ABB Power Quality Solutions PCS100 STATCOM, 100 kVAr to 10 MVAr Dynamic reactive power compensation Product Brochure

Upload: panapakorn-shinawatra

Post on 28-Mar-2016

265 views

Category:

Documents


0 download

DESCRIPTION

Catalog for PLC Statcom

TRANSCRIPT

Page 1: PLC Statcom

ABB Power Quality Solutions PCS100 STATCOM, 100 kVAr to 10 MVArDynamic reactive power compensation

Product Brochure

Page 2: PLC Statcom

2 Product Brochure | PCS100 STATCOM

Suited to traditional applications correcting power factor harmonics and other disturbances

Page 3: PLC Statcom

PCS100 STATCOM | Product Brochure 3

PCS100 STATCOM, 100 kVAr to 10 MVAr

Product overviewThe PCS100 STATCOM range is part of a family of STATCOM products available from ABB. Based around a low voltage converter platform, the PCS100 provides wide bandwidth performance with a flexible and highly reliable modular redundant power electronic configuration.

New renewable generation such as wind and solar are becoming an increasingly important part of our electricity grid, but to meet grid connection requirements STATCOM products must often be fitted. By injecting reactive current during a fault condition the STATCOM will help the system ride through fault events. During normal generation it can correct for voltage flicker and power factor. The PCS100 STATCOM utilises advanced control allowing it to damp voltage disturbances in the electricity network. This is very important when recovering from a fault, event or in maintaining power system stability.

The PCS100 STATCOM is also suited to the traditional industrial applications, correcting flicker and other disturbances created by industrial loads.

In certain applications stored real power is required to support the electricity network. The STATCOM is designed to be “MW Ready” allowing energy storage devices such as flywheels, super capacitors and batteries to be interfaced to the electricity network either at the initial install time or some time later.

Industrial loads such as arc furnaces and mesh grid welders can produce electrical supply disturbances such as flicker and current distortion. A PCS100 STATCOM provides the ideal solution.

User benefits- Improves power quality and plant reliability- Increases network stability and transmission capacity- Delivers grid compliance when necessary for renewable energy

Features- Power factor control- Voltage regulation- Negative sequence/unbalance compensation of current or voltage- Flicker compensation- Active resonance damping- Multiple system parallel control- High and low voltage ride through- Modular inverter blocks for simple long term maintenance

Options- Compact, self contained systems – small footprint indoor or outdoor enclosure options- MW Ready option for future energy storage integration

( For higher power levels, the medium voltage PCS 6000 system is recommended )

STATCOM unit

Master

CIOB(opt)

Local panel

Slavecontrol

Slavecontrol

Slavecontrol

Inverter cell Inverter cell Inverter cell

480 V / 690 V

Voltage & current measurement

Communication to overriding control

Page 4: PLC Statcom

2UC

D30

1103

-P_b

Technical specifications

Connection

Connection voltage - 480 / 690 VAC nominal (any LV

or MV with standard transformer)

Connection frequency - 50 or 60 Hz

Voltage variation - ±10% (other by request)

AC current distortion - < 3% at rated power

Performance

Efficiency - >97% at rated power

Overload capability - 30 seconds 150%, 3 seconds 75%

- 3 seconds 200% (75% preload)

Standards

Safety, EMC - Designed - CE mark requirements

Quality ISO9000

Environmental

Rack / enclosure rating - IP20 or IP23

Container rating - to IP54 (containerised option)

Ambient temperature - 0-+50oC, derating for temps > 40OC

Environmental cont /...

Pollution degree rating - 2

Cooling - Forced air ventilation

Altitude above sea level - < 1000m without derating

EMC emissions - CISPR 11 level A

Humidity - < 95% non-condensing

Standard colour - RAL7035 (IP20)

Interface

User interface - touch colour graphic display (GDM)

SCADA interface - Ethernet, Modbus-TCP,

- dry contacts

- Expanded interface option avail

MTTR - < 30 minute

by module exchange

Norms / standard - IEEE 1031-2000

- IEC62103, IEEE 519

EN 50178,CE

Contact usABB Limited LV Power converter products Discrete Automation and Motionwww.abb.com/powerquality (VAr compensation)