performance tests in accordance with …...performance tests in accordance with aama 501.1,...
TRANSCRIPT
AIR-INS inc.1320, boul. Lionel-Boulet, Varennes (Québec) J3X 1P7 – Tél. : (450) 652-0838 Fax : (450) 652-7588 [email protected]
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
PERFORMANCE TESTS IN ACCORDANCE WITH AAMA 501.1,
ASTM-E283, ASTM-E330, ASTM E331 AND ASTM-E547 TEST PROCEDURES
(WITH REFERENCE TO CAN/CSA A440-00 "WINDOWS" STANDARD)
Prepared for:
UNICEL ARCHITECTURAL2155, rue Fernand-LafontaineLongueuil, Québec, CANADA
J4G 2J4Tel. 450-670-6844
SUMMARY OF RESULTS
Product Type:
Product Series/Model:
Skylight dimensions:
Pyramidal insulated skylight with a square base.
Pyramidal skylight
3048 mm x 3048 mm x 759 mm in height (120 in. x 120 in. x 30 in height)
Results with reference to ASTM testing procedures only:
Air Tightness:
Static Water Tightness:
Dynamic Water Tightness:
Structural Resistance:
Qaverage = 0.02 L/s•m² @ 75 Pa (0.004 ft³/min-ft² @ 1.57 psf)
Qaverage = 0.06 L/s•m² @ 300 Pa (0.012 ft³/min-ft² @ 6.27 psf)
Qaverage = 0.07 L/s•m² @ 360 Pa (0.013 ft³/min-ft² @ 7.52 psf)
No water infiltration under a differential pressure of 720 Pa (15 psf)
No water infiltration under a differential pressure of 1367 Pa (29 psf) equivalent to
a wind velocity of 170 km/h (106 mph).
Negative and positive design load = 3360 Pa (70 psf)
Results with reference to CAN/CSA A400-00 "Windows" Standard:
Air Tightness:
Water Tightness:
Wind Load Resistance:
Condensation Resistance:
FIXED
B7
C5
I = 56.8 for Thermo 1" option
I = 62.8 for Vision Control 2-1/2" option
Test Completion Date: 07/10/2009
AIR-INS INC.
Report: AS-00248-A1 1320 Boul. Lionel-Boulet
Date: October 5th, 2009 Varennes, Québec
J3X 1P7
Total of pages: 11 (Tél): (450) 652-0838
Total of appendix: 3 (Fax): (450) 652-7588
AIR-INS inc.
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
TABLE OF CONTENTS
1.0 INTRODUCTION ...............................................................................................................................1
2.0 STANDARDS AND TEST PROCEDURES......................................................................................1
3.0 DESCRIPTION OF THE SPECIMEN TESTED ...............................................................................2
4.0 ALTERATION(S) ...............................................................................................................................6
5.0 TESTING RESULTS WITH REFRENCE TO AAMA & ASTM TESTING
PROCEDURES: ..................................................................................................................................7
6.0 TESTING RESULTS WITH REFERENCE TO CAN/CSA A440-00 "WINDOWS"..........................9
7.0 CONCLUSION..................................................................................................................................11
APPENDIX A: ASSEMBLY DRAWINGS
APPENDIX B: CONDENSATION RESISTANCE TEST PROCEDURE
APPENDIX C: PHOTOGRAPHS
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 1/11
PERFORMANCE TESTS IN ACCORDANCE WITH AAMA 501.1,
ASTM-E283, ASTM-E330, ASTM E331 AND ASTM-E547 TEST PROCEDURES
(WITH REFERENCE TO CAN/CSA A440-00 "WINDOWS" STANDARD)
1.0 INTRODUCTION
Air-Ins Inc. laboratories was retained by " UNICEL ARCHITECTURAL " to test a skylight
according to the procedures AAMA 501.1, ASTM-E283, ASTM-E330, ASTM-E331 and ASTM-
E547. Results with reference to the CAN/CSA A440-00 “Windows” Standard are provided for
comparative purposes. The sample components and manufacturing are documented in section
3.0.
2.0 STANDARDS AND TEST PROCEDURES
AAMA 501.1 “Standard Test Method For Water Penetration Of Windows, Curtain
Walls And Doors Using Dynamic Pressure”.
ASTM-E283 "Standard Test Method for Determining Rate of Air Leakage Through
Exterior Windows, Curtain Walls and Doors Under Specified Pressure Difference
Across the Specimen ".
ASTM-E330 "Standard Test Method for Structural Performance of Exterior Windows,
Doors, Skylights, and Curtain Walls by Uniform Static Air Pressure Difference".
ASTM-E331 "Standard Test Method for Water Penetration of Exterior Windows,
Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference".
ASTM-E547 "Standard Test Method for Water Penetration of Exterior Windows,
Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference".
CAN/CSA A440-00 “Windows”
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 2/11
3.0 DESCRIPTION OF THE SPECIMEN TESTED
Model: Pyramidal Skylight
Assembly drawings: - DEV2009SK1-SK-TRM2 eng 1/11 (3D view)
- DEV2009SK1-SK-TRM eng 2/11 (3D view & Dimensions)
- DEV2009SK1-SK- TRM eng 3/11 (Components List)
- DEV2009SK1-SK- TRM eng 4/11 (Angle rafter details)
- DEV2009SK1-SK- TRM eng 5/11 (Mullion details)
- DEV2009SK1-SK- TRM eng 6/11 (B, C & D Cross-sections)
- DEV2009SK1-SK- TRM eng 7/11 (E Cross-sections)
- DEV2009SK1-SK- TRM-T1B eng 8/11 (1" Insulating- trapezoid)
- DEV2009SK1-SK- TRM-T2B eng 9/11 (1" Insulating-triangle)
- DEV2009SK1-SK- TRM-T7B eng 10/11 (2-1/2" Vision-triangle)
- DEV2009SK1-SK- TRM-T8B eng 11/11 (2-1/2" Vision –trapezoid)
Others drawings: None.
Date of testing: 06/22/2009, 06/23/2009 and 07/10/2009.
Type: 26.6 slope pyramidal insulated skylight with a square base.
Sample installation and test chamber:
- Test chamber: A square chamber base of 3048 mm x 3048 mm
x 2077 mm in height (120 in. x 120 in. x 81.75
in. in height) built with 2 in. x 4 in. spruce studs,
at 410 mm (16 in.) c.c., covered with 19 mm
(3/4 in.) exterior grade plywood covered with
bitumen membrane and 16 mm (5/8 in.) gypsum
board on the interior. The test frame is secured
with a HSS 4x4x1/4 interior steel wall support
fixture.
- Anchoring method: The skylight was secured to the test chamber
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 3/11
with (2) #8x2" screws per anchor. (2) aluminium
angles (anchors) were located at the lower
extremities of each mullion and secured with a
Hex bolt 1/2"-13UNCx3-3/4".
- Sealant detail: The metallic flashing between the sill profiles and
the vertical exterior wall surface was secured to
the aluminium parts with rivets and to the test
chamber with nails. The flashings were covered
with bitumen membrane, sealed at membrane
junctions and at the liaisons with the prototype.
The membrane was covered with insulation
panels and protected by another flashing. The
flashing junctions were sealed.
Frame:
- Material: Aluminium
- Assembly method: (2) 3/8" – 14 x 1"-1/4 hex head metal screws
(with gasket and washer) for mullion-to-mullion
anchoring. (1) 3/8" – 14 x 1"-1/4 hex head metal
screw (with gasket and washer) for lower
gutter-to-mullion anchoring. (2) # 3/8" – 14 x
1"-1/4 hex head metal screws (with gasket and
washer) for intermediate gutter-to-mullion
anchoring.
- Sills: Parts no. SS1 and SS4.
- Center mullions: Parts no. T0 and T4.
- Intermediate mullions: Parts no. T1, T3, T5 and T11.
- Angle rafter: Parts no. T2, T6, T10 and T14.
- Lower gutters: Parts no. ET1A, ET2A, ET3A, ET4A, ET6A
and ET11A.
- Intermediate gutters: Parts no. ET3B, ET4B and ET6B.
- Pressure plates: Parts no. AL33-SHT080 for corner mullions
secured with (10) 1/4" – 20 x 3" mechanical
screws (with punctual isolator no.SPA1). Parts
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 4/11
no. AL-PPT250 for center and intermediate
mullions secured with (5) 1/4" – 20 x 1-1/2"
mechanical screws for 1" Thermo sides and
with (5) 1/4" – 20 x 3" mechanical screws for
Vision Control sides (with punctual isolator
no.SPA1). Parts no. AL-PPT-238 for gutters
secured with (4) 1/4" – 20 x 1-1/2" mechanical
screws for 1" Thermo sides and with (4) 1/4" –
20 x 3" mechanical screws for Vision Control
sides (with punctual isolator no.SPA1).
- Pressure caps: Parts no. AL55-SHT032 for angle rafters. Parts
no. AL-CAP87 for center and intermediate
mullions. Parts no. AL-CAP-B37for gutters.
- Head cap: Part no. PYR41.
- Auxiliary parts: Styrofoam insulation panels for back-pan
- Skylight dimensions: 3048 mm x 3048 mm x 759 mm in height
(120 in. x 120 in. x 30 in. in height)
- Overall dimensions: 3108 mm x 3108 mm x 984 mm in height
(122 in. x 122 in. x 39 in. in height)
*Including flashing detail
Sealant:
- Sealant at mullion-to-mullion junctions and at gutter-to-mullion junctions.
- Sealant at back-pan perimeter.
- Sealant between part no.AL33-SHT051 and part no.AL-MEN4509 (angle
rafter).
- Sealant at the junctions of the interior glazing seal (upper part of the pyramid).
- Sealant at pressure plate junctions.
- Sealant at pressure cap junctions.
- Sealant at pressure caps perimeter.
- Sealant at head cap perimeter.
- Sealant at flashing rivets.
- Sealant injection in the hole for the electricity cables (Vision Control device).
- Urethane foam application at the top of the skylight before head cap installation.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 5/11
Glazing method:
- Glass retention: With pressure plates
- Glazing seals: Exterior side: Gaskets no. PYF1 on pressure plates for
the center and intermediate mullions.
Butyl tape on pressure plates for the
corner mullions and gutters.
Interior side: Polyshim on mullions and gutters.
- Setting blocks: Aluminium support with neoprene 80 Duro setting block
(2 per bay) at the lower part of each sealed unit.
Glazing - Option no.1 (Thermo 1"):
- Type: Dual glazed insulated glass unit
- Total thickness: 25 mm (1 in.)
- Glass thickness: 6 mm (1/4 in) interior and 6 mm (1/4 in.) exterior.
- Type of glass: Interior laminated glass (3 mm clear + PVB 0.030 + 3
mm clear) and exterior tempered glass with LowE3-366
(Cardinal) on surface 2.
- Type of spacer: R-Max (non-conducting)
- Type of filling gas: Argon
Glazing - Option no.2 (Vision Control 2-1/2"):
- Type: Dual glazed insulated glass unit with integrated louvers.
- Total thickness: 65 mm (2.56 in.)
- Glass thickness: 6 mm (1/4 in) interior and 6 mm (1/4 in.) exterior.
- Type of glass: Interior laminated glass (3 mm clear + PVB 0.030 + 3
mm clear) and exterior tempered glass with Low-E
Energy Advantage (PPG) on surface 2.
- Type of spacer: Aluminium
- Type of filling gas: Air
Drainage system:
Drainage of interior cavities by the mullions, thru the exterior between the flashings.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 6/11
Hardware:
Opening and closing mechanism for Vision Control sides: (1) Electric motor (Baldor
Industrial Motor) per side with activating arm to operate the blades.
4.0 ALTERATION(S)
Alteration(s) performed in the laboratory on tested specimen to meet the reported performances:
None.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 7/11
5.0 TESTING RESULTS WITH REFRENCE TO AAMA & ASTM TESTINGPROCEDURES:
TESTTEST RESULTS
(METRIC UNITS)
TEST RESULTS
(IMPERIAL UNITS)
Air tightness
ASTM-E283-99
Skylight Surface = 9.76 m2
Qinf = 0.02 L/s•m2 @ 75 Pa
Qexf = 0.02 L/s•m2 @ 75 Pa
Qaverage = 0.02 L/s•m2 @ 75 Pa
Qinf = 0.07 L/s•m2 @ 300 Pa
Qexf = 0.06 L/s•m2 @ 300 Pa
Qaverage = 0.06 L/s•m2 @ 300 Pa
Qinf = 0.07 L/s•m2 @ 360 Pa
Qexf = 0.07 L/s•m2 @ 360 Pa
Qaverage = 0.07 L/s•m2 @ 360 Pa
Skylight Surface = 105.06 ft2
Qinf = 0.004 ft3/min•ft2 @ 1.57 psf
Qexf = 0.004 ft3/min•ft2 @ 1.57 psf
Qaverage = 0.004 ft3/min•ft2 @ 1.57 psf
Qinf = 0.013 ft3/min•ft2 @ 6.27 psf
Qexf = 0.011 ft3/min•ft2 @ 6.27 psf
Qaverage = 0.012 ft3/min•ft2 @ 6.27 psf
Qinf = 0.013 ft3/min•ft2 @ 7.52 psf
Qexf = 0.014 ft3/min•ft2 @ 7.52 psf
Qaverage = 0.013 ft3/min•ft2 @ 7.52 psf
Static waterinfiltrationresistance
ASTM-E547-00
ASTM-E331-00
No water infiltration under a differentialpressure of 720 Pa.
No water infiltration under a differentialpressure of 15 psf.
Dynamic waterinfiltrationresistance
AAMA 501.1-05
No water infiltration under a differentialpressure of 1367 Pa, equivalent to awind velocity of 170 km/h.
The equivalent velocity is calculated using theformula presented in article 3.2 of the AAMA501.1-05 Standard.
No water infiltration under a differentialpressure of 29 psf. equivalent to a windvelocity of 106 mph.
The equivalent velocity is calculated using theformula presented in article 3.2 of the AAMA501.1-05 Standard.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 8/11
Structuralresistance test
ASTM-E330-00
Deflection tests (Load design)
Net deflection measured at the mid-
height of vertical center mullion:
5.00 mm under a pressure + 3360 Pa.
6.62 mm under a pressure - 3360 Pa.
Deflection allowed (L/175): 7.98 mm
Net deflection measured at the mid-height of the angle rafter (cornermullion):4.73 mm under a pressure + 3360 Pa.
4.85 mm under a pressure - 3360 Pa.
Deflection allowed (L/175): 10.60 mm
Deflection tests (Load design)
Net deflection measured at the mid-
height of vertical center mullion:
0.196 in. under a pressure + 70 psf
0.261 in. under a pressure - 70 psf
Deflection allowed (L/175): 0.314 in.
Net deflection measured at the mid-height of the angle rafter (cornermullion):0.186 in. under a pressure + 70 psf
0.191 in. under a pressure - 70 psf
Deflection allowed (L/175): 0.417 in.
Structural tests (1.5 x Load of design)
Permanent deformation measured at the
mid-height of vertical center mullion:
0.74 mm under a pressure + 5040 Pa.
1.36 mm under a pressure - 5040 Pa.
Permanent deformation allowed :
(0.2% x L): 2.79 mm
Permanent deformation measured at the
mid-height of the angle rafter (corner
mullion):
0.76 mm under a pressure + 5040 Pa.
1.03 mm under a pressure – 5040 Pa.
Permanent deformation allowed :
(0.2% x L): 3.71 mm
Structural tests (1.5 x Load of design)
Permanent deformation measured at the
mid-height of vertical center mullion:
0.029 in. under a pressure + 105 psf
0.054 po. under a pressure - 105 psf
Permanent deformation allowed :
(0.2% x L): 0.110 in.
Permanent deformation measured at the
mid-height of the angle rafter (corner
mullion):
0.030 in. under a pressure + 105 psf
0.041 in. under a pressure - 105 psf
Permanent deformation allowed :
(0.2% x L): 0.146 in.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 9/11
6.0 TESTING RESULTS WITH REFERENCE TO CAN/CSA A440-00 "WINDOWS"
TEST SPECIFICATIONS TESTING RESULTS LEVEL
Airtightness
FIXED < 0.25 m3/h•m @ 75 Pa.
CAN/CSA-A440-00 par. 10.2 & 11.2ASTM-E283-99
Crack length = 57.66 m
Qinf = 0.01 m3/h•m @ 75 Pa
Qexf = 0.01 m3/h•m @ 75 Pa
Qaverage = 0.01 m3/h•m @ 75 Pa
FIXED
Watertightness
No water infiltration under apressure differential of:
B1: 150 Pa B5: 500 PaB2: 200 Pa B6: 600 PaB3: 300 Pa B7: 700 PaB4: 400 Pa
CAN/CSA-A440-00 par. 10.3 & 11.3
ASTM-E547-00
No water infiltration under adifferential pressure of 700 Pa.
B7
Wind loadresistance
Deflection Blow-outMullion Resistance
Pa Pa1000 C1 15001330 C2 20002000 C3 30002660 C4 40003330 C5 5000
CAN/CSA-A440-00 par. 10.4 & 11.4
ASTM-E330-00
Net deflection measured at the mid-
height of vertical center mullion:
5.00 mm under a pressure + 3360 Pa.
6.62 mm under a pressure - 3360 Pa.
Deflection allowed (L/175): 7.98 mm
Net deflection measured at the mid-height of angle rafter (cornermullion):4.73 mm under a pressure + 3360 Pa.
4.85 mm under a pressure - 3360 Pa.
Deflection allowed (L/175): 10.60 mm
Resistance to blow-out under apressure of 5.0 kPa
C5
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 10/11
Condensationresistance
Test in accordance with standardperspective of CAN/CSA-A440-00par. 10.12 & 11.12.
See Appendix B for a completedescription of the testingprocedure.
The surface temperaturesdistribution on the warm side ofthe specimen is shown in appendixB, Section B.4.
Glazing - Option no.1(Thermo 1"):
Ig (glass index) is: 64.8
If (Frame index) is: 56.8
I = 56.8
Glazing - Option no.2(Vision Control 2-1/2"):
Ig (glass index) is: 62.8
If (Frame index) is: 64.6
I = 62.8
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without the
written approval of Air-Ins Inc. 11/11
7.0 CONCLUSION
The results presented in this report confirm only the performance of the prototype as
described to Section 3.0. This report does not constitute certification of this product.
AIR-INS INC.
Prepared by : ________________________
Jean Miller, Eng.
Prepared by : ________________________
Jean Loubert, Eng.
Approved by :
Robert Jutras, Eng.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
APPENDIX A
ASSEMBLY DRAWINGS
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
APPENDIX BCONDENSATION RESISTANCE TEST PROCEDURE
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
B.1 INTRODUCTION
Air-Ins Inc. laboratories was retained by Unicel Architectural to test a skylight with
reference (and not according to) to the condensation resistance testing procedure outlined
in the CAN/CSA A440-00 Standard, as this type of product is not covered by this standard.
The scope of the CSA A440-00 Standard is intended for vertical installation in buildings
only. However, the global temperature Index (I-value) that can be obtained should be
perceived as a close approximation. This is because all the main requirements of this
standard such as: thermal conditions, data collection and calculations rules are respected.
Obviously, the testing setup has been adapted according to the particular geometry of the
sample. The sample components and manufacturing are documented in section 3.0 of this
report.
B.2 TESTING PROCEDURE
Description of testing
This type of thermal test consists of sealing the sample in a test unit with hot and cold
chambers. Thermocouples are installed on specific locations on the surface of the sample
as defined by the testing procedure. These thermocouples allow obtaining the temperature
distribution on the interior surface. A system composed of fans, heating, cooling and
controlling allowed obtaining testing conditions maintained in permanent rate of flow for
the required period. The illustration on the next page shows the set-up used for the
condensation resistance test.
Requirements of the CSA-A440-00 Standard
The room side temperature (Th) shall be maintained at 20 ± 1°C and the weather side
temperature (Tc) shall be maintained at –30 ± 1°C.
The pressure difference across the sample must be near zero ± 5 Pa when measured at
mid-height of the sample.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
Once the temperature stability is reached, the sample is maintained at this temperature for
five hours. After the five-hour period, 5 consecutive temperature readings are taken at 10-
minute intervals, for a total data collection period of 50 minutes. There shall be no
temperature difference between any two readings exceeding 1°C at each location.
The interior face of the frame sample shall be aligned with the interior face of the panel
that contains the sample. See note (1) below for deviation from this requirement.
The global temperature index "I" which characterizes the performance of the sample is the
smaller value between the glass temperature Index "Ig" and the frame temperature Index
"If" on the entire sample.
Note (1): The skylight geometry doesn’t allow aligning the interface of the room
side with each section of the skylight
Testing Set-up
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
B.3 RESULTS
Drawings in section B.4 of this Appendix show the surface temperature distribution on the
warm side of the sample. Note that two glazing options were simultaneously tested; one
side of the skylight had Thermo 1" glazing installed (option no. 1) and the opposite side
had Vision Control 2-1/2" glazing installed (option no. 2)
Option no. 1: Thermo 1" glazing
Determination of the Temperature Index (I)
For the glass: For the frame:
Weather side air temperature (Tc) = -30.2°C
Room side air temperature (Th) = 20.3°C
Average surface temperature of glass (Tg) = 2.5°C
Coldest frame temperature (Tf) = -1.5°C
Difference between the temperature (Tg) and
the weather side temperature (Tc) = 32.7°C
Difference between the temperature (Tf) and
the weather side temperature (Tc) = 28.7°C
Difference between the room side temperature
(Th) and the weather side temperature (Tc) = 50.5°C
Temperature Index for the glass Ig = 32.7°C x 100 = 64.850,5°C
Temperature Index for the frame If = 28.7°C x 100 = 56.850,5°C
Global Temperature Index (I) is: "I" = 56.8
100100 xTcTh
TcTfIx
TcTh
TcTgI
fg
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
Option no. 2: Vision Control 2-1/2" glazing
Determination of the Temperature Index (I)
For the glass: For the frame:
Weather side air temperature (Tc) = -30.2°C
Room side air temperature (Th) = 20.3°C
Average surface temperature of glass (Tg) = 1.5°C
Coldest frame temperature (Tf) = 2.4°C
Difference between the temperature (Tg) and
the weather side temperature (Tc) = 31.7°C
Difference between the temperature (Tf) and
the weather side temperature (Tc) = 32.6°C
Difference between the room side temperature
(Th) and the weather side temperature (Tc) = 50.5°C
Temperature Index for the glass Ig = 31.7°C x 100 = 62.850,5°C
Temperature Index for the frame If = 28.7°C x 100 = 64.650,5°C
Global Temperature Index (I) is: "I" = 62.8
100100 xTcTh
TcTfIx
TcTh
TcTgI
fg
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
B.4 TEMPERATURES DISTRIBUTION
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
APPENDIX C
PHOTOGRAPHS
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.
AIR-INS inc.
Project: AS-00248-A1
Performance Evaluation: Aluminium Skylight
The results in this report relate only to the items tested. This report shall not be reproduced except in full, without thewritten approval of Air-Ins Inc.