pdms model color codes _cp-00 extract
DESCRIPTION
pdms colour codeTRANSCRIPT
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
51
SF / General / 002 Rev.0 sheet 1 of 1
4.7 Platform / Area nomenclature Guidelines:
a. New platform or area which is similar to existing facilities should carry the same
existing facility name by adding sequence number such as CSP, CSP-1 or NRP,
NRP-1.
b. New facilities with new operation concept should carry an abbreviated name
agreed between project team and ESVT i.e. SARB, UL, GIF, GPF and TA …etc
c. Area number for all new facilities will be assigned by Engineering Record officer.
5. AVEVA PDMS
PDMS project folders, files, databases including any foreign project data, templates, reports
and all relevant document/ information associated with the project shall be submitted to
ADMA-OPCO.
The PDMS environment shall be set-up in accordance with this document.
5.1 Project Set-up
PDMS System administration of the Project set up shall be documented in detail and
submitted for ADMA-OPCO approval prior to modeling.
This shall include all team names, user names & passwords, administration
passwords, MDB/ database names/ numbers with description, design hierarchy &
naming convention with description.
All UDA’s required for the project shall be documented and submitted for ADMA-
OPCO approval.
5.2 Model Content
The individual areas of the detailed 3D model shall be the responsibility of the
respective engineering/design disciplines. Each discipline shall define and document
the items that are to be modeled in PDMS in their respective areas.
Any exclusion to the model content is subject to written approval by ADMA-OPCO.
The following shall be modelled as a minimum.
• Structure: Primary and secondary and tertiary steelwork (Columns, Beams, Bracings…)
Joints complete with details.
Floor, grating, plating and walls including penetration & sleeves and
fireproofing.
Jacket appurtenances, boat landing, riser fender, J-tube, Caissons, anodes…
Stairs, ladders, access/ maintenance platforms, walkways, handrails and kick
plates.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
52
SF / General / 002 Rev.0 sheet 1 of 1
Structural supports and guides for equipment, piping, trays, ducts….
Equipment handling fixtures like crane, monorail, lifting hoist, pulley/ chain
block…
Installation aids i.e. lifting pad eyes/ trunnions….
• Equipment:
Process and Utility equipment (to shape) shown on P&ID/ Equipment list
including within package/ skid complete with appurtenances such as nozzles,
hand hole, manway, covers, and davits…
Major proprietary and ancillary items.
Saddles, supports and any fixing mechanism.
Door/ cover swing and access volume.
Installation/ handling volumes and aids i.e. lifting pad eyes/ lugs, slings...
Jacket/ insulation volume complete with aids like rings, cleats...
Reinforcement items, platform/ support cleats.
Reserved volume for withdrawal/ removal, operation/ maintenance/ access,
dropout zone, handling space etc…
Future equipment (Modelled in separate Zone).
• Piping:
All process, auxiliary and utility piping (including piping covered under
legend drawing), piping within package/ skid (including vendor scope).
Vessel trim, bridle complete with instrument.
Inline items, fittings, accessories, special items, valves & instruments
complete with manual/ gear/ actuated operators and space required for
operation.
Insulation, jacket as per specification.
Vent, drain, instrument tapping/ connection, utility station.
Pipe supports.
Reserved volume for operation/ maintenance, removal and handling/
retrieving tools.
Conductors/ risers.
Bolt removal envelop to ensure no captive bolts and space for torqueing/
tensioning equipment.
All future piping (Modelled in separate Zone).
• Electrical and Instrumentation:
All equipment e.g. generator, transformer, switchgear, MCC, LCS…
Accessories for valve actuators.
Cable trays/ ladders with support, J-Tube.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
53
SF / General / 002 Rev.0 sheet 1 of 1
Electrical/ instrument panels & cabinets complete with door swing,
maintenance/ access volume, stanchion….
Junction box, Marshalling box, Distribution box, termination box…
Lighting fixtures, power sockets, switches, Nav-aid…
Field instruments with support/ stanchion and shade.
Radio mast/ tower.
• HSE:
All equipment i.e. Firefighting, safety, Lifeboat/ raft with davit, life buoy…
Deluge/ Foam skid (with piping), deluge and sprinkler system with coverage
envelop.
Fire mains, fire hydrants/ monitors, hose reel..
Primary & secondary escape route/ volume with indicators/ signage and
muster area.
F&G detection, PA system, Telecom, CCTV, beacon, sounder…
Maintenance/ operation/ access volume, lay-down & material handling
volume, dropout zone, crane & lifting hoist movement area/ volume.
Hatches, access openings with protective barriers.
Safety shower, eyewash.
• HVAC:
All equipment e.g. Chiller, Air handling unit, Compressor unit, Window
AC…
All piping (i.e. chilled water, refrigeration) with inline items, accessories,
instruments, valves, actuators…
Ductwork with accessories, dampers, actuators, grilles..
Support for equipment, ductwork, piping.
Duct and pipe insulation.
Reserved space/ volume for maintenance, handling..
• Architectural and Civil:
Foundations for structure & support, sleepers, piles, etc ..
Building detailing doors and windows.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
54
SF / General / 002 Rev.0 sheet 1 of 1
5.3 Database and Naming
The project shall be split into Multiple Databases (MDB’s) based on Area for Das
Island and Platform for Offshore. Area number shall be MDB Name. e.g.:
Each discipline shall be allocated databases based on the PDMS activity.
Databases numbers shall be obtained from ADMA-OPCO. Database file number shall
be same as database number. Sequential numbers shall be used without skipping except
for temporary DB’s (which are to be deleted upon as built) which shall use end of the
range, to maintain continuity of the numbers.
Naming format of all administrative elements and databases with description to have
a suitable convention.
Details of the naming convention and coding explanations used to be submitted to
ADMA-OPCO for approval.
An example database name and description is given below for information only:
DB Name: 201+DES+PIPE+01 e.g. 201DESPIPE01
= Serial Number (Incremental for same DB name)
= Discipline Code
= Database Type Code
= Area number / MDB name
DB Description: Piping Design DB for ZWSC - Riser Platform
Database Type Code
Data Base Type Code Data Base Type Code
Design (DESI) DES Dictionary (DICT) DIC
Draft (PADD) DRA ISODRAFT (ISOD) ISO
Catalogue (CATA) CAT Schematic (SCHE) SCH
Properties (PROP) PRO Engineering (ENGI) ENG
MDB Name MDB Description
08.3 Das - Zakum Separator Area
201 ZWSC - Riser Platform
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
55
SF / General / 002 Rev.0 sheet 1 of 1
Discipline Code
Discipline Description Codes
Structure (offshore topside)* Structural Discipline STRU
Structure (offshore Jacket)* Structural Discipline JCKT
Civil Civil CIVL
Architecture Architecture ARCH
Support Support SUPP
Equipment Mechanical Discipline EQUI
Piping Mechanical Discipline PIPE
Instrumentation Instrumentation Discipline INST
Electrical Electrical Discipline ELEC
HVAC HVAC HVAC
Safety HSE discipline HSE
General General Purpose GEN
Catalogue PDMS Administration Discipline CATA
* Discipline code STRU & JCKT for offshore and STRU for onshore shall be used.
5.4 Catalogues and Specifications Naming
All items shall be named in accordance with the catalogues component naming convention as
supplied with PDMS. There shall be project specific catalogue databases for components
and/or data items that are created for the project.
Catalogues and Specifications (e.g. Piping, Structural, etc.) shall be developed to ADMA-
OPCO standards and any deviations are to be noted and submitted to ADMA-OPCO for
approval.
5.5 PDMS Design Hierarchy
PDMS Design Sites and Zones shall be named (as illustrated below) in a manner such that
they can be easily identified and organised against plant area and discipline. Sites and Zones
shall have their description and purpose attributes set to reflect their intended use. Naming
format with description shall be submitted for ADMA-OPCO approval.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
56
SF / General / 002 Rev.0 sheet 1 of 1
• Site Naming
Sites shall be created and named in line with the respective DB for all disciplines with
the Datum Point and Purpose set for it. Site naming shall be in the following format:
Site Name: =XXXPIPE
Where PIPE =Discipline Code
XXX =Area number/ MDB name
e.g.: Site name for Piping in area 201 (ZWSC Riser Platform) shall be /201PIPE.
• Zone Naming
Zone naming will vary as per the discipline need. All zones created shall be named
appropriately and to follow the explained convention. For offshore Zone naming is
generally deck based and for Onshore it is based on type.
• Pipe Zone Naming
All pipes shall be modelled in proper zone which is based on process service code. The
zone name shall be as follows:
/201PIPE/NNNN e.g. /201PIPE/CO
Process Service Code
Site Name (Area Number/ MDB name +
Discipline Code) e.g.: Pipe having service code “CO” shall be created in zone /201PIPE/CO.
Detailed hierarchy as follows:
Site > /201PIPE
Zone> /201PIPE/CO
Zone> /201PIPE/LO
Zone> /201PIPE/PW > /CO-16”-AC0NA0-1234AD
> /CO-18”-AC0NA0-2345AD
> /CO-20”-AC0NA0-3456AD
• Equipment Zone Naming
All mechanical equipment (with proper origin) shall be modelled under equipment zone.
For offshore zones shall be deck based. Where equipment crosses into multiple decks it
shall be modelled under deck on which it rests. The zone naming shall be as follows:
For Onshore
08.3EQUI/NNNN e.g. /08.3EQUI/Static
Equipment type: Static/ Rotating
Site Name (Area Number/ MDB name +
Discipline Code)
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
57
SF / General / 002 Rev.0 sheet 1 of 1
For Offshore
201EQUI/NNNN e.g. /201EQUI/Deck name
Deck name (where necessary)
Site Name (Area Number/ MDB name +
Discipline Code)
Future equipment shall be created in separate zone as follows:
/201EQUI/FUTURE e.g. /201EQUI/FUTURE
Site Name (Area Number/ MDB name + Discipline Code)
Detailed hierarchy as follows:
/201EQUI/DECK NAME For modelling Mechanical equipment.
/201EQUI/PACKAGE: For modelling Mechanical package unit.
Detailed Hierarchy as follows:
Site > /201EQUI
Zone> /201EQUI/MAINDECK
Zone> /201EQUI/PACKAGE
/EQUI> /201-C-1234
NOZZ> /201-C-1234/N1 /EQUI> /201-P-1234
NOZZ> /201-C-1234/N2 /EQUI> /201-T-1234
SUBE> /201-C-1234/Platform-Clips /EQUI> /201-V-1234
SUBE> /201-C-1234/Ladder-Clips
SUBE> /201-C-1234/Supp-Clips
SUBE> /201-C-1234/Earthing-Boss
SUBE> /201-C-1234/Name-Plate
SUBE> /201-C-1234/Fixed-Saddle
SUBE> /201-C-1234/Sliding-Saddle
SUBE> /201-C-1234/Davit-XXX (Each davit to be SUBE and named appropriately)
SUBE> /201-C-1234/Boot
SUBE> /201-C-1234/Rein-Pad
SUBE> /201-C-1234/Insulation
SUBE> /201-C-1234/Access-Way/ Platform
SUBE> /201-C-1234/Reserved-Volume
SUBE> /201-C-1234/Reserved-Volume: Area /volume required/ reserved for operation and
maintenance of the equipment.
• Nozzle Naming
Nozzle names shall be equipment tag/nozzle number. e.g. /201-C-1234/N1
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
58
SF / General / 002 Rev.0 sheet 1 of 1
• Civil/Structure Zones:
Zone naming for Civil/ Structure for Offshore shall be deck based and as follows:
For Onshore Zone naming, sub division shown under deck shall be used (e.g.:
STRUCTURE, LAD-STAIR, HANDRAIL …).
/201STRU/HELI DECK
/201STRU/VALVE ACCESS DECK
/201STRU/MAIN DECK
/201STRU/CELLAR DECK
Detailed Hierarchy as follows:
Site > /201STRU Deck Code shall be used at /STRU> level and below
Zone> /201STRU/MAIN DECK /STRU>MDK/STRUCTURE For modelling main
structure.
/STRU>MDK/LAD-STAIR For modelling ladder &
staircase.
/STRU>MDK/HANDRAIL For modelling handrail.
/STRU>MDK/GRATING For modelling grating
/flooring.
/STRU>MDK/SUPPORT For modelling all
supports.
/FRMW>MDK/COLUMN
/FRMW>MDK/BEAM
/FRMW>MDK/BRACING
Access/ Maintenance platforms shall be created at /STRU> level and named appropriately.
All sections (SCTN) under framework shall be properly tagged.
Items like stiffeners shall be clubbed together and created under sub-framework and tagged
appropriately (as per the structure they belong to).
Deck Codes:
Deck/ Area Level Code Deck/ Area Level Code
Heli Deck HED Mezzanine Deck MZD
Above Weather Deck AWD Valve Access Deck VAD
Weather Deck WED Sub Cellar Deck SCD
Solar Panel Deck SPD Sump Deck SDK
Main Deck MDK Jacket Walkway and Boat Landing BLL
Cellar Deck CDK
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
59
SF / General / 002 Rev.0 sheet 1 of 1
Similar convention shall be followed for Jacket.
• Electrical Zones
Zone naming for Electrical shall be as follows:
/201ELEC/CABLE_TRAY-HI: For modelling Electrical high voltage cable tray.
/201ELEC/CABLE_TRAY-LO: For modelling Electrical low voltage cable tray.
/201ELEC/EQUI-Deck Name: For modelling Electrical equipment (Transformer,
Panels, DB, Bus duct etc.) based on deck for
offshore and one zone for onshore.
/201ELEC/SMALL-POWER-EQUIP: For modelling Electrical lighting fixture & poles
etc.
/201ELEC/EHT-SYSTEM: For modelling Electrical heat tracing equipment.
Detailed Hierarchy as follows:
Site > /201ELEC
Zone> /201ELEC/CABLE_TRAY-HI
Zone> /201ELEC/CABLE_TRAY-LO
Zone> /201ELEC/EQUI-Deck Name /PIPE> CABLE_TRAY-HI-150
/PIPE> CABLE_TRAY-HI-200
/PIPE> CABLE_TRAY-HI-300
/PIPE> CABLE_TRAY-HI-400
/STRU> DBs
/STRU> RTU
/STRU> PANELS
/STRU> TRANSFORMER
/STRU> SWITCH-GEAR
All equipment shall be created with proper origin.
• Instrument Zones
Zone naming for Instrument shall be as follows:
/201INST/F&G: For modelling fire and gas detector.
/201INST/EQUI: For modelling instrument equipment.
/201INST/TEL-EQUIP: For modelling telecom equipment, CCTV, PA system.
/201INST/MANIFOLD: For modelling instrument air manifold.
/201INST/CABLE-TRAY: For modelling instrument cable tray.
/201INST/V-BOTTLE: For modelling Volume bottle.
Detailed Hierarchy as follows:
Site > /201INST
Zone> /201INST/CABLE-TRAY
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
60
SF / General / 002 Rev.0 sheet 1 of 1
Zone> /201INST/EQUI
Zone> /201INST/CABLE-TRAY
Zone> /201INST/EQUI
/PIPE> CABLE_TRAY-150
/PIPE> CABLE_TRAY-200
/PIPE> CABLE_TRAY-300
/STRU> JBOX
/STRU> MBOX
/STRU> LOC-PANEL
/STRU> ANA-PANEL
/STRU> STANCHIONS
All equipment shall be created with proper origin.
• Safety Zones
Zone naming for HSE shall be as follows:
/201HSE/EQUI: For modelling firefighting & safety equipment.
/201HSE/ESCAPE-ROUTE: For modelling escape routes.
/201HSE/LAYDOWN: For modelling laydown area.
/201HSE/ACCESS: For modelling access and maintenance volume.
Detailed Hierarchy as follows:
Site > /201HSE
Zone> /201HSE/EQUI
/EQUI> Lifeboat-001(assigned tag shall be used)
/EQUI> Lifebouy-001
All equipment shall be created with proper origin.
• Support Zones:
/201SUPP/PIPE
/201SUPP/ELEC
/201SUPP/INST
/201SUPP/HVAC
Detailed Hierarchy as follows:
Site > /201SUPP
Zone> /201SUPP/PIPE /STRU>MDK/SUPP
/STRU>VAD/SUPP
/STRU>CDK/SUPP
Deck Code shall be used at /STRU> level and below for offshore.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
61
SF / General / 002 Rev.0 sheet 1 of 1
• Equipment Origin:
All equipment shall have a logical origin which can aid in its placement. Following are
examples of origin for some equipment.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
62
SF / General / 002 Rev.0 sheet 1 of 1
ISO VIEW
CENTRELINE & FLANGE FACE
OF LOWER RIGHT HAND NOZZLE
CL
PLAN
ELEVATION
CENTRELINE & FLANGE FACE
OF INLET NOZZLE
PLAN
PLAN
ELEVATION
CENTRELINE OF EQUIPMENT & BOTTOM TAN LINE
PLATE EXCHANGER
T/L
VERTICAL VESSEL/ COLUMN/ CYCLONE
ELEVATION
TAN LINE NEAR FIXED SUPPORT
CENTRELINE OF EQUIPMENT &
PLAN
CL
CONDENSERS
FIN-FAN COOLERS &HORIZONTAL VESSEL
F.S
S.S
T/L
SHELL & TUBE EXCHANGER
ELEVATION
& CENTRELINE OF TUBE INLET
CENTRELINE OF TUBE BUNDLE
ELEVATION
INLET/ OUTLET NOZZLES
CENTRELINE OF EXCHANGER &
REBOILER
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
63
SF / General / 002 Rev.0 sheet 1 of 1
& DISCHARGE NOZZLE
CENTRELINE OF PUMP
ELEVATION
PLAN
CL
EQUIPMENT & DRIVER
& FAN, HORZ. ROTARY
HORIZONTAL PUMP, BLOWER
DIS
CH
.
ELEVATION
& DISCHARGE NOZZLE
CENTRELINE OF PUMP
VERTICAL PUMP
OF SUCTION FLANGE
CENTRELINE & FACE
ISO VIEW
PLAN
DISPLACEMENT PUMP
POSITIVE
ISO VIEW
PLAN
SKID/PACKAGE
SOUTH WEST CORNER
BOTTOM OF BASE AT
ELEVATION
& TUBE INLET
CENTRELINE OF EQUIPMENT
EXCHANGER
PRINTED CIRCUIT
OF BASE AT SOUTH OR WEST END
CENTRELINE OF EQUIPMENT & BOTTOM
ELEVATION
PLAN
COMPRESSOR PACKAGE
EL
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
64
SF / General / 002 Rev.0 sheet 1 of 1
SOUTH WEST CORNER
BOTTOM OF BASE AT
ISO VIEW
PLAN
TANK OR VESSEL
RECTANGULAR STORAGE
ISO VIEW
CENTRELINE OF PUMP
& DISCHARGE NOZZLE
MOTOR
PUMP
VERTICAL SUBMERGED
PUMP
LIFEBOAT & DAVIT
& INLET NOZZLE
CENTRELINE OF EQUIPMENT
ISO VIEW
PLAN
FILTER/ STRAINER
FACE OF FLANGE
CENTRELINE AT FACE OF
ISO VIEW
PLAN
PIG LAUNCHER
& RECEIVER
ISO VIEW
BASE OF PEDESTAL
CRANE
ISO VIEW
SUPPORTS & TOP OF STEEL
MID WAY BETWEEN
BOTTOM OF BASE PLATE
CENTRELINE &
STORAGE TANK
For E&I Cabinets/ Panels - Centre bottom of back side/ panel.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
65
SF / General / 002 Rev.0 sheet 1 of 1
5.6 Tagged Items
All tagged items shall be named as per their Tag ID as given on P&IDs, plot-plans,
datasheets, lists, etc. and as per specified tagging philosophy. Any deviations shall be
documented and submitted to ADMA-OPCO for approval. This applies to but is not limited
to:
a. Equipment
b. Nozzles
c. Pipes
d. In-line piping items, i.e. Orifice Plates, Instruments, Valves, Filters, etc.
e. Steelwork i.e. columns, beams, stair, ladder, access platform etc.
f. Electrical & Instrument Cable Tray, Equipment, i.e. Junction Boxes, Control Panels,
etc.
g. Supports
5.7 Pipe Supports
AVEVA Multi-Discipline Supports (MDS) software shall be used for the 3D design of all
Pipe work supports in PDMS.
The catalogue, specification, design and drawing databases for VPD-MDS that are used on
the project complete with any modifications shall be submitted to ADMA-OPCO as part of
the project deliverable.
Support numbering shall comply with ADMA-OPCO numbering procedure.
E.g. 201-PS-00001
= Sequence Number
= Pipe Support
= Area number/ MDB name
PS = Pipe Support
TS = Cable Tray Support
SPS = Special Support
5.8 Colours
Colours specified in the following table which is basic identification colour (first band
colour) specified in ADMA-OPCO painting manual MNL-01 shall be used for PDMS model,
draft and review model.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
66
SF / General / 002 Rev.0 sheet 1 of 1
1.0 - STRUCTURE
SL.
No
.
3D Model Item ADMA Basic Colour
PDMS
Colour
Name
PDMS
DRAFT
Colour
Auto
Cad
Colour
PDMS
Review
Colour
1.1 STRUCTURE - JACKET BLACK 15 0
1.2 STRUCTURE - DECK
IVORY 185 255,255,
240
1.3 STEEL GRATING BLACK 15 8
1.4 GRP - GRATING
YELLOW 31 2
1.6 PLATING
LIGHT
GREY 1 9
2.0 – MECHANICAL
2.1 EQUIPMENT - NEW CYAN 56 4
2.3 EQUIPMENT (FUTURE)
PIPING (FUTURE) STEEL BLUE 67 165
2.3 HANDLING EQUIPMENT,
WAYS/VOLUMES DARKSLATE 46 117
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
67
SF / General / 002 Rev.0 sheet 1 of 1
3.0 – ELECTRICAL
SL.
No. 3D Model Item ADMA Basic Colour
PDMS
Colour
Name
PDMS
DRAFT
Colour
Auto
Cad
Colour
PDMS
Review
Colour
3.1 ELECTRICAL HIGH
VOLTAGE CABLE TRAYS RED 11 1
3.2 LOW VOLTAGE CABLE
TRAY MAGENTA 71 6
3.3 ELECTRICAL EQUIPMENT
(CONTROL PANELS) LIGHT
GREY 1 9
4.0 – INSTRUMENTATION
4.1 INSTRUMENTATION TRAY
/ LADDER ORANGE 140 30
4.2 INSTRUMENT EQUIPMENT
(CONTROL PANELS) LIGHT
GREY 1 9
5.0 – HSE
5.1 SAFETY PATH
AND
YELLOW WITH BLACK DIRECTIONAL
ARROWS AT 5 METER INTERVALS & AT
CHANGE OF DIRECTION.
5.2 FIRST AID EQUIPMENT
DARKSLATE 167 127
5.3 SAFETY NET SUPPORTS
RED 11 1
5.4 FIRE FIGHTING FACILITIES
RED 11 1
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
68
SF / General / 002 Rev.0 sheet 1 of 1
6.0 – PIPING
SL.
No. 3D Model Item ADMA Basic Colour
PDMS
Colour
Name
PDMS
DRAFT
Colour
Auto
Cad
Colour
PDMS
Review
Colour
6.1 CRUDE OIL (LIVE) BROWN 9 26
6.2 CRUDE OIL (STABILIZED) BROWN 9 26
6.3 CRUDE OIL (EXPORT) BROWN 9 26
6.4 SEPARATED OIL BROWN 9 26
6.5 RECOVERED OIL BROWN 9 26
6.6 SOUR GAS (WET) SALMON 322 21
6.7 SOUR GAS (DRY) SALMON 322 21
6.8 SWEET GAS (WET)
< 100 PPM H2S SALMON 322 21
6.9 SWEET GAS (DRY)
< 100 PPM H2S SALMON 322 21
6.10 FLARE GAS SALMON 322 21
6.11 CONDENSATE SALMON 322 21
6.12 GAS CONDENSATE SALMON 322 21
6.13 FUEL GAS SALMON 322 21
6.14 RELIEF VENT
SPRING
GREEN 127 110
6.15 PROPANE SALMON 322 21
6.16 PILOT GAS TO FLARE SALMON 322 21
6.17 REBOILER VENT GAS SALMON 322 21
6.18 GAS TO ATMOSPHERE SALMON 322 21
6.19 HALON STEEL BLUE 160 142
6.20 INERGEN STEEL BLUE 160 142
6.21 VACUUM STEEL BLUE 160 142
6.22 NITROGEN STEEL BLUE 160 142
6.23 OXYGEN STEEL BLUE 160 142
6.24 INSTRUMENT AIR STEEL BLUE 160 142
6.25 INDUSTRIAL AIR STEEL BLUE 160 142
6.26 CHLORINE GAS STEEL BLUE 160 142
6.27 CARBON DIOXIDE STEEL BLUE 160 142
6.28 FIRE WATER RED 11 1
6.29 FOAM (FIRE FIGHTING) RED 11 1
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
69
SF / General / 002 Rev.0 sheet 1 of 1
SL.
No. 3D Model Item ADMA Basic Colour
PDMS
Colour Name
PDMS
DRAFT
Colour
Auto
Cad
Colour
PDMS
Review
Colour
6.30 ACID MAUVE 12 204
6.31 CAUSTIC SODA MAUVE 12 204
6.32 STEAM
LIGHT GREY 1 9
6.33 STEM CONDENSATE
LIGHT GREY 1 9
6.34 BUNKER FUEL BLACK 15 0
6.35 AVIATION FUEL BLACK 15 0
6.36 FURNACE FUEL BLACK 15 0
6.37 KEROSINE BLACK 15 0
6.38 GASOLINE BLACK 15 0
6.39 DEISEL OIL BLACK 15 0
6.40 LUBE OIL BLACK 15 0
6.41 HYDRAULIC OIL BLACK 15 0
6.42 SEA WATER
FOREST GREEN 101 84
6.43 HOT WATER
FOREST GREEN 101 84
6.44 SOUR WATER
FOREST GREEN 101 84
6.45 COOLING WATER
FOREST GREEN 101 84
6.46 UTILITY WATER
FOREST GREEN 101 84
6.47 POTABLE WATER
FOREST GREEN 101 84
6.48 BALLAST WATER
FOREST GREEN 101 84
6.49 INJECTION SEA WATER
FOREST GREEN 101 84
6.50 BOILER FEED WATER
FOREST GREEN 101 84
6.51 EFFLUENT WATER
FOREST GREEN 101 84
6.52 DEOXYGENATED SEA
WATER FOREST GREEN 101 84
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
70
SF / General / 002 Rev.0 sheet 1 of 1
5.9 Draft Drawings Rules, Libraries, etc
All 2D Drawing Production Administration elements, e.g. Rules, Libraries,
Templates, etc. shall be named and documented accordingly and submitted to
ADMA-OPCO for approval.
5.10 Draft Drawing Databases Structure
Drawing databases shall be created in a structured manner to reflect the design areas
and disciplines, consideration given to maximize drawing production.
Drawings and Sheets shall be named/ numbered in accordance with ADMA-OPCO
document/ drawing numbering procedure.
All dimensioning & annotation shall be done in draft and shall be intelligent. The
extent of annotation and quality of the drawing shall be as specified in CP-00 Part-3.
Modifying/ editing drawings outside PDMS shall not be accepted. Zone based layers shall be created and all items within the zone shall be placed in the
same layer. The 2D drawing representation within PDMS shall adhere to ADMA-OPCO
standards and be subject to ADMA-OPCO approval.
All drawings shall be fully updated to reflect the as-built 3D plant model upon
completion of the project and prior to hand over.
DWG and DXF format copy of all 2D project drawings produced within PDMS to be
provided to ADMA-OPCO.
• Draft Naming Convention Drawing Type Code
Drawing Type Drawing Type Code Section Discipline*
Plot Plan DWG L
General Arrangement Drawings GAD M
Section & Elevation Drawings DWG M
Miscellaneous Drawings MIS
* Refer section discipline above
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
71
SF / General / 002 Rev.0 sheet 1 of 1
• Department Naming
Department Name = Discipline Code + Area Code + Platform Deck Code*
Example:-
• Registry Naming
Registry Name = Discipline Code + Area Code + Platform Deck Code* + Drawing Type Code
Example:-
Discipline
Code
Area
Code
Platform Deck
Code*
Drawing
Type Code Registry Name
PIPE XXX MDK (Main
Deck) GAD
/PIPEXXX-MDK-
GAD
* Platform Deck Code applicable to offshore only. For onshore use Elevations/ platform levels
where required.
• Sheet Naming
Example:-
Project
Code
Area
Code
Section /
Discipline Type
Drawing
Number
ADXXX XXX M 20010
5.11 Draft Text and Colours
• Text font, sizes & colour
The text font (with width factor 0.85), size and colour specified in the table below shall be
used for all engineering drawings and shall be in uppercase only. Exception to this shall be
ADMA Border template where provided fonts and colours shall be retained. Prior approval
shall be obtained for any deviation.
Discipline Code Area Code Platform Deck Code* Department Name
PIPE XXX MDK (Main Deck) /PIPEXXX-MDK
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
72
SF / General / 002 Rev.0 sheet 1 of 1
Drawing Item
Drawing Size
A0 A1 A2 A3 A4
General
Text
Text Height 3 mm 3 / 2.5 mm 2.5 mm 2 mm 2 mm
Text Font Romans Romans Romans Romans Romans
Text Colour White White White White White
Headings
Text Height 5 mm 5 mm 4 mm 3.5 mm 3.5 mm
Text Font Romand Romand Romand Romand Romand
Text Colour White White White White White
Dimension Line Red Red Red Red Red
Projection Line Red Red Red Red Red
Leader Line Red Red Red Red Red
LABEL frame Red Red Red Red Red
Note line White White White White White
• Drawing items colour coding and line thickness
Drawing Type Drawing item
Pipes Structure Equipment Cable tray Other discipline
Piping Drawing
Refer colour
table Grey
Refer colour
table Grey Grey
Thick lines
Thin line Thin line Thin line Thin line
Equipment Drawing Grey Grey
Refer colour
table Grey Grey
Thin line Thin line Thick line Thin line Thin line
Structural Drawing Grey Magenta Grey Grey Grey
Thin line Thick line Thin line Thin line Thin line
Cable Tray Layout Grey Grey Grey Refer colour
table Grey
5.12 Piping Isometric Production and Control
Only complete lines with acceptable clash and data consistency to be submitted for isometric
generation.
Isometric option file(s) shall be created per MDB (Platform/ Plant/ Area) and shall be
configured to reflect ADMA-OPCO standards.
All process information/ parameters, test, heat treatment & painting requirement,
insulation/tracing type & thickness, support location/ type with tag, reference to piping GA &
P&ID, stress analysis requirement/ reference and detailing where required shall be provided
in isometric along with BOM.
Isometric drawing number shall reflect tag given in the design hierarchy which is the line tag
as specified in `CP-00 Part-2 process and utility line tagging format’.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
73
SF / General / 002 Rev.0 sheet 1 of 1
As-Built Isometrics in DXF and PDF format to be delivered to ADMA-OPCO
Please Note: Annotation/ editing of Isometrics outside of PDMS is not permitted unless
approved in advance by ADMA-OPCO.
5.13 Reports
All reports and PDMS report templates generated for and used on the project shall be
submitted to ADMA-OPCO. Reports shall be in MS Excel format.
5.14 Data Consistency Checking (Reports)
A final report showing all Pipes to be free of inconsistent data shall be delivered upon project
completion.
A final report showing all Structural items logically connected shall be delivered upon
project completion.
5.15 Clash Checking (Reports)
A final report showing clash free design and approved clashes shall be delivered upon project
completion.
5.16 Database Integrity (Dice Checking Report)
A final report showing all databases clean of errors shall be delivered upon completion of the
project.
5.17 Miscellaneous
All PDMS database sessions shall be merged prior to submission.
5.18 Project Data
ADMA-OPCO may at any time request complete PDMS Project Data and/ or access to
PDMS Project Data during Project execution.
5.19 Project Review
For periodic/ milestone and as-built review of the 3D PDMS model, latest colour review
model with status file of the 3D PDMS model shall be provided.
Review model (RVM & RVS) shall be made available to ADMA prior to periodic/ milestone
reviews.
Colours specified in the table shall be used for review model.
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
74
SF / General / 002 Rev.0 sheet 1 of 1
5.20 Aveva P&ID
The As-built AVEVA P&ID drawings along with all related database and project files shall
be submitted to ADMA-OPCO upon project completion
P&ID representation shall be in accordance with ADMA-OPCO standards.
Symbols created for the project shall have a suitable naming convention and shall be
submitted to ADMA for approval.
Information detailing layer, line type, text font/ height, colour etc... for P&ID and PFD shall
be submitted to ADMA for approval.
5.21 Milestone Requirements
At project milestones the following shall be delivered to ADMA-OPCO;
a. P&IDs with .MON files
b. P&ID Reports generated reports
5.22 Project Completion
Upon project completion the following shall be delivered to ADMA-OPCO;
a. Project Set up & configuration
b. Project Symbols
c. Drawing Border Templates
d. P&IDs with .MON files
e. P&ID Reports MS Access database
f. P&ID Reports generated reports
g. Documented list of settings made to configure the VPE P&ID project.
6. END OF PROJECT DELIVERABLES:
At the end of the project, ADMA-OPCO’s, Engineering Services Team shall receive the
following deliverables from the Contractor/Consultant through ADMA-OPCO’s Project
Team Leader:-
6.1 One complete set of following Documents and Dossiers:
a. Main index of project completion dossiers/drawings (Deliverable List)
b. Engineering dossier consisting of all Specification, Calculation, Analysis, Data
sheets in its Native format
c. Certification Dossier
1a.0 04-2012 Issued For Implementation.
Rev. Date Description / Text Affected
Codes Of Practices For Plant Design - Part-1: Documentation & Archiving
ADMA-OPCO CP-00 Part-1 PAGE
75
SF / General / 002 Rev.0 sheet 1 of 1
6.2 As-Built drawing folder in native files as applicable
6.3 Drawing List
6.4 Process:
a. PFD’s
b. P & ID’s
6.5 Mechanical
a. Plot Plans
b. Piping General Arrangement
c. Vendor/ package GA’s (separate drawing for each package)
d. Sections & Details
e. Piping Isometric with BOM
f. Equipment Drawings (separate drawing for each equipment)
g. Line List
h. Valve List
i. Equipment List
j. MTO
k. Equipment and Valve Data Sheet (separate data sheet for each equipment and actuated/
safety valve).
6.6 Pipelines Drawing:
a. Profile & Alignment Sheets
b. Riser Details
6.7 Civil/Structural Drawing:
a. Site Layout, Plot Plan
b. General Arrangement
c. Architectural Drawings
d. Reinforced Concrete Detail