phase comparison
TRANSCRIPT
-
8/10/2019 Phase Comparison
1/55
GRID
Sankara Subramanian
Phase Comparison protection
-
8/10/2019 Phase Comparison
2/55
History of Phase comparison ...
-
8/10/2019 Phase Comparison
3/55
Principle of Phase Comparison -Normal Load Conditions
ON-OFF
channel
End X End Y
X (+)I Y(+)I
Mark Mark
Composite - (usually no PLC signal transmission for load)
MarkSpace
Modulated signals MarkSpace
-+
Terminal currents
+
-
-
8/10/2019 Phase Comparison
4/55
Principle of Phase Comparison -External Fault
Composite modulated signal
End X End Y
X (+)I Y(+)I
-+
Terminal currents -+
Modulated signals MarkSpace
MarkSpace
Mark Mark
ON-OFF
channel
-
8/10/2019 Phase Comparison
5/55
Principle of Phase Comparison -Internal Fault
Composite modulated signal
End X End Y
X (+)I Y(+)I
FI
-+
Terminal currents -+
Mark
SpaceModulated signals Mark
Space
Mark Space
ON-OFF
channel
180 180
GAP = TRIP
-
8/10/2019 Phase Comparison
6/55
Channel EquipmentPhase-segregated channel
Phase A
Phase B
Phase C
AI
BI
CI
-
8/10/2019 Phase Comparison
7/55
Channel EquipmentSingle-phase channel
Phase B typically
???,, CBA III
-
8/10/2019 Phase Comparison
8/55
Line Faults Current sequences
Fault
SequenceLoad 3-Ph Ph-Ph
Ph-Ground
Ph-Ph-Ground
Positive (1) + + + + +
Negative (2) - - + + +
Zero (0) - - - + +
-
8/10/2019 Phase Comparison
9/55
Modulating quantity
HISTORY
MODERN APPROACH
A.J. McConnel,
General Electric (1947)
H.W. Lensner, Westinghouse (1946),
A.P. Pleshko, Russia (1941)1 0I k I
2 0 1 (for 3-Ph fault)I k I I
Russian manufacturers
Alstom
General Electric
Phase-segregated (3 channels) France
-
8/10/2019 Phase Comparison
10/55
Line Faults Modulating quantity
Fault
Sequence
Load 3-Ph Ph-PhPh-
GroundPh-Ph-Ground
Positive (1) + + + + +
Negative (2) - - + + +
Zero (0) - - - + +
-
8/10/2019 Phase Comparison
11/55
Current angle errors
Sources angle difference
Signal propagation delay
Measurement errors
Charging currents
-
8/10/2019 Phase Comparison
12/55
Stability angle (1)
x - y =180
x - y = 0
BLOCK TRIP
s
s
SYSTEM STABILITY ANGLE- s.
Load and external faultsInternal faults
-
8/10/2019 Phase Comparison
13/55
Stability angle (2)
s is the system stability angle, recommended setting for shortlines is 30o.
s compensates for general tolerances in PLC, relay, CT non-linearity and changes in atmospheric conditions since the last
propagation delay measurement. A 30osetting (-30o to +30o) means that a carrier gap/space
of longer than s /360, is needed to trip.
-
8/10/2019 Phase Comparison
14/55
Long lines charging current
End X
End Y
Y
2
Y
2I
XIYUX UY
IY, cap.X, cap.
U
IY
IX
I X, cap.
IY, cap.
IYIX
Id
180
HV lines with LENGTH > 150km require charging current compensation
-
8/10/2019 Phase Comparison
15/55
Starters
PLC cannot be activated permanently
LOW STARTERSinitiate RF communication through channel(start PLC)
Some gap could appear in RF signal under normal condition
HIGH STARTERSactivate phase comparison element andallow trip to be issued.
IMPORTANT:
If any HIGH starter operated at one line terminal, some LOWstarter MUST be active at all other terminals (all PLCs should
be active)
!!!ONE-SIDED START OF PHASE COMPARISON = FALSE TRIP!!!
-
8/10/2019 Phase Comparison
16/55
Phase Comparison classification
Phase Comparison protection
Voltage-independent
(purely current)
Voltage-dependent
Starters:
- current
- voltage
- distance
- current starters
Voltage-independent Phase Comparison
should be used whenever possible, as itsmuch more reliable (immune to VTfailure). Unfortunately, its not suitable forlong HV lines.
- current modulation
- complex
modulation
Voltage-dependent PhaseComparison is universal, butprone to VT failure.
-
8/10/2019 Phase Comparison
17/55
Phase Comparison Typicalfunctional diagram
Sequencer
Ia
Ib
Ic I2
Charging
current
Compensation Yc
setting
Sequencer
I1High set
Starter
Mixer
RX
Angle
shift
Voltage
Input
Va
Vb
Vc
Sequencer
Compen-
sating
Zneg
Distance
Starter
Input
Low set
Starter
TX
Trip
Decision
Gap
Detectio
n
Phasecomparison
Mark / Space
Trip /
Block
V2 V2_comp
I I2
V
-
8/10/2019 Phase Comparison
18/55
Phase comparison protection utilizes sequence components based startersfor sensitivity.
Current Modulator to do the mixing of the positive sequence and negativesequence currents to enable the phase angle detection.
The calculated modulated current positive half cycle is communicated to
the remote end and is compared with the received remote Modulatedcurrent to do the phase angle measurement.
Phase angle Gap measurement starts only when the High set starter pickup.
WorkingStarters & Modulator
-
8/10/2019 Phase Comparison
19/55
As continuous transmission is not permitted Starter units are provided
(sensitive-to provide high speed operation) such that Low set initiatestransmission of carrier signal while high set initiates Gap measurements &trip in phase comparison protection.
Positive(I1) and negative sequence (I2)starters are provided to cover forbalanced and unbalanced fault conditions.
Low set and high set starters are provided to cater for the differences inthe magnitude between the currents at 2 ends and also to account for themagnitude errors in the CT, hence 2 levels are required.
Impulse (Delta ) starters and Non-Impulse (threshold) starters areprovided.
While generally, Impulse starters finds its application for most systemfault conditions, Non- impulse starters can be set for system conditionslike evolving fault scenarios from external to internal with out much rise inthe fault currents.
StartersApplication -Setting Tips(1)
-
8/10/2019 Phase Comparison
20/55
Impulse Positive sequence starters (I1):
High set Impulse must be set above total line charging current (2 x Ich) to avoidtripping for closing CB.
High set should be set < 3 phase fault level, typically 50% of If min 3 .
In order to make protection stable during through fault conditions, ensure the
difference between the minimum effective high set setting and maximum effectivelow set setting is > than the Positive sequence capacitive current. To meet thisrequirement set the ratio of HSS / LSS to a factor of 2.
Non-Impulse Positive sequence starters (I1):
I1 low set must be set above the maximum load current
I1 low set must be set above peak power swing current, to prevent continuoustransmission Alarm being raised for slow swings .Typical swing = 2 In ; set to 2.5or 3 In
I1 high set needs to be 125% to 200% of I1 low set to give adequate margin
StartersApplication -Setting Tips(2)
-
8/10/2019 Phase Comparison
21/55
Impulse Negative sequence starters (I2):
Impulse negative starters should be set to provide sensitivity for high resistance faults lessthan 10% of the rated current.
(3 x Impulse I2 High Set) = Effective earth fault sensitivity of the scheme. Ensure the following for long transmission line. (same can be adopted for medium lines):
Impulse I2 High set is NOT < IS * ((1/SIN) ( s - - ))
Where IS is sending end current (only line charging current is present under no
load condition, when the local breaker is closed);
s is stability angle setting;
- is typically taken as 15 deg (set to cover phase angle errors introduced by CT);
- is typically taken as 10 deg ( set to cover the phase angle difference between
compared line terminal currents due to signal propagation time and may be takenas 0.1 deg per mile).
Ensure HSS to LSS ratio is not less than 1.5 (alternatively, set Low set to 66% of
High set setting).
StartersApplication -Setting Tips(3)
-
8/10/2019 Phase Comparison
22/55
Non-Impulse (Threshold) Negative sequence starters (I2):
Non impulse I2 starters are set less sensitive than the impulse I2starters.
Non-Impulse starters are set above the standing I2 in the system. Example: Transmission system feeding 1-phase traction feeders.
Non-impulse I2 ensures, operation for certain faults-like slowdeveloping faults / evolving external to internal faults with noincrease in I2 current magnitude.
Non-impulse also provided with Low set and High set starters.
Set Non-Impulse I2 to typically between 1.5 and 5 times theImpulse I2 starters.
StartersApplication -Setting Tips(4)
-
8/10/2019 Phase Comparison
23/55
1-ph AR (single pole autoreclose)
Phase comparison is exceptionally good in case of 1-ph AR
Evolving faults are cleared during 1-ph AR dead time
Typically LOW and HIGH starters are active at both line ends as linemode is non-symmetrical (though that depends on load current andusage of voltage starters). Phase Comparison protection awaits only forGAPs.
IMPORTANT:
PLC transmission should be active at both line endsduring 1-ph AR dead time
!!!ONE-SIDED PLC TRANSMISSION = FALSE TRIP!!!
-
8/10/2019 Phase Comparison
24/55
Teed-off transformers
Phase comparison can be applied to teed-off transformer application
Internal Fault
- In many applications, there can be a step-down transformer teed-off the protected line. Thistransformer is not part of the protected unit, but is teed-off to out feed local load. The difficulty isthis tee-line is NOT treated as the third-end of the phase comparison protection.
- Hence the 2 end Phase comparison protection must function correctly for such scenario. Theprotection must refrain for internal load and also operate for internal fault scenarios.
RLOAD
R
IF
IL
IF DIRECTION
IL DIRECTION,DEPENDINGONTHESTRENGTH
OFSOURCES& CONNECTEDLOAD
LOAD
-
8/10/2019 Phase Comparison
25/55
Teed-off transformers Distance permissive
External Fault beyond the transformer
If teed-off transformer is extremely weak, it could be possible to select High Starters higherthen external fault currents (still sensitive for internal faults)
Otherwise we must use Distance permissive scheme. This scheme doesnt require anyadditional equipment
Permissive Scheme
R
LOAD
R
IFIF DIRECTION
LOAD
DISTANCE permission
Z2 Z2
-
8/10/2019 Phase Comparison
26/55
Teed-off transformers with blocking kit
External Fault beyond transformer
Sometimes Distance permissive scheme cant be used because of settings issue
Blocking-scheme works for most of teed-off cases, but requires additional PLC and, sometimes,
relays
PCLOAD
PC
IF
IF DIRECTION
LOAD
PLC PLC
Distance
Power
Direction
Transfo
prot.
PLC
Direction
PC Phase
Comparison
Blocking Kit
Injects continuous carrier
Block Block
3 ended Lines
-
8/10/2019 Phase Comparison
27/55
3-ended Lines
Phase comparison can be applied to 3-ended lines
For any through-fault one current is in opposite phase to others.
I1
PCLOAD
PC
LOAD
PC
IF
IF DIRECTION
I1 I2
I3
I2
I3
SUM
NO GAPS = BLOCK
Weak Infeed
-
8/10/2019 Phase Comparison
28/55
Weak Infeed
Phase comparison should be considered with great care in case of weak infeed.
If fault current is comparable with load current, this could lead to protection inaction(the angle of modulating quantity [I1+K*I2] is hard to predict)
PC
LOAD
PC
IF
IF DIRECTION
LOAD DIRECTION
Strong Source
Weak Source
-
8/10/2019 Phase Comparison
29/55
General advantages of Phase Comparison
Absolute selectivity
Reliable channel (power line itself)
Immune to Power Swings
Immune to VT failure (in voltage-independent version)
Channel is under the utilitys control, unlike third partytelecommunications
-
8/10/2019 Phase Comparison
30/55
FrontBehind
Local substation
To remote
substation
Coupling
Capacitor
Line
Matching
Unit
PLC terminal
Coaxial
Transformer s)
BusBar
Line Trap
The PLCsignal isrouted to HVLine
The PLC
signal is notabsorbed bythe substation
Coupling Scheme
Line Trap function
-
8/10/2019 Phase Comparison
31/55
= PLC signal Blocking
HV Line
Substation
Line Trap = High Impedance for PLC signal (High Freq)
Low Impedance for Power energy (50/60 Hz)
Power energy 50/60 Hz)
PLC Signal High Freq)
Line Trap function
-
8/10/2019 Phase Comparison
32/55
Two types of modulation
Signal
AM
FM
Effect of bad weather on PLC communication
-
8/10/2019 Phase Comparison
33/55
33
Losses increase for all inclement weather conditions
n The worst offender is when heavy frost is formed on the line
n Because of the skin effect, the carrier signal tries to propagate on
the ice instead of the conductor.n The attenuation can change as much as 4:1 depending on the
frequency.
n The contaminants (on the insulators) have a larger effect when it israining than when the line is dry.
n The worst condition is a light rain with the presence of contaminantson the insulators
Effect of bad weather on PLC communication
Dedicated PLC for Phase Comparison
-
8/10/2019 Phase Comparison
34/55
Dedicated PLC for Phase Comparison
Requirements:
SPEED (Fast pick-up, fast drop-off) REPEATABILITY (STABILITY) SYMMETRICAL
Communication PLCs:
Encoding Audio Frequency (AF) Radio Frequency (RF) Channel Radio
Frequency (RF) Audio Frequency (AF) Decoding Guard Frequency: at first a receiver must detect guard freq. drop, then appearanceof signal frequency
Command length: 5-10 ms for detection Several commands and other data transmission with different priorities
Communication PLCs dont provide desired speed and stability
Specific PLC for phase comparison
Fast keying Radio Frequency (RF) Channel Radio Frequency (RF) - Outputto relay
Translation : User audio signal (AF) into radio Spectrum (RF)
Amplification : To compensate the line attenuation
RF Noise
-
8/10/2019 Phase Comparison
35/55
35
RF noise in HV linetwo mains effects
Impulsive Noise = Caused by atmospheric discharges, breakers andisolator close/open operation
Corona effect = Due to sequences of pulse streams caused by arcs overconductors. It appears during positive-going half-cycle of the Line voltage(occurrance frequency for a 50Hz 3-phase system is 150 Hz)
The corona noise could be subject to considerable variations due todifferences in the design parameters of the overhead line.
Other variations are possible due to the construction, altitude andage of the line
Weather effect can also be significant
RF Noise
-
8/10/2019 Phase Comparison
36/55
ON-OFF and FSK channels
180 180ON ON ON
OFF OFF
Hi_F Hi_F Hi_FLo_F Lo_F
ON-OFF channel
FSK channel
-
8/10/2019 Phase Comparison
37/55
Breaker
Failure
Single End
Tripping
Thermal
Protection
Negative Sequence
Protection
BrokenConductor
Detection
1 &3 PoleTripping
Phase
Comparison
Overcurrent
& SEF
Unstabilising
Facility
Charging Current
Compensation
P547 80TE Protection Functions
Distance
protectionDEF
protection
-
8/10/2019 Phase Comparison
38/55
MiCOM P54x - 1-Jul-13 - P 38
MiCOM P547 80TE
The MiCOM P547 provides:
High-speed phase comparisonprotection using proven phase
comparison technique.
Phase Selection is based on proven
techniques.
1 & 3 pole tripping
High performance sub cycle distance
protection:
Universal mho characteristics
Quadrilateral characteristics for shortlines/cables, and where boosting of
resistive fault coverage is required
Phase segregated aided directional
earth fault DEF to provide high
resistance ground fault detection
-
8/10/2019 Phase Comparison
39/55
MiCOM P547 80TE
Phase Comparison and Distance protection can workindependently, as a main 1 or main 2 protection.
Alternatively, each zone can be set independently to work incase of communication failure.
Distance elements may run in parallel with the PhaseComparison protection, offering dual main protection.
A phase segregated aided directional earth fault DEF can alsobe configured as a main 1 or main 2 or backup protection toprovide high resistance ground fault detection
PLC E i PLC R t bilit
-
8/10/2019 Phase Comparison
40/55
PLC - Ensuring PLC Repeatability,Compatibility & Suitability
MiCOM
P547 80TE
End X End Y
PLC
Interface
PLC
CouplingThird Party
PLC,
Coupling
Equipment
Third Party
PLC,
Coupling
Equipment
Line Trap Line Trap
PLC
Interface
PLC
Coupling
Pulsar PLC, from the USA or PZSU whichis widely used in the Russian network.
Connections Relay PLC Relay:
-
8/10/2019 Phase Comparison
41/55
Not a comms. protocol,simply Cu leads
P547 and PLCcontacts are staticoutputs for fast
switching
P547 dedicated fast scanI/O is additional tostandard I/O
PLC
P547
Out
Opto
OptoOut
Connections Relay - PLC - Relay:Two Copper Wire Pairs (4 Leads)
-
8/10/2019 Phase Comparison
42/55
Unbalanced faults will have negative sequence component The positive sequence component is used to counter the
effects of the negative sequence component due tounbalanced charging current in the case of three phasefaults.
The modulating quantity is
where 3K20
-I1+ KI2
Modulating Quantity
-
8/10/2019 Phase Comparison
43/55
Adaptive K - Intelligent Mode Setting
0
5
10
15
20
25
30
35
0 2 4 6 8 10
Pre Fault Load /Earth Fault Setting
K
For heavy prefault load, or power
swings, need to boost I2 effect to keep
earth fault sensitivity
Earth Fault Sensitivity if
-
8/10/2019 Phase Comparison
44/55
Remote end AN fault
Load, IFLC
Local End Current
Contribution, IF
LOAD
K > 3*IFLC/IF + 1
Earth Fault Sensitivity ifSet to User Mode
Starters - to Detect the Fault and
-
8/10/2019 Phase Comparison
45/55
Control Carrier Send & Tripping
Starters
Delta/Impulse negative sequence (0.05- 0.6 In)
Delta/Impulse positive sequence
(0.05-0.6 In) Threshold negative sequence (I2)
(0.05 -5.0 In) Threshold positive sequence (I1)
(0.05 - 5.0 In) Threshold negative voltage (V2)
(0.001 - 1 Un)
Distance (chosen Zone) Delta could be set more sensitive
irly
=
imem
+
ir
Current :-
Prefault Fault
= Superimposed
-
8/10/2019 Phase Comparison
46/55
Propagation Delay
Where is the Propagation delay introduced?
Delay in supplying i/p pulse to PLC equipment, PLCequipment processing time (rising edge and lag at switchoff burst on falling edge).
Delay at receiving end - PLC processing time and delay bythe relay in measuring the time period of the input pulse.
Propagation delay of the HF carrier along the power line(negligible = 3 s per km).
-
8/10/2019 Phase Comparison
47/55
Why does the propagation delay need to be considered ? If it is not considered the effective stabilityangle s has to be set much higher
This would limit the maximum line length
Propagation delay test is automatically instigated at user settime intervals
Propagation Delay
MiCOM P547 Channel Auto Test
-
8/10/2019 Phase Comparison
48/55
Channel autotest
Chan Test should be enabled at least for MASTER
Relays must be configured as one MASTER and one or twoSLAVEs
Channel Fail ALARM:
MASTER: no reply (5 ms pulse) from SLAVE after request duringTest Time
SLAVE: no request (pulse 15 ms) from MASTER during Test Time
If channel failed, Phase Comparison isnt disabled, channel
propagation time is kept from previous test
If SLAVE has Chan Test disabled, autotest works Ok. Channel
Failure ALARM isnt raised in SLAVE relay
MiCOM P547 Channel Auto Test
Recommended Stability Angle Setting -
-
8/10/2019 Phase Comparison
49/55
For lines longer than 150 km, a 5 degree increase in s is recommended foreach additional 50 km.
Capacitive charging current constraints limit phase comparison application toa practical maximum of 400 km line length (250 miles).
Recommended Stability Angle Setting -Variation with km
Length(km)
150 km 200 km 250 km 300 km 350 km 400 km
Length(miles)
90 mi 125 mi 155 mi 185 mi 215 mi 250 mi
30 35 40 45 50 55
MiCOM P547 Charging current compensation
-
8/10/2019 Phase Comparison
50/55
MiCOM P547 Charging current compensation,Mode 1
End X
End Y
Y
2
Y
2
Mode 1
IX
IYUX UY
I
Y, cap.X, cap.
U
IY
IX
I X, cap.
IY, cap.
IY
IX
Id
180
Icomp (A,B,C) = Imeas (A,B,C)Icap (A,B,C)
Icomp (A,B,C)= Imeas (A,B,C)j*U(A,B,C) * Y/2 * f/fnom
compensated measured
-
8/10/2019 Phase Comparison
51/55
Stability angle Mode 1
x - y =180
x - y = 0
BLOCK TRIP
s
s
SYSTEM STABILITY ANGLE- s.
Icap 1
MiCOM P547 Charging current compensation,
-
8/10/2019 Phase Comparison
52/55
Icap =
Unom. ph*Y/2
= 2*arcsin(I./Iod)
In Mode 2 the relay doesnt measure real voltage
Mode 2 increases stability
angle by s
s
Iod= - I1 + K*I2
End X
End Y
Y
2Y
2
Mode 2
IXI
YUX UYIY, cap.X, cap.
MiCOM P547 Charging current compensation,Mode 2
bili l d
-
8/10/2019 Phase Comparison
53/55
c
c
Stability angle Mode 2
x - y =180 x - y = 0
BLOCK TRIP
s
s
SYSTEM STABILITY ANGLE- s.Charging Current Compensation- C.
IcapMode-2
MiCOM Phase Comparison
-
8/10/2019 Phase Comparison
54/55
MiCOM Phase ComparisonAdvantages
Mode of protection where PLC exists.
Provides unit protection without fibre optic connection.
Communication medium is as reliable as the Power Line itself
No additional Phase selection relay required along with phasecomparison relay.
No seperate charging current compensation setting needed.
Charging current compensation works all time.
Applicable to all lines, long or short, strong and weak infeeds
Applicable to teed-off transformer and 3-line terminal application.
-
8/10/2019 Phase Comparison
55/55
GRID