pg&e optimizing chilled water plants - rv 13 1 day version
TRANSCRIPT
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 1/196
Presented by:
Steve Taylor
The PG&E Pacific Energy Center Presents:The PG&E Pacific Energy Center Presents:
Optimizing the Design and Control ofOptimizing the Design and Control of
Chilled Water PlantsChilled Water Plants
March 7, 2012
Taylor Engineering LLCAlameda, CA
http://www.taylor-engineering.com
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 2/196
LogisticsLogistics
SafetyRestroomsRecycling
Cell phone etiquette
2
Review formsWebinar etiquette
PG&E Resources• Rebates• Tool Lending Library• Marlene Vogelsang ([email protected])
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 3/196
HandoutsHandouts
You can get a copy of the handoutsin PDF format as follows:• Type the following link into your web
browser: -
3
engineering.com/ftp/PECClassHandouts.html
• Click on the link for the Chilled Water PlantClass on 3/7/2012 to download the Acrobatfile of the presentation.
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 4/196
About Steve TaylorAbout Steve TaylorPrincipal, Taylor EngineeringEducation• Stanford University, BS Physics, 1976• Stanford University, MS Mechanical Engineering, 1977
ASHRAE• Fellow• Standard 62 Indoor Air Quality, 8 years, chair
• Standard 90.1 Energy Standard, Chair HVAC Subc., 14 years• Standard 55 Thermal Comfort
4
• Guideline 16 Economizer Dampers, chair • Guideline 13 Specifying Direct Digital Control Systems, chair • TC 4.3 Ventilation, vice-chair • TC 1.4 Control Theory & Applications, chair • Author “Fundamentals of Design and Control of Central Chilled Water Plants” Course• Distinguished Lecturer
USGBC LEED• Indoor Environmental Quality TAG, vice chair UMC/IAPMO (California Mechanical Code)• Mechanical Technical Committee, member and ASHRAE Liaison
CSU• Mechanical Review Board, member
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 5/196
Who are You?Who are You?
Consulting Engineers?Design/Build Engineers?Contractors?
5
Building Owners/Engineers?Equipment rep/supplier/manufacturer?Commissioning authority?Other?
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 6/196
AgendaAgenda
Introduction 9:00 AMCHW Distribution Systems 9:15 AMBreak 10:45 AMCHW Distribution System Balancing 11:00 AM
6
str ut on ystems :Lunch 12:00 PMSelecting CHW Distribution Systems 1:00 PMSelecting CHW ∆T 1:30 PMSelecting CW ∆T 2:00 PMSelecting Chillers 2:30 PMOptimizing control sequences 3:00 PMQuestions 4:15 PMCompletion 4:30 PM
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 7/196
ResourcesResourcesCoolTools™ Chilled Water Plant Design and Specification Guide,PG&E Pacific Energy Center Balancing Variable Flow Hydronic Systems. ASHRAE JournalOct 2002, Atlanta GA.Primary-Only vs. Primary-Secondary Variable Flow Systems.ASHRAE Journal February 2002, Atlanta GA.
Degrading Chilled Water Plant Delta-T: Causes and Mitigation,ASHRAE Transactions January 2002, Atlanta GA. AC-02-06
7
Sizing Pipe using Life Cycle Costs, ASHRAE Journal, October2008 – and LCC Piping spreadsheetWaterside Economizing in Data Centers: Design and ControlConsiderations, ASHRAE Transactions 2009, LO-09-015Optimized Design & Control of Chilled Water Plants, ASHRAEJournal• Part 1: Chilled Water Distribution System Selection• Part 2: Condenser Water Distribution System Design• Part 3: Pipe Sizing and Optimizing ∆T• Part 4: Chiller & Cooling Tower Selection• Part 5: Optimized Control Sequences
All are available at no charge from http://www.taylor-engineering.com/publications/artic les.shtml
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 8/196
Design Guide ScopeDesign Guide Scope
New Construction• Hydronic design
• Chiller selection
Retrofit• Replacement
chillers
8
• Cooling tower selection• Control optimizations• Commissioning
• on o s• Control optimization• Commissioning
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 9/196
Optimizing Energy UsageOptimizing Energy Usage
Chillers• Type, efficiency, size, VSD
Cooling Towers• Fan type, efficiency, approach, range, speed control, flow
turndownChilled Water Pum s
9
• Arrangement, flow rate (delta-T), pressure drop, VSD
Condenser Water Pumps• Flow rate (delta-T), pressure drop
Air Handling Units• Coil sizing, air-side pressure drop, water-side pressuredrop
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 10/196
Pop Quiz 1Pop Quiz 1
What happens to componentenergy usage if we lower CWSsetpoint?• Chiller
• Towers• Pumps
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 11/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 12/196
Pop Quiz 3Pop Quiz 3
What happens to componentenergy usage if we lower CW flowAND the CWS setpoint?• Chiller
• Towers• Pumps
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 13/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 14/196
14
SystemsSystems
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 15/196
Water Distribution System ClassesWater Distribution System Classes
Constant Flow• No control valves• 3-way control valves
Variable Flow• Primary-Only• Primary/Secondary
(/Tertiary)• Primar /Distributed
15
Secondary
• Primary/Variable SpeedCoil Secondary
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 16/196
CHILLER
CHWPUMP
SUPPLY WATERTEMPERATURE
Constant FlowConstant FlowSingle Chiller, Single Coil, No Control ValveSingle Chiller, Single Coil, No Control Valve
16
OPTIONALSTORAGE
TANK
COIL
SUPPLY AIRTEMPERATURE
Works also for boilers that havemodulating burners and verygood turndown, e.g. ≥10 to 1
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 17/196
Constant FlowConstant FlowTwo Chillers, Single Coil, No Control ValveTwo Chillers, Single Coil, No Control Valve
CHILLER #2
CHWPUMP
SUPPLY WATERTEMPERATURE
VFD
CHILLER#1
17
OPTIONALSTORAGE
TANK
COIL
SUPPLY AIRTEMPERATURE
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 18/196
Constant FlowConstant FlowSingle Chiller, Multiple CoilsSingle Chiller, Multiple Coils
CHILLER
CHWPUMP
COIL
18
3-WAY VALVE
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 19/196
CHILLER
CHWPUMP
SUPPLY WATERTEMPERATURE
VFD
Variable FlowVariable FlowSingle Chiller, Multiple CoilsSingle Chiller, Multiple Coils
19
COIL2-WAY VALVE
DP SENSOR
3-WAY VALVE
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 20/196
CHILLER #1
CHWPUMPS
SUPPLY WATERTEMPERATURE
CHILLER #2
Constant FlowConstant FlowMultiple Parallel Chillers, Multiple CoilsMultiple Parallel Chillers, Multiple Coils
CH2 240 gpm
CH1 240gpm How many
chillers do weneed to run?
20
COIL
3-WAY VALVEBallroom A 240 gpm
Ballroom B 240 gpm
Ballroom A240 gpm
100% Loaded
Ballroom B0 gpmUnoccupied
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 21/196
Variable FlowVariable Flow
Vary Flow Through Coil Circuit• Two-way valves• Variable speed coil pump
Confi urations
21
• Primary-secondary• Primary-secondary variations
• Primary-only
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 22/196
Variable Flow Chilled WaterSystems
Old Paradigm• Controls respond to changes in CHW
temperature
• Variable flow causes low temperature trips,
22
locks out chiller, requires manual reset(may even freeze)
• Hence: Maintain constant flow through
chillers
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 23/196
Primary/SecondaryPrimary/Secondary
23
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 24/196
Primary/SecondaryPrimary/Secondary
ON
ON
100gpm
100gpm
100gpm
24
ON
OFF
100gpm
100gpm
0 gpm
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 25/196
Variable FlowVariable FlowPrimary/Secondary, Multiple Chillers and CoilsPrimary/Secondary, Multiple Chillers and Coils
CHILLER #1
PRIMARYPUMPS
CHILLER #2
COMMON LEG (DECOUPLER)
25
COIL2-WAY VALVE
V F D
V F D
SECONDARYPUMPS
DP SENSOR
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 26/196
Variable FlowVariable FlowPrimary/Secondary, Series Flow, Multiple ChillersPrimary/Secondary, Series Flow, Multiple Chillers
26
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 27/196
Variable FlowVariable FlowPrimary/Distributed SecondaryPrimary/Distributed Secondary
27
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 28/196
Variable FlowVariable FlowPrimary/Secondary/TertiaryPrimary/Secondary/Tertiary
28
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 29/196
Variable Flow Chilled Water SystemsVariable Flow Chilled Water Systems
New Paradigm• Modern controls are robust and very
responsive to both flow and temperature
variations
29
• Variable flow OK within range and rate-of-change spec’d by chiller manufacturer
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 30/196
Variable FlowVariable FlowPrimaryPrimary- -only, Multiple Chillersonly, Multiple Chillers
CHILLER #1
PRIMARYPUMPS
CHILLER #2
FLOWMETER
VFD
VFD
PRIMARYPUMPS
VFD
30
2-WAY VALVECOIL
DP SENSOR
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 31/196
Variable FlowVariable FlowPrimary, Bypass ValvePrimary, Bypass Valve
Location• Near chillers
Best for energyControls less expensiveControl more difficult to
tune – fast response•
31
Smaller pressurefluctuations (easier tocontrol)Keeps loop cold for fastresponse
Sizing• Sizing critical when at
chillers/pumps• Different size if pump has
VFD or not
Flow measurement• Flow meter
Most accurateNeeded for Btu calc forstaging
• DP across chiller Less expensive
Accuracy reduced as tubesfoulOne required for each chiller
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 32/196
Primary CHW Pump OptionsPrimary CHW Pump Options
32
Dedicated Pumping Advantages:• Less control complexity• Custom pump heads w/ unmatchedchillers• Usually less expensive if each pumpis adjacent to chiller served• Pump failure during operation doesnot cause multiple chiller trips
Headered Pumping Advantages:• Better redundancy• Valves can “soft load” chillers with primary
onlysystems
• Easier to incorporate stand-by pump
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 33/196
Balancing Variable FlowS stems
33
See “ Balancing Variable Flow Hydronic Systems ” ASHRAE Journal Oct 2002
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 34/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 35/196
Variable Flow Balancing OptionsVariable Flow Balancing Options
1. No balancing• Relying on 2-way control valves to automatically provide
balancing
2. Manual balance• Using ball or butterfly valves and coil pressure drop
• Using calibrated balancing valves (CBVs)
35
3. Automatic flow limiting valves (AFLVs)4. Reverse-return5. Oversized main piping6.
Undersized branch piping7. Undersized control valves8. Pressure independent control valves
• Not studied in our ASHRAE paper
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 36/196
Piping Systems AnalysisPiping Systems Analysis
Heating system• 540 gpm• 400 VAV reheat coils• Constant speed pumps
• Based on actual building in Oakland
36
Cooling system• 1,200 gpm• 20 Floor-by-floor AHUs• Variable speed pumps
All valves: 2-way modulatingAnalyzed using Pipe-Flo
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 37/196
HW Piping Floor PlanHW Piping Floor Plan
37
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 38/196
Typical Coil PipingTypical Coil Piping
Options 1, 4, 5, 6, & 7
38
Option 2
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 39/196
Typical Coil PipingTypical Coil Piping
Option 3
39
Option 8
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 40/196
Option 1: No BalancingOption 1: No BalancingAdvantages• No balancing labor • Coils may be
added/subtractedwithout rebalance
Disadvantages• Imbalance during
transients or ifsetpoints areimproper
• Control valves near
40
pumps can be over-pressurized,reducingcontrollability
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 41/196
Option 2: Manual w/CBVsOption 2: Manual w/CBVs
Advantages• Valves can be used for
future diagnosis (flow canbe measured)
• Reduced over-
pressurization of control
Disadvantages• Added cost of calibrated
balancing valve• Higher balancing cost• Complete rebalance
may be required if coilsadded/subtracted
41
• Slightly higher pumphead due to balancingvalve
• Coils may be starved ifvariable speed drivesare used without DPreset
• Slightly higher pumpenergy depending onflow variations andpump controls
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 42/196
Starved Loads with CBVs and Fixed DPStarved Loads with CBVs and Fixed DPSetpoint: Design ConditionSetpoint: Design Condition
12 PSID38 PSID45 PSID
20
60
50
40
30
70
P R
E S S U R E P S I G
42
VFD L o a d
L o a d
DP
100 GPM5 PSID
100 GPM5 PSID
5 PSID
28 PSID, Cv=19
5 PSID
2 PSID
PUMP CLOSE LOAD REMOTE LOAD
10
0
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 43/196
Starved Loads with CBVs and Fixed DPStarved Loads with CBVs and Fixed DPSetpoint: No Remote Flow ConditionSetpoint: No Remote Flow Condition
12 PSID12 PSID19 PSID
20
60
50
40
30
70
P R E S S U R E P S I G
43
56 GPM
1.6 PSID
0 GPM
0 PSID
1.6 PSID
8.8 PSID
12 PSID
0 PSID
VFD L o a d
L o a d
DP
PUMP CLOSE LOAD REMOTE LOAD
0
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 44/196
Option 3: Automatic Flow LimitingOption 3: Automatic Flow LimitingValvesValves
Advantages• No balancing labor • Coils may be
added/subtracted withoutrebalance
Disadvantages• Added cost of strainer and
flow limiting valve• Cost of labor to clean
strainer at start-up
•Higher pump head andenergy due to strainer and
44
ow m ng va ve• Valves have custom flow
rates and must beinstalled in correct location
• Valves can clog or springs
can fail over time• Control valves nearpumps can be over-pressurized, reducingcontrollability
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 45/196
Option 4: ReverseOption 4: Reverse- -returnreturn
45
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 46/196
Reverse Return ConfigurationsReverse Return Configurations
C/C
C/CH/C
H / C
H / C
H/C
46
C/C
C/C
Reverse return riser (elevation)
Reverse return on floor (plan)
H/C H/C
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 47/196
Option 4: ReverseOption 4: Reverse- -returnreturnAdvantages• No balancing labor • Coils may be
added/subtracted withoutrebalance
• No significant over-
Disadvantages• Added cost of reverse-
return piping• Not always practical
depending on physical
layout of system
47
valves close to pumps.
• Usually lower pump headdue to reverse-returnpiping having lower
pressure drop than mains(due to larger pipe)
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 48/196
Option 5: Oversized Main PipingOption 5: Oversized Main Piping
C/C
C/C
6” 6”
C/C
C/C
2” 2”
3” 3”
48
Standard main design
C/C
C/C
Oversized main riser
6” 6”C/C
C/C
6” 6”
4” 4”
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 49/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 50/196
Option 6: Undersized Branch PipingOption 6: Undersized Branch Piping
Advantages• No balancing labor • Reduced cost of smaller
piping• Coils may be
added/subtracted withoutrebalance
Disadvantages• Limited effectiveness and
applicability due to limitedavailable pipe sizes
• High design and analysiscost to determine correctpipe sizing
50
• e uce over-pressurization of controlvalves close to pumpswhere piping has beenundersized
coils where piping hasbeen undersized
• Coils may be starved ifvariable speed drives areused without DP reset
• Slightly higher pumpenergy depending on flowvariations and pumpcontrols
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 51/196
Option 7: Undersized Control ValvesOption 7: Undersized Control Valves
Advantages• No balancing labor • Reduced cost of smaller
control valves• Coils may be
added/subtracted withoutrebalance
Disadvantages• Limited effectiveness and
applicability due to limitedavailable control valvesizes (Cv)
• High design and analysiscost to determine correct
51
• e uce over-pressurization of controlvalves close to pumpswhere control valves havebeen undersized
•Improved valve authoritywhich could improvecontrollability wherecontrol valves have beenundersized
• Coils may be starved ifvariable speed drives arewithout DP reset
• Slightly higher pumpenergy depending on flowvariations and pumpcontrols
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 52/196
Option 8: Pressure Independent Control ValvesOption 8: Pressure Independent Control Valves
Advantages• No balancing labor • Coils may be
added/subtractedwithout rebalance
• No over-pressurization
Disadvantages• Added cost of strainer and
pressure independent controlvalve
• Cost of labor to clean strainerat start-up
• Hi her um head and ener
52
to pumps
• Easy valve selection –flow only not Cv
• Perfect valve authority
will improvecontrollability• Less actuator travel and
start/stop may improveactuator longevity
due to strainer and pressureindependent control valve
• Valves have custom flow ratesand must be installed in correctlocation
• Valves can clog or springs canfail over time
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 53/196
PICVs May Improve ∆T?PICVs May Improve ∆T?
53
NBCIP Test Lab (as reportedby manufacturer)
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 54/196
Controllability & TransientsControllability & TransientsPercent of design flow
(percent of design coil sensible capacity)with all control valves 100% open
Maximumpressure drop
of control valverequired fordesign flow,
feet
Maximum flowthrough closest coil
Minimum flowthrough most
remote coil
Balancing Method
CHW HW CHW HW CHW HW
1 No balancing 20.5 44.4 143%(106%)
212%(119%)
73%(89%)
75%(96%)
54
anua a anceusing calibrated
balancing valves(100%) (100%) ( 100%) ( 100%)
3 Automatic flowlimiting valves
20.5* 44.4* 100%(100%)
100%(100%)
100%(100%)
100%(100%)
4 Reverse-return 1.2 10.4 103%(100%)
150%(109%)
99%(100%)
85%(97%)
5 Oversized main piping 7.0 20.9 122%(103%) 173%(112%) 94%(99%) 82%(97%)
6 Undersized branch piping
19.5 NA 142%(106%)
NA 73%(100%)
NA
7 Undersized controlvalves
8.0 NA 120%(103%)
NA 86%(89%)
NA
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 55/196
Energy & First CostsEnergy & First Costs
Incremental First Costsvs. Option 1Pump head,
feet
Annual PumpEnergy,
$/yr $$ per design
gpmBalancing Method
CHW
HW CHW HW CHW HW CHW HW
1 No balancing 58.5 82.7 $1,910 $3,930 – – – –
55
2 Manual balance using calibrated balancing valves
60.3 83.6 $1,970 $3,970 $7,960 $47,530 $6.60 $88.00
3 Automatic flow limiting valves 66.6 90.8 $2,170 $4,310 $11,420 $50,750 $9.50 $94.00
4 Reverse-return 55.3 80.0 $1,810 $3,800 $28,460 $17,290 $23.70 $32.00
5 Oversized main piping 45.0 59.3 $1,470 $2,820 $12,900 $7,040 $10.80 $13.00
6 Undersized branch piping 58.5 NA $1,910 NA ($250) NA ($0.20) NA7 Undersized control valves 58.5 NA $1,910 NA ($2,340) NA ($2.00) NA
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 56/196
RanksRanks Balancing Method Controllability
(all conditions)Pump Energy
Costs First Costs
1 No balancing 7 3 32 Manual balance using calibrated
balancing valves 4 6 6
3 Automatic flow limiting valves 7 7 7
4 Reverse-return 2 2 5
56
vers ze ma n p p ng
6 Undersized branch piping 6 4 27 Undersized control valves 5 4 18 Pressure independent control
valve 1 8 87
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 57/196
Conclusions & Recommendations forConclusions & Recommendations forVariable Flow Hydronic SystemsVariable Flow Hydronic Systems
Automatic flow-limiting valves are not recommended on any variableflow system• They only limit flow for transients which has little or no value
Calibrated balancing valves are also not recommended for balancingvariable flow systems• But useful for future diagnostics on small low pressure drop coils – just leave them
wide open (no throttling)
57
24/7 chilled water systemsUndersizing piping and valves near pumps improves balance and costsare reduced, but significant added engineering time requiredPressure independent valves should be considered on very largesystems (>100 ft head) for coils near pumps
• Cost is high but going down now with competition• When costs are competitive, this may be best choice for all jobs
For other than very large distribution systems, option 1 (no balancing)appears to be the best option• Low first costs with minimal or insignificant operational problems
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 58/196
Break Break
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 59/196
Problems caused by DegradingProblems caused by Degrading ∆∆∆∆∆∆∆∆ TT
Q= 500 X GPM X ∆ T
59
For a Given Load Q, When ∆∆∆∆ T Goes Down, GPM Goes upResult:• Increases pump energy• Can require more chillers to run at low load, or coils will be
starved of flow• Can result in reduced plant effective capacity: chiller capacitywithout the capability of delivering it
ResourceJanuary 2002 ASHRAE Symposium Paper, “Degrading ChilledWater Plant Delta-T: Causes and Mitigation
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 60/196
42 oF80%
Primary/secondary “death spiral”Primary/secondary “death spiral”
Chillers staged by Load
60
52 oF
42 oF
When ∆∆∆∆ T Degrades,Secondary Flow
Exceeds Primary50 oF
46 oFVFD
VFD
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 61/196
∆∆∆∆∆∆∆∆ T Degradation in Large Chiller PlantT Degradation in Large Chiller Plant(January through March)(January through March)
l t a T
( ° F )
35°F-40°F40°F-45°F
7.0°F-7.5°F
9.5°F-10.0°F
Coincident WetBulb Ranges
Design∆Τ=10 oF
0 100 200 300 400 500 600 700 800
Approximate hrs/yr
E v a p o r a t o r
D e
45°F-50°F50°F-55°F55°F-60°F
2.0°F-2.5°F
4.5°F-5.0°F
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 62/196
Causes of DegradingCauses of Degrading ∆ TT
1. Causes that can be avoided by properdesign or operation of the chilled watersystem;
2. Causes that can be mitigated, but
62
overall energy savings; and
3. Causes that are inevitable and simplycannot be avoided
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 63/196
DegradingDegrading ∆ TT#1. Causes that can be eliminated by design/operation#1. Causes that can be eliminated by design/operation
Improper Setpoints or Calibration• e.g. dropping coil SATsp by 2ºF will double the flow rate and halve the
∆TUse of Three-way Valves• Instant response is not a valid reason for 3-way valves
No Control Valve Interlock• i.e. valve open when fan is off
Coils Piped Backwards (parallel flow vs. counter-flow)
63
Uncontrolled Process Loads• need isolation valves
Incorrectly Selected Control Valves• Oversized valves hunt and result in higher average flow• Undersized actuators have insufficient close-off pressure
Incorrectly Selected Coils• Common problem when new buildings don’t follow the campusstandard ∆T
Improper “Bridge” Connection & Control• Bridge valve cannot raise the CHWRT without starving the load
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 64/196
DegradingDegrading ∆ TT#2 Measures that improve#2 Measures that improve ∆ T but energy tradeT but energy trade- -off off
Chilled Water Reset to Lower ChilledWater Supply Temperature• Lowering CHWST by 1ºF increases ∆ T by 1
to 2ºF but reduces chiller efficiency
64
• Net effect could be better (if high pumpenergy) or worse (low pump energy)
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 65/196
Coil Pumps to Prevent ∆∆∆∆ T Degradationat Low Flow Due to “Laminar FlowEffect”
DegradingDegrading ∆ TT#2 Measures that improve#2 Measures that improve ∆ T but energy tradeT but energy trade- -off off
65
coil pump energy is very high
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 66/196
12
14
16
18
20
r e e s - F )
Dual Row, 5/8" TubesFull Row, 5/8" TubesFull Row, 1/2" Tubes
Laminar Flow “Problem:”Laminar Flow “Problem:”Real or Myth?Real or Myth?
Data from MajorCoilManufacturer’s ARIcertified ratingprogramdeveloped fromlab tests
0
2
4
6
8
10
0%20%40%60%80%100%
% Sensible Load
D e l t a - T
( d e g
LaminarFlow
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 67/196
Primary/Secondary vs. Primary/SecondaryPrimary/Secondary vs. Primary/Secondarywith Coil Pumpswith Coil Pumps
P/S/T withconstant
∆∆∆∆ T25.00
30.00
35.00
40.00
45.00
50.00
p k W
67
P/S withdegrading
∆∆∆∆ T
0.00
5.00
10.00
15.00
20.00
0% 20% 40% 60% 80% 100%
% Plant Load
P u
3-chiller/3-pump plant,total 1440 gpm
Conclusion: even if the laminar flow problem were real, coilpumps are not a good solution. They add to both first costsand energy costs.
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 68/196
Causes of DegradingCauses of Degrading ∆ TT#3. Causes That Cannot Be Eliminated#3. Causes That Cannot Be Eliminated
Air Economizers and 100% Outdoor AirSystems
60 oF
42 oF
CHWST(Design CHWRT of62, based on design
68
Degrading Coil Effectiveness with AgeCHWST Setpoint ResetOthers as Yet Undetermined?
SAT EAT<<60 oFCHWRT
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 69/196
ConclusionsConclusions
Design, Construction, and OperationErrors that Cause Low DT can andShould be Avoided
But Other Causes for Low DT can Never
69
Conclusion: At Least Some DTDegradation is Inevitable
Therefore: Design the CHW Plant to Allowfor Efficient Chiller Staging DespiteDegrading DT
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 70/196
Some SolutionsSome Solutions
Use Variable Speed Drives on Chillers so thatthey Operate Efficiently at Low LoadDesign CHW Distribution System so Chillers canhave Increased Flow So They can be More Fully
Loaded at Low DT
70
• Primary-only pumping• Unequal chiller and primary pump sizes, headered pumps
so large pump can serve small chiller • Low design delta-T in primary loop
Insures low ∆T in secondaryHigher primary loop first costs & energy costs
• Primary/secondary pumping with check valve in commonleg
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 71/196
Check Valve in the Common LegCheck Valve in the Common Leg
71
CHECKVALVE INCOMMON
LEG
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 72/196
Supposed DisadvantagesSupposed DisadvantagesCheck Valve in Common LegCheck Valve in Common Leg
Circuits are not Hydraulically Independent• So what?
Flow Rate may Exceed Maximum Allowed byChiller Manufacturer• Seldom a real problem - pump capabilities usually fall off
fast enough due to high chiller ∆∆∆∆ P• –
72
excursions should not be a problem
• Resolved by using high design ∆∆∆∆ Ts (or adding auto-flowlimiting valves at chillers as last resort)
Pumps in Series may Force Control Valves Open• Not true with variable speed driven secondary pumps.
Primary Pumps may Ride Out Their Curves andOverload• Seldom a real problem - pump capabilities usually fall off
fast enough due to high chiller ∆∆∆∆ P, and motor may beselected to avoid this problem.
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 73/196
Real DisadvantagesReal DisadvantagesCheck Valve in Common LegCheck Valve in Common Leg
Possible Dead-heading SecondaryPumps if Primary Pumps are Off andChiller Isolation Valves are Closed
• Logically interlock secondary pumps to
73
primary pumps
“Ghost” Flow through InactiveChillers with Dedicated Pumps• Use isolation valves rather than dedicated
pumps
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 74/196
Check Valve in the Common LegCheck Valve in the Common Leg
Recommendation• For fixed speed chillers, put the check valve in
the common leg. Make sure pumpdesign/controls address secondary pump dead-heading and ghost-flow issues. Select a check
74
valve with low pressure drop (i.e. swing check,not spring)
• For variable speed chillers, do not put checkvalve in common leg. It has little value (unlessDT degradation is severe) since chiller plant willnot be inefficient by staging chillers on beforethey are fully loaded.
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 75/196
75
SystemsSystems
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 76/196
Condenser Water Systems
Old paradigm: constant flow & speedNew paradigm: variable flow & speed• Control logic to maximize efficiency?
76
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 77/196
$400,000
$500,000
$600,000
Variable Speed CW Pumps
OaklandOfficeBuilding
77
$
$100,000
$200,000
$300,000
C
& C
C
C &
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 78/196
Condenser Water Pump OptionsCondenser Water Pump Options
COOLINGTOWER #1
COOLINGTOWER #2
COOLINGTOWER #3
CHILLER #1
CHW PUMP #1
COOLINGTOWER #1
COOLINGTOWER #2
COOLINGTOWER #3
CHILLER #1
CHW PUMP #1
78
Dedicated Pumping Advantages:• Less control complexity• Custom pump heads w/ unmatched chillers• Usually less expensive if each pump isadjacent to chiller served and head pressurecontrol not required and no watersideeconomizer
Headered Pumping Advantages:• Better redundancy• Valves can double as head pressure control• Easier to incorporate stand-by pump• Can operate fewer CW pumps than chillersfor fixed speed pumps•Easier to integrate water-side economizer
CHILLER #2
CHILLER #3
CHW PUMP #2
CHW PUMP #3
CHILLER #2
CHILLER #3
CHW PUMP #2
CHW PUMP #3
OPTIONAL
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 79/196
Tower Isolation OptionsTower Isolation Options
1. Select tower weir dams& nozzles to allow onepump to serve alltowers
• Always most efficient• Almost always least
expensive
COOLINGTOWER #1
COOLINGTOWER #2
COOLINGTOWER #3
79
• Usually possible with 2 or 3cells
2. Install isolation valveson supply lines only
• Need to oversize equalizers
3. Install isolation valveson both supply & return
• Usually most expensive• Easiest to design• Valve sequencing issues and
possible failure
COOLINGTOWER #1
COOLINGTOWER #2
COOLINGTOWER #3
COOLINGTOWER #1
COOLINGTOWER #2
COOLINGTOWER #3
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 80/196
NonNon--integrated waterintegrated water- -side economizer (WSE)side economizer (WSE)
Don’t do this!
41F
Twb 36F
Twb 41F
44F
You have to shut off the economizer to
Heat
Exchangerin parallelwith chillers
44F 60F
44F
49F
>46F
satisfy the load!
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 81/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 82/196
Integrated waterIntegrated water- -side economizerside economizerPrimary OnlyPrimary Only
Bypass forWSE-only
V -1
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 83/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 84/196
Example WSE SavingsExample WSE Savings
~2%
84
~30% ~24%
~48%
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 85/196
Data Center in Santa ClaraData Center in Santa Clara
85
Cooling Tower
CWS
What’s Missing from this Picture?
A heat exchanger, pipe andtwo pumps
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 86/196
LunchLunch
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 87/196
Design ProcedureDesign Procedure
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 88/196
Design ProcedureDesign Procedure
Select Chilled Water Distribution SystemSelect Temperatures, Flow Rate andPrimary Pipe SizesSelect Cooling Tower Design Criteria
88
Finalize Piping System Design, SelectPumpsDevelop Optimum Control System and
Control Sequences
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 89/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 90/196
SecondaryPump w/ VFD
at ChillerPlant
2-Way ControlValves atAHUs
SecondaryPump w/ VFD
at ChillerPlant
2-Way ControlValves atAHUs
Primary/SecondaryPrimary/Secondary
90
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 91/196
Primary/Distributed SecondaryPrimary/Distributed Secondary
DistributedSecondary
Pump w/ VFD -Typical at each
Building
No Secondary
91
Central Plant
umps aPlant
Distributed P/S versus
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 92/196
Distributed P/S versusConventional P/S or P/S/T
Advantages• Reduced Pump HP - Each Pump Sized for Head
From Building to Plant• Self-balancing• No Over-pressurized Valves at Buildings Near Plant
• Reduced Pum Ener Particularl When One or
92
More Buildings Are off Line
• No Expensive, Complex Bridge Connections Usedin P/S/T Systems
• Similar or Lower First Costs
Disadvantages (vs. P/S)• Pump room needed at building• Higher expansion tank pre-charge and size
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 93/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 94/196
Hybrid systemsHybrid systems
94
Advantages of VFD Coil Pumps versus
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 95/196
Advantages of VFD Coil Pumps versusConventional P/S system
Reduced Pump HP• Each pump sized for head from coil to plant• Eliminated 10 feet or so for control valves
Self-balancing• No need for or advantages to balancing valves, reverse return
Lower Pum Ener
95
• No minimum DP setpoint• Pump efficiency constant
Better Control• Smoother flow control - no valve hysteresis
• No valve over-pressurization problemsUsually Lower First Costs Due to EliminatedControl Valves, Reduced Pump and VFD HP
Disadvantages of VFD Coil Pumps
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 96/196
Disadvantages of VFD Coil Pumpsversus conventional P/S system
Cannot Tap into Distribution Systemwithout Pump• May be problem with small coils (low flow, high
head pump)
96
unless Duplex Coil Pumps are AddedPossible Low Load TemperatureFluctuations
• Minimum speed on pump motor • May need to cycle pump at very low loads
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 97/196
PrimaryPrimary- -only Systemonly SystemHeadered Pumps & Auto Isolation ValvesPreferred to Dedicated Pumps:• Allows slow staging• Allows 1 pump/2 chiller operation• Allows 2 pump/1 chiller operation if there islow ∆T
97
BYPASSVALVE
Flow Meteror DP Sensor Across Chiller
Advantages of primary only versus
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 98/196
Advantages of primary-only versusprimary/secondary system
Lower First CostsLess Plant Space RequiredReduced Pump HP
•Reduced pressure drop due to fewer pump
98
,• Higher efficiency pumps (unless more expensive
reduced speed pumps used on primary side)
Lower Pump Energy
• Reduced connected HP• “Cube Law” savings due to VFD and variable flow
through both primary and secondary circuit
P EP E
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 99/196
Pump EnergyPump EnergyPrimary vs. Primary/Secondary (3Primary vs. Primary/Secondary (3- -chiller plant)chiller plant)
25.00
30.00
35.00
40.00
Primary-
99
0.00
5.00
10.00
15.00
20.00
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
% GPM
P u m p
k
Primary-only
secondary
Disadvantages of primary only versus
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 100/196
Disadvantages of primary-only versusprimary/secondary system
Failure of Bypass Control• Not as fail-safe - what if valve or controls fail?• Must avoid abrupt flow shut-off (e.g. valves interlocked with
AHUs all timed to stop at same time)• Must be well tuned to avoid chiller short-cycling
Flow Fluctuation when Staging Chillers On
100
• Flow drops through operating chillers• Possible chiller trips, even evaporator freeze-up• Must first reduce demand on operating chillers and/or slowly
increase flow through starting chiller; causes temporary highCHWS temperatures
(Problems above are seldom an issue with verylarge plants, e.g. more than 3 chillers)
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 101/196
PrimaryPrimary- -only System Stagingonly System Staging
1000 GPM
0 GPM
0 GPM
101
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 102/196
PrimaryPrimary- -only System Stagingonly System Staging
500 GPM
0 GPM
102
500 GPM
Variable FlowVariable Flow
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 103/196
Variable FlowVariable FlowPrimary/Secondary with CHW StoragePrimary/Secondary with CHW Storage
Advantages• Peak shaving• Simplifies chiller staging• Provides back-up for chiller
failure• Secondary water source for fire
department
103
• Secondary water source forcooling towers
Disadvantages• Installed cost• Space
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 104/196
Primary-only vs. Primary/Secondary
Use Primary-only Systems for:• Plants with many chillers (more than three) and with
fairly high base loads where the need for bypass isminimal or nil and flow fluctuations during staging
are small due to the large number of chillers; and
104
• Plants where design engineers and future on-siteoperators understand the complexity of the controlsand the need to maintain them.
Otherwise Use Primary-secondary• Also for plants with CHW storage
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 105/196
Pipe SizingPipe Sizing
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 106/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 107/196
Accurately sizing pump head
107
Guessing at pump heads• Wastes money in oversized pumps, motors and (sometimes)
VFDs and (sometimes) need for impeller trimming• Wastes energy (minor impact w/VFD or if impeller is trimmed)
Calculating pump heads• Takes about 20 minutes of engineering time
Guessing cannot possibly be cost effective!
d hd h
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 108/196
LCC SpreadsheetLCC Spreadsheet
108Available for free from the TE ftp site
l f d hl f d h
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 109/196
Simplified Pipe Sizing ChartSimplified Pipe Sizing ChartMaximum GPM for
High Performance Constant Flow,Constant Speed System
2000 4400 0 2000 4400 0 1/2 5.0 3.9 3.0 1.8 1.8 1.8 3/4 12 9.0 7.0 4.6 4.6 4.6
1 19 14 11 8.9 8.9 8.91 1/4 34 26 20 15 15 151 1/2 57 43 34 24 24 24
2 73 55 44 51 51 442 1/2 100 77 60 81 77 60
2000 4400 0 2000 4400 0 1/2 7.8 5.9 4.6 1.8 1.8 1.8 3/4 18 14 11 4.6 4.6 4.6
1 29 22 17 8.9 8.9 8.91 1/4 51 39 30 15 15 151 1/2 88 67 52 24 24 24
2 120 84 67 51 51 512 1/2 160 120 91 81 81 81
Maximum GPM for
High Performance Variable Flow, VariableSpeed System
109
3 180 140 110 140 140 1104 320 240 190 280 240 1905 430 330 260 430 330 2606 700 530 420 700 530 4208 1,200 900 720 1,200 900 720
10 1,900 1,500 1,200 1,900 1,500 1,20012 2,900 2,200 1,700 2,900 2,200 1,70014 4,000 3,000 2,400 4,000 3,000 2,40016 4,900 3,800 3,000 4,900 3,800 3,00018 7,000 5,300 4,200 7,000 5,300 4,20020 7,700 5,800 4,600 7,700 5,800 4,600
24 12,000 8,900 7,100 12,000 8,900 7,10026 14,000 11,000 8,500 14,000 11,000 8,500
Available from the ftp site
3 270 210 160 140 140 1404 480 360 290 280 280 2805 670 510 390 490 490 3906 1,100 800 630 770 770 6308 1,800 1,400 1,100 1,500 1,400 1,10010 2,900 2,200 1,800 2,700 2,200 1,80012 4,400 3,300 2,600 4,200 3,300 2,60014 6,000 4,600 3,600 5,400 4,600 3,60016 7,400 5,700 4,500 7,200 5,700 4,50018 10,000 8,000 6,300 9,200 8,000 6,30020 11,000 8,800 7,000 11,000 8,800 7,000
24 17,000 13,000 11,000 17,000 13,000 11,00026 21,000 16,000 13,000 20,000 16,000 13,000
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 110/196
Optimum ∆TOptimum ∆T
Fl d ∆TFl d ∆T
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 111/196
Flow rate and ∆TFlow rate and ∆T
TGPM500 ∆=Q
111
Load from LoadCalc’s (Btu/hr)
Conversion“constant”
=8.33 lb/gal *60 minutes/hr
Flow rate(GPM)
TemperatureRise or Fall (ºF)
CHWCHW ∆∆∆∆∆∆∆∆ TT T d ffT d ff
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 112/196
CHWCHW ∆∆∆∆∆∆∆∆ TT TradeoffsTradeoffs
Typical Range 8° F to 25° F
First Cost smaller coil smaller pipe
112
mpac sma er pumpsmaller pump motor
Energy Costimpact
lower fan energy lower pump energy
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 113/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 114/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 115/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 116/196
Ch i th “Ri ht” CHWCh i th “Ri ht” CHW ∆∆∆∆∆∆∆∆ TT
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 117/196
Choosing the “Right” CHWChoosing the “Right” CHW ∆∆∆∆∆∆∆∆ TT
Both energy and first costs arealmost always minimized by pickinga very high ∆T (>18°F to 25°F)
Savings even greater with systems
117
that have• Water-side economizers• CHW thermal energy storage
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 118/196
Sh tSh t t P dt P d
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 119/196
ShortShort- -cut Procedure:cut Procedure:
Use 42°F CHWSTUse 8 row 10 fpi coils• Standard 62.1 limit
119
using coil program; sum to determineplant flow and gpm-weighted averageCHWRT
This may result in a colder CHWST than would be possible with therecommended procedure but if CHWST is reset based on load, the energyimpact is small. First costs may be lower since pumps can be slightlysmaller.
Example Building
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 120/196
Example Building
16TH FLOOR
120
6THFLOOR
AUXFAN-
COILS &CRUs
Example Building
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 121/196
Example Building
Load
tons
Main system piping 1100 1056 Non-noise sensitive, variable 8” 1400 18.9
SectionGPM at25 °°°° F ∆∆∆∆ T Application Pipe size
MaximumGPM
Resulting∆∆∆∆ T
Load
tons
Main system piping 1100 1056 Non-noise sensitive, variable 8” 1400 18.9
SectionGPM at25 °°°° F ∆∆∆∆ T Application Pipe size
MaximumGPM
Resulting∆∆∆∆ T
Load
tons
Main system piping 1100 1056 Non-noise sensitive, variable 8” 1400 18.9
SectionGPM at25 °°°° F ∆∆∆∆ T Application Pipe size
MaximumGPM
Minimum∆∆∆∆ T
Fromsimplified
Table VFVS
121
flow, ~4400 hrs
Main riser to 6 th floor 820 787 Noise sensitive, variable flow,2000 hrs
8” 1500 13.1
Piping to main AHU coils 140 134 Non-noise sensit ive, variableflow, 2000 hrs
3” 210 16.0
Piping to main aux. coils 260 250 Noise sensit ive, variable flow,8760 hrs
4" 280 22.3
flow, ~4400 hrs
Main riser to 6 th floor 820 787 Noise sensitive, variable flow,2000 hrs
8” 1500 13.1
Piping to main AHU coils 140 134 Non-noise sensit ive, variableflow, 2000 hrs
3” 210 16.0
Piping to main aux. coils 260 250 Noise sensit ive, variable flow,8760 hrs
4" 280 22.3
Minimumaverage ∆∆∆∆ Tthis circuit
flow, ~4400 hrs
Main riser to 6 th floor 820 787 Noise sensitive, variable flow,2000 hrs
8” 1500 13.1
Piping to main AHU coils 140 134 Non-noise sensit ive, variableflow, 2000 hrs
3” 210 16.0
Piping to main aux. coils 260 250 Noise sensit ive, variable flow,8760 hrs
4" 280 22.3
Coil Selection Example
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 122/196
Coil Selection Example
122
Condenser Water (Tower) RangeCondenser Water (Tower) Range
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 123/196
Condenser Water (Tower) RangeCondenser Water (Tower) Rangeat Constant CWSTat Constant CWST
∆∆∆∆ T
Low High
Typical Range 8 °°°° F to 20 °°°° F
123
First Cost Impact smaller condenser smaller pipesmaller pump
smaller pump motorsmaller cooling tower
smaller cooling tower motor
Energy Costimpact
lower chillerenergy
lower pump energylower cooling tower energy
Condenser Water RangeCondenser Water Range
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 124/196
Condenser Water RangeCondenser Water Rangeat constant Tower Fan Energyat constant Tower Fan Energy
400
500
600Tower Fan
CW pumpChiller
124
0
100
200
300
73/16 73.5/14 74.5/12 75.5/10
CWST/Delta-T
k W h / t o n / y e a
LCC Analysis 1000 ton Plant
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 125/196
LCC Analysis – 1000 ton Plant
Chicago
125
15F ∆T LCC best forall climates analyzed
Recommended Procedure:
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 126/196
Recommended Procedure:
Determine CW Flow Rate at 15°FPick primary pipe sizes (pumps, headers,main risers) in “critical circuit”• Use pipe sizing spreadsheet or shortcut tables
126
n max mum ow or eac p pe s ze anrecalculate ∆T for these flow rates• Use pipe sizing spreadsheet or shortcut tables
The largest ∆T is then the plant design ∆TAdjust CW Flow up per selected ∆T
This procedure attempts to minimize cost by reducing pipe sizeas much as possible, but then taking full advantage of theresulting pipe size to minimize ∆T to reduce chiller energy.
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 127/196
Cooling Tower SelectionCooling Tower Selection
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 128/196
Cooling Tower SelectionCooling Tower Selection
180%190%200%210%
200%-210%190%-200%180%-190%170%-180%160%-170%
150%-160%
128
5
7
9
11
13
15
1719
1110
98
76
54
32
10%
10%20%30%40%50%60%70%80%90%
100%110%120%130%140%150%160%
% D e s i g n
C a p a c i t y
Approach (°F)
Range (°F)
140%-150%130%-140%120%-130%110%-120%100%-110%90%-100%80%-90%70%-80%60%-70%50%-60%40%-50%30%-40%20%-30%10%-20%0%-10%
Cooling Tower Approach & RangeCooling Tower Approach & Range
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 129/196
Cooling Tower Approach & RangeCooling Tower Approach & Range
ASHRAE Standard 90.1Rating Conditions
95 ° F
129
WETBULB TEMPERATURE
85 ° F
75 ° F
Propeller fan towersPropeller fan towers
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 130/196
Propeller fan towersPropeller fan towers
130
Tower Fan ControlTower Fan Control
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 131/196
Tower Fan ControlTower Fan Control
One Cell Tower
131
Free Cooling~ 15% of Capacity
Single SpeedFan
Two-Speed or Variable-SpeedFan
% Capacity
% Power
Tower Fan ControlTower Fan Control
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 132/196
Tower Fan ControlTower Fan Control
60%
70%
80%
90%
100%
Two 1-Speed Fans
One 1-Speed Fan andOne 2-Speed Fan
Two Cell Tower
132
0%
10%
20%
30%
40%
50%
0 % 5 % 10% 1 5% 2 0% 2 5% 3 0% 35% 40 % 4 5% 50% 5 5% 6 0% 6 5% 7 0% 7 5% 80% 85 % 9 0% 95% 1 00
%
% Capacity
% P o w e r
Two 2-Speed Fans
Free Cooling Below 15%Capacity
Two Variable Speed
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 133/196
Tower Efficiency LCCTower Efficiency LCC
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 134/196
Tower Efficiency LCCTower Efficiency LCC
ASHRAE Efficiency:
The flow rate the tower cancool from 95F to 85F at 75Fwetbulb temperature divided byfan power (GPM/HP)
134
90 GPM/HP 70 GPM/HP 50 GPM/HP
1000 ton
OaklandOffice
Tower ApproachTower Approach
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 135/196
Tower ApproachTower Approach
Oakland Office Oakland Data Center
135
Optimum Approach TemperatureOptimum Approach Temperature
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 136/196
Optimum Approach TemperatureOptimum Approach Temperature
15
20
25
30
+
CA
A
136
0
5
10
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
0
50CW A CDDT T 001.027 −∆−=
Tower Efficiency GuidelinesTower Efficiency Guidelines
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 137/196
Tower Efficiency GuidelinesTower Efficiency Guidelines
Use Propeller Fans• Avoid centrifugal except where high static needed or
where low-profile is needed and no prop-fan optionsavailable.
• Consider low-noise propeller blade option and high
137
.Efficiency• Minimum 80 gpm/hp for commercial occupancies• Minimum 100 gpm/hp for 24/7 plants (data centers)
Approach• Commercial occupancies: See previous slide8°F to 9°F for Bay Area
• 24/7 plants (data centers): 3°F
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 138/196
Break Break
CHILLER SELECTIONCHILLER SELECTION
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 139/196
CHILLER SELECTIONCHILLER SELECTION
139
Part-Load Ratio
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 140/196
Chiller Procurement ApproachesChiller Procurement Approaches
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 141/196
Chiller Procurement ApproachesChiller Procurement Approaches
Better Approach• Pick a short list of vendors based on past
experience, local representation, etc.• Request chiller bids based on a performance
s ecification. Multi le o tions encoura ed.
141
• Adjust bids for other first cost impacts• Estimate energy usage of options with a detailed
computer model of the building/plant
• Select chillers based on lowest life cycle cost• Bid the chillers at end of design developmentphase
Chiller Bid SpecificationChiller Bid Specification
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 142/196
Chiller Bid SpecificationChiller Bid Specification
Don’t Specify:• Number of chillers• Chiller size• Chiller efficiency
• Chiller unloading
Do Specify:• Total design load• Anticipated load profile• Minimum number of
chillers and redundancy
142
mechanism• As much as possible
• Design CHW/CW enteringand leaving temperaturesand/or flows (or tables ofconditions)
• Available energy sources
• Physical, electrical orother limitations
• Acoustical constraints• Acceptable refrigerants
Sample Load ProfileSample Load Profile
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 143/196
pp
60 0
70 0
80 0
143
0
10 0
20 0
30 0
40 0
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Percent Load
H o u r s p e r y e a
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 144/196
Zero Tolerance DataZero Tolerance Data
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 145/196
30%
35%
40%
45%
10F Delta-T
ARI 550/590 Tolerance Curve
145
0%
5%
10%
15%
20%
25%
0% 20% 40% 60% 80% 100% 120%
% of Full Load
% T o l e r a n c 15F Delta-T
20F Delta-T
Factory Tests and LiquidatedFactory Tests and LiquidatedD ClD Cl
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 146/196
Damage ClausesDamage ClausesCertified Factory Tests• Need to verify performance to ensure accurate
claims by chiller vendors in performance bids• Field tests are difficult or impossible and less
accurate
146
• Last chance to reject equipment
Liquidated Damage Clause• One-time penalty for failing tests as an option to
rebuilding or repairing chiller
Chiller Bid FormChiller Bid Form
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 147/196
Option:Manufacturer:Model:Compressor type:Refrigerant:Delivery lead time (weeks):
Chiller Performance Form
Fill out all yellow -highlighted cells. Others are f ixed or calculated automatically
Complete this w orksheet before completing Part Load and Full Load w orksheets (some fields are calculated automatically from the data on this sheet
Yellow: Fields to becompleted by Vendor
White: Fixed
147
Maximum CHW flow rate: Maximum CW flow rate:Minimum CHW flow rate: Minimum CW flow rate:Voltage/phase: 480/3 Minimum CW supply temperature:Full load amps:
CHW fouling factor: 0.0001 CW fouling factor: 0.00025Leaving CHWST: 42 Entering CWST:Entering CHWRT: 59 Leaving CWRT:Design CHW flow: Design CW flow:CHW DP (ft): CW DP (ft):
Design kW (w/o ARI Tolerance):Design capacity: 0 Design kW/ton: 0
Design Conditions
Gray: Calculatedfields
e s
Chiller Bid FormChiller Bid Form
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 148/196
Capacity Power Exit Temp Flow Rate Entering Temp Flow Rate Exit Temptons kW °F gpm °F gpm °F
43 550 85 700 8543 550 75 700 75
43 550 65 700 65
Evaporator Condenser
Please fill in all data on the "Start Here" tab before filling in the table. Please fill inthe yellow cells . The capacity and power inputs are for unmodulated operationassuming no power or current limits with all capacity control devices fully open.
Full Load Data
148
43 550 60 700 6045 550 85 700 8545 550 75 700 7545 550 65 700 6545 550 60 700 6050 550 85 700 8550 550 75 700 7550 550 65 700 6550 550 60 700 60
43 550 85 400 8543 550 75 400 7543 550 65 400 6543 550 60 400 6045 550 85 400 8545 550 75 400 7545 550 65 400 65
Min =
Min =
Min =
Min =
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 149/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 150/196
Example ProjectsExample Projects
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 151/196
p jp j
Large Central Plant• Central plant serving industrial/office/research
park,
San Jose, CA. 17,000 tons total ca acit
151
Large High-rise Office Building• Office plus small data center, retail,
San Francisco, CA. 15 stories, 540,000 ft 2
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 152/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 153/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 154/196
San FranciscoSan Francisco
16 TH FLOOR
AUX-
HighHigh--riseriseOfficeOffice
1100 tons1100 tons
6TH FLOOR
COILS& CRUs
HighHigh- -RiseRiseOfficeOffice Description
1stCostRank
EnergyCostRank
Life CycleCost
Savings vsBase
LCCRank
vs.
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 155/196
OfficeOfficeTowerTower
ChillerChillerOptionsOptions
p
Trane #1 400 ton, 0.50 kW/t;700 ton, 0.55 Kw/ton 6 9 $142,016 10
Trane #2 400 ton w/VFD, 0.50 kW/t;700 ton, 0.55 Kw/ton 9 2 $22,092 4
Carrier #1 365 ton, 0.56 kW/t;735 ton, 0.50 kW/t 1 12 $173,962 12
Carrier #2365 ton w/VFD, 0.56 kW/t;735 ton, 0.50 kW/t 3 5 $21,246 3
Carrier #3365 ton w/VFD, 0.56 kW/t;735 ton w/VFD, 0.50 kW/t 8 4 $7,702 2
Mc ua #1200 ton, 0.50 kW/t;
SelectedChillers
A #1
A #2
B #1
B #2
B #3
ton ua . t 2 8 78,159 5
McQuay #2 550 ton dual, 0.56 kW/t550 ton dual, 0.56 kW/t 5 11 $141,179 9
McQuay #3400 ton dual, 0.53 kW/t;700 ton dual 0.53 kW/t 4 7 $112,419 8
McQuay #4200 ton, 0.53 kW/t;350 ton dual 0.57 kW/t;550 ton dual 0.59 kW/t 7 10 $147,440 11
York #1 550 ton w/VFD , 0.49 kW/t;550 ton, 0.48 kW/t 11 6 $104,078 7
York #2300 ton w/VFD , 0.50 kW/t;800 ton, 0.48 kW/t 10 1 $0 1
York #3365 ton w/VFD , 0.52 kW/t;366 ton, 0.51 kW/t366 ton, 0.51 kW/t 12 3 $92,421 6
C #2
C #3
C #4
D #1
D #2
D #3
LCC Assumptions:Discount rate 8%Electricity Escalation 0%Analysis years 15
Considering “Soft Factors”Considering “Soft Factors”
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 156/196
Why Option B3 was Selected over OptionD2:• Close in LCC (2nd behind Option D2) – within the
margin of error in the analysis
•
156
client due to zero ODP (D2 used R-123)
• Both Option B3 chillers had VSDs (only one inOption D2)
•Small chiller pump can operate large chiller (flowminimum/design ranges overlap)
• Option B3 hermetic, Option D2 is open-drive• Option B3 had lower first cost
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 157/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 158/196
158
OPTIMIZING CONTROLSOPTIMIZING CONTROLS
Optimizing Control SequencesOptimizing Control Sequences
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 159/196
Optimizing Control SequencesOptimizing Control Sequences
Cookbook Solution• Staging Chillers• Controlling Pumps
•Chilled Water Reset
159
• Condenser Water Reset
Simulation Approach
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 160/196
Staging Chillers, continuedStaging Chillers, continued
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 161/196
Variable Speed Chillers• Operate as many chillers as possible
provided load on each exceeds 30% to 40%load (actual value can be determined by
161
−below)
• Energy impact small regardless of staginglogic
• You MUST use condenser water reset toget the savings
Part Load Chiller Performancew/ Zero ARI Tolerance
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 162/196
70%
80%
90%
100%
Fixed Speed
Variable Speed
162
0%
10%
20%
30%
40%
50%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
% Load (with Condenser Relief)
% k W
Two-Chiller Plant Performanceat Low Load
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 163/196
40%
50%
60%
W
& C W
p u m p s )
Running two fixed speedchillers alw ays usesmore energy
163
0%
10%
20%
30%
0% 10% 20% 3 0% 40% 5 0%
% Plant Load
% P l a n t k W
( i n c l u d i n g
P C H
Variable Speed - one chiller
Fixed Speed - one chiller
Variable Speed - two chillers
Fixed Speed - two chillers
Running two VFD
chillers is more efficientuntil 35% load
Cautionary NoteCautionary Note
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 164/196
Staging logic must limit possibility forsurge operation for centrifugal chillersSome variable speed chillers don’tdynamically measure surge conditions
164
• ou w ose some o e sav ngs w pr mary-only variable flow systems because minimumspeed may have to be increased to avoid surge
• You may have premature tripping due to onset of
surge otherwise• This is only an issue with variable evaporatorflow systems (like primary-only variable flow)
Staging & Surge
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 165/196
Sur e Re ion
1 0 0 % s p e e d
9 0 %
8 0 %
One Chiller Two Chillers
165
R
e f r i g e r a n t H e a
Load
7 0 %
6 0 %
One Chiller Two Chillers
Controlling CHW PumpsControlling CHW Pumps
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 166/196
Primary-only and Secondary CHWPumps• Control speed by differential pressure
measured as far out in system as possible
166
an or rese se po n y va ve eman• Stage pumps by differential pressure PID
loop speed signal:Start lag pump at 90% speedStop lag pump at 40% speedFor large HP pumps, determine flow and speedsetpoints with detailed energy analysis
VSD Pump Power vs. Setpoint
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 167/196
70%
80%
90%
100%
W
DP setpoint = Design Head
DP setpoint = Head*.75
DP setpoint =Head/2
DP setpoint =Head/3
DP setpoint = 0 (reset)
167
0%
10%
20%
30%
40%
50%
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Percent GPM
P e r c e n t P u m p
Chilled Water Setpoint ResetChilled Water Setpoint Reset
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 168/196
Reset Impacts• Resetting CHWST upwards reduces chiller energy but will
increase pump energy in VSD variable flow systems• Dehumidification
Reset with “open” or indirect control loops (e.g. OAT) can starve coilsand reduce dehumidification
−
168
humidity of supply determined almost entirely by supply airtemperature setpoint, not CHWST
Recommendations• Reset from control valve position using Trim & Respond logic• For variable flow systems with VSDs
Reset of CHWST and VSD differential pressure setpoint must besequenced − not independent like VAV systems since control valvesare pressure-dependentSequence reset of CHWST and DP − next slide
CHWST/DP Setpoint Reset for VSDCHW System
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 169/196
y
Tmin+15ºF
DPmax
CHWDP
169
Back off on CHWST firstThen back off on DP setpoint first
Tmin5 psi
CHWsetpoint
DPsetpoint
se po n
CHW Plant Reset0 100%50%
CHW vs. DP Setpoint Reset
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 170/196
170
Plant with 150 ft CHW pump head
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 171/196
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 172/196
ModelsModels
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 173/196
Chillers• Hydeman et al, Regression Based Electric Chiller Model• Multi-point calibration using zero-tolerance manufacturer’s
data
Towers
173
• DOE-2.2 model calibrated using manufacturer’s data
Pumps• Multiple piping sections ∆P=C*GPM1.8• Pump efficiency from regression of manufacturer’s data
VFD and motor efficiency• Part load curves from Advanced VAV Design Guide
Chiller and Tower Staging by LoadChiller and Tower Staging by Load
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 174/196
174
Stage Stage Down Stage Up Number of Chillers Number of Tower Cells1 340 1 32 240 550 1 43 450 750 1 53 650 1600 2 5
4 1500 3 5
CW Pump Staging and SpeedCW Pump Staging and Speed
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 175/196
175
Sample of Custom Sequences
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 176/196
Enable Economizer when• CHWRT > 0.9*Twb + 12.3
When Economizer is off • When Load <= 380 Ton:
Run one chiller, three towers, one CWP
Control CW um %s eed = 80
176
Control Tower Fan speed to maintain CWST = 0.86*Twb + 13.5• Else when Load <=1170 Ton
Run two chillers, five towers, and two CWPsControl CW pump %speed=0.90 + 2.74*%Load^2 – 1.41*%LoadControl Tower Fan speed to maintain CWST = 0.92*Twb +10.5
• Else when Load >1170 Ton
Run three chillers, five towers, and three CWPsControl CW pump %speed=0.58 + 0.428*%Load^2 +0.125*%LoadControl Tower Fan speed to maintain CWST = 0.892*Twb + 13.4
Theoretical Optimum Plant PerformanceTheoretical Optimum Plant Performance(TOPP) Model Simulation Results(TOPP) Model Simulation Results
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 177/196
Run 0 980,000 40,900 76,000 113,000 1,210,000 Run 1 980,000 -0.16% 38,800 -5.14% 84,000 10.93% 113,000 0.00% 1,210,000 0.39%Run 2 1,010,000 3.85% 38,800 -5.13% 63,000 -17.33% 113,000 0.00% 1,230,000 1.85%
Run 3990 000 0.81% 58 000 41.88% 175 000 130.90% 113 000 0.00% 1 330 000 10.31%
CHW Pumps TotalAnnual Energy Usage (kWh/yr, % of TOPP)
Chillers Cooling Towers CW Pumps
177
, . , . , . , . , , .
Run 4 1,140,000 16.42% 4,600 -88.71% 335,000 340.74% 113,000 0.00% 1,590,000 31.73%Run Descriptions:Run 0: TOPP modelRun 1: Recommended control sequencesRun 2: Run 1 with the cooling tower CWS temperature controlled by wet-bulb resetRun 3: "Standard control sequence" with ARI 550/590 CW ResetRun 4: "Standard control sequence" with CW temperature fixed at design
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 178/196
CWRT-CHWST vs. %Load
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 179/196
10
20
30
40
50
60
, , 3
10
20
30
40
50
60
, , 3
10
20
30
40
50
60
, , 3
179
0% 15% 30% 45% 60% 75% 90%
%
0% 15% 30% 45% 60% 75% 90%
%
0% 15% 30% 45% 60% 75% 90%
%
0
10
20
3040
50
60
0% 15% 30% 45% 60% 75% 90%
%
, , 3
0
10
20
3040
50
60
0% 15% 30% 45% 60% 75% 90%
%
, , 3
0
10
20
3040
50
60
0% 15% 30% 45% 60% 75% 90%
%
, , 3
%CW Loop Flow vs. %Plant Load
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 180/196
15%
30%
45%
60%
75%
90%
, , 3
15%
30%
45%
60%
75%
90%
, , 3
15%
30%
45%
60%
75%
90%
, , 3
180
0%
15%
30%
45%60%
75%
90%
0% 15% 30% 45% 60% 75% 90%
%
, , 3
0%
15%
30%
45%60%
75%
90%
0% 15% 30% 45% 60% 75% 90%
%
, , 3
0%
15%
30%
45%60%
75%
90%
0% 15% 30% 45% 60% 75% 90%
%
, , 3
0%0% 15% 30% 45% 60% 75% 90%
%
0%0% 15% 30% 45% 60% 75% 90%
%
0%0% 15% 30% 45% 60% 75% 90%
%
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 181/196
CWP Staging by %Plant CW flow rate
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 182/196
1
2
3
, , 3
1
2
3
, , 3
1
2
3
, , 3
182
00% 15% 30% 45% 60% 75% 90% 105%
%
00% 15% 30% 45% 60% 75% 90% 105%
%
00% 15% 30% 45% 60% 75% 90% 105%
%
0
1
2
3
0% 15% 30% 45% 60% 75% 90% 105%
%
, , 3
0
1
2
3
0% 15% 30% 45% 60% 75% 90% 105%
%
, , 3
0
1
2
3
0% 15% 30% 45% 60% 75% 90% 105%
%
, , 3
Generic Control SequencesGeneric Control SequencesAllAll--variable speed plantvariable speed plant
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 183/196
LIFT = A*PlantLoadRatio + B• Bounded by minimum LIFT at minimum PLR (frommanufacturer) and maximum LIFT (design lift)
• CWRT setpoint = LIFT + CHWST• Control CT fans to maintain CWRT
183
oop ow a o = an oa a o• Bounded by chiller minimum CW flow (from manufacturer)
and 100%• CWLoopFlow = CWLoopFlowRatio *DesignCWFlow• Control CWP speed to maintain CWLoopFlow
Chiller and CW pump staging• Stage up at 60% CWLoopFlowRatio• Stage down at 50% CWLoopFlowRatio
LIFT = A*PlantLoadRatio + BLIFT = A*PlantLoadRatio + B
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 184/196
Coefficient A Coefficient B
184
A = 9.235 + 0.002182 * C 55 + 0.351 * B + 75.775 * + 0.019 * / + 0.257 * A AC + 0.25 *AB = 112.384 + 0.00181 * C 55 + 5.286 * B + 734.447 * / + 67.574 * + 0.019 *
/ + 5.398 * A AC + 5.168 * A
CWLoopFlowRatio =CWLoopFlowRatio =C*PlantLoadRatio + DC*PlantLoadRatio + D
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 185/196
Coefficient C Coefficient D
185
C = 0.0000811 * C 55 + 0.01293 * B + 3.486 * + 0.02476 * A AC + 0.07400 * A = 0.797 + 2.282 * + 0.002196 * A AC + 0.00795 * A
Plant Energy vs. TOPP: OaklandPlant Energy vs. TOPP: Oakland
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 186/196
35%
40%
45%
50%
186
0%
5%
10%
15%
20%
25%
30%
A 3
C A 1
A 3
C A 2
A 3
C A 3
A 3
C B 1
A 3
C B 2
A 3
C B 3
A 3
C C 1
A 3
C C 2
A 3
C C 3
A 3
C 1
A 3
C 2
A 3
C 3
B 3
C A 1
B 3
C A 2
B 3
C A 3
B 3
C B 1
B 3
C B 2
B 3
C B 3
B 3
C C 1
B 3
C C 2
B 3
C C 3
B 3
C 1
B 3
C 2
B 3
C 3
C
( 2)
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 187/196
Staging vs. PRL and LIFTStaging vs. PRL and LIFT
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 188/196
Chiller J, Chicago, D-3Chiller J, Oakland, D-3
188
Chiller J, Miami, D-3 Chiller J, Atlanta, D-3
Revised Control SequencesRevised Control SequencesAllAll--variable plantvariable plant
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 189/196
LIFT = A*PlantLoadRatio + B• Bounded by minimum LIFT at minimum PLR (from manufacturer) andmaximum LIFT (design lift)
• CWRT setpoint = LIFT + CHWST• Control CT fans to maintain CWRT
CWLoopFlowRatio = C*PlantLoadRatio + D
•
189
• CWLoopFlow = CWLoopFlowRatio *DesignCWFlow• Control CWP speed to maintain CWLoopFlow
CW pump staging• Stage up at 60% CWLoopFlowRatio• Stage down at 50% CWLoopFlowRatio
StagingPLR = E*LIFT + F• When PLR≤ StagingPLR, run one chiller • When PLR> StagingPLR, run two chillers• Minimum time before changing stages
With Real Sequences, Are VFDs onWith Real Sequences, Are VFDs onCW Pumps Cost Effective?CW Pumps Cost Effective?
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 190/196
Previous analysis assumed TOPP could beachieved with simple correlations on PLR, CWFlowCorrelations are not good for C and Dcoefficients
190
Will real world sequences work well enough?Coefficient C Coefficient D
Even Optimum Savings are SmallEven Optimum Savings are Small
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 191/196
OaklandMiami AtlantaLas
Vegas Albuquerque Chicago
191
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 192/196
Optimized Control SequencesOptimized Control SequencesOakland plantOakland plant
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 193/196
Both CS and VS• LIFT = 50*PlantLoadRatio + 2.5Bounded by minimum LIFT (9F per Trane)CWRT setpoint = LIFT + CHWSTControl CT fans to maintain CWRT
• StagingPLR = 0.013*LIFT + 0.067When PLR≤ StagingPLR, run one chiller When PLR> StagingPLR, run two chillers
193
VS Only• CWLoopFlowRatio = 1.6*PlantLoadRatio + 0.13
Bounded by minimum CW flow (50% each chiller, 0.25 overall) and 100%CWLoopFlow = CWLoopFlowRatio *DesignCWFlowControl CWP speed to maintain CWLoopFlow
• CW pump stagingStage up at 60% CWLoopFlowRatio
Stage down at 50% CWLoopFlowRatio
CS Only• CW pumps stage with chillers
Answer: Not Cost EffectiveAnswer: Not Cost Effectivefor Office Buildingsfor Office Buildings
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 194/196
194
SummarySummary
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 195/196
In this course, you have learned techniques todesign and control chiller plants for near-minimum life cycle costs, including:• Selecting optimum chilled water distribution system• Selecting optimum CHW supply & return temperatures
195
• e ec ng op mum an ower range an approactemperatures, tower efficiency, and fan speed controls
• Selecting optimum chillers using a performance bid andLCC analysis
• Optimizing control sequences and setpoints
8/12/2019 PG&E Optimizing Chilled Water Plants - RV 13 1 Day Version
http://slidepdf.com/reader/full/pge-optimizing-chilled-water-plants-rv-13-1-day-version 196/196