physical properties - american wire groupwire.buyawg.com/asset/powerguard 35kv 100 shielded...
TRANSCRIPT
-
A: Conductor:1/0 AWG Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
748*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.355 0.362 0.366
0.012 0.018 ‐‐ ‐‐ 0.398 ‐‐
0.330 0.345 0.375 1.045 1.088 1.145
‐‐ 0.005 ‐‐ ‐‐ 1.163 ‐‐
0.024 0.030 0.060 1.095 1.148 1.235
0.070 0.080 0.105 ‐‐ 1.323 ‐‐
Insulation Level100%
Conductor Weight99
Met. Shield Weight84
Cable Weight
Electrical Properties
Cable Description: 1/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.189 0.619Rac @ 25°C: 0.189 0.619Rac @ 105°C: 0.248 0.814
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.584 1.915Rac @ 95°C: 0.741 2.431
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.039 0.127µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 68,336 20,829Shunt Capacitive Susceptance: 14.63 48.01
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 291.2 955.3mA/kf mA/km
4.05 13.30Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 53.22 V/mil 2,095.22 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 99.79 3,928.80V/mil V/mmInsulation ‐ Insulation Shield Interface: 36.28 V/mil 1,428.52 V/mm
Insulation Resistance: 8,734.9 2,662.4Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault11,737 9,351 7,715AmpsAmps Amps
3,525 2,966 2,57710 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
1/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.323 in
435.3 132.7ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
Conductor Spacing (S): 1.323 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.249Real
0.052Imag.
Inductice Reactance: 0.051Impedance
0.254 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.816 0.169 0.833
0.168 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.608 0.364 0.709 Ω/kft 1.995 1.195 2.325 Ω/kftZero Seq. Impedance (Earth Only): 0.302 0.750 Ω/kft 0.992 2.462 2.442 Ω/kft
Electrical Properties ContinuedCable Description: 1/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 202
75% Load Factor: 230 AmpsAmps
Conductor Spacing (S): 1.323 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.249Real
0.057Imag.
Inductice Reactance: 0.057Impedance
0.256 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.818 0.188 0.839
0.188 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.603 0.363 0.703 Ω/kft 1.977 1.190 0.839 Ω/kftZero Seq. Impedance (Earth Only): 0.302 0.739 0.798 Ω/kft 0.992 2.423 2.619 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 202
75% Load Factor: 230 AmpsAmps
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.252Real
0.096Imag.
Inductice Reactance: 0.097Impedance0.269 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.826 0.826 0.884
0.317 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.608 0.352 0.663 Ω/kft 1.844 1.153 2.175 Ω/kftZero Seq. Impedance (Earth Only): 0.302 0.660 0.726 Ω/kft 0.992 2.166 2.382 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 223
75% Load Factor: 249 AmpsAmps
Installation PropertiesCable Description: 1/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 845 3.8 1690 7.5Cable Basket Grip: 845 3.8 1690 7.5
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 16 40312xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:2/0 AWG Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
807*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.398 0.406 0.410
0.012 0.018 ‐‐ ‐‐ 0.442 ‐‐
0.330 0.345 0.375 1.090 1.132 1.190
‐‐ 0.005 ‐‐ ‐‐ 1.207 ‐‐
0.024 0.030 0.060 1.140 1.192 1.280
0.070 0.080 0.105 ‐‐ 1.367 ‐‐
Insulation Level100%
Conductor Weight128
Met. Shield Weight88
Cable Weight
Electrical Properties
Cable Description: 2/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.146 0.478Rac @ 25°C: 0.146 0.478Rac @ 105°C: 0.192 0.629
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.563 1.846Rac @ 95°C: 0.714 2.342
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.042 0.136µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 63,872 19,468Shunt Capacitive Susceptance: 15.66 51.37
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 311.5 1,022.0mA/kf mA/km
4.34 14.23Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 53.74 V/mil 2,115.76 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 96.04 3,781.00V/mil V/mmInsulation ‐ Insulation Shield Interface: 37.31 V/mil 1,468.85 V/mm
Insulation Resistance: 8,168.5 2,489.8Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault14,768 11,761 9,699AmpsAmps Amps
3,660 3,079 2,67610 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
2/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.367 in
428.7 130.7ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A2/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 1.367 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.192Real
0.049Imag.
Inductice Reactance: 0.049Impedance
0.198 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.631 0.162 0.651
0.162 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.550 0.049 0.552 Ω/kft 1.804 0.162 1.811 Ω/kftZero Seq. Impedance (Earth Only): 0.246 0.747 0.786 Ω/kft 0.807 2.450 2.580 Ω/kft
Electrical Properties ContinuedCable Description: 2/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 232
75% Load Factor: 265 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 1.367 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.191Real
0.055Imag.
Inductice Reactance: 0.055Impedance
0.199 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.627 0.181 0.653
0.182 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.542 0.350 0.645 Ω/kft 1.780 1.147 0.653 Ω/kftZero Seq. Impedance (Earth Only): 0.246 0.735 0.775 Ω/kft 0.807 2.410 2.542 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 232
75% Load Factor: 265 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.196Real
0.093Imag.
Inductice Reactance: 0.094Impedance0.217 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.643 0.643 0.712
0.308 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.550 0.340 0.609 Ω/kft 1.659 1.115 1.999 Ω/kftZero Seq. Impedance (Earth Only): 0.246 0.657 0.702 Ω/kft 0.807 2.157 2.303 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 256
75% Load Factor: 287 AmpsAmps
Installation PropertiesCable Description: 2/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 1065 4.7 2130 9.5Cable Basket Grip: 1065 4.7 2130 9.5
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 16 41712xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A2/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:3/0 AWG Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
877*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.447 0.456 0.461
0.012 0.018 ‐‐ ‐‐ 0.492 ‐‐
0.330 0.345 0.375 1.140 1.182 1.240
‐‐ 0.005 ‐‐ ‐‐ 1.257 ‐‐
0.024 0.030 0.060 1.190 1.242 1.330
0.070 0.080 0.105 ‐‐ 1.417 ‐‐
Insulation Level100%
Conductor Weight157
Met. Shield Weight90
Cable Weight
Electrical Properties
Cable Description: 3/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.115 0.376Rac @ 25°C: 0.115 0.377Rac @ 105°C: 0.151 0.496
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.540 1.773Rac @ 95°C: 0.685 2.247
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.045 0.146µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 59,501 18,136Shunt Capacitive Susceptance: 16.81 55.14
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 334.4 1,097.1mA/kf mA/km
4.66 15.28Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 54.22 V/mil 2,134.75 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 92.53 3,642.85V/mil V/mmInsulation ‐ Insulation Shield Interface: 38.35 V/mil 1,509.74 V/mm
Insulation Resistance: 7,613.0 2,320.5Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault18,599 14,806 12,205AmpsAmps Amps
3,814 3,208 2,78810 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
3/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.417 in
421.7 128.5ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A3/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 1.417 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.152Real
0.048Imag.
Inductice Reactance: 0.048Impedance
0.159 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.497 0.156 0.521
0.156 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.506 0.336 0.608 Ω/kft 1.661 1.104 1.994 Ω/kftZero Seq. Impedance (Earth Only): 0.205 0.742 0.770 Ω/kft 0.673 2.435 2.526 Ω/kft
Electrical Properties ContinuedCable Description: 3/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 265
75% Load Factor: 303 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 1.417 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.151Real
0.054Imag.
Inductice Reactance: 0.054Impedance
0.160 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.495 0.176 0.525
0.176 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.499 0.334 0.601 Ω/kft 1.638 1.096 0.525 Ω/kftZero Seq. Impedance (Earth Only): 0.205 0.730 0.758 Ω/kft 0.673 2.395 2.488 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 265
75% Load Factor: 304 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.156Real
0.091Imag.
Inductice Reactance: 0.091Impedance0.180 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.511 0.511 0.591
0.300 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.506 0.327 0.568 Ω/kft 1.524 1.074 1.864 Ω/kftZero Seq. Impedance (Earth Only): 0.205 0.655 0.686 Ω/kft 0.673 2.148 2.251 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 292
75% Load Factor: 328 AmpsAmps
Installation PropertiesCable Description: 3/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 1342 6 2685 ####Cable Basket Grip: 1342 6 2685 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 17 43212xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A3/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:4/0 AWG Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
960*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.502 0.512 0.517
0.012 0.018 ‐‐ ‐‐ 0.548 ‐‐
0.330 0.345 0.375 1.195 1.238 1.295
‐‐ 0.005 ‐‐ ‐‐ 1.313 ‐‐
0.024 0.030 0.060 1.245 1.298 1.386
0.070 0.080 0.105 ‐‐ 1.473 ‐‐
Insulation Level100%
Conductor Weight196
Met. Shield Weight95
Cable Weight
Electrical Properties
Cable Description: 4/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.089 0.293Rac @ 25°C: 0.089 0.294Rac @ 105°C: 0.118 0.386
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.516 1.694Rac @ 95°C: 0.656 2.152
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.048 0.157µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 55,304 16,857Shunt Capacitive Susceptance: 18.08 59.32
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 359.8 1,180.4mA/kf mA/km
5.01 16.44Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 54.66 V/mil 2,151.94 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 89.31 3,515.97V/mil V/mmInsulation ‐ Insulation Shield Interface: 39.38 V/mil 1,550.44 V/mm
Insulation Resistance: 7,078.8 2,157.6Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault23,420 18,637 15,358AmpsAmps Amps
3,986 3,353 2,91310 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
4/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.473 in
414.3 126.3ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A4/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 1.473 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.118Real
0.046Imag.
Inductice Reactance: 0.046Impedance
0.127 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.388 0.151 0.416
0.150 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.469 0.046 0.472 Ω/kft 1.540 0.151 1.547 Ω/kftZero Seq. Impedance (Earth Only): 0.172 0.738 0.757 Ω/kft 0.564 2.420 2.484 Ω/kft
Electrical Properties ContinuedCable Description: 4/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 303
75% Load Factor: 349 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 1.473 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.118Real
0.052Imag.
Inductice Reactance: 0.052Impedance
0.129 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.386 0.169 0.422
0.169 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.463 0.319 0.563 Ω/kft 1.520 1.047 0.422 Ω/kftZero Seq. Impedance (Earth Only): 0.172 0.726 0.746 Ω/kft 0.564 2.383 2.448 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 310
75% Load Factor: 349 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.123Real
0.088Imag.
Inductice Reactance: 0.089Impedance0.151 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.402 0.402 0.495
0.291 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.469 0.314 0.533 Ω/kft 1.411 1.031 1.747 Ω/kftZero Seq. Impedance (Earth Only): 0.172 0.652 0.674 Ω/kft 0.564 2.140 2.213 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 333
75% Load Factor: 376 AmpsAmps
Installation PropertiesCable Description: 4/0 AWG FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 1693 7.5 3386 ####Cable Basket Grip: 1693 7.5 3386 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 18 44912xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A4/0‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:250 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
1,039*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.547 0.558 0.564
0.016 0.022 ‐‐ ‐‐ 0.602 ‐‐
0.330 0.345 0.375 1.250 1.292 1.350
‐‐ 0.005 ‐‐ ‐‐ 1.367 ‐‐
0.024 0.030 0.060 1.300 1.352 1.330
0.070 0.080 0.105 ‐‐ 1.527 ‐‐
Insulation Level100%
Conductor Weight238
Met. Shield Weight99
Cable Weight
Electrical Properties
Cable Description: 250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.075 0.247Rac @ 25°C: 0.076 0.248Rac @ 105°C: 0.099 0.326
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.496 1.627Rac @ 95°C: 0.630 2.065
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.051 0.168µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 51,804 15,790Shunt Capacitive Susceptance: 19.30 63.33
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 384.1 1,260.1mA/kf mA/km
5.35 17.55Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 54.99 V/mil 2,165.13 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 86.73 3,414.46V/mil V/mmInsulation ‐ Insulation Shield Interface: 40.26 V/mil 1,585.14 V/mm
Insulation Resistance: 6,633.3 2,021.9Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault27,652 22,000 18,125AmpsAmps Amps
4,152 3,493 3,03510 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.527 in
406.1 123.8ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A250‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 1.527 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.100Real
0.044Imag.
Inductice Reactance: 0.045Impedance
0.109 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.328 0.146 0.359
0.146 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.448 0.308 0.543 Ω/kft 1.469 1.010 1.783 Ω/kftZero Seq. Impedance (Earth Only): 0.154 0.735 0.751 Ω/kft 0.504 2.411 2.463 Ω/kft
Electrical Properties ContinuedCable Description: 250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 333
75% Load Factor: 384 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 1.527 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.100Real
0.051Imag.
Inductice Reactance: 0.051Impedance
0.112 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.327 0.166 0.367
0.167 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.441 0.306 0.537 Ω/kft 1.448 1.003 0.367 Ω/kftZero Seq. Impedance (Earth Only): 0.154 0.722 0.738 Ω/kft 0.504 2.368 2.421 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 333
75% Load Factor: 384 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.105Real
0.086Imag.
Inductice Reactance: 0.087Impedance0.135 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.343 0.343 0.444
0.284 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.448 0.302 0.510 Ω/kft 1.346 0.992 1.672 Ω/kftZero Seq. Impedance (Earth Only): 0.153 0.650 0.668 Ω/kft 0.504 2.133 2.192 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 365
75% Load Factor: 413 AmpsAmps
Installation PropertiesCable Description: 250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 2000 8.9 4000 ####Cable Basket Grip: 2000 8.9 4000 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 18 46512xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A250‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:350 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
1,212*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.648 0.661 0.668
0.016 0.022 ‐‐ ‐‐ 0.705 ‐‐
0.330 0.345 0.375 1.355 1.395 1.455
‐‐ 0.005 ‐‐ ‐‐ 1.470 ‐‐
0.024 0.030 0.060 1.405 1.455 1.545
0.070 0.080 0.105 ‐‐ 1.630 ‐‐
Insulation Level100%
Conductor Weight326
Met. Shield Weight106
Cable Weight
Electrical Properties
Cable Description: 350 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.054 0.177Rac @ 25°C: 0.054 0.178Rac @ 105°C: 0.071 0.233
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.461 1.512Rac @ 95°C: 0.585 1.918
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.057 0.188µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 46,271 14,103Shunt Capacitive Susceptance: 21.61 70.90
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 430.0 1,410.8mA/kf mA/km
5.99 19.65Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 55.53 V/mil 2,186.03 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 82.84 3,261.25V/mil V/mmInsulation ‐ Insulation Shield Interface: 41.76 V/mil 1,644.01 V/mm
Insulation Resistance: 5,927.7 1,086.8Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault38,628 30,721 25,299AmpsAmps Amps
4,468 3,759 3,26610 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
350 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.630 in
394.5 120.2ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A350‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 1.630 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.072Real
0.043Imag.
Inductice Reactance: 0.042Impedance
0.083 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.235 0.140 0.274
0.139 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.412 0.284 0.500 Ω/kft 1.352 0.932 1.642 Ω/kftZero Seq. Impedance (Earth Only): 0.125 0.727 0.737 Ω/kft 0.411 2.384 2.419 Ω/kft
Electrical Properties ContinuedCable Description: 350 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 401
75% Load Factor: 464 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 1.630 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.072Real
0.048Imag.
Inductice Reactance: 0.048Impedance
0.086 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.235 0.156 0.283
0.157 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.407 0.282 0.495 Ω/kft 1.335 0.926 0.283 Ω/kftZero Seq. Impedance (Earth Only): 0.125 0.716 0.727 Ω/kft 0.411 2.350 2.386 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 400
75% Load Factor: 463 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.077Real
0.082Imag.
Inductice Reactance: 0.083Impedance0.112 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.251 0.251 0.368
0.272 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.412 0.281 0.472 Ω/kft 1.243 0.922 1.547 Ω/kftZero Seq. Impedance (Earth Only): 0.125 0.646 0.658 Ω/kft 0.411 2.120 2.160 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 436
75% Load Factor: 469 AmpsAmps
Installation PropertiesCable Description: 350 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 2800 #### 5600 ####Cable Basket Grip: 2800 #### 5600 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 20 49712xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A350‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:500 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
1,544*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.774 0.789 0.797
0.016 0.022 ‐‐ ‐‐ 0.833 ‐‐
0.330 0.345 0.375 1.480 1.523 1.580
‐‐ 0.005 ‐‐ ‐‐ 1.598 ‐‐
0.024 0.030 0.060 1.530 1.583 1.670
0.100 0.110 0.150 ‐‐ 1.818 ‐‐
Insulation Level100%
Conductor Weight467
Met. Shield Weight117
Cable Weight
Electrical Properties
Cable Description: 500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.037 0.122Rac @ 25°C: 0.038 0.124Rac @ 105°C: 0.049 0.162
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.423 1.388Rac @ 95°C: 0.537 1.763
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.065 0.213µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 40,890 12,463Shunt Capacitive Susceptance: 24.46 80.24
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 486.6 1,596.4mA/kf mA/km
6.78 22.23Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 56.01 V/mil 2,204.97 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 79.26 3,120.56V/mil V/mmInsulation ‐ Insulation Shield Interface: 43.30 V/mil 1,704.77 V/mm
Insulation Resistance: 5,241.1 1,597.5Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault55,136 43,833 36,084AmpsAmps Amps
3,608 3,608 3,60810 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 1.818 in
377.8 115.1ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A500‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 1.818 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.050Real
0.040Imag.
Inductice Reactance: 0.041Impedance
0.064 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.164 0.133 0.211
0.134 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.381 0.258 0.460 Ω/kft 1.249 0.847 1.509 Ω/kftZero Seq. Impedance (Earth Only): 0.103 0.719 0.726 Ω/kft 0.339 2.358 2.382 Ω/kft
Electrical Properties ContinuedCable Description: 500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 489
75% Load Factor: 567 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 1.818 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.050Real
0.046Imag.
Inductice Reactance: 0.046Impedance
0.068 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.165 0.152 0.224
0.152 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.376 0.257 0.455 Ω/kft 1.232 0.842 0.224 Ω/kftZero Seq. Impedance (Earth Only): 0.103 0.707 0.715 Ω/kft 0.339 2.320 2.344 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 487
75% Load Factor: 566 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.055Real
0.078Imag.
Inductice Reactance: 0.079Impedance0.095 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.181 0.181 0.313
0.258 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.381 0.258 0.436 Ω/kft 1.154 0.845 1.430 Ω/kftZero Seq. Impedance (Earth Only): 0.103 0.642 0.650 Ω/kft 0.339 2.107 2.134 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 524
75% Load Factor: 599 AmpsAmps
Installation PropertiesCable Description: 500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 4000 #### 8000 ####Cable Basket Grip: 4000 #### 8000 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 22 55412xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A500‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:750 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
1,934*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 0.949 0.968 0.978
0.020 0.026 ‐‐ ‐‐ 1.020 ‐‐
0.330 0.345 0.375 1.670 1.710 1.770
‐‐ 0.005 ‐‐ ‐‐ 1.785 ‐‐
0.024 0.030 0.060 1.720 1.770 1.860
0.100 0.110 0.150 ‐‐ 2.005 ‐‐
Insulation Level100%
Conductor Weight705
Met. Shield Weight128
Cable Weight
Electrical Properties
Cable Description: 750 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.026 0.084Rac @ 25°C: 0.026 0.087Rac @ 105°C: 0.034 0.113
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.379 1.242Rac @ 95°C: 0.480 1.576
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.076 0.249µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 34,994 10,666Shunt Capacitive Susceptance: 28.58 93.75
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 568.6 1,865.4mA/kf mA/km
7.92 25.98Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 56.42 V/mil 2,221.24 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 75.57 2,975.14V/mil V/mmInsulation ‐ Insulation Shield Interface: 45.01 V/mil 1,772.18 V/mm
Insulation Resistance: 4,487.9 1,367.9Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault82,567 65,618 53,998AmpsAmps Amps
5,435 4,573 3,97310 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
750 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 2.005 in
360.4 109.9ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A750‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 2.005 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.035Real
0.038Imag.
Inductice Reactance: 0.038Impedance
0.052 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.115 0.125 0.170
0.126 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.351 0.226 0.418 Ω/kft 1.153 0.741 1.370 Ω/kftZero Seq. Impedance (Earth Only): 0.088 0.709 0.715 Ω/kft 0.290 2.327 2.345 Ω/kft
Electrical Properties ContinuedCable Description: 750 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 598
75% Load Factor: 698 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 2.005 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.036Real
0.044Imag.
Inductice Reactance: 0.044Impedance
0.057 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.116 0.145 0.186
0.145 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.347 0.225 0.413 Ω/kft 1.138 0.738 0.186 Ω/kftZero Seq. Impedance (Earth Only): 0.088 0.697 0.703 Ω/kft 0.290 2.287 2.306 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 595
75% Load Factor: 696 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.040Real
0.073Imag.
Inductice Reactance: 0.074Impedance0.084 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.132 0.132 0.274
0.243 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.351 0.228 0.399 Ω/kft 1.074 0.747 1.309 Ω/kftZero Seq. Impedance (Earth Only): 0.088 0.638 0.644 Ω/kft 0.289 2.092 2.111 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 630
75% Load Factor: 726 AmpsAmps
Installation PropertiesCable Description: 750 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 6000 #### 12000 ####Cable Basket Grip: 6000 #### 12000 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 24 61112xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A750‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:1000 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
2,290*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 1.095 1.117 1.128
0.024 0.030 ‐‐ ‐‐ 1.177 ‐‐
0.330 0.345 0.375 1.815 1.867 1.920
‐‐ 0.005 ‐‐ ‐‐ 1.942 ‐‐
0.024 0.030 0.060 1.865 1.927 2.010
0.100 0.110 0.150 ‐‐ 2.162 ‐‐
Insulation Level100%
Conductor Weight937
Met. Shield Weight141
Cable Weight
Electrical Properties
Cable Description: 1000 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.019 0.061Rac @ 25°C: 0.020 0.065Rac @ 105°C: 0.025 0.083
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.348 1.141Rac @ 95°C: 0.442 1.449
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.085 0.279µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 31,237 9,521Shunt Capacitive Susceptance: 32.01 105.03
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 637.0 2,089.8mA/kf mA/km
8.87 29.10Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 56.66 V/mil 2,230.63 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 73.33 2,886.94V/mil V/mmInsulation ‐ Insulation Shield Interface: 46.16 V/mil 1,817.45 V/mm
Insulation Resistance: 4,007.4 1,221.5Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault110,011 87,410 71,916AmpsAmps Amps
5,918 4,978 4,32510 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
1000 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 2.162 in
347.7 106.0ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1000‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 2.162 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.026Real
0.037Imag.
Inductice Reactance: 0.037Impedance
0.045 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.086 0.120 0.148
0.121 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.330 0.203 0.388 Ω/kft 1.084 0.666 1.272 Ω/kftZero Seq. Impedance (Earth Only): 0.080 0.702 0.707 Ω/kft 0.261 2.304 2.318 Ω/kft
Electrical Properties ContinuedCable Description: 1000 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 705
75% Load Factor: 825 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 2.162 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.027Real
0.042Imag.
Inductice Reactance: 0.042Impedance
0.050 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.088 0.137 0.163
0.138 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.327 0.202 0.384 Ω/kft 1.072 0.664 0.163 Ω/kftZero Seq. Impedance (Earth Only): 0.080 0.692 0.696 Ω/kft 0.261 2.269 2.284 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 698
75% Load Factor: 819 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.031Real
0.070Imag.
Inductice Reactance: 0.071Impedance0.077 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.103 0.103 0.251
0.232 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.330 0.206 0.373 Ω/kft 1.017 0.677 1.222 Ω/kftZero Seq. Impedance (Earth Only): 0.079 0.634 0.639 Ω/kft 0.260 2.081 2.097 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 730
75% Load Factor: 847 AmpsAmps
Installation PropertiesCable Description: 1000 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 8000 #### 16000 ####Cable Basket Grip: 8000 #### 16000 ####
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 26 65912xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1000‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:1250 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
2,799*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 1.225 1.250 1.263
0.024 0.030 ‐‐ ‐‐ 1.310 ‐‐
0.330 0.345 0.375 1.960 2.000 2.065
‐‐ 0.005 ‐‐ ‐‐ 2.075 ‐‐
0.024 0.030 0.060 2.010 2.060 2.155
0.100 0.110 0.150 ‐‐ 2.295 ‐‐
Insulation Level100%
Conductor Weight1,197
Met. Shield Weight148
Cable Weight
Electrical Properties
Cable Description: 1250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.015 0.048Rac @ 25°C: 0.016 0.053Rac @ 105°C: 0.020 0.067
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.329 1.080Rac @ 95°C: 0.417 1.370
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.091 0.299µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 29,094 8,868Shunt Capacitive Susceptance: 34.37 112.77
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 683.9 2,243.6mA/kf mA/km
9.53 31.25Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 56.80 V/mil 2,236.18 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 72.09 2,838.17V/mil V/mmInsulation ‐ Insulation Shield Interface: 46.86 V/mil 1,844.87 V/mm
Insulation Resistance: 3,675.2 1,120.2Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault137,446 109,194 89,825AmpsAmps Amps
6,254 5,261 4,57110 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
1250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 2.295 in
340.1 103.7ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1250‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6/24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 2.295 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.021Real
0.036Imag.
Inductice Reactance: 0.036Impedance
0.042 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.069 0.118 0.137
0.117 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.317 0.189 0.369 Ω/kft 1.040 0.620 1.211 Ω/kftZero Seq. Impedance (Earth Only): 0.074 0.697 0.701 Ω/kft 0.244 2.288 2.301 Ω/kft
Electrical Properties ContinuedCable Description: 1250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 794
75% Load Factor: 933 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 2.295 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.022Real
0.041Imag.
Inductice Reactance: 0.041Impedance
0.046 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.072 0.134 0.152
0.135 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.314 0.189 0.366 Ω/kft 1.029 0.618 0.152 Ω/kftZero Seq. Impedance (Earth Only): 0.074 0.687 0.691 Ω/kft 0.244 2.254 2.268 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 784
75% Load Factor: 923 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.026Real
0.068Imag.
Inductice Reactance: 0.069Impedance0.073 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.086 0.086 0.238
0.225 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.317 0.193 0.356 Ω/kft 0.981 0.634 1.168 Ω/kftZero Seq. Impedance (Earth Only): 0.074 0.632 0.636 Ω/kft 0.242 2.074 2.088 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 811
75% Load Factor: 945 AmpsAmps
Installation PropertiesCable Description: 1250 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 10000 #### 20000 89Cable Basket Grip: 10000 #### 20000 89
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 28 70012xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1250‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6/24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
A: Conductor:1500 kcmil Class B Compressed Stranded Filled AL ConductorB: Conductor Shield:Semiconducting Thermoset PolymerC: Insulation:Tree Retardant Crosslinked Polyethylene
E: Metallic Shield:1 x 1.5" x 0.005" Bare Copper Tape
D: Insulation Shield:Semiconducting Thermoset Polymer
F: Jacket:Overlaying Polyvinyl Chloride with 3 Red Extruded StripesSingle Conductor Finished Cable Nominal Weights: lbs/kft*
3,140*Nominal values are subject to manufacturing tolerances:
Component DescriptionThickness Diameter
Min. Min.Nom. Nom.Max. Max.
Physical Properties
‐‐ ‐‐ ‐‐ 1.343 1.370 1.384
0.024 0.030 ‐‐ ‐‐ 1.430 ‐‐
0.330 0.345 0.375 2.100 2.120 2.205
‐‐ 0.005 ‐‐ ‐‐ 2.195 ‐‐
0.024 0.030 0.060 2.150 2.180 2.295
0.100 0.110 0.150 ‐‐ 2.415 ‐‐
Insulation Level100%
Conductor Weight1,411
Met. Shield Weight157
Cable Weight
Electrical Properties
Cable Description: 1500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Conductor Resistance:Rdc @ 25°C: 0.012 0.040Rac @ 25°C: 0.014 0.046Rac @ 105°C: 0.018 0.057
Ω/kftΩ/kftΩ/kft
Ω/kmΩ/kmΩ/km
Shield Resistance:Rac @ 25°C: 0.308 1.009Rac @ 95°C: 0.391 1.281
Ω/kftΩ/kft
Ω/kmΩ/km
Capacitance: 0.100 0.327µF/kft µF/km
Shunt Capacitive Reactance/Susceptance:
Shunt Capacitive Reactance: 26,647 8,122Shunt Capacitive Susceptance: 37.53 123.12
Ω‐kftµS/kft
Ω‐kmµS/km
Charging Current: 746.7 2,449.7mA/kf mA/km
10.40 34.12Dielectric Losses (Per Phase): W/kft W/km
Electrical Stress:Insulation Average Stress ‐ V/mil: 56.93 V/mil 2,241.34 V/mm
Conductor Shield ‐ Insulation Interface Maximum: 70.71 2,783.73V/mil V/mmInsulation ‐ Insulation Shield Interface: 47.65 V/mil 1,875.85 V/mm
Insulation Resistance: 3,420.0 1,042.4Ω‐kft Ω‐km
Velocity of Propagation:
Conductor Fault164,872 130,969 107,726AmpsAmps Amps
6,695 5,632 4,89310 Cycles 16 Cycles 24 Cycles
AmpsAmps Amps
Current @ 250°C:
Shield FaultCurrent @ 200°C:
1500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Input Parameters:
Electrical Properties Based onNormal Operating Temp: 105
Dielectric Constant: 2.32IR Constant @ 60°F: 20000
Earth Resistivity: 100
°C
Ω‐m
Dissipation Factor: 0.07%Voltage (Line to Ground: 19.94 kVConductor Spacing (S): 2.415 in
330.8 100.8ft/µs m/µs
10 Cycles 16 Cycles 24 Cycles
ABC
DEF
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1500‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com
-
S
TrefoilArrangement
Conductor Spacing (S): 2.415 in
Three‐Phase Trefoil Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.018Real
0.035Imag.
Inductice Reactance: 0.035Impedance
0.039 Ω/kft
Ω/kfReal Imag. Impedance
Ω/kft0.060 0.114 0.129
0.114 Ω/km
Zero Seq. Impedance (Earth Met. Shield) 0.304 0.173 0.349 Ω/kft 0.996 0.567 1.146 Ω/kftZero Seq. Impedance (Earth Only): 0.072 0.692 0.696 Ω/kft 0.235 2.270 2.283 Ω/kft
Electrical Properties ContinuedCable Description: 1500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Trefoil Conductor Ampacity @ 105°C: 100% Load Factor: 866
75% Load Factor: 1020 AmpsAmps
S S
2S
Flat AdjacentArrangement
Conductor Spacing (S): 2.415 in
Three‐Phase Flat Adjacent Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.019Real
0.040Imag.
Inductice Reactance: 0.040Impedance
0.044 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.063 0.130 0.144
0.130 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.301 0.172 0.347 Ω/kft 0.986 0.566 0.144 Ω/kftZero Seq. Impedance (Earth Only): 0.072 0.682 0.686 Ω/kft 0.235 2.238 2.251 Ω/kft
Flat Adjacentl Conductor Ampacity @ 105°C: 100% Load Factor: 851
75% Load Factor: 1006 AmpsAmps
S S
2S
Flat SpacedArrangement
Conductor Spacing (S): 7.5 in
Three‐Phase Flat Spaced Reactance/Impedance:
Pos/Neg Seq. Impedance (Met. Shield): 0.023Real
0.065Imag.
Inductice Reactance: 0.066Impedance0.069 Ω/kft
Ω/kftReal Imag. Impedance
Ω/kft0.076 0.076 0.227
0.217 Ω/km
Zero Seq. Impedance (Earth+Met. Shield): 0.304 0.178 0.338 Ω/kft 0.945 0.583 1.110 Ω/kftZero Seq. Impedance (Earth Only): 0.071 0.630 0.634 Ω/kft 0.233 2.065 2.160 Ω/kft
Flat Spaced Conductor Ampacity @ 105°C: 100% Load Factor: 874
75% Load Factor: 1024 AmpsAmps
Installation PropertiesCable Description: 1500 KCMIL FILLED STRANDED AL ‐ 0.345" TRXLPE ‐ 1/0.005" CU TAPE SHIELD ‐ PVC JACKET POWERGUARD 35KV 100%
Maximum Pulling Tension
Single Conductor
Conductor Pulling Eye/Bolt: 12000 #### 24000 ####Cable Basket Grip: 10000 #### 20000 89
lbslbs
kN lbs kN
3x1/C Parallel
kN lbs kN
Maximum Sidewall Bearing Pressure:
1500 22lb/ft of bend radius kN/m of bend radius
Maximum Bending Radius:
NEC Applications: 29 73612xO.D. inches mm
Specification / Standard:AEIC CS8, ICEA S‐97‐682, ICEA T‐31‐610, MV 105 UL 1072
Item No:A1500‐01MV35GT10501
Prepared By:J. DORFMAN
Date:6 /24/2013
Dimensions and weights not designated minimum or maximum are nominal and subject to manufacturing tolerances.Spec No: 314American Wire Group
Tel: 954‐455‐3050 www.buyawg.com