All rights reserved Printed in Japan 08/06/003 Y.K c Dealer Head Office: Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 2-18-1, Konan, Minato-ku, Tokyo, 108-0075 Japan http://www.daikin.com/global/ 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment. Cautions on product corrosion Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation. Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any inquiries, please contact your local importer, distributor and/or retailer. Printed on 100% recycled paper with soy ink. Specifications, designs and other content appearing in this brochure are current as of August 2006 but subject to change without notice. ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the About ISO 14001 ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at About ISO9001 JMI-0107 JQA-1452 EC99J2044 JQA-E-90108 HEAT PUMP A special air conditioning system designed for small offices and shops Heat Pump Type 50 Hz For high outdoor temperature use HEAT PUMP Heat Pump Type 50 Hz PCVME0614 A special air conditioning system designed for small offices and shops For high outdoor temperature use

Upload: doanphuc

Post on 15-Feb-2018

227 views

Category:

Documents


1 download

TRANSCRIPT

All rights reservedPrinted in Japan 08/06/003 Y.Kc

DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan

Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global/

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.

Cautions on product corrosion

Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any inquiries, please contact your local importer, distributor and/or retailer.

Printed on 100% recycled paper with soy ink.Specifications, designs and other content appearing in this brochure are current as of August 2006 but subject to change without notice.

ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the

About ISO 14001

ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the “ design, development, manufacture, installation, and supplementary service” of products manufactured at

About ISO9001

JMI-0107 JQA-1452 EC99J2044 JQA-E-90108

HE AT P UM P

A s p e c i a l a i r c o n d i t i o n i n g s y s te m d e s i g n e df o r s m a l l o f f i c e s a n d s h o p s

Heat P ump Type 50 Hz

PCVME0614

For high outdoor temperature use

HE AT P UM PHeat P ump Type 50 Hz

PCVME0614

A s p e c i a l a i r c o n d i t i o n i n g s y s te m d e s i g n e df o r s m a l l o f f i c e s a n d s h o p s

For high outdoor temperature use

SSThe 5S +2E c onc epts of

E xtending the c ore “ 5S ” c onc ept—S pac e s aving, S uffic ient c apac ity, S lim des ign,

S ound- reduc ed operation and S ingle phas e power s upply—Daikin’ s VR V III- S

offers added value with the “ 2E ” c onc ept—E as y ins tallation and E as y

maintenanc e. With all thes e features and more, we proudly pres ent the ideal air

c onditioning s ys tem des igned for s mall- s ized buildings .

The ideal air conditioning system for

small offices and shops

S pac e s aving

S uffic ient c apac ity

S lim des ign

S ound-reduc ed operation

S ingle phas e power s upply

E as y ins tallation

E as y maintenanc e E2Econcept

5Sconcept

21

The VRV III-S is highly space saving, featuring slim and compact outdoor units. It is suitable for small offices and shops with the capacity of 6 HP.

Slim, compact and sufficient capacity

The compact, trunk-shaped outdoor unit can easily be installed on a balcony, realizing complete system installation within each floor. This enables more useful utilization of the space on the building rooftop.

Outdoor unit can be installed on a balcony

ContentContent

Introduction..............page 1

Main features...........page 3

Control systems.....page 9

Indoor units line up.....page 15

Specifications.................page 27

Indoor units . . . . . . . . . . . .page 27

Outdoor units . . . . . . . .page 34

Option list..........................page 35

Indoor units . . . . . . . . . . . . . .page 35

Outdoor units . . . . . . . . . . .page 37

C ontrol s ys tems . . . . . .page 37

A slim outdoor unit and a wide range of indoor unitsTo s uit the variety of rooms found in s mall

offic es and s hops , the VR V III- S s ys tem offers a

s lim outdoor unit and a wide range of indoor

units .

VR V III- S indoor and outdoor units are almos t

as eas y to ins tall as res idential air c onditioning

s ys tems , making them ideal for s mall offic es

MAIN FEATURERS

The trunk-shaped outdoor unit can be neatly installed outside the office.

A wide range of indoor units includes 82 models in 15 types. The indoor units can be selected to match every room and preference.

15 types 82 models

6 HP (15.5 kW)

Indoor units

Outdoor unit

RXYMQ6PV4A

43

Conversion rates

Btu/h = kW x 3412RT = kW x 0.284

Indoor unit lineup

Ceiling mounted cassette(Double flow)

Type Capacity

IndexHP

20 40 62.5 80 100 1255031.25250.8 HP 1.6 HP 2.5 HP 3.2 HP 4 HP 5 HP2 HP1.25 HP1 HP

Btu 7500 15400 24200 30700 38200 4780019100123009600

Ceiling mountedcassette (Multi flow)super cassette

FXCQ-M

FXFQ-M

Slim ceilingmounted duct

Ceiling mountedduct

Ceiling suspended

Wall mounted

Floor standing

Concealedfloor standing

Ceiling mountedcassette corner

FXDQ-NAVE(with drain-up pump)

FXDQ-NVET(without drain-up pump)

FXMQ-MA

FXHQ-MA

FXAQ-MA

FXLQ-MA

FXNQ-MA

FXKQ-MA

Ceiling mountedbuilt-in FXSQ-M

FXDQ-PVET(without drain-up pump)

FXDQ-PVE(with drain-up pump)

(700 mm width type)

(900/1,100 mm width type)

• R410A VRV system indoor units are not compatible with the R22 VRV system.Notes:

New

New

New

New

New

New

NewCeiling suspendedcassette

Type

1.6 HP0.8 HP 1.25 HP1 HP

— — — —

HP

Connection Unit20 4031.2525

BEVQ125MAVE

5 HP

BEVQ100MAVEBEVQ71MAVE

2 HP 4 HP3 HP

— FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1

50 12510071Index

1.3 ton0.6 ton 1.0 ton0.8 tonRTCapacity7500 15400123009600

4.0 ton1.6 ton 3.2 ton2.3 ton19100 478003820027300Btu

• Indoor units in the 63 class are not available for the above model.• BEV units are necessary for Connection unit series indoor units. Refer to the Connection unit series catalog for details.

Notes:

600X600 multi flow ceiling mounted cassette

FXZQ-M

RT 0.6 ton 1.3 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton1.6 ton1.0 ton0.8 ton

New

New

Energy efficiency and quiet operationOutdoor units have been newly des igned us ing the new c ompres s or

to realize energy s aving performanc e and quiet operation.

MAIN FEATURERS

Higher COP during both coolingand heating operations

Quiet operation provides luxurious comfortQuietness is yet another important feature of Daikin’s VRV III-S system. To reduce noise and realize comfortable operation, latest technologies and features are applied to the outdoor units.

One of the top features of the VRV III-S is its energy efficiency. It achieves high COP during cooling and heating operations by employing the new compressor.

These two new features work to significantly reduce noise. Guides are added to the bell mouth intake to reduce turbulence in the airflow generated by fan suction. The new Aero Spiral Fan features fan blades with the bent blade edges, further reducing turbulence.

Smooth Air Inlet Bell Mouth and Aero Spiral Fan

A larger sub-cooled area reduces refrigerant flow sound by making it easer to form a liquid seal in front of the electrical valve.

SC heat exchanger

Super Aero Grille Refined ventilation mechanism enables further reduction in required fan power.

Escaping eddies are sucked in by the bent blade edges, reducing overall turbulence.

Conventional Newly developed

A collection of cutting-edge technologies realizes efficient and quiet operation.

Improving the high efficiency compressor to achieve a higher COP

2

5

1

Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.

Above values are based on the following nominal conditions:Note: • 2 build-in units are connected (4 HP: FXFQ50M x 2; 5 HP:

FXFQ63M x 2; and 6 HP: FXFQ63M + FXFQ80M.)• Indoor temp. of 27°C DB/19°C WB, and outdoor temp. of 35°C DB.

DC fan motorEfficiency improved in all areas compared to conventional AC motors, especially at low speeds.

4

Sine wave DC inverter >> Smooth sine wave DC inverter Use of an optimized sine wave smoothes motor rotation, further improving operating efficiency.

Use of neodymium magnets in the motor enables efficient generation of high torque, reducing the size of the compressor.

>> Powerful magnets

Changes to the shape of the spiral and volume ratio result in optimal refrigerant layout.

>> Optimal refrigerant configurationThe strength of the casing has been increased by boosting the internal dome pressure.

>> Stronger materials

Overheating losses are reduced by pressurizing the area around the motor, boosting energy saving performance in conjunction with other features.

Reluctance DC Scroll Compressor

Neodymium magnets are much more powerful than the commonly used ferrite magnets.Ferrite magnet

Neodymium magnet

3DC motor efficiency

(comparison with a conventional AC motor)

200 300 400 500 600 700 800 900 10000

20

40

80

60

100

Effic

ienc

y (%

)

Motor speed (rpm)

AC motorAC motorAC motorApprox.40%

increase

Approx.20%

increase

DC motorDC motorDC motorDC fan motor structure

Neo aero spiral fan blade tips

Lower operation sound is achieved!

RXYMQ6PV4A

ReluctanceDC motorBy introducing high pressure oil, the

reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses. This results in improved efficiency and suppressed sound levels.

High thrust mechanism

3

4 1

5

2

Cooling

Heating

Heating

Cooling 5 3

5 5

3 . 0 3

3 . 6 2

6 HP

6 HP

6 HP

6 HP

65

Nighttime quiet operation function

Set on the outdoor PCB. Time of maximum temperature is memorized. The low operating mode will become active 8 hours*2 after the peak temperature in the daytime, and operation will return to normal 10 hours*3 after that. The operation sound level for the night mode can be selected from 47 dB (Step 1), 44 dB (Step 2) and 41 dB (Step 3).

Automatic modeMode 1.

Automatic modeMode 1.

Starting time and ending time can be input. (External control adaptor for outdoor unit, DTA104A61 or DTA104A62, and a subsequently obtained timer are necessary.)

Manual modeMode 2.

Combination of mode 1 and 2 can be used depending on your needs.

Combined modeMode 3.

*1. Determine which mode to select depending on the climatic characteristics of each country.

*2. Initial setting. Can be selected from 6, 8 and 10 hours.*3. Initial setting. Can be selected from 8, 9 and 10 hours.

Note: • This function is available in setting at site.• The relationship of outdoor temperature (load) and time shown in the graph is just an example.

Peak in the outdoor temperature

Cap

acity

%

8 hrs 10 hrs

Ope

ratio

n so

und

dB

47

8:00 12:00 16:00 20:00 0:00 4:00 8:00

50

100

500

Load

%

Night mode endsNight mode starts Night mode endsNight mode starts

Night Mode

44

41

(Initial setting)(Initial setting)

Step 1 max. - 3dB( 4 HP/11.2 kW)

Step 2 max. - 6dB( 4 HP/11.2 kW)

Step 3 max. - 9dB( 4 HP/11.2 kW)

Step 1: 47 dB

Step 2: 44 dB

Step 3: 41 dB

Operation sound level selectablefrom 3 steps for the night mode

The capacity reduction rate differs depending on the operation sound level step selected.

Design flexibility Easy installationVR V III- S s ys tems offer broad des ign flexibility with long refrigerant piping

lengths and multiple indoor unit c ombinations , whic h provides generous freedom

for offic e and s hop des ign both ins ide and out.

A variety of func tions are provided that make ins tallation eas ier, s uc h as

s imple wiring and piping and automatic tes t operation.

Easy maintenanceVR V III-S features a self-diagnosis function for outdoor units that can determine the

status of each component. Also, a new memory function helps to identify the problem if

MAIN FEATURERS

Unique piping and wiring systems make it possible to install a VRV III-S system quickly and easily. Simple wiring and piping connection

A new type of printed circuit board has been adopted that is easy to see and wire during installation.

Easy wiring

Simply press the test operation button and the unit performs an automatic system check, including wiring, shutoff valves, sensors, and refrigerant volume. The results are returned automatically after the check finishes.

Automatic test operation

Operating data for the preceding 3 minutes is automatically stored in memory. Should a malfunction occur, this speeds up the process of identifying and fixing the cause of the problem.

Memory function for operation data

Daikin’s advanced REFNET piping system makes installation easy. Only two main refrigerant lines are required in any one system. REFNET greatly reduces the imbalances in refrigerant flow between units, while using small-diameter piping.

>> REFNET piping system A super wiring system is used to enable shared use of the wiring between indoor and outdoor units and the central control wiring, with a relatively simple wiring operation. The DIII-NET communication system is employed to enable the use of advanced control system.

>> Super wiring system

For a 6 HP installation

Multiple indoor unit combinations are possible*. As many as 9 indoor units can be connected to single outdoor unit, making the VRV III-S a remarkably versatile system.* Indoor units can be connected up to 130% of the capacity of the outdoor unit.

As many as 9 indoor units can be connected to single outdoor unit

The VRV III-S provides the long piping length possibility of 150 m, with a total piping length of 300 m. If the outdoor unit is installed above indoor units the height difference can be up to a maximum of 50 m. These generous allowances facilitate an extensive variety of system designs.

Long piping design possible

Actual piping length

150 mTotal piping length

300 m

1 2 3 4

5 6 7 8

units9

50 m*1

*2 15 m

Height difference

Level differencebetween indoorunits.

*1. 40 m when the outdoor unit is installed below indoor units.*2. Maximum piping length between the indoor unit and the first branch is 40 m.

Note:

The versatile operating range of the VRV III-S system works to reduce limitations on installation locations. The operating temperature range for heating goes all the way down to -20°C, while cooling can be performed with outdoor temperatures as high as 50°C. Both these achievements are due to the employment of a high-pressure dome-type compressor.

-20

-10

0

10

20

30

40

50

15.5°C WBHeating

50°C DBCooling

-5°C DB

–20°C WB

Outdoor temperature operating rangeWide operating temperature range

Outdoor unitCentralremote

controllerIndoor unit

87

New

New

New

* Refer to the Engineering Data for cooling/heating capacities.* Please contact your distributor to confirm cooling/heating capacities when outdoor

temperatures are 46°C or higher.

Control systemsThe VR V III- S s ys tem us es the s ame DIII- NE T c ommunic ation s ys tem

as the VR V, enabling the us e of advanc ed c ontrol s ys tems .

CONTROL SYSTEMS

Wired remote controller (Optional)

The same operation modes and settings as with wired remote controllers are possible.

Signal receiver unit(Separate type)

Wireless remote controller

The concealed-type remote controller smartly fits into a night table or console panel in a hotel room.

Wireless remote controller (Optional)

Simple remote controller (Optional)

Wide variation of remote controllers for indoor units

Individual control systems

* Refer to the page 35 for the model names.

• A light receiving unit for a ceiling-mounted cassette (double-flow, multi-flow) type, ceiling-suspended type and wall-mounted type is mounted into the indoor unit.

Signal receiver unit(Installed type)

Signal receiving unit can be installed on the panel ex. Ceiling mounted cassette (multi-flow) type

Wired remote controller with weekly schedule timer (Optional)

BRC1D61

24-hour clock function (1-hour backup for power failures)

Includes ventilation mode and airflow rate switching, the main functions of HRV series.

Programming function for each day of week.

Scheduling possible of start/stop and temperature limit (5 settings/day)

Programming can be enabled or disabled.

Copy function for programmed schedules.

Adds new, advanced functions to those of the above wired remote controller.

Notes: 1. Standard remote controllers (BRC1C62) not required. 2. If the BRC1D61 is connected to the centralized remote controller, the schedule function is not available.

Easier to read because LCD screen is larger.Digital display lets you set temperature in 1°C units.Lets you individually program by timer the respective times for operation start and stop within a maximum of 72 hours.Equipped with a thermostat sensor in the remote controller that makes possible more comfortable room temperature control.Enables you to select cool/heat/fan operation mode with the indoor remote controller of your choice without using the cool/heat selector.

Constantly monitors malfunctions in the system for 80 items, and is equipped with a "self-diagnosis function" that lets you know by message immediately when a malfunction occurs.Lets you carry out various field settings by remote controller.Enables you to select the ventilation mode and the volume of the HRV.The rubber switch and the oil-resisting resin casing have been adopted for durability.

* When the auto-swing function is not available, the message, THIS FUNCTION IS NOT AVAILABLE is displayed when the wind direction adjustment button is pressed.BRC1C62

The remote controller has centralized its frequently used operation selectors and switches (on/off, operation mode, temperature setting and airflow volume), making itself suitable for use in hotel rooms or conference rooms.The exposed type remote controller is fitted with a thermostat sensor.

Concealed type(For hotel use)

(BRC3A61)

Exposed type(BRC2C51)

Outdoor unit

Indoor unit

Forced OFF input

Remote controllerRemote controller

Remote controllerRemote controller

Remote controllerRemote controller

Remote controller

Remote controller

HRV

The indoor unit can be connected by the two remote controller, for example one in the room and the other one in the control room, which can control the operation of indoor unit freely.(The last command has a priority.) Of course, the group control by two remote controller is also possible.

Control by two remote controller

The system can be expanded to add several controllers, such as BMS, Forced OFF input and etc.

Expansion of system control

In all the series of VRV, Cool/Heat changeover in the same refrigerant circuit can be changed by the remote controller of the indoor unit.

Control of Cool/Heat changeover

One remote controller can control the operation of max.16 indoor units at the same time.

Group controlEquipment related to the central control

1 2 3

The wiring of remote controller can be extended to max.500m and it is possible to install the remote controllers for the different indoor units in one place.

Remote control

The operation of HRV can be controlled by the remote controller of the indoor unit. Of course, the remote controller can display the time to clean the filter.

Control for the combined operation

4

4

3

2

1

Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.

The wired remote controller supports a wide range of control functions

109

Wired remote controller

Wired remote controller with weekly schedule timer

Wireless remote controller(Installed signal receiver unit)

Wireless remote controller(Separate type signal receiver unit)

Simple remote controller(Exposed type)

Simple remote controller(Concealed type: for Hotel use)

FXCQ FXZQ FXKQ FXSQ FXMQ FXHQ FXAQ FXL(N)Q FXUQFXDQFXFQ

CONTROL SYSTEMS

Up to 64 groups of indoor units (128 units) can be centrally controlled.

Optional controllers for centralized control can be combined freely, and system can be designed in accordance with building scale and purpose.

System integration with various air-conditioning peripheral equipment such as HRV (Heat Reclaim Ventilation) is easy.

Wiring can be run up to a total length of 2 km, and adapts easily to large-scale system expansion.

Centralized control systems

Central remote controllerDCS302CA61

Unified ON/OFF controllerDCS301BA61

Schedule timerDST301BA61

Central remote controller (Optional)

Unified ON/OFF controller (Optional)

Schedule timer (Optional)

16 groups of indoor units can be operated simultaneously/individually.

Max. 128 indoor units can be operated as programmed schedule.

• Max. 64 groups (128 indoor units controllable)• Max. 128 groups (128 indoor units) are controllable by using 2 central remote controllers,

which can control from 2 different places.• Zone control• Malfunction code display• Max. wiring length 1,000 m (Total: 2,000 m)• Combination with Unified ON/OFF controller, schedule timer and BMS system• Airflow volume and direction can be controlled individually for indoor units in each group

operation.• Ventilation volume and mode can be controlled for Heat Reclaim Ventilation (HRV).• Up to 4 Operation/Stop pairs can be set per day by connecting a schedule timer.

• Max. 16 groups (128 indoor units) controllable• 2 remote controllers can be used to control from 2 different places.• Operating status indication (Normal operation, Alarm)• Centralized control indication• Max. wiring length 1,000 m (Total: 2,000 m)• Compact size casing (Thickness: 16 mm)• Combination with Central Remote controller, Schedule timer and BMS system

• Max. 128 indoor units controllable• When used in combination with a central remote controller, a maximum of 8 weekly schedule

patterns can be set, while the central controller can be used to select desired zones. Up to 2 Operation/Stop pairs can be set per day.

• Max. 48 hours back up power supply• Max. wiring length 1,000 m (Total: 2,000 m)• Compact size casing (Thickness: 16 mm)• Combination with Central Remote controller, Unified ON/OFF controller and BMS system

64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.

For more details, please refer to the Engineering Data.

1. Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.• Certain indoor units limit the functions of some control systems.

Central control adaptor kit (DTA107A55).

Wiring adaptorfor other air-conditioners (DTA103A51)

Central remote controller(DCS302CA61)

Up to 2 units connectable

Unified on/off controller(DCS301BA61)

Connection of up to 8 unitspossible

Schedule timer (DST301BA61)1 unit connection possible ; 8 weekly schedule control patterns possible

Forced shut-down input

Independent and centralized control of HRV is possible.

Unification adaptor for computerized control * (DCS302A52)

Interlink Building Management System (host computer monitor panel) also possible

6 cores 7 cores max.

Address setting of central control can be performed from the remote controller.

Group control of up to 16 units is possible (group control via automatic address setting)

System without remote control is also available.

Interface adaptor for SkyAir series (built-in indoor unit) (DTA102A52)

Connectable number of centralized control equipment

Central remotecontoroller 2 units

Unified on /offcontoroller 8 units

Schedule timer 1 unit

Outdoor-air processing unit can be connected.

1

1211

CONTROL SYSTEMS

1413

Color LCD touch panel icon displaySmall manageable size Simplified engineeringMulti language (English, French, Italian, German, Spanish and Chinese)Yearly scheduleP.P.D. (Power Proportinal Distribution function) (Optional)Auto heat/cool change-overTemperature limitationHistory of 500 actionsAir Conditioning Network Service System (Optional Maintenance Service)Simple Interlock Function

New communication functions in the user-friendly icon-based multilingual controller simplify centralized control of the VRV system.

ACC center• Air Conditioning Network Service System

Forced OFF from the fire alarm

Pi Port

• Connection to power consumption meter when using power proportional distribution function. (Optional)

DIII-NETPlus Adapter(option)(DCS601A52)

Number of indoor unit expanded from 64 to 128.

Indoor Unit

RS-232C

Control pump, lighting

Monitoring of roomenter/exit sign

Simple Interlock Function

Public phone line

Air Conditioning Network Service System modem for connections

• CSV output of power proportional distribution results (Optional)

PCMCIAFlash

Memory

Mobile PhoneTrouble reports

Forced OFF contact input

HRV

Dio Unit (DEC102A51)

Di Unit (DEC101A51)

D -NET

SpecialFunction 6

SpecialFunction 1

Remote monitoring and control

SpecialFunction 5

SpecialFunction 3

SpecialFunction 2

SpecialFunction 4

SpecialFunction 6

SpecialFunction 1

SpecialFunction 3

SpecialFunction 5

SpecialFunction 3

SpecialFunction 2

SpecialFunction 4

SpecialFunction 6

SpecialFunction 7

SpecialFunction 7

SpecialFunction 1

SpecialFunction 3

SpecialFunction 5

SpecialFunction 3

SpecialFunction 2

SpecialFunction 4

Doubling of number of control points by adding a D -NET Plus Adapter (Optional)SpecialFunction 1

SpecialFunction 1

Support for centralized control from elsewhere using a PC with a Web browser (Optional)SpecialFunction 2

SpecialFunction 2

Sending of e-mail alerts to a specified address when malfunctions occur (Optional)SpecialFunction 3

SpecialFunction 3

Built-in modem for connecting to Airnet Service System (Optional)SpecialFunction 4

SpecialFunction 4

Built-in Ethernet port for connecting to the Internet or an intranetSpecialFunction 5

SpecialFunction 5

Management of facilities / equipment other than A/C units(Compatible with Dio unit and Di unit)Special

Function 6Special

Function 6

SpecialFunction 7

SpecialFunction 7 Simple Interlock Function

S pe c ia l F u n c t io n s

Trouble reports

Unification adaptorfor computerized control

[DCS302A52]

Unified ON/OFF andstatus monitoring from the central monitoring panel

DCS601C51

E-mail

Advanced control systems

INDOOR UNITS LINE UP

1615

600 mm

Class 20

32/27

25/32

34/28

63

37/32

40/50

34/29

80

39/34

125

44/38

34/29 36/30 39/3437/32 41/36 46/40

(dB(A))

350mm

The thin unit (only 350 mm high) can be installed in a ceiling space as narrow as 355 mm. All models feature a compact design with a depth of only 600 mm.

(When a high-efficiency filter is attached, the unit's height is 400mm.)

Low operating sound

Designed with higher air flow suitable for high ceiling application up to 3 meter.

Providing 2 different settings of standard and ceiling soiling prevention, the auto swing mechanism ensures even distribution of airflow and room temperature.

Two types of optional high-efficiency filter are available (65% and 95% NBS).

A long-life filter (maintenance free up to one year) is equipped as standard accessory.

Drain-up pump is equipped as standard accessory with 600 mm lift. Major maintenance work can be performed by

removing the panel. A flat-type suction grille and a detachable blade make cleaning easy.

220V

240VOperating

Sound (H/L)

Ceiling mounted cassette(double-flow) type

FXCQ20M/FXCQ25M/FXCQ32MFXCQ40M/FXCQ50M/FXCQ63MFXCQ80M/FXCQ125M

Thin, lightweight, and easy to install in narrow ceiling space

Ceiling MountedCassette(Double-flow)

Type

Ceiling MountedCassette(Multi-flow)Super Cassette

Ceiling MountedCassette Corner

Wall Mounted

Floor Standing

Concealed FloorStanding

FXCQ-MVE

FXFQ-MVE

FXHQ-MAVE

HPIndex

FXKQ-MAVE

FXLQ-MAVE

FXNQ-MAVE

FXMQ-MAVE

Model name

20 25 31.25 40 50 62.5 80 100 1250.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP

RT

Capacity Btu 7500 9600 12300 15400 19100 24200 30700 38200 478000.6 ton 0.8 ton 1.0 ton 1.3 ton 1.6 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton

FXDQ-NAVE(900/1,100 mm

width type)

FXDQ-NVET(900/1,100 mm

width type)

with drain-up pump

without drain-up pump

FXSQ-MVECeiling MountedBuilt-in

Ceiling Suspended

Ceiling Mounted Duct

FXAQ-MAVE

Ceiling SuspendedCassette

Type

FXUQ-MAV1

Model name20 4031.2525

BEVQ125MAVEBEVQ100MAVEBEVQ71MAVE50 12510071

• Indoor units in the 63 class are not available for the above models.• BEV units are necessary for Connection unit series indoor units. Refer to the Connection unit series catalog for details.

Notes:

• R410A VRV system indoor units are not compatible with the R22 VRV system.Note:

Connection unit series indoor units

154007500 123009600 4780019100 3820027300Btu

Connection UnitIndex

1.3 ton0.6 ton 1.0 ton0.8 ton

0.8 HP 1.6 HP1.25 HP1 HP

4.0 ton1.6 ton 3.2 ton2.3 ton

2 HP 5 HP4 HP3 HP

RT

Capacity HP

Slim Ceiling Mounted Duct

FXDQ-PVE(700 mm

width type)

FXDQ-PVET(700 mm

width type)

with drain-up pump

without drain-up pump

New

600X600multi flow ceiling mounted cassette

FXZQ-M7V1B

New

New

New

New

New

New

New

Conversion rates

Btu/h = kW x 3412RT = kW x 0.284

INDOOR UNITS LINE UP

1817

Ceiling mounted cassette(multi-flow) type

Compact, quiet and easy-to-install Super Cassette type

Regardless of their difference in capacity, all indoor units feature the same panel size and design, in consideration of harmonized interior decor.

The FXFQ25M-80M are thin models (246mm) which can be installed in narrow false ceilings of at least 265mm depth.

(220V-240V)(dB(A))

Single branch– 8 patterns

2 branches–2 patterns

Number of discharge outlets usedFXFQ25M-80M FXFQ100M-125M

4-way air discharge

3-way air discharge

2-way air discharge

4-way air discharge

3-way air discharge

2-way air discharge

Ceilingheight

Standard 2.7m3.0m3.5m

3.0m3.3m3.5m

3.5m3.8m

3.2m3.6m4.2m

3.6m4.0m4.2m

4.2m4.2m

–High ceilingHigh ceiling

Note: Set standard 4-way discharge when shipped.High ceiling types and will be set for remote control operation1 2

12

40˚40˚10˚ 10˚

Pattern

2 Draft Prevention setting

Pattern

1 Standard setting

7 discharge patterns in 2 to 4 directions can be selected to suit the requirements of installation site or the shape of the room.The number of installation method using ducts has increased as shown below.

Pipinglocation

Has been set to standard setting at time of shipment. This can be changed using the remote control

Closed

Branched

Pipinglocation

ClosedBranched

25˚ 25˚

60˚ 60˚35˚35˚

65˚ 65˚

Pattern

3 Setting to prevent soiling of ceiling

750mm

Because of the light weight, suspension is easy.Low operating sound

Installing the fresh air intake is easy using the optional kit which requires no special chambers.A long-life filter (maintenance free up to two years) is equipped as a standard accessory.

Provided with high lift drain water lift-up mechanism. (Increased lift of drain pipe up to 750 mm from the ceiling.)

Note: Operating sound may increase more than that when using with 3-way discharge or 2-way discharge, or when using together with a optional kit. : The values of Hi mode Sound level represent those during cooling operation. Those during heating operation are shown in brackets for two models only.

42(43) /36

125

39/33

100

36/31

80

33(34) /28

63

32/27

50

31/27

40

30/27

32

30/27

25Operating

sound (H/L)

Class

FXFQ25M/FXFQ32M/FXFQ40MFXFQ50M/FXFQ63M/FXFQ80MFXFQ100M/FXFQ125M

Can also be installed in high ceilings.

There are 3 patterns in auto swing operation

Quiet, stylish unitwith a horizontal blow capability

Exactly matches the European style architectural module (600 mm x 600 mm).

Switch box is inside the unit, which makes maintainance and installation easy.

Less draft than FXFQ cassette discharge angle: 25° to 60° 0° to 60°

Low operating sound(240V)(dB(A))

600 x 600 multi flow ceiling mountedcassette type

FXZQ20M/FXZQ25M/FXZQ32MFXZQ40M/FXZQ50M

New model

60°

60°

Auto swing

Settable to 5 different levels between 0° and 60°

Angles can be set on site to prevent drafts (0°-35°) or soiling of the ceiling (25°-60°)

32/26OperatingSound (H/L)

20 25 32 40 50

32/26 34/28 37/29 42/35

Class

INDOOR UNITS LINE UP

2019

Slim ceiling mountedduct type

Slim design, quietness and static pressure switching

FXDQ20N(A)/FXDQ25N(A)/FXDQ32N(A)FXDQ40N(A)/FXDQ50N(A)/FXDQ63N(A)FXDQ20P/FXDQ25P/FXDQ32P

External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.10 Pa-30 Pa/factory set: 10 Pa for FXDQ-P models.15 Pa-44 Pa/factory set: 15 Pa for FXDQ-N(A) models.

Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.

Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.

Low operating sound

36/32

63

35/31

50

34/30

40

33/29

32

33/29

25

33/29

20Operating

sound (H/L)

Class(dB(A))

The values of operation sound level represent those for rear-suction operation.Sound level values for bottom-suction operation can be obtained by adding 5 dB. Values are based on the following conditions:FXDQ-P: external static pressure of 10 Pa; FXDQ-N(A): external static pressure of 15 Pa.

1,100 mm in width for the FXDQ63N(A) model.

200mm900 mm

Suction grille*AIR

AIR

Discharge grille*

Air filterSuspension bolt*

240 mm

*: To be obtained locally

750mm

Ceiling

FXDQ-P and FXDQ-N(A) models are available in two types to suit different installation conditionsFXDQ-PVE, FXDQ-NAVE: with a drain-up pump (750 mm lift) as a standard accessoryFXDQ-P(N)VET: without a drain-up pump

Only 700 mm200 mm

Great for hotel use!

Compliant with the RoHS Directive ** For FXDQ-PVE and FXDQ-NAVE models only.

Suited to use in drop-ceilings!

Ceiling mounted cassettecorner type

Slim design for flexible installation

3

32˚C 30˚C28˚C 26˚C 24˚C

22˚C

20˚C

2

1

0 1 2 3 4 5 6 (m)

(m)

Panel spac er

20 mm

Min.195 mm

Main body

Air disc harge grille (option)

Set for front discharge using a suspended ceiling.

Downward discharge is shut off and air is blown straight out (front discharge).

Compliant with the RoHS Directive*

Single-flow type allows effective air discharge from corner or from drop-ceiling.

Front discharge is possible with a air discharge unit (optional), which allows the installation in the drop-ceiling or sagging wall.

Slim body needs only 220 mm space above the ceiling. If you use panel spacer (optional), the unit can be installed in the min. space of 195 mm.

A long-life filter (maintenance free up to one year) is equipped as standard accessory.

Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism ensures even distribution of airflow and room temperature.

500 mm

Drain-up pump is equipped as standard accessory with 500 mm lift.

Main body

Downward disc harge

Air disc harge grille (option)

FXKQ25MA/FXKQ32MAFXKQ40MA/FXKQ63MANew

NE W

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

NE W

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

INDOOR UNITS LINE UP

2221

Ceiling mountedduct type

High static pressure allows flexible duct design

More than 150 Pa of external static pressure

Compliant with the RoHS Directive*

High external static pressure allows extensive duct work for flexible applications.

Optional accessories include a drain-up kit, high-efficiency filters (65% and 95% NBS) and a long-life filter (maintenance free up to 1 year).

Full line-up of 8 models from 40 to 250 type.

Indoor unit

Min450mm390mm

Without drain Drain-up pump is equipped as optional ac c essory with 750 mm

750mm

120mm

FXMQ40MA/FXMQ50MAFXMQ63MA/FXMQ80MAFXMQ100MA/FXMQ125MA

New

NE W

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

Ceiling mountedbuilt-in type

Highly flexible for various application

FXSQ20M/FXSQ25M/FXSQ32MFXSQ40M/FXSQ50M/FXSQ63MFXSQ80M/FXSQ100M/FXSQ125M

250 mm

Min.350 mm

Highly flexible installation is possible with a complete line-up of optional kits to satisfy the various needs, such as the design concept, interior decoration and so on.

The unit can be installed, if there is a space of 350 mm above ceiling. (when suction panel is used.)

Drain-up pump is equipped as standard accessory with 250 mm lift.

High external static pressure allows to use even flexible ducts of various length.

Low operating sound

Two types of optional high-efficiency filter are available (65% and 95% NBS).

A long-life filter (maintenance free up to one year) is equipped as standard accessory.

37/32

39/34Operating

Sound (H/L)

20 25

37/32

32

38/32

40

38/32

50

41/36

63

42/35

80

43/37

100

43/37

125

46/41

39/34 40/34 40/34 43/38 44/37 45/39 45/39 48/43

(dB(A))

Class

Standard

With duct (case 1)

With duct (case 2)

Cassette style (standard filter)

Cassette style (high efficiency filter)

Long-life filter

Long-life filter

Air suc tion c anvas bellows

Air suc tion panel

Air suc tion panel

Ac c ess panel Ac c ess panel

Ac c ess panel Air suc tion c anvas bellows

Ceiling returnLong-life filter

Long-life filter

S c reening door

S c reening door

High effic ienc yfilter

220V

240V

Installation examples ( Optional parts)

INDOOR UNITS LINE UP

2423

Wall mounted type

Sophisticated design and compact casing harmonized with your interior décor

Drain pan and air filter can be kept clean by mildew-proof polystyrene.

Compact and stylish design that does not detract from the décor of the room.

Drain-up kit

1,000mm

Height of drain-up

Indoor unit

Drain-pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.

Auto-swing ensures efficiency of air distribution. The louver closes automatically when the unit stops.

5 steps of discharge angle can be set by remote controller.

Washable grille, the front grille can be easily removed for washing.

Discharge angle is automatically set at the same angle as the previous operation when restarts. (Initial setting; 10˚ for cooling and 70˚ for heating)

1,050 mm

For 50, 63 Class–70 mm

–200 mm

290

mm

More compact than compared with previous model. (50, 63 class)

Drastic 10 kg weight reduc tion from 24 kg to 14 kg.Volume reduc ed by 22%. S pac e savings of up to 47%.

Flexible installation.Drain pipe c an be fitted to from either left or right s ides .

Low operating sound

46/39

63

42/36

50

39/34

40

37/29

32

36/29

25

35/29

20Operating

sound (H/L)

Class(220V-240V)(dB(A))

FXAQ20MA/FXAQ25MAFXAQ32MA/FXAQ40MAFXAQ50MA/FXAQ63MA

Compliant with the RoHS Directive*

New

NE W

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

Ceiling suspended type

Slim body with quiet and wide air flow

Compliant with the RoHS Directive*

Adoption of newly designed QUIET STREAM FAN

Drain-up kit (optional) c an be eas ily inc orporated.

E asy-to-c lean flat des ign

Maintenanc e is eas ier bec ause everything c an be performed from below the unit.

Non-dew Flap with no implanted bris tles

Class

Operating sound (H/L)

32

36/31

63

39/34

100

45/37

(220V-240V)(dB(A))Low operating sound

Uses the quiet s tream fan and many more advanc ed tec hnologies .

S ound absor ption member

Turbulent flow is produc ed

S traightening vane

Quiet s tream fan

Installation is easy

Maintenance is easy

Drain-up kit(built ins ide main unit)

600mm

B ristle-free Flap minimizes c ontamination and makes c leaning s impler.

Non-dew Flap

100°New model

Wide air discharge openings produce a spreading 100° air flow.

A long-life filter (maintenanc e free up to one year) is equipped as s tandard

FXHQ32MA/FXHQ63MAFXHQ100MA

New

NE W

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

INDOOR UNITS LINE UP

2625

Ceiling suspendedcassette type

This ultra-thin indoor unit achieves optimumair distribution, and can be installedwithout the need for ceiling cavity

FXUQ71MAV1FXUQ100MAV1FXUQ125MAV1

Connection unitNew

New

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

Connection unit is the device for connecting above indoor units to VRV III-S.

Depending on installation site requirements or room conditions, 2-way, 3-way and 4-way discharge patterns are available.

Compliant with the RoHS Directive*NE W

Compliant with the RoHS Directive*NE W

4-way air flowfrom the center of the store.

The 3-way air flow can distributecomfortable air throughout the room.

Only one unit is needed to distribute comfortable airthroughout an L-shaped store.

BEVQ-MAVE

Connection unit for indoor unit

Indoor unitPiping length*1

Indoor unit

R emote c ontroller

S uper wiring ( DIII-NE T )

S ingle-phase 220-240 Vpower supply

VR V -S series outdoor unit

Refrigerant piping layout External wiring layout

Notes:G as pipeLiquid

pipe

ModelMaximum piping lengthbetween the BEV unitand the indoor units.

FXUQ-MAV1 5 m

*1

• When connecting centralized-control device, it is necessary to install an interface adaptor for an indoor unit (DTA102A52).

• Connection unit BEVQ-MA is necessary for each indoor unit.

• The refrigerant piping height difference between the indoor units and the BEV unit must be within 4 m.

• The BEV unit must be installed within a maximum height difference between indoor units of 15 m.

• Branching of the refrigerant piping is not possible downstream of the BEV unit.

Floor standing type

A great unit for perimeter zone air conditioning

Wall hanging Floor installation

Floor standing types can be hung on the wall for easier cleaning. Since running the piping from the back allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is considerably easier.

A long-life filter (maintenance free up to one year) is equipped as standard accessory.

Compliant with the RoHS Directive*

The adoption of a fiber-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier.

Concealed floorstanding type

A great unit to be concealed in the skirting-wall of perimeter

C onnec ting port

R efrigerant piping

Applies also to floor standing type (FXNQ-MA).

The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.

Compliant with the RoHS Directive*

The connecting port faces downward, greatly facilitating on-site piping work.

A long-life filter (maintenance free up to one year) is equipped as standard accessory.

FXNQ20MA/FXNQ25MAFXNQ32MA/FXNQ40MAFXNQ50MA/FXNQ63MA

New

New

FXLQ20MA/FXLQ25MAFXLQ32MA/FXLQ40MAFXLQ50MA/FXLQ63MA

NE W

NE W

New

* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.

SPECIFICATIONS

INDOOR UNIT SINDOOR UNITS

2827

FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE

Galvanized steel plate

7/5

247/17732/27

305X775X600

26.0

6.4

12.7

VP25 (External Dia, 32/Internal Dia, 25)

BYBC32G-W1

White (10Y9/0.5)

53X1,030X680

8.0

9/6.5

318/23034/28

305X775X600

26.0

6.4

12.7

53X1,030X680

8.0

9/6.5

318/23034/28

305X775X600

26.0

6.4

12.7

53X1,030X680

8.0

12/9

424/31834/29

305X990X600

31.0

6.4

12.7

BYBC50G-W1

53X1,245X680

8.5

12/9

424/31834/29

305X990X600

32.0

6.4

12.7

53X1,245X680

8.5

16.5/13

582/45937/32

305X1,175X600

35.0

9.5

15.9

BYBC63G-W1

53X1,430X680

9.5

26/21

918/74139/34

305X1,665X600

47.0

9.5

15.9

BYBC125G-W1

53X1,920X680

12.0

33/25

1,165/88344/38

34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40305X1,665X600

48.0

9.5

15.9

53X1,920X680

12.0

C e ilin g M o u n t e d C a s s e t t e <D o u b le f lo w > T y p e

MODEL FXFQ25MVE

Galvanized steel plate

246X840X840

24.0

6.4

12.7

VP25 (External Dia, 32/Internal Dia, 25)

BYCP125D-W1

White (10Y9/0.5)

45X950X950

5.5

45X950X950

5.5

45X950X950

5.5

45X950X950

5.5

45X950X950

5.5

45X950X950

5.5

45X950X950

5.5

45X950X950

5.5

246X840X840

24.0

6.4

12.7

FXFQ32MVE

15/1113/10 13/10

30/27 30/27

530/388

31/27

246X840X840

24.0

6.4

12.7

FXFQ40MVE

16/11

565/388459/353 459/353

32/27

246X840X840

24.0

6.4

12.7

FXFQ50MVE

18.5/14

653/494

33(34) /28

246X840X840

25.0

9.5

15.9

FXFQ63MVE

20/15

706/530

36/31

246X840X840

25.0

9.5

15.9

FXFQ80MVE FXFQ100MVE FXFQ125MVE

26/21

918/741

39/33

288X840X840

29.0

9.5

15.9

30/24

1,059/847

42(43) /36

288X840X840

29.0

9.5

15.9

Casing

1 phase, 220-240 V, 50 HzPower supply

Air flow rate (Hi/Lo) m3/min

cfm

Dimensions (HXWXD) mm

Machine weight kg

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping

Panel(Option) Model

Colour

mm

C e ilin g M o u n t e d C a s s e t t e <M u lt i- f lo w > T y p e

MODEL

Casing

1 phase, 220-240 V, 50 HzPower supply

Air flow rate (Hi/Lo) m3/min

cfm

Dimensions (HXWXD) mm

Machine weight kg

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping

Panel(Option) Model

Colour

mm

Sound level (Hi/Lo)

Dimensions(HXWXD)

Dimensions(HXWXD)

weight kg

weight kg

dB (A)

50 Hz/60 Hz 220V50 Hz 240V

dB(A)Sound level (Hi/Lo)

Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)•Sound level : Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

: The values of Hi mode Sound level represent those during cooling operation.Those during heating operation are shown in brackets for two models only.

7,800/7,500

2,000/1,900

2.5

8,500

2,200

9,900/9,600

2,500/2,400

3.2

10,900

2,800

12,600/12,300

3,200/3,100

4.0

13,600

3,400

16,000/15,400

4,000/3,900

5.0

17,100

4,300

19,800/19,100

5,000/4,800

6.3

21,500

5,400

24,900/24,200

6,300/6,100

8.0

27,300

6,900

31,700/30,700

8,000/7,700

10.0

34,100

8,600

2.3/2.2 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 14.5/14.0

49,500/47,800

12,500/12,000

16.0

54,600

13,800

Cooling capacity (*1)/(*2)

kW

Btu/h

0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 4.1/4.0RT

kcal/h

Heating capacity (*3)

kW

Btu/h

0.7 0.9 1.1 1.4 1.8 2.3 2.8 4.5RT

kcal/h

Cooling capacity(*1)/(*2)

kW

9,900/9,600

2,500/2,400

3.2

10,900

2,800

12,600/12,300

3,200/3,100

4.0

13,600

3,400

16,000/15,400

4,000/3,900

5.0

17,100

4,300

19,800/19,100

5,000/4,800

6.3

21,500

5,400

24,900/24,200

6,300/6,100

8.0

27,300

6,900

2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0

31,700/30,700

8,000/7,700

10.0

34,100

8,600

39,600/38,200

10,000/9,600

12.5

42,700

10,800

11.6/11.2 14.5/14.0

49,500/47,800

12,500/12,000

16.0

54,600

13,800

Btu/h

0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 3.3/3.2 4.1/4.0RT

kcal/h

Heating capacity(*3)

kW

Btu/h

kcal/h

0.9 1.1 1.4 1.8 2.3 2.8 3.6 4.5RT

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

C e ilin g M o u n t e d C a s s e t t e C o r n e r T y p e

Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m •Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level (FXZQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.

(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

FXKQ25MAVE

Galvanized steel plate11/9

FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE

11/9 13/10 18/15388/318 388/318 459/353 635/530

215X1,110X71031.0 6.4

12.7VP25 (External Dia, 32/Internal Dia, 25)

BYK45FJW1White (10Y9/0.5)

70X1,240X8008.5

215X1,110X71031.0 6.4

12.7

70X1,240X8008.5

215X1,110X71031.0 6.4

12.7

70X1,240X8008.5

215X1,310X71034.0 9.5

15.9

BYK71FJW1

70X1,440X8009.5

Dimensions (HXWXD) mmMachine weight kgPiping connections Liquid(Flare)mm

Gas(Flare)mmDrain piping

Panel (Option) ModelColour

mmweight kg

Dimensions(HXWXD)

38/33 38/33 40/34 42/3740/35 40/35 42/36 44/39

Casing

1 phase, 220-240 V, 50 HzPower supply

Air flow rate (Hi/Lo)

MODEL

m3/mincfm

50 Hz50 Hz

Sound level (Hi/Lo) dB (A)

50 Hz/60 Hz 220V50 Hz 240V

MODEL

50Hz

kcal/h 2,000/1,900

9/7

Btu/hRT

Heating capacity (*3)

RTBtu/h

318/247

FXZQ25M7V1B

2,500/2,4009,900/9,600

0.8/0.8

0.910,900

9/7318/247

FXZQ32M7V1B

3,200/3,10012,600/12,300

1.1/1.0

1.113,600

9.5/7.5335/265

FXZQ40M7V1B

4,000/3,900kW 2.9/2.8 3.7/3.6 4.7/4.5

16,000/15,4001.3/1.3

1.417,100

11/8388/282

600X600 Multi Flow Ceiling Mounted Cassette Type

260X575X57518

6.4 12.7

VP20 (External Dia, 26/Internal Dia, 20)BYFQ60B7W1

White (6.5Y9.5/0.5)55X700X700

2.7

6.4 12.7

55X700X7002.7

6.4 12.7

55X700X7002.7

6.4 12.7

55X700X7002.7

Dimensions (HXWXD) mmMachine weight kgPiping connections Liquid(Flare)mm

Gas(Flare)mmDrain piping

Panel (Option) ModelColour

mmweight kg

Dimensions(HXWXD)

Casing

Power supply

50HzAir flow rate (Hi/Lo)

Cooling capacity (*1)/(*2)

FXZQ50M7V1B

5,000/4,8005.8/5.6

19,800/19,1001.6/1.6

1.821,500

14/10494/353

6.4 12.7

55X700X7002.7

cfmm3/min

8,5002,800 3,400 4,300kcal/h 5,4002,200

Galvanized steel plate

0.7

kW 3.2 4.0 5.0 6.32.5

7,800/7,5000.7/0.6

1 phase, 220-240 V, 50 Hz

FXZQ20M7V1B

2.3/2.2

Sound level (Hi/Lo) dB(A) 240V 32/26 32/26 34/28 37/29 42/35

kW

9,900/9,6002,500/2,400

3.2

10,9002,800

Btu/hkcal/h

Heating capacity(*3)

kW

Btu/h

12,600/12,3003,200/3,100

4.0

13,6003,400

16,000/15,4004,000/3,900

5.0

17,1004,300

2.9/2.8 3.7/3.6 4.7/4.5 7.3/7.1

24,900/24,2000.8/0.8RT 1.1/1.0 1.3/1.3 2.1/2.0

6,300/6,100

8.0

27,3000.9RT 1.1 1.4 2.3

6,900kcal/h

Cooling capacity(*1)/(*2)

INDOOR UNIT SINDOOR UNITS

SPECIFICATIONS

3029

S lim C e ilin g M o u n t e d D u c t T y p e

Galvanized steel plate

8.0/6.4

282/226

8.0/6.4

282/226

8.0/6.4

282/226

33/29 33/29 33/29

Air flow rate (Hi/Lo) m3/min

cfm

dB(A)

Casing

1 phase, 220-240 V, 50 HzPower supply

200X700X620

23.0

6.4

12.7

200X700X620

23.0

6.4

12.7

200X700X620

23.0

6.4

12.7

Dimensions(HXWXD)

Sound level (Hi/Lo)

PaExternal static pressure

mm

Machine weight kg

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping VP20 (External Dia, 26/Internal Dia, 20)

30-10 1

32

S lim C e ilin g M o u n t e d D u c t T y p e

Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.

1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is 10 Pa for FXDQ-P models and 15 Pa for FXDQ-N(A) models.)

2 : The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB. 3 : Values are based on the following conditions: FXDQ-P: external static pressure of 10 Pa; FXDQ-N(A): external static pressure of 15 Pa.•Equivalent piping length : 7.5m •Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level (FXDQ-P, FXDQ-N(A)) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Galvanized steel plate

9.5/7.5

335/265

9.5/7.5

335/265

10.5/8.5

371/300

10.5/8.5

371/300

12.5/10.0

441/353

16.5/13.0

583/459

33/29 33/29 33/29 34/30 35/31 36/32

Air flow rate (Hi/Lo) m3/min

cfm

dB(A)

Casing

1 phase, 220-240 V, 50 HzPower supply

200X900X620

26.0

6.4

12.7

200X900X620

26.0

6.4

12.7

200X900X620

26.0

6.4

12.7

200X900X620

27.0

6.4

12.7

200X900X620

28.0

6.4

12.7

200X1,100X620

31.0

9.5

15.9

Dimensions(HXWXD)

PaExternal static pressure

mm

Machine weight kg

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping VP20 (External Dia, 26/Internal Dia, 20)

44-15 1

Sound level (Hi/Lo) 32

Cooling capacity(*1)/(*2)

kW

7,800/7,500

2,000/1,900

9,900/9,600

2,500/2,400

12,600/12,300

3,200/3,100

RT 0.7/0.6

Btu/h

kcal/h

8,500

2,200

10,900

2,800

13,600

3,400

Btu/h

0.7 0.9 1.1RT

2.5 3.2 4.0kW

kcal/h

Heating capacity(*3)

0.8/0.8 1.1/1.0

2.3/2.2 2.9/2.8 3.7/3.6

Cooling capacity(*1)/(*2)

kW

7,800/7,500

2,000/1,900

9,900/9,600

2,500/2,400

12,600/12,300

3,200/3,100

16,000/15,400

4,000/3,900

19,800/19,100

5,000/4,800

24,900/24,200

6,300/6,100

2.3/2.2

Btu/h

0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0RT

kcal/h

8,500

2,200

10,900

2,800

13,600

3,400

17,100

4,300

21,500

5,400

27,300

6,900

Btu/h

0.7 0.9 1.1 1.4 1.8 2.3RT

2.5 3.2 4.0 5.0 6.3 8.0kW

kcal/h

Heating capacity(*3)

2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

C e ilin g M o u n t e d B u ilt - in T y p e

Galvanized steel plate

FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE

9/6.5 9/6.5 9.5/7 11.5/9 15/11 21/15.5 27/21.5 28/22 38/28318/230 318/230 335/247 406/318 530/388 741/547 953/759 988/777 1,341/988

Casing

1 phase, 220-240 V, 50 HzPower supply

300X550X80030.0 6.4

12.7VP25 (External Dia, 32/Internal Dia, 25)

300X550X80030.0 6.4

12.7

38/32

300X550X80030.0 6.4

12.7

38/32

300X700X80030.0 6.4

12.7

300X700X80031.0 6.4

12.7

300X1,000X80041.0 9.5

15.9

43/37

300X1,400X80051.0 9.5

15.9

43/37

300X1,400X80051.0 9.5

15.9

46/41

300X1,400X80052.0 9.5

15.9

Dimensions(HXWXD) mm

External static pressure Pa

Machine weight kgPiping connections Liquid(Flare)mm

Gas(Flare)mm

White (10Y9/0.5)55X650X500

3.0

55X650X5003.0

55X650X5003.0

55X800X5003.5

55X800X5003.5

55X1,100X5004.5

55X1,500X5006.5

55X1,500X5006.5

55X1,500X5006.5

Panel(Option)Colour

mm

BYBS32DJW1 BYBS32DJW1 BYBS32DJW1 BYBS45DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1

41/36 42/3537/32 37/3240/34 40/34 45/39 45/39 48/4343/38 44/3739/34 39/34

Sound level (Hi/Lo)

Model

Dimensions(HXWXD)

Drain piping

weight kg

MODEL

Air flow rate (Hi/Lo)

220V240V

50 Hz

88-39-20 88-39-20 64-39-15 88-49-20 88-59-29 88-49-20 113-82 107-75 78-391 1 1 1 1 1 2 22

m3/mincfm

50 Hz50 Hz50 Hz

dB (A)

Cooling capacity(*1)/(*2) 7,800/7,500

2,000/1,900

2.5

8,5002,200

9,900/9,6002,500/2,400

3.2

10,9002,800

12,600/12,3003,200/3,100

4.0

13,6003,400

16,000/15,4004,000/3,900

5.0

17,1004,300

19,800/19,1005,000/4,800

6.3

21,5005,400

24,900/24,2006,300/6,100

8.0

27,3006,900

31,700/30,7008,000/7,700

10.0

34,1008,600

39,600/38,20010,000/9,600

12.5

42,70010,800

2.3/2.2

49,500/47,80012,500/12,000

16.0

54,60013,800

Btu/h0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 3.3/3.2 4.1/4.0RT

kcal/h

kW

Btu/hkcal/h

0.7 0.9 1.1 1.4 1.8 2.3 2.8 3.6 4.5RT2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 11.6/11.2 14.5/14.0

Heating capacity(*3)

kW

MODEL FXMQ40MAVE FXMQ50MAVE FXMQ63MAVE FXMQ80MAVE FXMQ100MAVE FXMQ125MAVE

Galvanized steel plate

14/11.5

494/406

39/35

390X720X690

44.0

6.4

12.7

VP25 (External Dia, 32/Internal Dia, 25)

14/11.5

494/406

39/35

390X720X690

44.0

6.4

12.7

14/11.5

494/406

39/35

390X720X690

44.0

9.5

15.9

19.5/16

688/565

42/38

390X720X690

45.0

9.5

15.9

29/23

1,024/812

43/39

390X1,110X690

63.0

9.5

15.9

36/29

1,271/1,024

45/42

390X1,110X690

65.0

9.5

15.9

41/37 41/37 41/37 44/40 45/41 47/44

m3/min

cfm

Dimensions (HXWXD) mm

Machine weight kg

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping

C e ilin g M o u n t e d D u c t T y p e

Casing

1 phase, 220-240 V, 50 HzPower supply

Air flow rate (Hi/Lo)

Sound level (Hi/Lo)Pa (50Hz) 157-118 157-118 157-118 157-108 157-98 191-152 External static pressure 2 2 2 2 2 2

dB (A)

50 Hz/60 Hz 220V

50 Hz 240V

Cooling capacity(*1)/(*2)

kW

16,000/15,400

4,000/3,900

5.0

17,100

4,300

19,800/19,100

5,000/4,800

6.3

21,500

5,400

24,900/24,200

6,300/6,100

8.0

27,300

6,900

31,700/30,700

8,000/7,700

10.0

34,100

8,600

49,500/47,800

12,500/12,000

16.0

54,600

13,800

4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 14.5/14.0

Btu/h

1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 4.1/4.0RT

kcal/h

Heating capacity(*3)

kW

Btu/h

1.4 1.8 2.3 2.8 4.5

39,600/38,200

110,000/9,600

12.5

42,700

10,800

11.6/11.2

3.3/3.2

3.6RT

kcal/h

Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB. 1 : External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard-Low static pressure". 2 : External static pressure is changeable to change over the connectors inside electrical box, this pressure means "High static pressure-Standard".•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)•Sound level : (FXSQ-M, FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

without drain-up pump

with drain-up pump

FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVETMODEL

FXDQ20NAVE FXDQ25NAVE FXDQ32NAVE FXDQ40NAVE FXDQ50NAVE FXDQ63NAVE

FXDQ20PVET FXDQ25PVET FXDQ32PVETMODEL without

drain-up pump

FXDQ20PVE FXDQ25PVE FXDQ32PVEwith drain-up pump

INDOOR UNITS INDOOR UNIT S

SPECIFICATIONS

3231

MODEL FXHQ32MAVE

White (10Y9/0.5)

FXHQ63MAVE FXHQ100MAVE

C e ilin g S u s p e n d e d T y p e

cfm

12/10 17.5/14 25/19.5

Dimensions(HXWXD) mm

Machine weight kg

Piping connections Liquid(Flare)mmGas(Flare)mm

Drain piping

36/31 39/34 45/37

195X960X680

24.0

6.4 12.7

VP20 (External Dia, 26/Internal Dia, 20)

195X1,160X680

28.0

9.5 15.9

195X1,400X680

33.0

9.5 15.9

Casing

1 phase, 220-240 V, 50 HzPower supply

m3/minAir flow rate (Hi/Lo)

424/353 883/688618/494

dB(A)Sound level (Hi/Lo)

Note : Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level : (FXHQ-MA, FXAQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

W a ll M o u n t e d T y p e

MODEL FXAQ25MAVE

White (3.0Y8.5/0.5)

36/29

290X795X230

11.0

Casing

1 phase, 220-240 V, 50 HzPower supply

37/29

290X795X230

11.0

FXAQ40MAVE

39/34

290X1,050X230

14.0

282/177 318/194 424/318

Dimensions (HXWXD) mm

Machine weight kg

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping

m3/minAir flow rate (Hi/Lo)

cfm

8/5 9/5.5

FXAQ32MAVEFXAQ20MAVE

35/29

290X795X230

11.0

265/159

7.5/4.5 12/9

VP13 (External Dia, 18/Internal Dia, 13)

6.4 6.4 6.4 6.4

12.7 12.7 12.7 12.7

42/36

290X1,050X230

14.0

FXAQ63MAVE

15/12 19/14

530/424

46/39

290X1,050X230

14.0

671/494

FXAQ50MAVE

6.4 9.5

12.7 15.9

dB(A)Sound level (Hi/Lo)

Cooling capacity(*1)/(*2)

kW

12,600/12,300

3,200/3,100

4.0

13,600

3,400

24,900/24,200

6,300/6,100

8.0

27,300

6,900

3.7/3.6 7.3/7.1 11.6/11.2

39,600/38,200

10,000/9,600

12.5

42,700

10,800

Btu/h

1.1/1.0 2.1/2.0 3.3/3.2RT

kcal/h

Heating capacity(*3)

kW

Btu/h

1.1 2.3 3.6RT

kcal/h

Cooling capacity(*1)/(*2)

3.2

Btu/h

kcal/h

Heating capacity(*3)

kW

Btu/h

kcal/h

5.0

9,900/9,600 16,000/15,400

2,500/2,400 4,000/3,900

10,900 17,100

2,800 4,300

13,600

3,400

12,600/12,300

3,200/3,100

4.0

2.9/2.8

2.5

7,800/7,500

2,000/1,900

8,500

2,200

2.3/2.2 4.7/4.53.7/3.6kW

24,900/24,200

6,300/6,100

27,300

6,900

8.0

21,500

RT 0.9 1.41.10.7 2.31.8

5,400

6.3

5,000/4,800

19,800/19,100

RT 0.8/0.8 1.3/1.31.1/1.00.7/0.6 2.1/2.01.6/1.6

7.3/7.15.8/5.6

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

Note : Specifications are based on the following conditions ;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)•Sound level : (FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

F lo o r S t a n d in g T y p e / C o n c e a le d F lo o r S t a n d in g T y p e

MODELFXLQ20MAVE

FXLQ:Ivory white (5Y7.5/1) / FXNQ:Galvanized steel plateCasing

Power supply

Air flow rate (Hi/Lo) m3/min

cfm

7/6

247/212

600X1,000X222

25.0

6.4

12.7

21O.D.

Dimensions (HXWXD)

Machine weight

Piping connections Liquid(Flare)mm

Gas(Flare)mm

Drain piping

FXLQ25MAVE

7/6

247/212

600X1,000X222

25.0

6.4

12.7

282/212 388/300 494/388 565/424

FXLQ32MAVE

8/6

600X1,140X222

30.0

6.4

12.7

FXLQ40MAVE

11/8.5

600X1,140X222

30.0

6.4

12.7

FXLQ50MAVE

14/11

600X1,420X222

36.0

6.4

12.7

FXLQ63MAVE

FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE

16/12

600X1,420X222

610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220

36.0

19.0 19.0 23.0 23.0 27.0 27.0

9.5

15.9

mmFXLQ

FXNQ

kgFXLQ

FXNQ

35/32 35/32 35/32 38/33 39/34 40/35

37/34 37/34 37/34 40/35 41/36 42/37

FXLQ

FXNQ

1 phase, 220-240 V, 50 Hz

Sound level (Hi/Lo) dB (A)

50 Hz/60 Hz 220V

50 Hz 240V

Cooling capacity(*1)/(*2) 7,800/7,500

2,000/1,900

8,500

2,200

Btu/h

kcal/h

Heating capacity(*3)

kW

Btu/h

kcal/h

2.3/2.2

9,900/9,600

2,500/2,400

10,900

2,800

2.9/2.8

12,600/12,300

3,200/3,100

13,600

3,400

3.7/3.6

16,000/15,400

4,000/3,900

17,100

4,300

4.7/4.5

19,800/19,100

5,000/4,800

6.3

21,500

5,400

5.8/5.6

24,900/24,200

0.7/0.6RT 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0

6,300/6,100

8.0

27,300

0.7RT 0.9 1.1 1.4 1.8 2.3

6,900

7.3/7.1kW

2.5 3.2 4.0 5.0

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

INDOOR UNITS OUT DOOR UNIT S

SPECIFICATIONS

3433

C e ilin g s u s p e n d e d c a s s e t t e t y p e

Power supply 1 phase, 220-240 V, 50 Hz

Indoorunit m3/minAir flow rate (H/L)

Sound level (230 V)

Casing

dBAmmDimensions (HXWXD)kgMachine weight

40/35

Piping connectionsLiquidGas

Drain piping VP 20 (External Dia. 26/Internal Dia. 20)

25

White(10Y9/0.5)19/14

671/494cfm

165X895X895

9.5 (Flare)15.9 (Flare)

43/38

31

29/211,024/741

230X895X89544/39

31

32/231,130/812

230X895X895

mm

ModelIndoor unit

Connection unit BEVQ71MAVEFXUQ71MAV1

BEVQ100MAVEFXUQ100MAV1

BEVQ125MAVEFXUQ125MAV1

Note : Specifications are based on the following conditions ;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.•Equivalent piping length : 7.5m•Level difference : 0m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)•Sound level : (FXUQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m below the unit center. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Connection unit series indoor units* A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data for details.* If indoor units from the Connection unit series are connected within a single refrigerant system to indoor units from any other series,

cooling/heating switchover will not be possible using the remote controller of the Connection unit series indoor units. However, if the remote controller of an indoor unit from the other series is set as a master remote controller, cooling/heating switchover will be possible.

* If all indoor units are from the Connection unit series, an outdoor unit Cool/Heat selector will be needed to enable cooling/heating switchover. * Group control between Connection Unit series equipment within one system is possible. However, group control with the other VRV II indoor

units is not possible.

Heat Pump TypeModel

Power supply

Heating capacity (*5)

Capacity control %

Motor output kWm3/min

Casing colorCompressor

Air flow ratemmDimensions (H x W x D)

1 phase, 230/240 V, 50 Hz

24 to 100

Hermetically sealed scroll type

1,345 x 900 x 320kgMachine weight 125

Liquid pipe mmPiping connections ø9.5 (Flare)Gas pipe mm ø19.1 (Brazing)

dB (A)Sound level (C/H) (*6)

kgRefrigerant chargeRefrigerant oil

53/55Refrigerant R410A

61,400

RXYMQ6PV4A

15,500

kW

18.0

Cooling capacity (*1)/(*2)

Cooling (*1)/(*2)Cooling (*3)/(*4)Heating (*5)Cooling (*1)/(*2)Cooling (*3)/(*4)Heating (*5)

Kcal / h

RT

Cooling capacity (*3)/(*4)

54,100/40,0004.5/3.3

4.4/3.3

5.1

4.67/4.384.59

3.29/2.673.32/2.62

3.92

4.82/4.39

52,900/39,100

Btu / h13,600/10,100

13,300/9,850

kW

Kcal / h

RTBtu / h

kW

Kcal / h

RTBtu / h

kW

15.8/11.7

15.5/11.5

4.0

1063.5

Ivory white (5Y7.5/1)

Refer to the name plate of the compressor.

Power consumption

COP

Note : 1. Specifications are based on the following conditions;•Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 46°CDB. (*3) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35°CDB. (*4) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 46°CDB.•Heating : (*5) Indoor temp. of 20°CDB, and outdoor temp. 7°CDB/6°CWB.•Sound level : (*6) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.• Refrigerant charge is required. (Chargeless piping length 0 m) Apply C1220T-1/2H for over ø19.1. Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

Conversion rates

kcal/h = kW x 860Btu/h = kW x 3412RT = kW x 0.284cfm = m3/min x 35.3

kWKcal/h 7,100/6,900Btu/h 28,300/27,300

kWKcal/h

Heating capacity (Max.)(*3)

9.07,700

Btu/h 30,700

10,000/9,60039,600/38,200

12.510,80042,700

8.3/8.0 11.6/11.2 14.5/14.012,500/12,00049,500/47,800

RT 2.4/2.3 3.3/3.2 4.1/4.0

14.012,00047,800

RT 2.6 3.6 4.0

Cooling capacity(*1)/(*2)

OPTION LIST

INDOOR UNIT SINDOOR UNITS

3635

FXFQ25M FXFQ32M FXFQ40M FXFQ50M FXFQ63M FXFQ80M FXFQ100M FXFQ125M1

4

BYCP125D-W1

KAFP556D80 KAFP556D160KAFP557D80 KAFP557D160KAFP552H80 KAFP552H160KAFP553H80 KAFP553H160

KDT-55D160

KDP55D160

Filter related

5 Fresh air intake kit

Decoration Panel2 KDBH55D160WSealing Member of air discharge outlet3 KDBP55H160WAPanel spacer

High efficiency filter unit 65%High efficiency filter unit 90%Replacement high efficiency filter 65%Replacement high efficiency filter 90%Filter chamberLong life replacement filter Non-woven type

Chamber type Without T shape and fanWith T shape without fan

KDDFP55D160

Ultra long-life filterReplacement ultra long-life filter

Direct installation type

KAFJ551C160KAFP55D160KAFJ55K160HKDDP55D160

KDDP55D160KKDDJ55X160

No.

C e ilin g m o u n t e d s u p e r c a s s e t t e t y p e ( M u lt i f lo w t y p e )Type

Item

6 KDP55D80Branch duct chamber7 KKSJ55K160Chamber connection kit8 KDT-55D80Insulation kit for high humidity

C e ilin g m o u n t e d c a s s e t t e t y p e ( D o u b le f lo w t y p e )

No.

1

2

Decoration PanelHigh efficiency filter 65% 1 High efficiency filter 90% 1

Long life replacement filter

Filter related bottom suction

FXCQ20MFXCQ25MFXCQ32M

FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M

KAFJ532G36 KAFJ532G56 KAFJ532G160KAFJ532G80KAFJ533G36 KAFJ533G56 KAFJ533G160KAFJ533G80KDDFJ53G36Filter chamber KDDFJ53G56 KDDFJ53G160KDDFJ53G80KAFJ531G36 KAFJ531G56 KAFJ531G160KAFJ531G80

TypeItem

BYBC32G-W1 BYBC50G-W1 BYBC125G-W1BYBC63G-W1

Note: 1 Filter chamber is required if installing high efficiency filter.

C e ilin g m o u n t e d c a s s e t t e c o r n e r t y p eNo. Type

Item FXKQ25MA,FXKQ32MA,FXKQ40MA FXKQ63MA

1

2

BYK45FJW1 BYK71FJW1KPBJ52F56W KPBJ52F80WKAFJ521F56 KAFJ521F80

K-HV7AW K-HV9AWKDBJ52F56W KDBJ52F80WKFDJ52FA56 KFDJ52FA80

Panel related

Air inlet and air discharge outlet related

Decoration PanelPanel SpacerLong life replacement filterAir discharge grilleAir discharge blind panelFlexible duct (with shutter)

Note: 1 For without drain-up pump type only.

Note: 1 For without drain-up pump type only.

No. FXDQ20N, FXDQ25N, FXDQ32N, FXDQ40N, FXDQ50N FXDQ63N

1 KDT25N50 KDT25N63Insulation kit for high humidity

S lim c e ilin g m o u n t e d d u c t t y p e ( 9 0 0 / 1, 10 0 m m w id t h t y p e 1)Type

Item

No. FXDQ20P,FXDQ25P,FXDQ32P

1 KDT25N32Insulation kit for high humidity

S lim c e ilin g m o u n t e d d u c t t y p e ( 7 0 0 m m w id t h t y p e 1)Type

Item

No.

C e ilin g m o u n t e d d u c t t y p eFXMQ40MA FXMQ50MA FXMQ63MA FXMQ80MA FXMQ100MA FXMQ125MA

1 Drain pump kit

3 Filter chamber

KDU-30L125VE

2 High efficiency filterKAFP372A8065%

90%KAFP372A160

KAFP373A80 KAFP373A160KDDFP37A80 KDDFP37A160

4 Long life replacement filter KAFP371A80 KAFP371A160

TypeItem

C e ilin g s u s p e n d e d t y p eFXHQ32MA

1 Drain pump kit2 Replacement long-life filter (Resin net)

KDU50M60VEKAFJ501D56

3 L-type piping kit (for upward direction) KHFP5M35

FXHQ63MAKDU50M125VE

KAFJ501D80KHFP5M63

FXHQ100MA

KAFJ501D112

No. TypeItem

W a ll m o u n t e d t y p eFXAQ25MAFXAQ20MA

1 Drain pump kit K-KDU572CVE

FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MANo. TypeItem

F lo o r s t a n d in g t y p eFXLQ20MA

1 Long life replacement filter

FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MAKAFJ361K28 KAFJ361K45 KAFJ361K71

No. TypeItem

C o n c e a le d f lo o r s t a n d in g t y p eFXNQ20MA

1 Long life replacement filter

FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MAKAFJ361K28 KAFJ361K45 KAFJ361K71

No. TypeItem

C e ilin g s u s p e n d e d c a s s e t t e t y p eNo.

Replacement long-life filter12345

Sealing member of air discharge outlet (*1)

Decoration panel for air dischargeVertical flap kitL-shape piping kit

FXUQ71MAV1

KDBHJ49F80KDBTJ49F80KDGJ49F80

KHFP49M140

KDBHJ49F140KDBTJ49F140KDGJ49F140

FXUQ100MAV1 FXUQ125MAV1KAFJ495F140

(*1): This option is necessary for setting up 2-way (opposing directional) air flow when the air conditioner is installed.Note:

TypeItem

C e ilin g m o u n t e d b u ilt - in t y p eFXSQ20MFXSQ25MFXSQ32M

1 BYBS32DJW1KTBJ25K36W

FXSQ40MFXSQ50M

BYBS45DJW1KTBJ25K56W

FXSQ63M

BYBS71DJW1KTBJ25K80W

FXSQ80MFXSQ100M

BYBS125DJW1KTBJ25K160W

FXSQ125M

Panel related Decoration PanelAccess panel

3

KAFJ252L36KAFJ253L36

KAFJ252L56KAFJ253L56

KAFJ252L80KAFJ253L80

KAFJ252L160KAFJ253L160

Filter related

2 High efficiency filter 65% 2 High efficiency filter 90%

KAFJ251K36 KAFJ251K56 KAFJ251K80 KAFJ251K160KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160DKAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160B

Long life replacement filter

KSA-25K36KBBJ25K36

KSA-25K56KBBJ25K56

KSA-25K80KBBJ25K80

KSA-25K160KBBJ25K160

Air suction canvasScreening door

KDJ2507K36 KDJ2507K56 KDJ2507K80 KDJ2507K160Air suction flangeKDAJ25K36 KDAJ25K56 KDAJ25K71 KDAJ25K140Air discharge adaptor

KNM25K32V1 KNM25K50V1 KNM25K63V1 KNM25K125V1

2 KEA25K32VE0.75

KEA25K50VE1.2

KEA25K63VE1.4

KEA25K100VE2.1

KEA25K125VE2.8

1 Auxiliary electric heater

4Air inlet and air discharge outlet related

5 Natural evaporating pan type humidifier 1 3

ModelCapacity

240V/220VkW

Filter chamber

For bottom suctionFor rear suction

No.Type

Item

Note: 1 One adaptor for wiring (KRP1B61) per indoor unit is required if installing an electric heater or a natural evaporating pan type humidifier. An electric heater cannot be used for VRV system cooling only.

2 If installing a high filter in the ceiling mounted built-in type, an assembly chamber for either bottom or rear suction is required. 3 For 50 Hz models only. A special order is required for 60 Hz models.

6 0 0 x 6 0 0 m u lt i f lo w c e ilin g m o u n t e d c a s s e t t e t y p eNo. FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M

1 Decoration panel2 Sealing member of air discharge outlet3 Panel spacer4 Replacement long-life filter

BYFQ60B7W1KDBHQ44B60KDBQ44B60KAFQ441B60

5 Fresh air intake kit Direct installation type KDDQ44X60

TypeItem

C ONT R OL S Y S T E MS

C ONTR OL S Y S TE MS

OUTDOOR UNITS

OPTION LIST

3837

O p e r a t io n c o n t r o l s y s t e m o p t io n a l a c c e s s o r ie s

Note: 1. Installation box is necessary for each adaptor marked .2. Up to 2 adaptors can be fixed for each installation box.3. Only one installation box can be installed for each indoor unit.

No.

34

FXCQ-M FXFQ-M FXKQ-MA FXSQ-MFXDQ-PFXDQ-N(A) FXAQ-MA FXLQ-MA

FXNQ-MA

Remote controllerWireless H/PWired

Simplified remote controller (Exposed type)

5 Adaptor for wiring6-1 Wiring adaptor for electrical appendices (1)6-2 Wiring adaptor for electrical appendices (2)

Remote controller for hotel use (Concealed type)

7 Remote sensor

9 External control adaptor for outdoor unit (Must be installed on indoor units)

TypeItem

BRC7C62 BRC7E61W BRC4C61 BRC4C62 BRC7E618

KRP1B59

DTA104A62

—Wired remote controller with weekly schedule timer

— KRCS01-1

KRP1B61 KRP2A62 KRP2A61 KRP4A53 KRP4A51

——

BRC4C62BRC4C62

KRP2A61KRP1B61BRC3A61BRC2C51

FXMQ-MA

BRC4C62

DTA104A61

8 Installation box for adaptor PCB Note 2,3KRP1D98 —Note 3

KRP1C93Note 2,3KRP4A93

Note 2,3KRP1B96

BRC2C51BRC3A61

KRP1B61KRP2A61KRP4A51

KRP2A62 KRP2A61 KRP4A52 KRP4A51 KRP4A51

—— Note 4,6KRP1B101

DTA104A61

FXUQ-MA

BRC7C528W

KRP2A62———

KRP1B97

KRP4A53

—DTA104A53DTA104A61 DTA104A61 DTA104A62DTA104A61

BRC1D61

FXZQ-M

BRC7E61W

KRP1B57

Note 4,6KRP1B101

FXHQ-MA

BRC7E63W

—KRP1B3KRP1B56KRP2A53KRP4A54

KRP1B61KRP2A61KRP4A51

2

1

KRCS01-1Note 5KRP4A91

4. Up to 2 installation boxes can be installed for each indoor unit.5. Installation box is necessary for second adaptor.6. Installation box is necessary for each adaptor.

BRC1C62

Wire fixture for preventing overturning

H e a t p u m p t y p eNo.

1 Cool/Heat Selector1-1 Fixing Box

2 REFNET Header

3 REFNET Joint

KJB111AKHRP26M22H (Max. 4 branch)KHRP26M33H (Max. 8 branch)

KHRP26M22T

KRC19-26A

RXYMQ6PV4A

5 Fixture for preventing overturning KPT-60B1606 K-KYZP15C

4 KKPJ5F180Central drain plug

S y s t e m c o n f ig u r a t io n

•Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one system.

Note 2,DCS302CA61Central remote controller1

•Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.

Note 2DST301BA61Schedule timer3

•Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.

Note 2DCS301BA61Unified ON/OFF controller2

KJB212AElectrical box with earth terminal (2 blocks)2-1

KEK26-1Noise filter (for electromagnetic interface use only)2-1

KJB311AElectrical box with earth terminal (3 blocks)1-1

DTA102A52Interface adaptor for SkyAir-series4

DTA107A555

DTA103A51Wiring adaptor for other air-conditioner6

No. Part name Model No. Function

•Up to 1024 units can be centrally controlled in 64 different groups.•Wiring restrictions (max. lengh : 1,000m, total wiring lengh : 2,000m, max. number of branches : 16) apply to each adaptor.

DTA109A51D -NETExpander Adaptor

7

•Fixing plate for DTA109A51KRP4A92Mounting plate7-1

•Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.

* To use any of the above optional c ontrollers , an appropriate adaptor must be installed on the produc t unit to be c ontrolled.

For UAT(Y)-K(A),FD-K

For SkyAir, FD(Y)M-FA, FDY-KAFDYB-KA, FDY-KA, FVY(P)J-A

Central control adaptor kit

B u ild in g m a n a g e m e n t s y s t e m

•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through LONWORKS® communication.DMS504B514

3

•Expansion kit, installed on DMS502A51, to provide 3 more DIII-NET communication ports. Not usable independently.DAM411A13-1

•Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to 4 units.DPF201A515

•Enables temperature measurement output for 4 groups; 0-5VDC.DPF201A526

•Enables temperature setting input for 16 groups; 0-5VDC.DPF201A537

No. Part name Model No. Function

*2 Interface for use in LONWORKS®

•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through BACnet® communication.DMS502A51*1 Interface for use in BACnet®

Optional DIII board

Cont

act/a

nalog

signa

l

Parallel interfaceBasic unitTemperaturemeasurement unitsTemperaturesetting units

•Air conditioner management system that can be controlled by personal computers.DAM602B51

KJB411ADAM602B52

256 unitsDAM602B51x2512 unitsDAM602B51x3768 unitsDAM602B51x41024 unitsintelligent Manager III

128 units

2Number of units to be connected

HardwareBasic

•Expansion kit, installed on DMS502A51, to provide 16 more wattmeter pulse input points. Not usable independently.

•External temperature sensor for intelligent Manager.

DAM412A1

DAM101A51

Optional Di board

Optional DIII Ai unit2-4

•8 pairs based on a pair of On/Off input and abnormality input.DEC101A51Di unit2-5

3-2

1-11-4

1

Electrical box with earth terminal (4 blocks)

DCS601A521-1 •Additional 64 groups (10 outdoor units) is possible.

DCS004A511-3 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.•Wall embedded switch box.

DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.

Com

mun

icat

ion

line

Note : *1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

*2. LONWORKS® is a registered trade mark of Echelon Corporation. *3. Installation box for adaptor must be procured on site.

DCS002C511-2intelligent Touch Controller

DIII-NET plus adaptor

Web

intelligent Touch Controller

P. P. D.HardwareHardware

Software

Basic

Option •P. P. D.: Power Proportional Distribution function

•4 pairs based on a pair of On/Off input and abnormality input.DEC102A51Dio unit2-6

2-1

2-2

2-3

•Power Proportional Distribution functionDAM002A51

Option Software

2-1

•Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.DAM004A512-2

•ECO (Energy saving functions.)DAM003A51

P.P.D.

Web

Eco2-3

•Interface between the central monitoring board and central control units.DCS302A528 Unification adaptor forcomputerized control

Notes: 1. Installation box for adaptor must be procured on site. 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary.