.75

    ΔIDiff 

    ΔIBias

    k=1

     

    Figure 3.5-2 Operation characteristic of DPFC current differential element (stage 2)

    When the above criterion is met, the stage 2 of DPFC current differential element will operate after

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    33/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 19

    25ms. 

    3.5.2.3 Steady-state Current Differential Element (stage 1)

    Operation criteria :

    ⎩⎨⎧

    >

    ×>

    HDiff Φ

    BiasΦDiff Φ

    II

    I0.6I  Equation 3.5-3

    Where:

    Diff ΦI : The phase differential current ( NΦMΦDiff Φ III  &&   += )

    BiasΦI : The phase restraint current ( NΦMΦBiasΦ III  &&   −= )

    HI : Max(1.5×[I_Diff],C1L

    N

    X

    1.5U)

    Figure 3.5-3 Operation characteristic of steady-state current differential element (stage 1)

    3.5.2.4 Steady-state Current Differential Element (stage 2)

    Operation criteria :

    ⎩⎨⎧

    >

    ×>

    MDiff Φ

    BiasΦDiff Φ

    II

    I0.6I  Equation 3.5-4

    Where:

    MI : Max([I_Diff],C1L

    N

    X

    1.25U)

    Diff ΦI and BiasΦI are the same as those mentioned above.

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    34/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD20

     

    Figure 3.5-4 Operation characteristic of steady-state current differential element (stage 2)

    When the above criterion is met, the stage 2 of steady-state differential current relay will operate

    after 25ms. 

    3.5.2.5 Zero-sequence Current Differential Element

    Zero-sequence differential current element is sensitive to high resistance ground fault.

    operation criteria:

    ⎪⎪

    ⎪⎪

    >

    ×>>

    ×>

    MDiff Φ

    BiasΦDiff Φ

    MDiff0

    Bias0Diff0

    II

    I0.15III

    I0.75I

      Equation 3.5-5

    Where:

    Diff0I : The zero-sequence differential current

    Diff ΦI : The phase differential current

    Bias0I : The zero-sequence restraint current ( N0M0Bias0 III  &&   −= )

    MI : [I_Diff]

    BiasΦI is the same to those mentioned above

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    35/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 21

     

    Figure 3.5-5 Operation characteristic of zero-sequence current differential element

    When the above criterion is met, the zero sequence differential current relay will operate after

    45ms.

    3.5.2.6 Capacitive Current Compensation

    For the long transmission line whose capacitance current is very large, in order to increase the

    sensitivity of zero-sequence current differential element when a ground fault associated with fault

    resistance occurs, capacitance current must be compensated to  eliminate the effect that

    capacitance current has on differential current. The traditional method of compensating

    capacitance current can only compensate steady-state capacitance current. However, during the

    transient period, such as closing circuit breaker to no-load line, clearing external fault and so on,

    there are large transient capacitance current in the line. The traditional method cannot

    compensate the capacitance current completely, hence, a new method is available, which can

    compensate transient component of capacitance current.

    1. For long transmission line without shunt reactor

    Phase capacitance current of line can be derived from “∏” equivalent circuit. For normal operation

    condition, closing circuit breaker to no-load line and clearing external fault, not only steady-state

    component of capacitance current but also transient component of capacitance current can be

    compensated. It can improve the sensitivity of differential protection.

    Figure 3.5-6∏ equivalent circuit

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    36/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD22

    For different system frequency, the capacitance current which is shown in above figure can be

    calculated by:

    dt

    duCi cc  =   Equation 3.5-6

    Where:

    ci : Capacitance current flowing through each capacitance

    C : Capacitance value

    cu : Voltage between both ends of capacitance

    Based on the result of above equation, i.e. Equation 3.5-6, capacitance of each phase can be gained.

    2. For long transmission line with shunt reactor

    Because a part of capacitance current has been compensated by shunt reactor, reactance current

    IL must be subtracted from capacitance current calculated by above equation, i.e. Equation 3.5-6.

    Figure 3.5-7 Equivalent circuit of shunt reactor

    Because the current and voltage of reactor meet the following relation:

    dt

    (t)diL(t)U-(t)U LPf L   =   Equation 3.5-7

    To perform integral operation for Equation 3.5-7 from t to t-∆t, IL can be calculated by:

    [ ]dt(t)U(t)UL

    1Δt)-(ti(t)i

    t

    Δttf L

    P

    LL ∫ − −+=   Equation 3.5-8

    Then,

    (t)idt

    duCi L

    cc   −=   Equation 3.5-9

    3. For short transmission line

    Because capacitance current is very small, the sensitivity of current differential protection can still

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    37/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 23

    meet the requirement. The function, capacitance current compensation, will be disabled

    automatically if differential current is smaller than 01IN.

    3.5.2.7 CT Supervision

    If CT circuit failure occurs, delayed alarm will be issued. When CT circuit failure occurs on an end,

    the FD and current differential protection on this end might operate at once. However, FD on

    another end will not operate and not send any permissive signal of current differential relay.

    Therefore, the current differential protection will not maloperate. Meanwhile the healthy end will

    issue alarm signal [Alm_Diff_ChA] which will be treated as the same as the alarm [Alm_CTS].

    However, if CT circuit failure associated with internal fault or pickup due to system disturbance is

    detected, the protective device will show two kinds of behavior.

    If logic setting [En_CTSBlkDiff] (differential protection being blocked during CT circuit failure) is set

    as “1”, the differential protection will be blocked.

    If logic setting [En_CTSBlkDiff] is set as “0” and the differential current of the faulty phase is more

    than the differential current setting [I_Diff_CTS] during CT circuit failure, the differential protection

    will operate with alarm signal being issued at the same time. 

    3.5.2.8 CT Saturation

    The incorrect operating of current differential protection would occur due to transient CT saturation

    at the moment when external fault occurs. Hence, the protective device adopts high restraint

    coefficient and self-adaptive floating restraint threshold, which can prevent current differential

    protection from mal-operation even in serious saturation case.

    3.5.2.9 Synchronous Sampling

    One of the protection devices on both ends is set as reference end (the end whose ID code is

    greater, [ID_Local]>[ID_Remote]) and normally called “master”; the device on the other end is set

    as synchronous end (the end whose ID code is smaller, [ID_Local]

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    38/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD24

    message. Side S will receive the message from side M at the time “tsr” and obtain “tms-tmr”.

    Therefore, we can obtain the time delay of the channel “Td” through calculation:

    2

    )t(t)t(tT mr mssssr d

    −−−=  

    Figure 3.5-8 Calculation schematic diagram of channel time delay

    2. Measure the sampling time error of the protection devices on both ends through the slave and

    adjust the slave’s time of sampling pulse according to the time delay of the channel, to realize

    synchronous sampling.

    The master implements the sampling in fixed interval “Tsm” and meanwhile sends message to the

    slave on the basis of internal clock of the protection device. When the slave receives the message

    from the master, it can know the sampling time of the master according to the time delay of the

    channel and obtain the sampling time error “ΔT” of the protection devices on both ends accordingto its current sampling time. It is shown in Figure 3.5-9. The slave adjusts the next sampling time to

    make “ΔT”→0. When ΔT is less than the error, we can think the protection devices on both endsrealize synchronous sampling.

    Figure 3.5-9 Schematic diagram for synchronous sampling adjustment

    3.5.2.10 Communication Channel Interface

    Depending on the difference of the amount of optic fibre core and the distance permitted to

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    39/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 25

    transmit, the protection device can select two modes including dedicated optical fibre channel and

    multiplex channel. The multiplex channel is not recommended unless the receiver power does not

    meet the requirement due to too long transmission line.

    Dedicated 2048kbit/s channel is shown in Figure 3.5-10, Two fibre cores of optical cable are

    dedicated to differential protection

    Figure 3.5-10 Application of dedicated 2048kbit/s channel 

    Multiplex 2048kbit/s channel is shown in Figure 3.5-11.

    TX

    RXMUX2M

    Pig Tail

    2048kbit/s

    SDH Device

    E1Interface

    Coaxial cableOptic fibre

    communication

    net

    Differential

    ProtectionPig Tail

     

    Figure 3.5-11 Application of multiplex channel

    3.5.2.11 Communication Clock

    Data exchange is very important to digital differential protection.

    The differential relay sends and receives data based on respective clock, which are called transmit

    clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be extractedfrom data frame, which can ensure no drop-out data code generated and no receive error data

    code received. Clock TX has two options:

    1) Use internal crystal clock, which is called internal clock. (master clock) 

    2) Use clock TX, which is called external clock. (slave clock)

    Depend on the difference of the clock used by the differential relays of the two terminals, there are

    three modes.

    1. Master-master mode

    Both ends use internal clock.

    2. Slave-slave mode

    Both ends use external clock.

    3. Master-slave mode

    One of them uses internal clock, the other uses external clock. (Not recommended)

    Depending on the logic setting [En_InnClock_ChA], current differential protection selects the

    communication clock mode. The inner clock is enabled automatically when the logic setting[En_InnClock_ChA] is set as “1”. Contrarily, the outer clock is enabled automatically when the

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    40/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD26

    logic setting [En_InnClock_ChA] is set to “0”.

    If the protection device uses multiplex PCM channel, logic setting [En_InnClock_ChA] at both

    ends should be set as “0”. If the protection device uses dedicated optical fibre channel, logic

    setting [En_InnClock_ChA] at both ends should be set as “1”.

    3.5.2.12 Identity Code

    In order to ensure reliability of protection device when digital communication channel is applied,

    providing settings [ID_Local] and [ID_Remote] is used as identity code to distinguish uniquely

    protection device in the remote end using same channel.

    During normal operation, the identity code of protection device in the end should be different with

    that of protection device in the remote end. In addition, it should be different with that of protection

    device used to protect other transmission line. In one word, identity code of protection device, i.e.,

    the setting [ID_Local], should have uniqueness in the power grid. The setting range is from 0 to

    65535. Only under the test mode, they can be set as the same.

    The end of which setting [ID_Local] should be same as the [ID_Remote] of the other and the

    greater [ID_Local] between the two ends is chosen as a master end for sampling synchronism, the

    other is a slave end. If the setting [ID_Local] is set as same as [ID_Remote], that means the

    equipment in loopback testing state.

    The setting [ID_Local] is packaged in the data frame and send to the remote end of line through

    channel. When [ID_Local] received by protection device is same to the setting [ID_Remote] of this

    protection device, the message received comes from the remote end of line certainly and is valid,

    and protection information involved in message is read. When they are not equal, the message is

    thought as invalid and protection information involved in message is ignored. corresponding

    alarms [Alm_ID_ChA] and [Alm_ChA] will be issued. 

    3.5.2.13 Channel Statistics

    The protection device has the function of channel statistics and can monitor the channel status on

    line. The protection device can form a channel statistic report automatically at 9:00 every day and

    the report can be printed for operator to understand the channel quality. The monitoring contents

    of channel status are shown as follows, and they can be gained by the menu “VALUES→ COMM_CH_STATE”.

    1. Beginning time, [Time_Start]

    It shows the starting time of the channel status statistics of the protection device in the local end.

    2. Master-slave mode of local device [Equip_Local]

    It shows that local protection device is master or slave.

    3. ID code of the remote end, [ID_Remote_ChA]

    It shows the ID information received by the device on this end under present conditions.

    4. Time delay of channel A, [t_Dly_ChA]

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    41/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 27

    It shows the calculated data of the channel time delay of the protection device on this end under

    present conditions. (unit:us)

    5. Total amount of error frame of channel A, [N_CrcFail_ChA]

    It shows the total numbers of the wrong frames of the device on this end from starting time of

    channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)

    Error frame means that this frame fails in CRC check.

    6. Total amount of abnormal messages of channel A, [N_FrameErr_ChA]

    It shows the total numbers of abnormal messages of the device on this end from starting time of

    channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)

    7. Total amount of loss frames of channel A, [N_FrameLoss_ChA]

    It shows the total numbers of the invalid frames of the device on this end from starting time of

    channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)

    8. Total amount of abnormal messages from the remote end of channel A,

    [N_RemoteAbnor_ChA]

    It shows the total numbers of abnormal messages received from the remote end from starting time

    of channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535)

    9. Seconds of serious error frames of channel A, [t_Second_CrcFail_ChA]

    It shows the total numbers of seriously error frame seconds of the protection device on this side

    from starting time of the channel statistics till now. (the maximum is 65535, counted again from 0 ifbeyond 65535)

    10. Desynchronizing times of channel A, [N_LossSyn_ChA]

    It shows the desynchronizing times of the protection device on this end from starting time of

    channel statistics till now. (the maximum is 65535, counted again from 0 if beyond 65535) 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    42/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD28

    3.5.3 Logic Scheme

    3.5.3.1 Common Element

    Where:

    DIFF Enable (Local end): local current differential protection is enabled

    DIFF Enable (Remote end): remote current differential protection is enabled

    Common differential condition (A)

    Common differential condition (B)

    Common differential condition (C)

    IDiff >0.15×IBias (A)

    IDiff >0.15×IBias (B)

    IDiff >0.15×IBias (C)

    IDiff >[I_Diff] (A)

    IDiff >[I_Diff] (B)

    IDiff >[I_Diff] (C)

    &

    &

    &

     

    Where:

    IDiff : differential current

    IBias: restraint current

     A: phase A

    B: phase B

    C: phase C

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    43/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 29

    Differential condition 1 (A)

    Differential condition 1 (B)

    Differential condition 1 (C)

    Common differential condition (A)

    Common differential condition (B)

    Common differential condition (C)

    Idiff>[I_Diff_CTS]

    [En_CTSBlkDiff ]

    [Alm_Diff_ChA]

    DIFF Enable (Local end)

    DIFF Enable (Remote end)

    >=1

    &

    >=1

    &

    &

    &

    &

    CT circuit failure

    &

     

    When binary input [EBI_DiffP], virtual binary input [VEBI_DiffP] and logic setting [En_DiffP_ChA]are all set as “1”, the signal “DIFF Enable” is valid. They can be visible or invisible in the protection

    device through configuration based on different project. If they are invisible, the signal “DIFF

    Enable (Local end)” is valid by default.

    The signal “DIFF Enable (Remote end)” is an information from the remote end via optical fibre

    channel, which is used to indicate whether current differential protection in the remote end is

    enabled or not.

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    44/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD30

    3.5.3.2 DPFC Differential Element (stage 1)

    DPFC DIFF1 (A)

    DPFC DIFF1 (B)

    DPFC DIFF1 (C)

    Differential condition 2 (A)

    Differential condition 2 (B)

    Differential condition 2 (C)

    [En_DPFC_Diff1]

    Op_DPFC_Diff1 (A)

    Op_DPFC_Diff1 (B)

    Op_DPFC_Diff1 (C)

    &

    &

    &

    Op_DPFC_Diff1 (A)

    Op_DPFC_Diff1 (B)

    Op_DPFC_Diff1 (C)

    >=1

    Op_DPFC_Diff1

     

    Where:

    DPFC DIFF1: stage 1 of DPFC differential element

    3.5.3.3 DPFC Differential Element (stage 2)

    DPFC DIFF2 (A)

    DPFC DIFF2 (B)

    DPFC DIFF2 (C)

    Differential condition 2 (A)

    Differential condition 2 (B)

    Differential condition 2 (C)

    [En_DPFC_Diff2]

    Op_DPFC_Diff2 (A)

    Op_DPFC_Diff2 (B)

    Op_DPFC_Diff2 (C)

    25ms 0ms

    25ms 0ms

    25ms 0ms

    &

    &

    &

    Op_DPFC_Diff2 (A)

    Op_DPFC_Diff2 (B)

    Op_DPFC_Diff2 (C)

    >=1Op_DPFC_Diff2

     

    Where:

    DPFC DIFF2: stage 2 of DPFC differential element 

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    45/229

      Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD 31

    3.5.3.4 Steady-state Differential Element (stage 1)

    [En_Stdy_Diff1]

    Steady-state DIFF1 (A)

    Differential condition 2 (B)

    Steady-state DIFF1 (B)

    Differential condition 2 (C)

    Steady-state DIFF1 (C)

    Op_Stdy_Diff1 (A)

    Op_Stdy_Diff1 (B)

    Op_Stdy_Diff1 (C)

    &

    &

    &

    Op_Stdy_Diff1 (A)

    Op_Stdy_Diff1 (B)

    Op_Stdy_Diff1 (C)

    >=1

    Op_Stdy_Diff1

    Differential condition 2 (A)

     

    Where:

    Steady-state DIFF1: stage 1 of steady-state differential element

    3.5.3.5 Steady-state Differential Element (stage 2)

    Steady-state DIFF2 (A)

    Steady-state DIFF2 (C)

    Differential condition 2 (C)

    Steady-state DIFF2 (B)

    Differential condition 2 (B)

    Differential condition 2 (A)

    Op_Stdy_Diff2 (A)

    Op_Stdy_Diff2 (B)

    Op_Stdy_Diff2 (C)

    25ms 0ms

    25ms 0ms

    25ms 0ms

    [En_Stdy_Diff2]

    &

    &

    &

    Op_Stdy_Diff2 (A)

    Op_Stdy_Diff2 (B)

    Op_Stdy_Diff2 (C)

    >=1Op_Stdy_Diff2

     

    Where:

    Steady-state DIFF2: stage 2 of steady-state differential element

  • 8/19/2019 PCS-931 MY Instruction Manual en General X R1.00 (en XLBH5104.0060.1101)

    46/229

    Chapter 3 Protection Description 

    NANJING NARI-RELAYS ELECTRIC CO., LTD32

    3.5.3.6 Zero-sequence Differential Element

    REF DIFF (A)

    REF DIFF (C)

    Differential condition 2 (C)

    REF DIFF (B)

    Differential condition 2 (B)

    Differential condition 2 (A)

    Op_REF (A)

    Op_REF (B)

    Op_REF (C)

    40ms 0ms

    40ms 0ms

    40ms 0ms

    [En_REF]

    &