phasor mesurement system in brazil

Upload: rodrigosaa

Post on 06-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 Phasor Mesurement System in Brazil

    1/8

    1

    Abstract-- This paper describes recent results of the MedFaseeproject aiming at the development and performance testing of a

    Synchronized Phasor Measurement System (SPMS) prototype and

    its applications for monitoring of power system operation. The

    prototype consists of a Phasor Data Concentrator (PDC) and three

    Phasor Measurement Units (PMUs) installed in cities in Southern

    Brazil. Results from monitoring system frequency and voltage in

    normal and abnormal conditions are shown. These results indicate

    that is possible to obtain important information on power systemdynamics using SPMS connected at low-voltage and Internet.

    Index Terms Phasor Measurements, PMU, power system

    monitoring, wide-area monitoring, SPMS, WAMS.

    I. INTRODUCTION

    N the last years, economic considerations associated to the

    electricity market and environment restrictions have led grid

    operators to postpone or reduce investments. This scenario

    combined with the continuous load increase leads the power

    system and its components to operate closer to their limits.

    Furthermore, reliable electricity supply is now essential for

    society, and blackouts are becoming more costly [1].

    To operate the power system closer to limits and still to

    keep a high reliability is a challenging task and requires tools

    that allow the prompt detection of instabilities. SCADA data

    provide a comprehensive record of power system conditions

    but at a relatively slow rate [2]. New tools such as

    Synchronized Phasor Measurement Systems (SPMS), which

    use advances in communications, computers and Global

    Positioning System (GPS) technologies, are needed for

    monitoring and control to improve the security of large power

    systems [3]. The SPMS can capture the faster power system

    variations enabling operators to monitor and often control

    critical power system operating indices, which are essentialfor secure operation of a large power system, including static

    phase-angle limits (power system stress), critical intermediate

    voltage support when operating at large phase-angle

    Work partially supported by contract FNDCT CT-Energ/Finep

    01.02.0039.00 and Reason Technology S.A.

    I. C. Decker, D. Dotta, M. N. Agostini , and A. S. e Silva are with Federal

    University of Santa Catarina, Florianpolis, SC 88.040-900 Brazil (e-mail:

    [email protected],[email protected],[email protected],agui

    [email protected]).

    S. L. Zimath is with Reason Technology S. A., Florianpolis, SC 88.025-

    500 Brazil (e-mail: [email protected]).

    separation, dynamic/transient phasor movements indicating

    dynamic/transient swings among different areas and modal

    inter area oscillation frequencies and their modal damping [3].

    The SPMS, sometimes referred to more generically as a

    Wide Area Measurement System (WAMS), are basically

    composed by PMUs (Phasor Measurements Units)

    connected to a Phasor Data Concentrator (PDC) and

    application methodologies for monitoring and control of

    power system real time operation [2]. The first developmentsin SPMS started in 1989 with the WAMS project in

    subsystems of the WECC (Western Electricity Coordinating

    Council) of U.S.A. [4]. This project involved the use of GPS-

    synchronized measurements over a large area of that power

    network [5]. In the last few years, several others countries

    started to install SPMS in their electrical systems. Besides the

    U.S.A., the following countries are reported to have installed

    and integrated phasor measurement units for research or are

    developing prototypes: Brazil [4], Scandinavia [9], Korea

    [10], Taiwan [11], China [12], Japan [13], and France, Italy,

    Switzerland, Croatia, Greece, Mexico, South Africa [5].

    In the beginning of 2003, following the experience gainedin the western power system, the U.S. Department of Energy

    (DOE) launched the Eastern Interconnection Phasor Project

    (EIPP), which is being executed by a work group comprising

    transmission owing utilities, hardware and software vendors,

    power system operators, reliability councils and government.

    The EIPP seeks to improve power system reliability through

    wide area measurement, monitoring and control [6]. To reach

    this goal six task teams were created by EIPP. As the SPMS

    technology is so incipient, the main work developed for the

    task team was the identification, description and specification

    of the functional requirements for components of software and

    hardware for SPMS. These components include the

    equipments (PMUs, PDC, network, etc) and the monitoring,

    protection and control applications. Specifically, the

    Performance Requirements Task Team (PRTT) has been

    working in a report including guidelines/requirements for a

    PMU Testing Guide. The main objective of PMU Testing

    Guide is to define a testing procedure to assess the PMUs

    that will be installed in the Eastern Interconnection. The PMU

    assessment is important as shown in [7]. That work shows that

    PMUs of different manufacturers can be only compared under

    nominal frequency operations conditions. In off-nominal

    frequency operation every tested PMU unit yielded a different

    Performance of a Synchronized Phasor

    Measurements System in the Brazilian Power

    SystemI. C. Decker, D. Dotta, M. N. Agostini, S. L. Zimath, andA. S. e Silva.

    I

    1-4244-0493-2/06/$20.00 2006 IEEE.

  • 8/3/2019 Phasor Mesurement System in Brazil

    2/8

    2

    phase and magnitude for the common measured voltage

    signal. These measurement errors must be taken into account

    to allow the connection between PMUs of different

    manufactures.

    This paper describes new results of a research project on

    SPMS in Brazil, the MedFasee project. The main goal of this

    paper is to show the performance of a SPMS prototype

    comprising three PMUs and one PDC, under normal and

    abnormal power system conditions.The paper is organized as follows. In Section 2, the

    MedFasee project is presented and the main software and

    hardware components of the SPMS prototype are described.

    In Section 3, the performance of the PMU prototype is

    presented. In Section 4, the performance of the SPMS

    prototype in monitoring the power system under normal and

    abnormal conditions is presented. Finally, in Section 5 and 6,

    the future developments and main conclusions are,

    respectively, presented.

    II. MEDFASEE PROJECT

    The MedFasee project was started in 2003 aiming at thedevelopment of a phasor measurement system prototype and

    applications for power systems monitoring and control. The

    prototype was installed in the end of 2004 and since then the

    frequency and disturbances, in the Southern Brazil power

    system, have been monitored.

    A. SPMS Prototype

    The SPMS prototype is composed by one PDC and three

    PMUs. The three PMUs were installed in laboratories of three

    universities in Southern Brazil: Federal Center of

    Technological Education of Parana (CEFET-PR) in Curitiba,

    Federal University of Santa Catarina (UFSC) in Florianpolis

    and Catholic University (PUCRS) in Porto Alegre. The PMUsmeasure the instantaneous three-phase distribution voltage and

    frequency. Each PMU is connected to the Internet through an

    ethernet network interface and sends the phasors to the PDC

    located in the Electrical Systems Planning Research

    Laboratory (LabPlan) at UFSC. In Figure 1 the geographical

    location of the PDC and PMUs in Brazil is shown.

    The main hardware components and the prototype

    functionalities are described as follows:

    1) PMU

    The PMUs were entirely designed and built as part of the

    MedFasee project. To implement the main PMU functions,

    phasor calculation and transmission to the PDC, the voltageand current samples, acquired synchronously with the GPS

    reference, are processed by Discrete Fourier Transform

    (DFT), and formatted in data frames, using the IEEE Std.

    1344-1995 format [15]. Each PMU has a GPS receiver to

    synchronize the samples, so that the phasor angles measured

    by all PMUs in the power system are in the same time

    reference. The PMUs have eight analogue channels (four for

    voltage and four for current), and 16 digital channels. The

    PMU generated data are continuously sent to the PDC, at a

    rate of 60Hz, using an Ethernet link (UDP/IP protocol). This

    rate and an angle precision of 0.1 electric degrees are suited

    for the analysis of long term dynamic phenomena [15].

    Fig. 1. PMUs and PDC geographical location.

    2) PDC

    The PDC receives and correlates time-tagged phasor data

    sent by all the PMUs. It has the following main functions:

    a) Acquisition of the phasors, continuously sent by the

    PMUs and handling of transmission errors;b) Storage of phasors in a central database;

    c) Support for real time system monitoring;

    d) Support for offline study applications, making

    available old phasors.

    These functions are designed and implemented in

    computing routines using the Object Oriented Modeling

    paradigm and C++ programming language. As the PDC needs

    to support real time applications it is necessary to rank the

    routines priorities. For example, the task of phasors

    acquisition has a higher priority than a request from the off-

    line study application. To solve this problem a real time

    environment needed to be implemented. The PDC was built

    using the GNU/Linux operating system that does not have

    native real time support. The real time support is enabled in

    GNU/Linux applying a patch to the GNU/Linux kernel. There

    are two main packages for this finality: RT-Linux and RTAI.

    The latter was chosen since it presented a better support for

    object-oriented programming tasks.

    3) Network

    The PMUs and PDC are connected by ethernet using the

    Internet network. The Internet connection was chosen due to

    its availability and the facilities provided to manage the PMUs

    remotely. The phasors are sent by the PMUs using the UDP/IP

    protocol and the remote administration is performed by theSSH (Security Shell) application.

    Figure 2 shows the phasors loss (in percentage) in a typical

    workday (Tuesday). The worse period is about midday when

    up to 2% of the data sent did not arrive at the PDC. The same

    behavior was found in all weekdays. In holidays and

    weekends the data loss is almost 0%. The measured

    transmission delay in the Internet is about 130 ms. In the local

    100 Mbps Ethernet network (LabPlan network) this delay falls

    to 30 ms. These results support the choice of the Internet for

    the MedFasee project purposes.

  • 8/3/2019 Phasor Mesurement System in Brazil

    3/8

    3

    Fig. 2. Network performance (data lost in percentage).

    4) Database

    The database is an independent process in the PDC and it is

    accessed by the storage routines through specific database

    functions [4]. The external applications are connected directly

    to the database. The database structure was designed to

    facilitate the data access and stores up to seven days of

    continuous data of all PMUs in the power system. Thedatabase is circular; new data replaces the oldest data. The

    database was implemented using the MySQL software for

    GNU/Linux. The MySQL database fulfills the requirements of

    the SPMS prototype. However, further studies and

    developments on Real Time Databases are necessary to

    improve the PDC capacity.

    B. Support for Monitoring Applications

    Facilities for monitoring applications using the PDC

    phasors were developed and implemented. These facilities are

    divided in two modules [14]:

    1) Real Time Module

    This module supports the monitoring of real time data provided by the PDC. The application shows the real-time

    phasors arriving in the PDC.

    2) On-Line Module

    This module allows the monitoring of the phasors kept in

    the PDC database. The main screen allows access to the

    database and graphics plotting. This screen enables the user to

    choose which phasors he wants to observe. One of the phasors

    can be chosen as the system reference. The user can still

    choose which measurements to observe: voltage magnitude,

    voltage angle or frequency. Due to the characteristics of this

    module it was developed in Matlab. This environment

    facilitates the development of graphical applications and the

    mathematical treatment.

    C. SPMS Architecture

    The architecture of the SPMS system is divided in four

    main layers:

    1) Data acquisition: The PMUs are located in strategic

    points to measure voltage and current. The phasors are

    calculated and sent to the PDC.

    2) Data Management: The phasors sent by the PMUs are

    correlated in a uniform data stream.

    3) Data Services: This layer includes the set of services

    required for supplying data for the different applications.

    4) Applications: This is the layer where the monitoring,

    control and protection applications are executed.

    In the Figure 3, the overview of the SPMS architecture is

    presented.

    Fig. 3. SPMS Architecture of the MedFasee Project.

    III. PMU PROTOTYPE PERFORMANCE TESTS

    As shown in Figure 3, the PMUs are located in the first

    layer of the SPMS architecture and they are responsible for

    the phasors determination. The performance of this

    component is crucial for the performance of any SPMS in

    monitoring and control applications. For monitoring

    applications, if the measurements do not represent the real

    power system state an operator, who is using a SPMS tomonitor the power system variation, could make wrong

    decisions. For control applications, especially in emergency

    control, there is not much time to take into account

    measurement errors.

    The main application reported in this paper, presented in

    the next section, concerns power system monitoring. To

    ensure the reliability of the data obtained by the SPMS, it

    was necessary to verify the performance of the PMU

    prototype under normal and abnormal conditions. The goal of

    the tests presented in this section is simply to validate the data

    obtained by the PMUs and not to test the performance of the

    prototype against any commercial PMU currently available.

    The Synchrophasors Standard IEEE 1344-1995 [15] does

    not specify PMU performance tests. The new Synchrophasors

    Standard PC 37.118 [16] defines measurement requirements,

    compliance verification and accuracy, but at the time that the

    tests were performed it was under revision. Discussions

    promoted by PRTT on this issue [8] show that further work

    needs to be done in this area. However for evaluating the

    reliability of data acquired by the prototype PMUs tests based

    on [7] were realized.

  • 8/3/2019 Phasor Mesurement System in Brazil

    4/8

    4

    A. Test Settings

    As remarked in section II, the PMUs prototypes measure

    the instantaneous three-phase distribution voltage. Therefore

    the tests realized in this work emphasized the performance of

    the voltage measurement under nominal and off-nominal

    conditions using the modern test sets. Two main tests were set

    up as follows.

    B. Balanced three phase voltages at nominalfrequency

    This test compares the performance of the PMU under

    balanced three phase voltage conditions in a range from 10%

    to 120% of the nominal voltage rating in steps of 10% at

    nominal frequency. For every voltage step a three second

    window of data was aligned according to the time stamp

    provided by each PMU unit. The aligned phasor magnitudes

    were compared against a reference value measured at every

    voltage step using certificate measuring instruments. The

    following results only measure accuracy with respect to the

    instruments used. In Figure 4 the deviation of the

    measurement phasor magnitude with respect to the reference

    value is shown.

    These results shows that the phasor magnitudes measured

    by the PMU presents a satisfactory performance with errors

    lower than 0.35% with respect to the reference value.

    -0,35%

    -0,30%

    -0,25%

    -0,20%

    -0,15%

    -0,10%

    -0,05%

    0,00%

    0,05%

    0,10%

    0,15%

    1 0% 2 0% 3 0% 4 0% 5 0% 6 0% 7 0% 8 0% 9 0% 1 00 % 1 10 % 1 20 %

    Voltage %

    Error

    Fig. 4. Absolute error in magnitude.

    Figure 5 shows the phase difference between the measured

    data and the reference.

    C. Unbalanced (single phase) voltage at off-

    nominal frequencyThis test is intended to evaluate the performance of the

    PMU under unbalanced and off-nominal frequency operation.

    The unbalanced condition is simulated by applying a single-

    phase voltage (phase A) to the PMU unit. The frequency is

    varied in a range between 55 and 65 Hz. The variation of the

    phasor magnitude with respect to the off-nominal frequency is

    shown in Figure 6.

    From this figure it can be concluded that the phasor

    magnitude measured by PMU is not significantly affected by

    off-nominal frequencies in the range 55 and 65 Hz. The tests

    carried out in this section show that the characteristics of

    PMU prototype ensure the reliability of the results described

    in the next section.

    -0,12

    -0,1

    -0,08

    -0,06

    -0,04

    -0,02

    0

    0,02

    0,04

    0,06

    0,08

    0,1

    1 0% 20 % 3 0% 4 0% 50 % 6 0% 7 0% 80 % 9 0% 1 00 % 11 0% 1 20 %

    Voltage %

    Degrees

    Fig. 5. Phase shift with respect to the reference.

    -0,020%

    -0,015%

    -0,010%

    -0,005%

    0,000%

    0,005%

    0,010%

    0,015%

    0,020%

    0,025%

    55 56 57 58 59 60 61 62 63 64 65

    Frequency

    Error

    Fig. 6. Magnitude error under off-nominal frequency.

    IV. SPMS PROTOTYPE PERFORMANCE

    The development of phasor measurement applications for

    monitoring is part of the MedFasee project. This section

    describes the SPMS prototype performance under normal and

    abnormal operating conditions using the software applications

    developed in the MedFasee project.

    A. Monitoring and Analysis of Frequency

    OscillationsSeveral examples of frequency oscillations monitoring in

    the Southern Brazil 60 Hz power system based on measured

    data from the SPMS prototype were monitored. Two

    weekdays were chosen to be show in the paper.

    In Figure 7, the behavior of voltage frequency measured by

    the PMU in Curitiba at heavy load (between 21h and

    21h30min), is presented. Periods of 30 minutes, on

    Wednesday 30/11/2005, and on Thursday 31/11/2005, were

    analyzed. This graphics shows frequency oscillations with

    large magnitude in periods of heavy load.

  • 8/3/2019 Phasor Mesurement System in Brazil

    5/8

    5

    Fig. 7. Curitiba, Frequency Voltage.

    In Figure 8, the frequency spectrum of the system

    frequency, at the heavy load period, is shown.

    Fig. 8. Curitiba, Frequency Spectrum.

    An oscillation mode near 0.02Hz, corresponding to a

    period of approximately 50 seconds, can be observed. This

    mode appears with evidence in all load periods (heavy,

    medium, low). The use of the phasors obtained from the

    SPMS prototype allows many analyses in real time, including

    the identification of oscillation modes, using system real data,

    without the need of simulations with complex models.

    1) Disturbance Detection Outage of a 765kV

    Transmission Line

    An important disturbance was registered by the SPMS

    prototype in October 04, 2005. At 20h38min, the circuit two

    of a three circuits of the 765 kV transmission line

    Itaipu/Ivaipor (shown in Figure 9) was tripped.

    Fig. 9. Brazil South/Southeast Power System.

    At 20h40min, circuits one and three of the same line were

    tripped. This caused the loss of 13 generators including 8

    Itaipu generators, with a total generation shedding of 6,920

    MW. There was a disconnection between the

    Northern/Southern and Southeastern/Northeastern regions of

    the Brazilian System. The first stage of the SPS (SpecialProtection Scheme) was activated with load shedding of

    approximately 2,842 MW. Figure 10 shows the frequency

    evolution from 20h35min until 21h00min.

    Fig. 10. Voltage frequency at three locations.

    Figure 10 shows that at 20h40min26s the frequency started

    to fall reaching the minimum value of 58.25Hz in Porto

    Alegre, at 20h40min30s. The frequency recovery started at

    20h40min33s and at about 20h43min33s the frequencyreached 59.6 Hz. At approximately 20h56min the frequency

    returned to the nominal value. To show the SPMS prototype

    capability, it is shown, in Figure 11, the moment where circuit

    two (Itaipu/Ivaipor) was tripped and the subsequent attempt

    to reconnect the circuit.

  • 8/3/2019 Phasor Mesurement System in Brazil

    6/8

    6

    Fig. 11. Voltage frequencies zoom.

    At 21h06min, all loads and the Northern/Southern

    Interconnection were restored. At 21h30 min, circuit one

    (Itaipu/Ivaipor) was reconnected. However, at 21h52min,circuit one was tripped again and it was followed by a

    generation tripping of 1,800 MW in Itaipu. In this disturbance

    there was no load shedding and the protection scheme kept all

    circuits of the Itaipu/Ivaipor line open. The frequency

    evolution of this disturbance is shown in Figure 12.

    Fig. 12. Voltage frequency evolution in the second Itaipu disturbance.

    Figure 12 shows that at 21h50min50s the frequency started

    to fall reaching the minimum value of 58.4Hz. After threeminutes the frequency returned to the nominal value.

    2) Disturbance Detection Outage of a 230 kV Substation

    On August 23, 2005, at 14h43min58s, part of an important

    230 kV substation (Cidade Industrial), in Porto Alegre, was

    tripped. This disturbance resulted in a tripping of seven 230

    kV lines, generation shedding of 215 MW and a load

    shedding of 38 MW. The loss of these components caused

    under voltage in the southernmost state area.

    Figure 13 shows the Brazilian System frequency calculated

    from the angular variation registered at the PMU located in

    Florianopolis. At 14h43min50s, an oscillatory process started

    in the frequency leading to an over frequency of 60.178 Hz,

    eight seconds after the disturbance (14h43min58s). The

    frequency returned to the nominal value approximately three

    minutes after the disturbance start, at 14h47min.

    Fig. 13. Voltage frequency evolution at Florianpolis.

    In Figure 14, the angular difference between the voltages

    measured by the PMUs installed in Curitiba and in

    Florianpolis, during the disturbance, is shown. The fast

    oscillations during the disturbance can be observed again. The

    angular difference between the points fell to approximately

    1.8 degrees as a result of the active power flow redistribution

    in the network.

    Fig. 14. Angular difference between Florianpolis and Curitiba.

    The data sent by the PMU located in Porto Alegre, during

    the disturbance, did not arrive at the PDC as a consequence of

    an Internet connection failure between UFSC and PUCRS.

    The failure duration was of approximately 1 minute, although

    the PMU kept registering the data since it was connected to a

    no-break system. In Figure 15 the voltage magnitude

    monitored by the PMU in Porto Alegre is shown. The

  • 8/3/2019 Phasor Mesurement System in Brazil

    7/8

    7

    disturbance caused an over voltage that was only partially

    observed due to the Internet connection failure.

    Fig. 15. Voltage magnitude at Porto Alegre.

    V. FUTURE DEVELOPMENTSThe prototype described in this paper has been working for

    a year monitoring variables of Southern Brazil system during

    normal and abnormal conditions.

    Although the prototype was installed in the distribution

    system, many transmission system phenomenons could be

    observed. However, the connection at the distribution system

    level makes the analysis more complex since transient

    components due to switching in the distribution system add to

    frequency components associated to power oscillations at the

    transmission system level. Therefore, the next phase of the

    project comprises the installation and tests of a SPMS in the

    EHV (Extra High Voltage) Brazilian transmission system.Monitoring applications were giving special attention in

    this paper. However other applications are being developed

    such as model improvement of power system components

    using SPMS, fault location, emergency control and control

    applications aiming the small-disturbance angle stability.

    VI. CONCLUSIONS

    This paper described the performance of a SPMS prototype

    developed by the MedFasee project. The PMUs were installed

    in geographically distant cities of Southern Brazil.

    Performance tests were realized and have shown that the

    PMUs are able to monitor power system disturbances under

    normal and abnormal conditions.

    Performance results of SPMS under Internet have shown

    its capability in providing network connection for SPMS. The

    Internet has proved a good choice for the project but

    reliability can be an issue for industrial applications. The use

    of private networks by the utilities can be a reliable

    alternative.

    Monitoring of normal and abnormal conditions were

    accomplished by the SPMS prototype. The measured data

    allowed the analysis of the low-voltage frequency and

    identification of a natural oscillation mode with a period of

    approximately 50 seconds in the Brazilian Interconnected

    system. The prototype robustness was tested with the capture

    of important power system disturbances. The disturbances

    were registered with high precision and enabled the analysis

    of the disturbance effects at specific points of the low-voltage

    system.

    Finally, the paper results indicate that it is possible to

    obtain important information on power system dynamics usingSPMS connected at low-voltage and Internet. The authors

    believe that the evolution of this technology could make the

    system operating conditions available to the wider public.

    VII. ACKNOWLEDGMENT

    The authors gratefully acknowledge the contributions of

    Professor F. Neves, from CEFET-PR, and Professors F. B.

    Lemos and A. Manzoni, from PUCRS, and their laboratory

    staff for their cooperation to support PMUs installation.

    VIII. REFERENCES

    [1] J Karlsson, D. Hemmingsson, M. and Lindahl, S., "Wide Area SystemMonitoring and Control," IEEE Power and Energy Magazine, Vol. 2,

    pp. 68-76, Sep. 2004.

    [2] R. Klump, R. E. Wilson, and K. E. Martin, Visualizing Real-Time

    Security Threats Using hybrid SCADA/PMU Measurement Displays

    Proceedings of the 38th Hawaii International Conference on System

    Sciences, Hawaii, U.S.A. 2005.

    [3] B. Bharat, G. Rodriguez, Monitoring the Power Grid Transmission

    and Distribution World Magazine, pp. 28-34, Dec. 2004.

    [4] I. C. Decker, et al.: Synchronized Phasor Measurement System:

    Development and Applications,IX Symposium of Specialists in Electric

    Operational and Expansion Planning SEPOPE, Rio de Janeiro, Brazil,

    May, 2004.

    [5] C. Martinez, M. Parashar, J. Dyer, J. Coroas, Phasor Data Requiments;

    Real Time Wide-Area Monitoring, Control and Protection, Consortium

    for Electricity Realiability Technology Solutions (CERTS)., Tech.

    Report., Jan. 2005.[6] M. Donnelly, P. Barber, and J. Dyer, Progress Toward a High-Speed

    Data Network for the Eastern Interconnection The Eastern

    Interconnection Phasor Project. pp. 1-6. EIPP.

    [7] J. Depablos, V. Centeno, A. G. Phadke, M. Ingram, "Comparative

    Testing of Synchronized Phasor Measurements Units," Power

    Engineering Society General Meeting, vol. 1, pp. 948-954, Jun. 2004.

    [8] EIPP [Online]. Available:

    http://phasors.pnl.gov/resources_performance.html

    [9] A. Akke, D. Karlsson, Phasor Measurement Applications in

    Scandinavia in Proc. 2002 Transmission and Distribution Conference

    and Exhibition IEEE Asia Pacific, pp. 480-484.

    [10] K. K. Yi, , J. B. Choo, S. H. Yoon, Development of Wide Area

    Measurement and Dynamic Security Assessment Systems in Koreain

    Proc. 2001 IEEE Power Engineering Society Summer Meeting, pp.

    1495-1499.

    [11] C. W. Liu, Phasor Measurement Applications in Taiwan inProc 2002.

    Transmission and Distribution Conference and Exhibition - IEEE - Asia

    Pacific, pp. 490-493.

    [12] Y. Min, Phasor Measurement Applications in China in Proc. 2002

    Transmission and Distribution Conference and Exhibition - IEEE - Asia

    Pacific, pp. 485-489.

    [13] M. Hojo, et al.: Observation of Frequency Oscillation in Western Japan

    60 Hz Power System Based on Multiple Synchronized Phasor

    Measurements. Power Tech Conference Proceedings. IEEE Bologna,

    Italy. 2003.

    [14] I. C. Decker, et al., Phasor Measurement Development and

    Applications in Brazil, presented in First International Conference in

    Electrical Engineering. Coimbra, Portugal, 2005.

    [15] IEEE Standard for Synchrophasors for Power Systems, IEEE Standard

    1344-1995, 1995.

  • 8/3/2019 Phasor Mesurement System in Brazil

    8/8

    8

    [16] IEEE Standard for Synchrophasors for Power Systems, IEEE Standard

    PC37.118-2005, Jun. 2005. (under revision)

    IX. BIOGRAPHIES

    Ildemar Cassana Decker received his B. Sc. from the Catholic University of

    Pelotas, RS., Brazil. He obtained his M.Sc. (1984) and D.Sc. (1993) degrees in

    Electrical Engineering from Federal University of Santa Catarina and Rio de

    Janeiro, Brazil, respectively. From 1980 to 1985 he worked in Federal

    University of Santa Maria, RS. Since 1985 he has been Associate Professor ofthe Federal University of Santa Catarina, in Department of Electrical

    Engineering. His general research interest is in the area of computer methods

    for power systems analysis and control and high performance scientific

    computing.

    Daniel Dotta received his B. Sc. and M.Sc. degrees in Electrical Engineering

    from the Federal University of Santa Catarina, SC., Brazil. Since 2004 he has

    been developing his Ph.D. in Federal University of Santa Catarina, in

    Department of Electrical Engineering. His general research interest is in the

    area of modeling and object-oriented programming for power systems analysis

    and control and high performance scientific computing.

    Marcelo Neujhar Agostini received his degree in Electrical Engineering

    from Federal University of Santa Maria in 1996. He worked as a research

    engineer at the same institution before starting postgraduate studies. He

    obtained his D.Eng. degree in Electrical Engineering from the Federal

    University of Santa Catarina in 2002. Currently he works at this university as

    a researcher engineer. His general research interest are phasor measurements,

    software engineering applied to Electric Power Systems, Object-Oriented

    Modeling, Electric Power Systems Modeling, Electric Power Systems

    Dynamics and High Performance Scientific Computing.

    Sergio Luiz Zimath received his degree in Automation and Control

    Engineering from Federal University of Santa Catarina in 1997. Since 1995,

    he has been with Reason Technology where he was responsible for the

    development of the Digital Fault Recorder model RPIV, GPS Based time

    references among other products. Since 2005 he is in charge of the Research

    Projects Department, involved in the study of new technologies.

    Aguinaldo Silveira e Silva received his degree in Electrical Engineering from

    Federal University of Parana in 1977, and the M.Sc. and Ph.D degrees in

    Electrical Engineering from Federal University of Santa Catarina, in 1982 and

    UMIST, UK, in 1990, respectively. Since 1980, he has been with Federal

    University of Santa Catarina. His main research interests are in the area of

    power systems dynamics and control applications.