plc: analog voltage gain setting

12
Analog Signal Processing PLC Analog Cards www.nfiautomation.org

Upload: nfi-industrial-automation-training-academy

Post on 10-Jan-2017

3.555 views

Category:

Technology


1 download

TRANSCRIPT

Page 1: PLC: Analog Voltage Gain Setting

Analog Signal ProcessingPLC Analog Cards

www.nfiautomation.org

Page 2: PLC: Analog Voltage Gain Setting

Basic Analog to Digital CurveDVP 04 AD

Page 3: PLC: Analog Voltage Gain Setting

Basic Analog to Digital Curve

10 VDC

0 VDC

5 VDC

0 4000 8000

1 Volt =800 bitsResolution: 1.25mV

www.nfiautomation.org

Page 4: PLC: Analog Voltage Gain Setting

Basic A/D Curves

0 40008000

2.5 VDC

0 VDC

5 VDC

GAIN:Voltage Input value when digital

Output is K4,000

Should be -3200 ~ +16,000LSB.

Gain2000 (2.5*800)

www.nfiautomation.org

If Input Voltage range is 0 ~ 5 VDC

Page 5: PLC: Analog Voltage Gain Setting

Basic A/D Curves

0 4000 8000

2.5 VDC3.75 VDC

5 VDC

GAIN:Voltage Input value when digital

Output is K4,000 Should be 0LSB ~ +4,000LSB.

OFFSET:Voltage Input value when digital

Output value is K0 should be -4,000LSB ~

+4,000LSB.

OFFSET2000 (2.5*800) Gain

3000 (3.75*800)

www.nfiautomation.org

Page 6: PLC: Analog Voltage Gain Setting

Basic Digital to Analog CurveDVP 04 DA

Page 7: PLC: Analog Voltage Gain Setting

Basic Digital to Analog Curves

10 VDC

0 VDC

5 VDC

0 2000 4000

1 Volt = 400 bitsResolution: 0.0025 V 2.5 mV

0 Hz

25 Hz

50 Hz

www.nfiautomation.org

Page 8: PLC: Analog Voltage Gain Setting

Basic D/A Curves

0 20004000

2.5 VDC

0 VDC

5 VDC 1 Volt = 800 bitsResolution: 0.00125 mV 1.25 mV

Resolution Increases with dec. in range

GAIN:The setting range of voltage

output value when digitalinput value is K2,000

Should be 0LSB ~ +4,000LSB.Gain

1000 (2.5*400)

0 Hz

12.5 Hz

25 Hz

www.nfiautomation.org

Page 9: PLC: Analog Voltage Gain Setting

Basic D/A Curves

0 2000 4000

2.5 VDC3.75 VDC

5 VDC

1 Volt = 800 bitsResolution: 0.00125 mV 1.25 mV

Resolution Increases with dec. in range

GAIN:The setting range of voltage output

value when digitalinput value is K2,000

Should be 0LSB ~ +4,000LSB.

OFFSET:The setting range of voltage output

value when digitalinput value is K0

should be -2,000LSB ~ +2,000LSB.

OFFSET1000 (2.5*400) Gain

1500 (3.75*400)

18.75 Hz12.5

Hz

25 Hz

www.nfiautomation.org

Page 10: PLC: Analog Voltage Gain Setting

Learn 4 PLC’s in a Day100+ Video Tutorials

Life time Access

nfipresents

Lear

n to

Cod

e | C

ode

to L

earn

Coupon Code https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare

in $99 $49

For more courses visit www.nfiautomation.org

Course Outline

• 100+ PLC Video Tutorials• Doubt Clearing Complementary LIVE Sessions on Team Viewer• Ladder Logic Programming• PLC Presentations, PLC Circuits, PLC Codes• FREE PLC Simulation Software for Practice

PLC – Programmable Logic Controller

Delta DVP 14 SS + 16 SPAllen Bradley M1000

Siemens S7 200Schneider

Analog Cards Programming04 AD – Analog to Digital

04DA- Digital to Analog

Page 11: PLC: Analog Voltage Gain Setting

PLC & VFD Advanced Course 4 PLC’s Training

Platforms

For more courses visit www.nfiautomation.org

Course Highlights:

• 30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD• 100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator• FREE Circuits Diagram

$149Course Link:http://www.wiziq.com/course/28882-plc-and-ac-drives-online-certificate-trainaing-course

Page 12: PLC: Analog Voltage Gain Setting

Thankswww.nfiautomation.org

nfi