phase comparison

Upload: neelakandan-masilamani

Post on 02-Jun-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Phase Comparison

    1/55

    GRID

    Sankara Subramanian

    Phase Comparison protection

  • 8/10/2019 Phase Comparison

    2/55

    History of Phase comparison ...

  • 8/10/2019 Phase Comparison

    3/55

    Principle of Phase Comparison -Normal Load Conditions

    ON-OFF

    channel

    End X End Y

    X (+)I Y(+)I

    Mark Mark

    Composite - (usually no PLC signal transmission for load)

    MarkSpace

    Modulated signals MarkSpace

    -+

    Terminal currents

    +

    -

  • 8/10/2019 Phase Comparison

    4/55

    Principle of Phase Comparison -External Fault

    Composite modulated signal

    End X End Y

    X (+)I Y(+)I

    -+

    Terminal currents -+

    Modulated signals MarkSpace

    MarkSpace

    Mark Mark

    ON-OFF

    channel

  • 8/10/2019 Phase Comparison

    5/55

    Principle of Phase Comparison -Internal Fault

    Composite modulated signal

    End X End Y

    X (+)I Y(+)I

    FI

    -+

    Terminal currents -+

    Mark

    SpaceModulated signals Mark

    Space

    Mark Space

    ON-OFF

    channel

    180 180

    GAP = TRIP

  • 8/10/2019 Phase Comparison

    6/55

    Channel EquipmentPhase-segregated channel

    Phase A

    Phase B

    Phase C

    AI

    BI

    CI

  • 8/10/2019 Phase Comparison

    7/55

    Channel EquipmentSingle-phase channel

    Phase B typically

    ???,, CBA III

  • 8/10/2019 Phase Comparison

    8/55

    Line Faults Current sequences

    Fault

    SequenceLoad 3-Ph Ph-Ph

    Ph-Ground

    Ph-Ph-Ground

    Positive (1) + + + + +

    Negative (2) - - + + +

    Zero (0) - - - + +

  • 8/10/2019 Phase Comparison

    9/55

    Modulating quantity

    HISTORY

    MODERN APPROACH

    A.J. McConnel,

    General Electric (1947)

    H.W. Lensner, Westinghouse (1946),

    A.P. Pleshko, Russia (1941)1 0I k I

    2 0 1 (for 3-Ph fault)I k I I

    Russian manufacturers

    Alstom

    General Electric

    Phase-segregated (3 channels) France

  • 8/10/2019 Phase Comparison

    10/55

    Line Faults Modulating quantity

    Fault

    Sequence

    Load 3-Ph Ph-PhPh-

    GroundPh-Ph-Ground

    Positive (1) + + + + +

    Negative (2) - - + + +

    Zero (0) - - - + +

  • 8/10/2019 Phase Comparison

    11/55

    Current angle errors

    Sources angle difference

    Signal propagation delay

    Measurement errors

    Charging currents

  • 8/10/2019 Phase Comparison

    12/55

    Stability angle (1)

    x - y =180

    x - y = 0

    BLOCK TRIP

    s

    s

    SYSTEM STABILITY ANGLE- s.

    Load and external faultsInternal faults

  • 8/10/2019 Phase Comparison

    13/55

    Stability angle (2)

    s is the system stability angle, recommended setting for shortlines is 30o.

    s compensates for general tolerances in PLC, relay, CT non-linearity and changes in atmospheric conditions since the last

    propagation delay measurement. A 30osetting (-30o to +30o) means that a carrier gap/space

    of longer than s /360, is needed to trip.

  • 8/10/2019 Phase Comparison

    14/55

    Long lines charging current

    End X

    End Y

    Y

    2

    Y

    2I

    XIYUX UY

    IY, cap.X, cap.

    U

    IY

    IX

    I X, cap.

    IY, cap.

    IYIX

    Id

    180

    HV lines with LENGTH > 150km require charging current compensation

  • 8/10/2019 Phase Comparison

    15/55

    Starters

    PLC cannot be activated permanently

    LOW STARTERSinitiate RF communication through channel(start PLC)

    Some gap could appear in RF signal under normal condition

    HIGH STARTERSactivate phase comparison element andallow trip to be issued.

    IMPORTANT:

    If any HIGH starter operated at one line terminal, some LOWstarter MUST be active at all other terminals (all PLCs should

    be active)

    !!!ONE-SIDED START OF PHASE COMPARISON = FALSE TRIP!!!

  • 8/10/2019 Phase Comparison

    16/55

    Phase Comparison classification

    Phase Comparison protection

    Voltage-independent

    (purely current)

    Voltage-dependent

    Starters:

    - current

    - voltage

    - distance

    - current starters

    Voltage-independent Phase Comparison

    should be used whenever possible, as itsmuch more reliable (immune to VTfailure). Unfortunately, its not suitable forlong HV lines.

    - current modulation

    - complex

    modulation

    Voltage-dependent PhaseComparison is universal, butprone to VT failure.

  • 8/10/2019 Phase Comparison

    17/55

    Phase Comparison Typicalfunctional diagram

    Sequencer

    Ia

    Ib

    Ic I2

    Charging

    current

    Compensation Yc

    setting

    Sequencer

    I1High set

    Starter

    Mixer

    RX

    Angle

    shift

    Voltage

    Input

    Va

    Vb

    Vc

    Sequencer

    Compen-

    sating

    Zneg

    Distance

    Starter

    Input

    Low set

    Starter

    TX

    Trip

    Decision

    Gap

    Detectio

    n

    Phasecomparison

    Mark / Space

    Trip /

    Block

    V2 V2_comp

    I I2

    V

  • 8/10/2019 Phase Comparison

    18/55

    Phase comparison protection utilizes sequence components based startersfor sensitivity.

    Current Modulator to do the mixing of the positive sequence and negativesequence currents to enable the phase angle detection.

    The calculated modulated current positive half cycle is communicated to

    the remote end and is compared with the received remote Modulatedcurrent to do the phase angle measurement.

    Phase angle Gap measurement starts only when the High set starter pickup.

    WorkingStarters & Modulator

  • 8/10/2019 Phase Comparison

    19/55

    As continuous transmission is not permitted Starter units are provided

    (sensitive-to provide high speed operation) such that Low set initiatestransmission of carrier signal while high set initiates Gap measurements &trip in phase comparison protection.

    Positive(I1) and negative sequence (I2)starters are provided to cover forbalanced and unbalanced fault conditions.

    Low set and high set starters are provided to cater for the differences inthe magnitude between the currents at 2 ends and also to account for themagnitude errors in the CT, hence 2 levels are required.

    Impulse (Delta ) starters and Non-Impulse (threshold) starters areprovided.

    While generally, Impulse starters finds its application for most systemfault conditions, Non- impulse starters can be set for system conditionslike evolving fault scenarios from external to internal with out much rise inthe fault currents.

    StartersApplication -Setting Tips(1)

  • 8/10/2019 Phase Comparison

    20/55

    Impulse Positive sequence starters (I1):

    High set Impulse must be set above total line charging current (2 x Ich) to avoidtripping for closing CB.

    High set should be set < 3 phase fault level, typically 50% of If min 3 .

    In order to make protection stable during through fault conditions, ensure the

    difference between the minimum effective high set setting and maximum effectivelow set setting is > than the Positive sequence capacitive current. To meet thisrequirement set the ratio of HSS / LSS to a factor of 2.

    Non-Impulse Positive sequence starters (I1):

    I1 low set must be set above the maximum load current

    I1 low set must be set above peak power swing current, to prevent continuoustransmission Alarm being raised for slow swings .Typical swing = 2 In ; set to 2.5or 3 In

    I1 high set needs to be 125% to 200% of I1 low set to give adequate margin

    StartersApplication -Setting Tips(2)

  • 8/10/2019 Phase Comparison

    21/55

    Impulse Negative sequence starters (I2):

    Impulse negative starters should be set to provide sensitivity for high resistance faults lessthan 10% of the rated current.

    (3 x Impulse I2 High Set) = Effective earth fault sensitivity of the scheme. Ensure the following for long transmission line. (same can be adopted for medium lines):

    Impulse I2 High set is NOT < IS * ((1/SIN) ( s - - ))

    Where IS is sending end current (only line charging current is present under no

    load condition, when the local breaker is closed);

    s is stability angle setting;

    - is typically taken as 15 deg (set to cover phase angle errors introduced by CT);

    - is typically taken as 10 deg ( set to cover the phase angle difference between

    compared line terminal currents due to signal propagation time and may be takenas 0.1 deg per mile).

    Ensure HSS to LSS ratio is not less than 1.5 (alternatively, set Low set to 66% of

    High set setting).

    StartersApplication -Setting Tips(3)

  • 8/10/2019 Phase Comparison

    22/55

    Non-Impulse (Threshold) Negative sequence starters (I2):

    Non impulse I2 starters are set less sensitive than the impulse I2starters.

    Non-Impulse starters are set above the standing I2 in the system. Example: Transmission system feeding 1-phase traction feeders.

    Non-impulse I2 ensures, operation for certain faults-like slowdeveloping faults / evolving external to internal faults with noincrease in I2 current magnitude.

    Non-impulse also provided with Low set and High set starters.

    Set Non-Impulse I2 to typically between 1.5 and 5 times theImpulse I2 starters.

    StartersApplication -Setting Tips(4)

  • 8/10/2019 Phase Comparison

    23/55

    1-ph AR (single pole autoreclose)

    Phase comparison is exceptionally good in case of 1-ph AR

    Evolving faults are cleared during 1-ph AR dead time

    Typically LOW and HIGH starters are active at both line ends as linemode is non-symmetrical (though that depends on load current andusage of voltage starters). Phase Comparison protection awaits only forGAPs.

    IMPORTANT:

    PLC transmission should be active at both line endsduring 1-ph AR dead time

    !!!ONE-SIDED PLC TRANSMISSION = FALSE TRIP!!!

  • 8/10/2019 Phase Comparison

    24/55

    Teed-off transformers

    Phase comparison can be applied to teed-off transformer application

    Internal Fault

    - In many applications, there can be a step-down transformer teed-off the protected line. Thistransformer is not part of the protected unit, but is teed-off to out feed local load. The difficulty isthis tee-line is NOT treated as the third-end of the phase comparison protection.

    - Hence the 2 end Phase comparison protection must function correctly for such scenario. Theprotection must refrain for internal load and also operate for internal fault scenarios.

    RLOAD

    R

    IF

    IL

    IF DIRECTION

    IL DIRECTION,DEPENDINGONTHESTRENGTH

    OFSOURCES& CONNECTEDLOAD

    LOAD

  • 8/10/2019 Phase Comparison

    25/55

    Teed-off transformers Distance permissive

    External Fault beyond the transformer

    If teed-off transformer is extremely weak, it could be possible to select High Starters higherthen external fault currents (still sensitive for internal faults)

    Otherwise we must use Distance permissive scheme. This scheme doesnt require anyadditional equipment

    Permissive Scheme

    R

    LOAD

    R

    IFIF DIRECTION

    LOAD

    DISTANCE permission

    Z2 Z2

  • 8/10/2019 Phase Comparison

    26/55

    Teed-off transformers with blocking kit

    External Fault beyond transformer

    Sometimes Distance permissive scheme cant be used because of settings issue

    Blocking-scheme works for most of teed-off cases, but requires additional PLC and, sometimes,

    relays

    PCLOAD

    PC

    IF

    IF DIRECTION

    LOAD

    PLC PLC

    Distance

    Power

    Direction

    Transfo

    prot.

    PLC

    Direction

    PC Phase

    Comparison

    Blocking Kit

    Injects continuous carrier

    Block Block

    3 ended Lines

  • 8/10/2019 Phase Comparison

    27/55

    3-ended Lines

    Phase comparison can be applied to 3-ended lines

    For any through-fault one current is in opposite phase to others.

    I1

    PCLOAD

    PC

    LOAD

    PC

    IF

    IF DIRECTION

    I1 I2

    I3

    I2

    I3

    SUM

    NO GAPS = BLOCK

    Weak Infeed

  • 8/10/2019 Phase Comparison

    28/55

    Weak Infeed

    Phase comparison should be considered with great care in case of weak infeed.

    If fault current is comparable with load current, this could lead to protection inaction(the angle of modulating quantity [I1+K*I2] is hard to predict)

    PC

    LOAD

    PC

    IF

    IF DIRECTION

    LOAD DIRECTION

    Strong Source

    Weak Source

  • 8/10/2019 Phase Comparison

    29/55

    General advantages of Phase Comparison

    Absolute selectivity

    Reliable channel (power line itself)

    Immune to Power Swings

    Immune to VT failure (in voltage-independent version)

    Channel is under the utilitys control, unlike third partytelecommunications

  • 8/10/2019 Phase Comparison

    30/55

    FrontBehind

    Local substation

    To remote

    substation

    Coupling

    Capacitor

    Line

    Matching

    Unit

    PLC terminal

    Coaxial

    Transformer s)

    BusBar

    Line Trap

    The PLCsignal isrouted to HVLine

    The PLC

    signal is notabsorbed bythe substation

    Coupling Scheme

    Line Trap function

  • 8/10/2019 Phase Comparison

    31/55

    = PLC signal Blocking

    HV Line

    Substation

    Line Trap = High Impedance for PLC signal (High Freq)

    Low Impedance for Power energy (50/60 Hz)

    Power energy 50/60 Hz)

    PLC Signal High Freq)

    Line Trap function

  • 8/10/2019 Phase Comparison

    32/55

    Two types of modulation

    Signal

    AM

    FM

    Effect of bad weather on PLC communication

  • 8/10/2019 Phase Comparison

    33/55

    33

    Losses increase for all inclement weather conditions

    n The worst offender is when heavy frost is formed on the line

    n Because of the skin effect, the carrier signal tries to propagate on

    the ice instead of the conductor.n The attenuation can change as much as 4:1 depending on the

    frequency.

    n The contaminants (on the insulators) have a larger effect when it israining than when the line is dry.

    n The worst condition is a light rain with the presence of contaminantson the insulators

    Effect of bad weather on PLC communication

    Dedicated PLC for Phase Comparison

  • 8/10/2019 Phase Comparison

    34/55

    Dedicated PLC for Phase Comparison

    Requirements:

    SPEED (Fast pick-up, fast drop-off) REPEATABILITY (STABILITY) SYMMETRICAL

    Communication PLCs:

    Encoding Audio Frequency (AF) Radio Frequency (RF) Channel Radio

    Frequency (RF) Audio Frequency (AF) Decoding Guard Frequency: at first a receiver must detect guard freq. drop, then appearanceof signal frequency

    Command length: 5-10 ms for detection Several commands and other data transmission with different priorities

    Communication PLCs dont provide desired speed and stability

    Specific PLC for phase comparison

    Fast keying Radio Frequency (RF) Channel Radio Frequency (RF) - Outputto relay

    Translation : User audio signal (AF) into radio Spectrum (RF)

    Amplification : To compensate the line attenuation

    RF Noise

  • 8/10/2019 Phase Comparison

    35/55

    35

    RF noise in HV linetwo mains effects

    Impulsive Noise = Caused by atmospheric discharges, breakers andisolator close/open operation

    Corona effect = Due to sequences of pulse streams caused by arcs overconductors. It appears during positive-going half-cycle of the Line voltage(occurrance frequency for a 50Hz 3-phase system is 150 Hz)

    The corona noise could be subject to considerable variations due todifferences in the design parameters of the overhead line.

    Other variations are possible due to the construction, altitude andage of the line

    Weather effect can also be significant

    RF Noise

  • 8/10/2019 Phase Comparison

    36/55

    ON-OFF and FSK channels

    180 180ON ON ON

    OFF OFF

    Hi_F Hi_F Hi_FLo_F Lo_F

    ON-OFF channel

    FSK channel

  • 8/10/2019 Phase Comparison

    37/55

    Breaker

    Failure

    Single End

    Tripping

    Thermal

    Protection

    Negative Sequence

    Protection

    BrokenConductor

    Detection

    1 &3 PoleTripping

    Phase

    Comparison

    Overcurrent

    & SEF

    Unstabilising

    Facility

    Charging Current

    Compensation

    P547 80TE Protection Functions

    Distance

    protectionDEF

    protection

  • 8/10/2019 Phase Comparison

    38/55

    MiCOM P54x - 1-Jul-13 - P 38

    MiCOM P547 80TE

    The MiCOM P547 provides:

    High-speed phase comparisonprotection using proven phase

    comparison technique.

    Phase Selection is based on proven

    techniques.

    1 & 3 pole tripping

    High performance sub cycle distance

    protection:

    Universal mho characteristics

    Quadrilateral characteristics for shortlines/cables, and where boosting of

    resistive fault coverage is required

    Phase segregated aided directional

    earth fault DEF to provide high

    resistance ground fault detection

  • 8/10/2019 Phase Comparison

    39/55

    MiCOM P547 80TE

    Phase Comparison and Distance protection can workindependently, as a main 1 or main 2 protection.

    Alternatively, each zone can be set independently to work incase of communication failure.

    Distance elements may run in parallel with the PhaseComparison protection, offering dual main protection.

    A phase segregated aided directional earth fault DEF can alsobe configured as a main 1 or main 2 or backup protection toprovide high resistance ground fault detection

    PLC E i PLC R t bilit

  • 8/10/2019 Phase Comparison

    40/55

    PLC - Ensuring PLC Repeatability,Compatibility & Suitability

    MiCOM

    P547 80TE

    End X End Y

    PLC

    Interface

    PLC

    CouplingThird Party

    PLC,

    Coupling

    Equipment

    Third Party

    PLC,

    Coupling

    Equipment

    Line Trap Line Trap

    PLC

    Interface

    PLC

    Coupling

    Pulsar PLC, from the USA or PZSU whichis widely used in the Russian network.

    Connections Relay PLC Relay:

  • 8/10/2019 Phase Comparison

    41/55

    Not a comms. protocol,simply Cu leads

    P547 and PLCcontacts are staticoutputs for fast

    switching

    P547 dedicated fast scanI/O is additional tostandard I/O

    PLC

    P547

    Out

    Opto

    OptoOut

    Connections Relay - PLC - Relay:Two Copper Wire Pairs (4 Leads)

  • 8/10/2019 Phase Comparison

    42/55

    Unbalanced faults will have negative sequence component The positive sequence component is used to counter the

    effects of the negative sequence component due tounbalanced charging current in the case of three phasefaults.

    The modulating quantity is

    where 3K20

    -I1+ KI2

    Modulating Quantity

  • 8/10/2019 Phase Comparison

    43/55

    Adaptive K - Intelligent Mode Setting

    0

    5

    10

    15

    20

    25

    30

    35

    0 2 4 6 8 10

    Pre Fault Load /Earth Fault Setting

    K

    For heavy prefault load, or power

    swings, need to boost I2 effect to keep

    earth fault sensitivity

    Earth Fault Sensitivity if

  • 8/10/2019 Phase Comparison

    44/55

    Remote end AN fault

    Load, IFLC

    Local End Current

    Contribution, IF

    LOAD

    K > 3*IFLC/IF + 1

    Earth Fault Sensitivity ifSet to User Mode

    Starters - to Detect the Fault and

  • 8/10/2019 Phase Comparison

    45/55

    Control Carrier Send & Tripping

    Starters

    Delta/Impulse negative sequence (0.05- 0.6 In)

    Delta/Impulse positive sequence

    (0.05-0.6 In) Threshold negative sequence (I2)

    (0.05 -5.0 In) Threshold positive sequence (I1)

    (0.05 - 5.0 In) Threshold negative voltage (V2)

    (0.001 - 1 Un)

    Distance (chosen Zone) Delta could be set more sensitive

    irly

    =

    imem

    +

    ir

    Current :-

    Prefault Fault

    = Superimposed

  • 8/10/2019 Phase Comparison

    46/55

    Propagation Delay

    Where is the Propagation delay introduced?

    Delay in supplying i/p pulse to PLC equipment, PLCequipment processing time (rising edge and lag at switchoff burst on falling edge).

    Delay at receiving end - PLC processing time and delay bythe relay in measuring the time period of the input pulse.

    Propagation delay of the HF carrier along the power line(negligible = 3 s per km).

  • 8/10/2019 Phase Comparison

    47/55

    Why does the propagation delay need to be considered ? If it is not considered the effective stabilityangle s has to be set much higher

    This would limit the maximum line length

    Propagation delay test is automatically instigated at user settime intervals

    Propagation Delay

    MiCOM P547 Channel Auto Test

  • 8/10/2019 Phase Comparison

    48/55

    Channel autotest

    Chan Test should be enabled at least for MASTER

    Relays must be configured as one MASTER and one or twoSLAVEs

    Channel Fail ALARM:

    MASTER: no reply (5 ms pulse) from SLAVE after request duringTest Time

    SLAVE: no request (pulse 15 ms) from MASTER during Test Time

    If channel failed, Phase Comparison isnt disabled, channel

    propagation time is kept from previous test

    If SLAVE has Chan Test disabled, autotest works Ok. Channel

    Failure ALARM isnt raised in SLAVE relay

    MiCOM P547 Channel Auto Test

    Recommended Stability Angle Setting -

  • 8/10/2019 Phase Comparison

    49/55

    For lines longer than 150 km, a 5 degree increase in s is recommended foreach additional 50 km.

    Capacitive charging current constraints limit phase comparison application toa practical maximum of 400 km line length (250 miles).

    Recommended Stability Angle Setting -Variation with km

    Length(km)

    150 km 200 km 250 km 300 km 350 km 400 km

    Length(miles)

    90 mi 125 mi 155 mi 185 mi 215 mi 250 mi

    30 35 40 45 50 55

    MiCOM P547 Charging current compensation

  • 8/10/2019 Phase Comparison

    50/55

    MiCOM P547 Charging current compensation,Mode 1

    End X

    End Y

    Y

    2

    Y

    2

    Mode 1

    IX

    IYUX UY

    I

    Y, cap.X, cap.

    U

    IY

    IX

    I X, cap.

    IY, cap.

    IY

    IX

    Id

    180

    Icomp (A,B,C) = Imeas (A,B,C)Icap (A,B,C)

    Icomp (A,B,C)= Imeas (A,B,C)j*U(A,B,C) * Y/2 * f/fnom

    compensated measured

  • 8/10/2019 Phase Comparison

    51/55

    Stability angle Mode 1

    x - y =180

    x - y = 0

    BLOCK TRIP

    s

    s

    SYSTEM STABILITY ANGLE- s.

    Icap 1

    MiCOM P547 Charging current compensation,

  • 8/10/2019 Phase Comparison

    52/55

    Icap =

    Unom. ph*Y/2

    = 2*arcsin(I./Iod)

    In Mode 2 the relay doesnt measure real voltage

    Mode 2 increases stability

    angle by s

    s

    Iod= - I1 + K*I2

    End X

    End Y

    Y

    2Y

    2

    Mode 2

    IXI

    YUX UYIY, cap.X, cap.

    MiCOM P547 Charging current compensation,Mode 2

    bili l d

  • 8/10/2019 Phase Comparison

    53/55

    c

    c

    Stability angle Mode 2

    x - y =180 x - y = 0

    BLOCK TRIP

    s

    s

    SYSTEM STABILITY ANGLE- s.Charging Current Compensation- C.

    IcapMode-2

    MiCOM Phase Comparison

  • 8/10/2019 Phase Comparison

    54/55

    MiCOM Phase ComparisonAdvantages

    Mode of protection where PLC exists.

    Provides unit protection without fibre optic connection.

    Communication medium is as reliable as the Power Line itself

    No additional Phase selection relay required along with phasecomparison relay.

    No seperate charging current compensation setting needed.

    Charging current compensation works all time.

    Applicable to all lines, long or short, strong and weak infeeds

    Applicable to teed-off transformer and 3-line terminal application.

  • 8/10/2019 Phase Comparison

    55/55

    GRID