International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531 © Research India Publications. http://www.ripublication.com 5525 Performance Analysis of Cascaded Multilevel Inverter Based DSTATCOM Adepu Sateesh Kumar Associate Professor, Department of EEE, Vaagdevi College of Engineering, Warangal, Telangana India. K.Prakash Professor, Member IEEE Department of EEE, Vaagdevi College of Engineering, Warangal, Telangana India. Hareesh Kumar Yada Associate Professor, Department of EEE, Vaagdevi College of Engineering, Warangal, Telangana India. Abstract In this paper, a single-phase Seven-Level and Five-Level cascaded H-Bridge Inverter (CHB) based Distribution Static Compensator (DSTATCOM) is presented. A simple control algorithm based on inverse park PLL was proposed for both five-level and seven-level inverters. Synchronous Reference Frame theory (SRF) as control algorithm is used for reference source current extraction and to generate gating pulses for the DSTATCOM. The main aim of the CHB is to eliminate source current harmonics and improve input power factor in the single-phase distribution system. The multilevel inverter has some limitations in its applications due to high complexity and size. The proposed control algorithm has two components, converting the load current into stationary reference frame coordinates and estimation of peak amplitude of load currents. Hence, a simple and reliable controller with ease of implementation was developed. The algorithm for single- phase DSTATCOM is aiming to perform with accurate tracking performance under step changes in load currents and to provide good dynamic compensation. In this paper, Inverse- Park transformation is adopted for generating quadrature component of current because of its dynamic performance under all varying conditions. The performance of the control algorithm is tested and evaluated using MATLAB/Simulink. Keywords: Distribution Synchronous Compensator (DSTATCOM), Cascaded H-Bridge Inverter (CHB), Power Quality (PQ), Phase-Locked Loop (PLL). INTRODUCTION In recent years, harmonics is the most important issue in terms of power quality due to wide-spread of power electronic devices in commercial, industrial and domestic loads. In distribution systems, the usage of non-linear loads such as computers, variable/adjustable speed drives, LED lighting systems and compact fluorescent lamps etc are using widely and prone to harmonics. These harmonics are causing severe problems such as power losses in equipments, malfunctioning of devices, damaging of sensitive loads and motor failures. Therefore, it is a serious concern in distribution systems for both consumers and suppliers to eliminate harmonics and meet the requirements of IEEE 519-1992 or IEC 61000-3-2 [1]-[2]. The harmonics produced by the loads are causing grid voltages to be distorted. Conventionally, passive filters are employed for harmonic mitigation and reactive power compensation. But, these suffer from disadvantages like, cost, bulkiness, resonance and fixed compensation [3]. Therefore, a dynamic solution is preferred that fits the compensation is a DSTATCOM. The role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced by the load. The controller has to track the step changes in the load accurately and to choose reference current properly for better compensation. Keeping accuracy and reliability in view, many techniques are proposed in literature for quadrature signal generation. Zero Crossing Detector (ZCD) [4] method is simple but, sensitive to grid variations. The most widely used method is synchronous reference frame theory and SOGI based theory [4]-[5]. It is less accurate to unbalanced and lower harmonic components. But, SRF theory with inverse park transformation based algorithm is found satisfactory under distorted conditions with low computational burden. However, application and implementation of this control strategy for a five level cascaded H-bridge active power filters has not gained much attention in the literature. Multilevel inverters have gained much attention due to its enormous advantages over conventional voltage source inverters. The conventional two-level inverter is also capable of handling reactive power, harmonic reduction and power factor improvement under various load changes. But, due to advancement of power electronic devices and controllers, multilevel inverters have shown their ability to compensate power quality problems with simplicity, low cost, reliability and high-quality output. There are many topologies proposed in the literature [7]-[9], Flying capacitor based inverter, neutral point clamped inverter and cascaded H-bridge type multilevel inverter is found suitable for DSTATCOM application with ease of control. In this paper, CHB type of multilevel inverter is used to reduce the rating of the devices used and elimination of harmonics with an increase in levels of the converter. This method also reduces the switching losses and decreases the ratings of the DC link capacitors used. The control algorithm is found effective in linear/ non-linear and increase in load conditions. In order to all these topologies, various PWM techniques were also proposed in the literature which includes selective harmonic elimination based PWM, Multilevel space vector based PWM and Carrier based PWM etc [10]-[24]. The main advantage of this CHB inverter is increasing of switching

Upload: truongnhu

Post on 30-Jan-2018

229 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5525

Performance Analysis of Cascaded Multilevel Inverter Based DSTATCOM

Adepu Sateesh Kumar

Associate Professor, Department of EEE,

Vaagdevi College of Engineering, Warangal, Telangana India.

K.Prakash

Professor, Member IEEE Department of EEE,

Vaagdevi College of Engineering, Warangal, Telangana India.

Hareesh Kumar Yada

Associate Professor, Department of EEE,

Vaagdevi College of Engineering, Warangal, Telangana India.

Abstract

In this paper, a single-phase Seven-Level and Five-Level

cascaded H-Bridge Inverter (CHB) based Distribution Static

Compensator (DSTATCOM) is presented. A simple control

algorithm based on inverse park PLL was proposed for both

five-level and seven-level inverters. Synchronous Reference

Frame theory (SRF) as control algorithm is used for reference

source current extraction and to generate gating pulses for the

DSTATCOM. The main aim of the CHB is to eliminate source

current harmonics and improve input power factor in the

single-phase distribution system. The multilevel inverter has

some limitations in its applications due to high complexity and

size. The proposed control algorithm has two components,

converting the load current into stationary reference frame

coordinates and estimation of peak amplitude of load currents.

Hence, a simple and reliable controller with ease of

implementation was developed. The algorithm for single-

phase DSTATCOM is aiming to perform with accurate

tracking performance under step changes in load currents and

to provide good dynamic compensation. In this paper, Inverse-

Park transformation is adopted for generating quadrature

component of current because of its dynamic performance

under all varying conditions. The performance of the control

algorithm is tested and evaluated using MATLAB/Simulink.

Keywords: Distribution Synchronous Compensator

(DSTATCOM), Cascaded H-Bridge Inverter (CHB), Power

Quality (PQ), Phase-Locked Loop (PLL).

INTRODUCTION

In recent years, harmonics is the most important issue in terms

of power quality due to wide-spread of power electronic

devices in commercial, industrial and domestic loads. In

distribution systems, the usage of non-linear loads such as

computers, variable/adjustable speed drives, LED lighting

systems and compact fluorescent lamps etc are using widely

and prone to harmonics. These harmonics are causing severe

problems such as power losses in equipments, malfunctioning

of devices, damaging of sensitive loads and motor failures.

Therefore, it is a serious concern in distribution systems for

both consumers and suppliers to eliminate harmonics and meet

the requirements of IEEE 519-1992 or IEC 61000-3-2 [1]-[2].

The harmonics produced by the loads are causing grid voltages

to be distorted. Conventionally, passive filters are employed

for harmonic mitigation and reactive power compensation.

But, these suffer from disadvantages like, cost, bulkiness,

resonance and fixed compensation [3]. Therefore, a dynamic

solution is preferred that fits the compensation is a

DSTATCOM. The role of DSTATCOM is to compensate

harmonic currents and reactive power with improved power

factor produced by the load. The controller has to track the

step changes in the load accurately and to choose reference

current properly for better compensation.

Keeping accuracy and reliability in view, many techniques are

proposed in literature for quadrature signal generation. Zero

Crossing Detector (ZCD) [4] method is simple but, sensitive to

grid variations. The most widely used method is synchronous

reference frame theory and SOGI based theory [4]-[5]. It is

less accurate to unbalanced and lower harmonic components.

But, SRF theory with inverse park transformation based

algorithm is found satisfactory under distorted conditions with

low computational burden. However, application and

implementation of this control strategy for a five level

cascaded H-bridge active power filters has not gained much

attention in the literature.

Multilevel inverters have gained much attention due to its

enormous advantages over conventional voltage source

inverters. The conventional two-level inverter is also capable

of handling reactive power, harmonic reduction and power

factor improvement under various load changes. But, due to

advancement of power electronic devices and controllers,

multilevel inverters have shown their ability to compensate

power quality problems with simplicity, low cost, reliability

and high-quality output. There are many topologies proposed

in the literature [7]-[9], Flying capacitor based inverter, neutral

point clamped inverter and cascaded H-bridge type multilevel

inverter is found suitable for DSTATCOM application with

ease of control.

In this paper, CHB type of multilevel inverter is used to reduce

the rating of the devices used and elimination of harmonics

with an increase in levels of the converter. This method also

reduces the switching losses and decreases the ratings of the

DC link capacitors used. The control algorithm is found

effective in linear/ non-linear and increase in load conditions.

In order to all these topologies, various PWM techniques were

also proposed in the literature which includes selective

harmonic elimination based PWM, Multilevel space vector

based PWM and Carrier based PWM etc [10]-[24]. The main

advantage of this CHB inverter is increasing of switching

Page 2: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5526

levels by increasing the number of H-bridges in the circuit.

This paper uses a simple SRF based control in addition with

inverse park transformation based PLL to generate quadrature

signal for harmonic elimination and reactive power

compensation.

A CHB based DSTATCOM is proposed in this paper, Non-

linear load conditions under steady state and dynamic

conditions are carried out using Simulink, simpower systems

block set and its performance found satisfactory.

PROPOSED CONFIGURATION AND CONTROL

ALGORITHM

The CHB based DSTATCOM shown in Fig. 1. Each H-bridge

consists of a two-leg Voltage Source Converter (VSC)

consisting of 8 IGBT switches for five-level and Three VSC’s

with 12 IGBT switches with separate DC sources for each

VSC as shown in Fig. 2. DSTATCOM is connected in

between source and load in parallel through an interfacing

inductor Lf at the point of common coupling (PCC). The

proposed controller for DSTATCOM is capable of

maintaining the total harmonic distortion (THD %) within the

limits by eliminating the harmonics in the source current.

Power factor correction, reactive power and harmonic

compensation is also done even under varying linear and non-

linear load conditions to test the performance of the controller.

The DSTATCOM can be operated with required active and

reactive power injection by adjusting the magnitude and phase

of the system. The ratings of the proposed system are listed in

appendix. The rating of the DSTATCOM should be 15% more

than the Load rating for safer and economic operation.

I = Iα

Iq

αβ

dq

Id

Inverse Park Transform

wt

dq

αβ

I’α

I’β

wt

Figure 3: Inverse Park Transformation based Quadrature

Signal Generation

A. Inverse Park Transformation Fig.3 shows the structure of inverse park transformation. In

this method, two loops are formed that are nonlinear and

interdependent. In order to eliminate algebraic loops, First-

order low pass filters are employed for each d and q signal.

Park transformation is done (i.e, αβ0/dq0s) and these outputs

are used for inverse park transformation as shown in fig.3.

Vs

RL

LL

RsLs

Cdc

N

A

Five-Level or

Seven-Level

DSTATCOM

Linear

LoadLf

PCC

Vdc

Figure 1: Line Diagram of the Proposed System.

Seven-Level

DSTATCOM

PCC

Cdc1

Cdc2

S21 S23

S12S14

S13S11

S24 S22

Vdc1

Vdc2

Cdc2

S21 S23

S24 S22

Vdc3

Five-Level

Figure 2: Cascaded H-Bridge Multilevel Inverter

IP-PLL

Vg

wt

Fig. 3 IL

LPFILP

Σ

LPF Σ-

V*dc

PI

Icd

Vdc1

Is*αβ0/d

Id

Σ

Is-

Σ

Vdc2

dq0/αPWM

Generator

Vdc3

CHB-1

CHB-2

CHB-3

Figure 4: Block Diagram of Reference Source Current Generation

Page 3: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5527

q

d

VV

VV

ˆcosˆsin

ˆsinˆcos (1)

The dynamics of the phase detector mainly depends on the low

pass filter that is used after the transformation to filter out any

noises or harmonics that are present in Vd and Vq.

c

c

wswsLPF

)( where, cw is the cut-off frequency (2)

The difference from other PLL’s is generating a dummy

voltage signal from the feedback loops.

B. Reference Current Generation The peak amplitude of active component of current is

calculated as shown in Fig. 4. The Load current is sensed and

supplied to inverse park transformation to generate quadrature

signals (ILα and ILβ) and then transformed back to Id and

supplied to a low-pass filter. The output is then added with the

output generated by the DC voltage control loop to produce

reference active component of current (ILP + ICD). The

measured voltage (Vdc) across the two DC capacitors for five-

level (Vdc1+Vdc2) and three capacitors for seven level

(Vdc1+Vdc2+Vdc3) are summed and compared with the DC bus

reference voltage (Vdc*). The error of the signal at nth sampling

instant is given by:

Vd(n) = V*dc(n) - Vdc(n) (3)

The voltage error Vd(n) is then supplied to Proportional-

Integral controller to regulate the DC bus voltage of

DSTATCOM. At nth sampling instant, the output of the PI

controller is as:

Icd(n)=Icd(n-1)+kp{Vdcer(n)-Vdcer(n-1)}+kiVdcer(n) (4)

Where, Kp and Ki are proportional gain and integral gains of

the PI controller. Vdcer(n) and Vdcer(n-1) are the DC bus voltage

errors in nth and (n-1)th instant and Icd(n) and Icd(n-1) are the

amplitudes of active component of currents at the fundamental

reference current in nth and (n-1)th instant.

The average magnitude of current (ILP) and the output of the PI

controller (Icd) are summed up and transformed to Iα (reference

source current) from dq0 component and then compared with

the actual source current to produce error magnitude of current

and then supplied to a PWM controller to generate gating

pulses to the multilevel inverter.

SIMULATION RESULTS AND DISCUSSION

In this section, the proposed control algorithm is evaluated and

tested using MATLAB / Simulink on a single-phase

distribution system loaded with linear and non-linear loads.

Fixed time step of 20µs with ode3 (Bogacki - Shampine)

solver is chosen for simulation.

Few test cases are performed for evaluation of DSTATCOM

are: The performance of the controller when a linear load is

applied is shown in fig.5 when time t=0.4s to 0.5s. In Fig.6,

Non - linear load is applied from time t=1s to 2s and increase

in load from time t=2s to 3s is shown in Fig.7. A mixed load

(Linear and Non-linear load) is applied from time t=3s to 4s as

shown in Fig.8. All these test cases are performed under

sinusoidal grid conditions. The five-level and seven-level

results are shown and prove that the seven-level inverter is

found more effective with low total harmonic distortion. The

five-level inverter shows a staircase output across the inverter

whereas the seven-level inverter output is near sinusoidal. This

indicates that the filter capacity that is required is more for

five-level inverter compared to seven-level inverter. The

performance under dynamic conditions is found satisfactory.

The DC bus voltage regulation, reactive power and harmonic

compensation with power factor improvement shows the

effectiveness of the controller. A sinusoidal PWM strategy

was employed for gating the inverters. THD (%) of all the four

cases mentioned above are presented in table-I prove the

effectiveness of the controller.

CONCLUSION

In this paper, a simple and effective control algorithm based

on SRF theory and Inverse-Park based transformation based

PLL for single-phase five-level and seven-level cascaded H-

bridge inverters has been analyzed, compared and validated

using MATLAB / Simulink. This theory is adopted to work in

sinusoidal grid voltage conditions and Non-Linear load

conditions. The source current THD (%) is maintained within

IEEE 519-1992 limits in both the inverter configurations.

Seven-level inverter has proven more promising and reliable

compared to five-level inverter. Seven-level also reduces the

cost of additional filtering component that is required and low

rating DC bus capacitors can be used which makes the overall

cost low. The control algorithm is very promising and easy to

implement because of its simple structure and accuracy. The

harmonic compensation and power factor is effectively done

under all steady-state and dynamic conditions. The injected

current of the DSTATCOM was also very close to the

reference values and proved a smooth and reliable profile. The

DC link voltage is well balanced in seven-level converter

compared to five-level cascaded H-bridge Inverter. Therefore,

a Seven-level CHB is preferred for low to medium power

ratings at the distribution level.

Table-I

THD (%) of Test Cases (Table-I)

Five-level Seven Level

Fig No. Is IL Is IL

5 2.47 2.03 1.8 2.03

6 3.15 35.63 2.4 35.63

7 2.76 33.22 1.96 33.22

8 2.40 27.82 2.12 27.82

APPENDIX (Table-II)

Grid Voltage & Frequency Single-Phase, 230V, 50Hz

Source-side Impedance Rs=0.1 Ω, Ls =2.5mH

Non-linear: Single-phase

diode bridge rectifier

R=40Ω, L= 250mH,

Linear Load R=40 Ω, L=250mH

PWM Switching frequency 2kHz

Reference voltage of DC bus 400V

Interfacing inductor Lf=1.5mH

Gains of PI controller for DC bus Kp =0.32, Ki=6

Page 4: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5528

Fig.5 Performance of CHB with Linear Load (5 and 7 Level CHB)

Figure 6: Performance of CHB with Non-Linear Load (5 and 7 Level CHB)

-350

0

350

-30

0

30

-10

0

10

-10

0

10

170

200

230

0.46 0.48 0.5 0.52 0.54 0.56 0.58 0.6 0.62 0.64

-350

0

350

Time (s)

Source Voltage (V)

Source Voltage (V)

Source Current (A)

Source Current (A)

Vdc1 (V)

Vdc2 (V)

DSTATCOM Voltage (V)

-10

0

10

Injected Current (A)

Load Current (A)

-350

0

350

-10

0

10

-1

0

1

-3

0

3

125

145

0.46 0.48 0.5 0.52 0.54 0.56 0.58 0.6 0.62 0.64

-350

0

350

-3

0

3

Time (Sec)

Source Voltage (V)

Source Current (A)

Source Current (A)

Load Current (A)

Inverter Voltage (V)

Scaled

Source Voltage (V)

Injected Current (A)

DC Link Voltage (V)

-350

0

350

-30

0

30

-20

0

20

-20

0

20

170

200

230

1.06 1.08 1.1 1.12 1.14 1.16 1.18 1.2 1.22 1.24

-350

0

350

Time (s)

Source Voltage (V)

Source Voltage (V)

Source Current (A)

Source Current (A)

Vdc1 (V)

Vdc2 (V)

DSTATCOM Voltage (V)

-20

0

20

Injected Current (A)

Load Current (A)

-350

0

350

-10

0

10

-101

-303

125

145

1.06 1.08 1.1 1.12 1.14 1.16 1.18 1.2 1.22 1.24

-350

0

350

-303

Time (Sec)

Source Voltage (V)

Source Current (A)

Source Current (A)

Load Current (A)

Inverter Voltage (V)

Scaled

Source Voltage (V)

Injected Current (A)

DC Link Voltage (V)

Page 5: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5529

Figure 7: Performance of CHB with Increase in Non-Linear Load (5 and 7 Level CHB)

Figure 8: Performance of CHB with Linear and Non-Linear Load (5 and 7 Level CHB)

-350

0

350

-30

0

30

-20

0

20

-20

0

20

170

200

230

1.96 1.98 2 2.02 2.04 2.06 2.08 2.1 2.12 2.14

-350

0

350

Time (s)

Source Voltage (V)

Source Voltage (V)

Source Current (A)

Source Current (A)

Vdc1 (V)

Vdc2 (V)

DSTATCOM Voltage (V)

-20

0

20

Injected Current (A)

Load Current (A)

-350

0

350

-10

0

10

-303

125

145

1.46 1.48 1.5 1.52 1.54 1.56 1.58 1.6 1.62 1.64

-350

0

350

-303

Time (Sec)

Source Voltage (V)

Source Current (A)

Source Current (A)

Load Current (A)

Inverter Voltage (V)

Scaled

Source Voltage (V)

Injected Current (A)

DC Link Voltage (V)

-350

0

350

-30

0

30

-20

0

20

-20

0

20

170

200

230

2.96 2.98 3 3.02 3.04 3.06 3.08 3.1 3.12 3.14

-350

0

350

Time (s)

Source Voltage (V)

Source Voltage (V)

Source Current (A)

Source Current (A)

Vdc1 (V)

Vdc2 (V)

DSTATCOM Voltage (V)

-20

0

20

Injected Current (A)

Load Current (A)

-350

0

350

-10

0

10

-101

-303

125

145

2.06 2.08 2.1 2.12 2.14 2.16 2.18 2.2 2.22 2.24

-350

0

350

-303

Time (Sec)

Source Voltage (V)

Source Current (A)

Source Current (A)

Load Current (A)

Inverter Voltage (V)

Scaled

Source Voltage (V)

Injected Current (A)

DC Link Voltage (V)

Page 6: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5530

REFERENCES

[1] IEEE Recommended Practices and Requirements for

Harmonic Control in Electrical Power Systems. ,

IEEE Std. 519, 1992.

[2] Electromagnetic Compatibility (EMC)—Part 3-2:

Limits—Limits for Harmonic Current Emissions

(Equipment Input Current=16 A per Phase), IEC

61000-3-2, 2005.

[3] Timbus, A., Liserre, M., Teodorescu, R. and

Blaabjerg, F., “Synchronization methods for three

phase distributed power generation systems: an

overview and evaluation,” IEEE PESC 2005, pp.

2474-2481, Jun. 2005.

[4] V. Kaura and V. Blasco, “Operation of a phase

locked loop system under distorted utility

conditions,” IEEE Trans. Ind. Appl., Vol. 33, no. 1,

pp. 58–63, Jan./Feb. 1997.

[5] Yada, Hareesh Kumar, and M. S. R. Murthy. "A new

topology and control strategy for extraction of

reference current using single phase SOGI-PLL for

three-phase four-wire Shunt Active Power Filter",

proc. 2014 IEEE International Conference on Power

Electronics Drives and Energy Systems (PEDES),

2014.

[6] Yada, Hareesh Kumar, and M. S. R. Murthy. "Phase

Locked Loop Techniques for power quality

improvement in polluted grids", Proc. 2016 IEEE

International Conference on Power Electronics,

Integrated Circuits and Energy Systems (ICPEICES),

2016.

[7] K. H. Law, M. S. A. Dahidah, and N. Marium,

“Cascaded multilevel inverter based STATCOM with

power factor correction feature,” in Proc. IEEE Conf.

Sustainable Utilization Develop. Eng. Technol., 2011, pp. 1–7.

[8] F. Z. Peng and J. S. Lai, “Dynamic performance and

control of a static Var generator using cascade

multilevel inverters,” IEEE Trans. Ind. Appl., vol. 33,

no. 3, pp. 748–755, Jun. 1997.

[9] Y. Cheng, Q. Chang, L. C. Mariesa, S. Pekarek, and

S. Aticitty, “A comparison of diode-clamped and

cascaded multilevel converters for a STATCOM with

energy storage,” IEEE Trans. Ind. Electron., vol. 53,

no. 5, pp. 1512–1521, Oct. 2006.

[10] R. Naderi and A. Rahmati, “Phase-shifted carrier

PWM technique for general cascaded inverters,”

IEEE Trans. Power Electron., vol. 23, no. 3, pp.

1257–1269, May 2008.

[11] W. Yao, H. Hu, and Z. Lu, “Comparisons of space-

vector modulation and carrier-based modulation of

multilevel inverter,” IEEE Trans. Power Electron.,

vol. 23, no. 1, pp. 45–51, Jan. 2008.

[12] J. Rodriguez, L. Moran, P. Correa, and C. Silva, “A

vector control technique for medium-voltage

multilevel inverters,” IEEE Trans. Ind. Electron., vol.

49, no. 4, pp. 882–888, Aug. 2002.

[13] G. Narayanan and V. T. Ranganathan, “Extension of

operation of space vector PWM strategies with low

switching frequencies using different overmodulation

algorithms,” IEEE Trans. Power Electron., vol. 17,

no. 5, pp. 788–798, Sep. 2002.

[14] S. Wei, B. Wu, F. Li, and C. Liu, “A general space

vector PWM control algorithm for multilevel

inverters,” in IEEE Appl. Power Electron. Conf.

Expo., vol. 1, Feb. 2003, pp. 562–568

[15] A. K. Gupta and A. M. Khambadkone, “A general

space vector PWM algorithm for multilevel inverters,

including operation in over modulation range,” IEEE

Trans. Power Electron., vol. 22, no. 2, pp. 517–526,

Mar. 2007.

[16] W. Yao, H. Hu, and Z. Lu, “Comparisons of space-

vector modulation and carrier-based modulation of

multilevel inverter,” IEEE Trans. Power Electron.,

vol. 23, no. 1, pp. 45–51, Jan. 2008.

[17] M. S. A. Dahidah and V. G. Agelidis, “Selective

harmonic elimination PWM control for cascaded

multilevel voltage source converters: A generalized

formula,” IEEE Trans. Power Electron., vol. 23, no.

4, pp. 1620–1630, Jul. 2008.

[18] B. Ozpineci, L. M. Tolbert, and J. N. Chiasson,

“Harmonic optimization of multilevel converters

using genetic algorithms,” in Proc. Power Electron.

Spec. Conf., 2004, pp. 3911–3916.

[19] V. G. Agelidis, A. Balouktsis, and M. S. A. Dahidah,

“A five-level symmetrically defined selective

harmonic elimination PWM strategy: Analysis and

experimental validation,” IEEE Trans. Power

Electron., vol. 23, no. 1, pp. 19–26, Jan. 2008.

[20] M. S. A. Dahidah and V. G. Agelidis, “Single-carrier

sinusoidal PWM-equivalent selective harmonic

elimination five-level inverter control,” Electr. Power

Syst. Res., vol. 78, no. 11, pp. 1826–1836, Jun. 2008.

[21] M. S. A. Dahidah, G. Konstantinou, and V. G.

Agelidis, “SHE-PWM and optimized DC voltage

levels for cascaded multilevel inverters control,” in

Proc. IEEE Symp. Ind. Electron. Appl., 2010, pp.

143–148.

[22] K. H. Law, M. S. A Dahidah, and V. G. Agelidis,

“SHE-PWM cascaded multilevel converter with

adjustable DC sources control for STATCOM

applications,” in Proc. IEEE 7th Int. Power Electron.

Page 7: Performance Analysis of Cascaded Multilevel Inverter Based ... · PDF fileThe role of DSTATCOM is to compensate harmonic currents and reactive power with improved power factor produced

International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 16 (2017) pp. 5525-5531

© Research India Publications. http://www.ripublication.com

5531

Motion Control Conf., 2012, pp. 330–334.

[23] Adepu Sateesh Kumar, K.Prakash, “Analysis of Split

Capacitor Based DSTATCOM with LCL Filter Using

Instantaneous Symmetrical Components Theory”

With an ISBN Number: 978-1-4673-9745-2 ©2016

IEEE explore (Ref. no. -37745) 2nd IEEE

International Conference (AEEICB-2016).

[24] Adepu Sateesh Kumar, K.Prakash, Dr.Swati Sharma,

“A Five-Level Cascaded DSTATCOM for Single-

Phase Distribution System”, National Conference &

Journal on Challenges and Issues in Operation of

Competitive Electricity Markets (CIOCEM-2016)

CPRI, Bangalore 2016.