pf2100i quick user guide v1.1 - profire energy · 2016. 6. 14. · profire pf2100i - quick user...
TRANSCRIPT
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Pagei
PROFIREPF2100IQUICKUSERGUIDE
v1.1
RevisedOct20,2014LastRevisedbyAlexMessner
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Pageii
TableofContents
1 Introduction.................................................................................................................................................2
2 Hardware.....................................................................................................................................................3
2.1 Overview..........................................................................................................................................3
2.2 Wiring...............................................................................................................................................3
2.3 ThermocoupleInputs.......................................................................................................................3
3 ProcessControl............................................................................................................................................4
3.1 Overview..........................................................................................................................................4
3.2 Timing..............................................................................................................................................4
3.3 Setpoints..........................................................................................................................................5
3.4 Deadband.........................................................................................................................................6
3.5 Shutdown/Warning/Alarmcodes....................................................................................................6
4 Accessories...................................................................................................................................................7
4.1 4-20mAOutput................................................................................................................................7
4.2 ProportionalValveControl..............................................................................................................7
4.3 StartContact....................................................................................................................................7
4.4 ModbusExpansionCardSupport.....................................................................................................7
4.5 4-20mAExpansionCardSupport.....................................................................................................7
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page2
1 IntroductionThePF2100IisanIncineratorManagementSystemdesignedforusewithincineratorsandcombustorswhereassistgasisutilized.Thecombustionchambermustbemaintainedaboveacertaintemperaturebeforethewastegasispermittedtoflow.ThePF2100Iachievesthisbyutilizingathermocoupletomonitorthechambertemperatureandavalvetocontroltheassistgas.Oncethechamberisheateduptothesettemperaturewiththeassistgasthevalveforthewastegasopens.
Optionalexpansioncardscanbeaddedtothesystemtoenableremotecontrolofthesystem,remotemonitoring,analogpressuremeasurementordatalogging.
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page3
2 Hardware2.1 Overview
ThePF2100IusesthesamehardwareasthePF2100BMS.AlthoughtheLEDbehaviorofthePF2100Iisslightlydifferent.ThePF2100Igetshippedwithanewkeypad.ThenewLEDlabelsare:
§ Pilot§ AssistGas§ WasteGas
2.2 Wiring
The2100IfollowsthesamewiringconventionasthePF2100BMSwiththefollowingexceptions:
§ ConnecttheAssistGasValvetotheLowFirecontacts§ ConnecttheWasteGasValvetotheHighFirecontacts
2.3 ThermocoupleInputs
ThePF2100Irequirestwothermocoupleslocatedinthesamethermowelltooperate:
§ ChamberTC(ProcessTempinPF2100)§ HighTempTC
Thesetwothermocouplesarecontinuouslycomparedtoeachother,iftheydonotmatchthesystemwillshutdown.
ThePF2100IhastheabilitytousetheAuxiliaryTCforeitherdisplaypurposes,ortocheckanadditionalhightempESDcondition.
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page4
3 ProcessControl3.1 Overview
ThefollowinggraphillustratesthePF2100I’sprocesscontrolwhenthesystemisstarted.Thisgraphisintendedasaroughoverviewoftheprocesscontrolalgorithm,andassuchitdoesnotincludeeverydetailintheprocesscontrolalgorithmsuchasdeadbands.
1. 30secondsafterthepilotflameisdetected,theassistgasvalveopenstoincreasetherateofheating2. Whenthechambertemperaturereachesthe“WasteGasOn”setpoint,thewastegasvalveimmediately
opensandincinerationbegins3. Whenthechambertemperatureexceedsthe“AssistGasOff”setpoint,theassistgasvalveimmediately
closes.Incinerationofwastegascontinues4. Whenthechambertemperaturedropsbelowthe“AssistGasOff”setpoint,theassistgasvalve
immediatelyopens.5. See#3
3.2 Timing
§ Fixed30seconddelaybetweenpilotlightandassistgasvalveopening§ Nominimumtimedelaybetweenassist/wastegasvalvetransitions.PF2100Ireliesondeadbandto
preventvalveinstability
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page5
3.3 Setpoints
ThePF2100Ialwaysrequiresatleastthreesetpoints:
§ “WasteGasOn”setpoint(WGONSP):Whentheprocesstemperatureisabovethissetpoint,thewastegasvalveopens.Ifthetemperaturedropsbelowthissetpointthewastegasvalvecloses.Thissetpointhasnoimpactontheassistgasvalve
§ “AssistGasOff”setpoint(AGOFFSP):ThissetpointmustbehigherthantheWGONSP.Iftheprocesstemperatureisabovethissetpoint,theassistgasvalvecloses.Ifthetemperaturedropsbelowthissetpointtheassistgasvalvere-opens.Thissetpointhasnoimpactonthewastegasvalve.
§ HighTempESD
Eachofthesesetpointsiscomparedagainstthechambertemperature(ChamberTCandHighTempTCinputs).
Ifanauxiliarythermocoupleisconnected,itcanalsobeconfiguredforhightempESDs,withitstemperatureandsetpointhandledindependentlyfromtheotherthermocouples.
ThefollowingdiagramillustratesthesetpointsusedbythePF2100I:
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page6
3.4 Deadband
WhenthechambertemperaturefallsbelowtheWasteGasOnorAssistGasOffsetpoints,thecorrespondingstatetransitionisnotmadeimmediatelybythePF2100I.Thetemperaturemustfallbelowthesetpointminusaspecifieddeadbandvaluebeforeastatetransitionoccurs.Theexactbehaviourisdifferentforeachsetpoint:
WasteGasOn§ Fixed2⁰C(3⁰F)deadband
AssistGasOff
§ Adjustabledeadbandfrom30-200⁰C(50-300⁰F)§ AssistGasOffsetpointminusthedeadbandmustbehigherthantheWasteGasOnsetpoint.
3.5 Shutdown/Warning/Alarmcodes
Shutdown/Warning/AlarmcodesareconsistentwithPF2100BMS.
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page7
4 Accessories4.1 4-20mAOutput
The4-20mAOutputsupportsmirroringofthechambertemperatureaswellasproportionalvalvecontrol.
The4-20mAtemperaturesignalisencodedaccordingtothefollowing:
§ 4mA=0⁰C(32⁰F)§ 20mA=HighTempESDSetpoint
4.2 ProportionalValveControl
ThePF2100IincludesthemostrecentPIDcontrollerusedbythePF2100BMS.
ThePIDwilltrytomaintainWasteGasSetpoint+Deadband.
4.3 StartContact
TheStartContactonthePF2100IbehavesidenticallytoitsPF2100counterpart.
4.4 ModbusExpansionCardSupport
ThePF2100IsupportModbuscardswiththemostrecentfirmwareversions.
TheModbusExpansionCardRegisterMap,availableatwww.profireenergy.com,providesdescriptionsoftheModbusregister.
4.5 4-20mAExpansionCardSupport
ThePF2100Isupportsthe4-20mAexpansioncardforpressureonly.Thelevelandauxiliaryinputsontheexpansioncardwillnotprovideanyfunctionality.
4.6 DataLoggingExpansionCardSupport
ThePF2100IsupportDataLoggingcardswiththemostrecentfirmwareversions.
PROFIREPF2100I-QUICKUSERGUIDE
©2014ProfireEnergyInc.-Thisdocumentcontainsconfidentialandproprietaryinformationnotintendedtobereleasedoutsideofthecompany.
v1.1Jun14,2016
Page8