plumbing & firefighting enq. for rapid metro at gurgaon
TRANSCRIPT
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
1/94
Summary R
Schedu
Sub Head Description Unit DLF Phase III Belvedere Gateway Tower DLF Phase II Mall of Ind
PART-3 PLUMBING & FIRE FIGHTING
A PLUMBING WORKSP.01 SANITARY FIXTURES Rs.
P.02 SOIL WASTE, VENT & FITTINGS Rs.
P.03 RAIN WATER SUPPLY Rs.
P.04 INTERNAL WATER SUPPLY SYSTEM Rs.
P.05 EXTERNAL WATER SUPPLY SYSTEM Rs.
P.06 EXTERNAL SEWERAGE SYSTEM Rs.P.07 EXTERNAL DRAINAGE SYSTEM Rs.
P.08 WATER SUPLLY PUMPS AND TREATMENT Rs.
P.09 PANEL Rs.
B FIRE SUPPRESSION WORKSF.01 FIRE HYDRANT SYSTEM (Wet-Riser) Rs.
F.02 AUTOMATIC SPRINLER SYSTEM Rs.
F.03 FIRE PUMPS & ACCESSORIES Rs.
F.04 HAND APPLIANCES Rs.
F.05 GAS SUPPRESSION SYSTEM Rs.
TOTAL FOR PART-3
Grand Total - 6 Stations Rs.
TENDER FOR E & M WORKS
RAPID METRO RAIL GURGAON LIMITED
6 ELEVATED METRO STATION
SCHEDULE OF QUANTITY
Confidential Page 1 of 91
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
2/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
PART-3 PLUMBING & FIRE FIGHTING
A PLUMBING SYSTEM
P.01 SANITARY FIXTURES
1 Providing and Fixing white/coloured vitreous china European type water closet with
concealed 'P' or 'S' trap ,C.P.Bolts, nuts, C.I. Chair or other hanging/fixing arrangement
with mult i f lexi connector to mains, solid plastic seat with lid, C.P. brass hinges and
rubber buffers with wall mounted dual low volume flushing cistern , C.P. brass screws
and washers complete, including cutting holes in walls,floors and making good the
same complete in all respects. (Hindware or eq.)
a) Supply Each 2
b) Installation Each 2
2 Providing and Fixing vitreous china wash basin Under Water Counter round/oval
with waste coupling fitting,32mm CP cast brass bottle trap and pipe to wall with CP wall
flange and rubber adopter for waste connection, CP deck mounted mixer with battery
operated and built in sensor for auto cut in/cut off operation complete including cutting
and making good the walls where required complete in all respects.(Hindware or eq.)
a) Supply Each 2
b) Installation Each 2
3 Providing and Fixing 15 mm C.P. brass long body bib cock with C.P.brass flange
complete including cutting and making good the walls where required.
a) Supply (Jaguar continental or eq.) Each RO
b) Installation Each RO
4 Providing and Fixing C.P brass ablution health faucet assembly with 1.2 m long
braided PVC hose with mounting bracket fixed on wall complete.a) Supply (Jaguar continental or eq.) Each 2
b) Installation Each 2
5 Providing and fixing Stainless Steel finish toilet paper holder with stainless steel roller
complete, including cutting and making good the walls where required.
a) Supply (utec or eq.) Each 2
b) Installation Each 2
6 Providing &fixing 15 mm dia angle valve with flanges including 450 mm long copper
connecting pipe with nuts complete.a) Supply (Jaguar continental or eq.) Each 6
b) Installation Each 6
7 Providing and Fixing Stainless steel twin coat hooks fixed on toilet door with C.P.
brass screws.
a) Supply (Utec or eq.) Each 2
b) Installation Each 2
8 Providing and fixing wall mounted auto aerosol dispenser with digital display fixed
with brackets and rowl plug complete in all respects.
a) Supply (Utec UT 650 or eq.) Each 2
b) Installation Each 2
9 Providing &Fixing 15 mm C.P. brass wall mounting single lever mixing fitting for
kitchen sink with swinging and Swivel spout complete including cutting and making
ood the walls wherever re uired.a) Supply (Jaguar Savoy 11163 ) Each RO
b) Installation Each RO
TOTAL FOR P.01
Quantity
RAPID METRO RAIL GURGAON LIMITED
TENDER FOR E & M WORKS
SCHEDULE OF QUANTITY
Rate
(Rs.)
Amount
(Rs.)
ELEVATED METRO STATION - DLF PHASE III
Sl No. Description Unit
Confidential Page 2 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
3/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
P.02 SOIL, WASTE,VENT & FITTINGS
1 Providing, fixing & testing uPVC pipes confirming to IS 13592 (Type B) alongwitF all
required fittings like tees, bends, crosses witF or witFout access doors jointed witF
approved solvent cement as per manufacturer's recommendations, fixed to walls andceilings witF clamps complete including cutting and making good tFe floors and walls
wFere required complete of outer diameter. ( price to be inclusive of fire rated UPVC
wFerever crossing from one floor to anotFer floor occurs.)
I Vertical Pipe
a) 75 mm OD m RO
b) 110 mm OD m 40
II Pipe at Ceiling
a) 110mm OD m RO
b) 160mm OD m RO
III Pipe at Floor
a) 110mm OD m 12
2 Providing, fixing & testing uPVC pipes, conforming to IS 4985 class 3 (6 kg/cm2)
including injection moulded fittings, jointing with solvent cement, cutting and making
good the floors and walls and jointing to trap/waste pipe, complete of outer dia.
a) 40 mm OD m 3
b) 50 mm OD m RO
c) 63 mm OD m RO
3 Providing and laying cement concrete 1:2:4 mix (1 cement:2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) 75 mm in bed and alround uPVC soil & waste
pipes including excavation, refil ling where required complete in all respect as per
standard desi n.
a) Pipe 90 to 110 mm OD m 12
b) Pipe 40 to 63 mm OD m 3
4 Providing, fixing and testing of uPVC P or S trap including jointing with solvent cement
and making good the walls, floors etc., complete of nominal size.a) 110x 110mm Each 2
5 Providing, fixing and testing of uPVC SWR inlet fittings with two or three saddle inlets
of 40, 50 or 63 mm size, fabr icated from 110 mm outer dia uPVC pipes and fixed to
uPVC traps with solvent cement joint complete. Each
2
6 Providing and fixing uPVC reducing elbow as floor drain in cement concrete 1:2:4
float with floor com lete in all res ects.a) 110 x63 mm outlet Each RO
7 Providing and fixing 125 mm dia, 1 mm thick Stainless steel grating with frame for
floor traps or drains of required pattern including cutting and making good the floors
com lete.
a) 125mm dia over Floor Trap Each 2
TOTAL FOR P.02
Confidential Page 3 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
4/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
P.03 RAIN WATER PIPES & FITTINGS
1 Providing, fixing testing uPVC pipes, conforming to IS 4985 class III (6 kg per sqcm)
including injection moulded fittingswitF bosses like bents tee's adopters etc. suitable for
rubber ring jointing witF solvent cement including cutting, fixing to walls /ceiling witFsupporting clamps etc. all complete in all respects.
a) 110 mm OD m RO
b) 160 mm OD m 210
c) 210 mm OD m RO
d) 260 mm OD m RO
2 Providing & fixing dura coating cast iron hopper with cast aluminium ring and dome
grating with S.S screw for rain water outlet including making joint to uPVC rain water
pipe as per manufacturer's recommendations, complete making good the walls and
floors wherever re uiered.
a) Flat type with 110 mm dia outlet Nos. RO
b) Flat type with 160 mm dia outlet Nos. 14
c) Flat type with 210 mm dia outlet Nos. RO
d) Flat type with 260 mm dia outlet Nos. RO
3 Providing and fixing floor drain with supporting clamp ceiling or in sunken portion
including cutting and making good the walls and floors wherever required complete in
all respects.(Basement Drainage)
a) 150 x150 mm Greating Each RO
4 Providing and fixing cast iron grating in lengths of 0.6 to 1 metre with angle iron
frame with hold fasts (25 mm wide 3 mm thick M.S. f lat) welded to frame, setting with
cement mortar 1:3 (1 cement : 3 coarse sand) true to level as required by the
En ineer-in-Char ea) 300 mm wide 40 mm thick including 50x50x5 mm angle iron frame for basement car
parking areas. m RO
5 300 mm wide 25 mm thick including 30x30x50 mm angle iron frame and M.S. hold
fasts as required for plant rooms. m 10
TOTAL FOR P.03
Confidential Page 4 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
5/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
P.04 INTERNAL WATER SUPPLY SYSTEM
1 Providing and fixing CPVC (Chlorinated Poly Vinyl Chloride) water supply pipes with
pipe as per CTS SDR-13.5 at a working pressure of 22.5 kg/sqcm PSI at 23 deg C &
80 PSI at 82 deg. C, using solvent welded CPVC fittings ie. Tees, Elbows, Couplers,Unions, Reducers, brushings etc. including transition fittings connection between CPVC
& metal pipe /GI) ie. Brass Adaptors (both Male & Female threaded) conforming to
ASTM D-2846 with only CPVC solvent cement conforming to ASTM F-493 with
fabricated & subssequently epoxy painted clamps/ structural steel supports as required
for directed at site including cutting chases and fitting the same with cement concrete
/cement mortar as required or exposed in shaft/ ceiling as required with all supports
clamps etc. complete. All termination points for installation of faucets shall have brass
termination fittings.
a) 15 mm nominal bore m 15
b) 20 mm nominal m 5
c) 25 mm nominal m RO
d) 32 mm nominal m RO
2 Providing, laying, jointing and testing, GI medium class pipes conforming to IS:1239,
including all fittings couplings, adapters & two or more coats of synthetic
enamel paint over a coat of primer of approved quality and shade (shade as per pipe
colour code)complete in all respect as directed by the Engineer-in-Charge.
i) For Toilet
a) 15 mm nominal boe m 12
b) 20 mm nominal bore m 30
c) 25 mm nominal bore m RO
ii) In Pum rooma) 32 mm nominal bore m 10
b) 40 mm nominal bore m 5
c) 50 mm nominal bore m 10
d) 65 mm nominal bore m 10
e) 80 mm nominal bore m 15
f) 100 mm nominal bore m 5
3 Providing & fixing stainless steel ball valve with wheel & female screwed ends of
approved quality to I complete in all respects.
a) 15 mm nominal bore Nos. 2
b) 20 mm nominal bore Nos. 2
c) 25 mm nominal bore Nos. 2
d) 32 mm nominal bore Nos. 1
e) 40 mm nominal bore Nos. RO
4 Providing and fixing C.I. double flanged butterfly valves complete with bolts, nuts,
washers 3 mm thick insertion neo rene asket.
a) 50 mm nominal bore Nos. 3
b) 65 mm nominal bore Nos. 1
c) 80 mm dia Nos. 6
d) 100 mm dia Nos. 2
5 Providing and fixing float valve (brass) with copper float of approved quality suitable
for high or low pressure complete in all respects.
a) 32mm dia Nos. 1
b) 40 mm dia Nos. RO
c) 50 mm dia Nos. RO
TOTAL FOR P.04
Confidential Page 5 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
6/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
P.05 EXT. WATER SUPPLY
1 Excavating trencFes of required width for pipes, cables etc. including road cutting
,excavation for sockets and dressing of sides, ramming of bottom deptF upto 1.5 M
including getting out tFe excavated soil and tFen returning tFe soil as requiredin layers not exceeding 20 cms in deptF including filling jamuna sand alround,
consolidating eacF deposited layer by ramming, watering etc. and road reparing ,
disposing of surplus excavated soil outside tFe site.
a) Pipes, cables etc.not exceeding 80 dia. m 15
b) Pipes, cables etc.exceeding 80 dia but not exceeding 150 mm dia. m RO
2 Providing, laying, jointing and testing, GI Medium class pipes conforming to IS:1239,
including all fittings with expansion loop at intervals with flanged joints including all
couplings, adapters etc., complete, including excavation, trenching and back filling
complete in all respect.
a) 32 mm dia m 15
b) 40 mm dia m RO
c) 50 mm dia m RO
d) 80 mm dia m RO
3 Painting G.I. pipes with two coats of bitumastic paint, wrapping with one layer of
polythene tape 400 micron thickness and applying a final coat of bitumastic paint.
a) 32 mm dia m 15
b) 40 mm dia m RO
c) 50 mm dia m RO
d) 80 mm dia m RO
4 Providing and fixing water meter with direct reading dial in KL with all internal
parts in gunmetal or brass, strainer, flanged distance piece for easy removal in
future, 100 mm dia. Bourden type Municipal pressure guage and isolation cock
including necessary isolation cock including necessary test certificate for the meter
from Local Authorities (For Municipal Connection & tubewell outlets).
50 mm nominal bore Each 1
5 Constructing brick valve chamber 600x450x750mm, inside with 75 class designation
brick work in cement mortar 1 : 5 (1 cement : 5 coarse sand) for sluice/butterfly
valve,with C.I. surface box 100mm. top diameter,160mm bottom diameter and 180mm
deep (inside) with chained lid and RCC top slab1:2:4 mix (1 cement : 2 coarse sand : 4
graded stone aggregate 20mm nominal depth, refilling and disposal of surplus earthas
directed, foundation concrete 1 : 5 : 10 (1cement : 5 coarse sand : 10 graded stone
aggregate 40 mm nominal size) and inside plastering with cement mortar 1 : 3 (1
cement : 3 coarse sand) 12 mm thickfinished with a floating coat of neat cement
outside plastering with 1 : 3 cement mortar (1 cement : 3 coarse sand) 12 mm thick
complete as per standard design.Each 1
6 Making connection from municipal /borewell exising line to water meter including
required pipe length up to water meter including pipe corrosion treatment,trench,road
cuttingand complete with all respect Each 1
TOTAL FOR P.05
Confidential Page 6 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
7/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
P.06 EXTERNAL SEWERAGE SYSTEM
Note -quantity measured up to first manhole . Piping from first manhole as per
site not included .
1 Exacavation trencFes of required width for pipes, cables etc. including excavation for
sockets and dressing of sides, ramming of bottom deptF of 1.5 m including getting outof tFe excavated soil and tFen returning tFe soil as required in layers by ramming,
watering,road cutting and repairing etc. and disposing of surplus excavated soil as
directed witFin a lead of 200 m in Dense soil .
a) Pipes, cables etc.exceeding 80 dia but not exceeding 300 mm dia. m 20
b) Pipes cables etc. exceeding 300 mm m RO
2 Extra for excavating trenches pipes, cables etc. for depth exceeding1.5 m. but not
exceedin 3m.
a) Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. Dia m RO
b) Pipes cables etc. exceeding 300 mm dia. m RO
3 Providing and laying PVC socketed Pipes to IS 15328 class-SN-4 KN/sqm with
solvent cement joints laid on 150 mm thick concrete base over 300 mm thick stone dry
soling 150 mm concrete all around of 1:3:6 mix ( 1 cement:3 coarse sand:6 aggreagte
20 mm nominal size ) including testing of joints etc. complete:
a) 160 mm OD pipe m 10
b) 210 mm OD pipe m 10
4 Constructing brick masonry Rectunglar manhole with Ist class bricks in cement
mortar 1:5 (1 cement : 5 fine sand) RCC top slab with 1:2:4 mix (1 cement: 2 coarse
sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1
cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside and
outside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand)
finished with a floating coat of neat cement inside and rough plaster on outside and
making channels in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) neatly finished including PVC foot rests @ 300
mm spacing complete as per standard design including excavation, refil ling, and
disposal of surplus earth and PVC coated M.S. foot rest at 300 mm spacing.
a) Inside size 90 x 80x 60 cms deep including heavy duty SFRC manhole cover and
frame complete in all respects. Each 1
5 Extra for additional depth of manholes
a) Size 90x80 cms beyond 60 cms depth m RO
6 Constructing brick masonry circular type manhole with 75 class designation bricks in
cement mortar 1:4 mix (1cement: 4 coarse sand) inside and outside cement
plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) inside with
a floating coat of neat cement, and outside with water proofing compound,225 - 300
mm thick P.C.C.base concrete 1:3:6 mix (1 cement:3 coarse sand: 6 graded stone
aggregate 20 mm nominal size) including excavation, back fil ling and disposal of
surplus earth, providing and embedding 12mm dia M.S polypropylene coated manhole
steps embedded in cement concrete block 1:2:4 at 300 mm apart neatly finished
complete as per CPWD specification/design.
a) 0.91m. internal bottom dia * 1.67 m deep with steel fibre reinforced concrete (SFRC)
manhole cover with frame (heavy duty) 560mm internal dimeter, total weight of
cover and frame to be not less than 182 kg. (weight of cover 80 kg and weight of
frame 102 kg) fixed in Cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone
aggregate 20 mm nominal size) including centring & shuttering
Each RO
7 Providing and fixing square mouth SW gully trap grade 'A' complete with C.I. grating
brick masonry chamber and water tight C.I. cover with frame of 300x300 mm size
(inside) the weight of cover to be not less than 4.53 kg and frame to be not less than
2.72 k as er standard desi n.
150x100 mm size P type F.P.S. bricks of class designation 75. Each 2
8 Making connection of sewer line with existing manhole including breaking into and
making good the walls,floors with cement concrete branch sewer line to main sewer
sewer manhole including cement concrete 1:2:4(1 cement :2 fine sand :4 graded
stone aggrigate 20 mm nominal size ) cement plastered on both sides with1:3 (1
cement : 3 coarse sand) inside with a floating coat of neat cement, and outside
required channels complete as per standred design and specifications.Each 1
TOTAL FOR P.06
Confidential Page 7 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
8/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
P.07 EXTERNAL DRAINAGE SYSTEM
Note -Extenal Drainage pipe up to propoded recharge pit
1 Exacavation trenches of required width for pipes, cables etc. including excavation for
sockets and dressing of sides, ramming of bottom depth of 1.5 m including getting out
of the excavated soil and then returning the soil as required in layers by ramming,watering,road cutting and repairing etc. and disposing of surplus excavated soil as
directed within a lead of 200 m in Dense soil .
a) Pipes, cables etc.exceeding 80 dia but not exceeding 300 mm dia. m 155
b) Pipes, cables etc. exceeding 300mm m RO
2 Extra for excavating trenches pipes, cables etc. for depth exceeding1.5 m. but not
exceedin 3.5m.a) Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. Dia m RO
b) Pipes, cables etc. exceeding 300mm m RO
3 Providing and laying non-pressure NP2 class S/S RCC pipes with collars joined with
stiff mixture of cement mortar in the proportion of 1:2(1 cement :2 fine sand) including
testing of joints etc. completea) 150 mm dia R.C.C. pipe m RO
b) 250 mm dia R.C.C. pipe m 10
c) 300 mm dia R.C.C. pipe m 145
d) 400 mm dia R.C.C. pipe m RO
4 Providing and laying cement concrete 1:4:8 (1 cement : 4 coarse sand: 8
aggregate 40 mm nominal size) alround R.C.C pipes including in bed concrete 150
mm thick ,alround or haunching etc. as per standard design.a) 150 mm dia m RO
b) 250 mm dia m 10
c) 300 mm dia m 145
5 Constructing brick masonry road gully chamber 50x45x60 cm wtth bricks of class
designation 75 in cement mortar 1:5 (1cement : 5 fine sand) including 500x450 mm
precast RCC horizontal grating wilh frame complete as per standard design. With
F.P.S. bricks Each 16
6 Constructing brick masonry Rectunglar manhole with Ist class bricks in cement
mortar 1:5 (1 cement : 5 fine sand) RCC top slab with 1:2:4 mix (1 cement: 2 coarse
sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1
cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside and
outside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand)
finished with a floating coat of neat cement inside and rough plaster on outside and
making channels in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) neatly finished including PVC foot rests @ 300
mm spacing complete as per standard design including excavation, refil ling, and
disposal of surplus earth and PVC coated M.S. foot rest at 300 mm spacing.
a) Inside size 90 x 80x 60 cms deep including heavy duty SFRC manhole cover and
frame com lete in all res ects. Each 3
7 Extra for additional depth of manholes
a) Size 90x80 cms beyond 60 cms depth m RO
8 Constructing brick masonry circular type manhole with 75 class designation bricks in
cement mortar 1:4 mix (1cement: 4 coarse sand) inside and outside cement
plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) inside with
a floating coat of neat cement, and outside with water proofing compound,225 - 300
mm thick P.C.C.base concrete 1:3:6 mix (1 cement:3 coarse sand: 6 graded stone
aggregate 20 mm nominal size) including excavation, back fil ling and disposal of
surplus earth, providing and embedding 12mm dia M.S polypropylene coated manhole
steps embedded in cement concrete block 1:2:4 at 300 mm apart neatly finished
complete as per CPWD specification/design.
a) 0.91m. internal bottom dia * 1.67 m deep with steel fibre reinforced concrete
(SFRC) manhole cover with frame (heavy duty) 560mm internal dimeter, total weight
of cover and frame to be not less than 182 kg. (weight of cover 80 kg and weight of
frame 102 kg) fixed in Cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone
aggregate 20 mm nominal size) including centring & shutteringEach RO
9 Making connection of drainage line with existing drain / manhole including breaking
into and making good the walls,floors with cement concrete branch sewer line to main
sewer sewer manhole including cement concrete 1:2:4(1 cement :2 fine sand :4
graded stone aggrigate 20 mm nominal size ) cement plastered on both sides with1:3
(1 cement : 3 coarse sand) inside with a floating coat of neat cement, and
outside required channels complete as per standred design and specifications.Each RO
10 Construction of ground water re-charge pit 5m X 1M wide and 4m effict ive depth
s ecifications and com lete as er drawin .a) Peripherial brick masonry in cement mortar 1:4 (1 cement: 4 coarse sand)
b) Foundation concrete 1:5:10c) 300mm thick dry stone aggregate bed (40 to 65mm
nominal grade)
d) 200mm depth thick R.C.C. (1:3:4) slab to cover the well
at top including necessary reinforcement.
Confidential Page 8 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
9/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
e) 2*160 mm dia PVC perforated pipe upto 5 mtr above water. depth Rate to include
excavation, back filling and all other operations necessary for complete the job
including obtaining approval from local and other Govt. bodies Each 2
f) 1*160 mm dia PVC perforated pipe upto 5 mtr above water. depth Rate to include
excavation, back filling and all other operations necessary for complete the job
including obtaining approval from local and other Govt. bodies Each 1
TOTAL FOR P.07
P.08 WATER SUPPLY PUMPS & WTP EQUIPMENTS
A Water Supply & Drainage Pumps
Supply,Installation, testing and commissioning of Vertical monoblock centrifugal
transfer pumping set with SS body and S.S impeller, S.S shaft mechanical seal,
connected to a TEFC induction motor suitable for 415 volts % 3 phase 50 cycles A.C
supply with a common suction header of 100 mm dia with valves on main connecting &
pumps inlet and a common delivery header with valves, includingt water shock
absorber, non return valves with M.S. galvanized supports and painting with one coat
of pr imer and two coats of synthetic enamel paint including a 80mm dia pressure
gauge , Vibration eliminating pads under foundation, all mounted on a common base
plate of MS 80x40mm I section bolted to RCC foundation complete complete in all
respects. (For detail refer tender drawing ).
1 Raw Water filter PumpOne Set
(1 working + 1 stand by)
Capacity : 100 lpm
Head :35 m
Each 1
2 Submersible pumps for drainage /Sewage
Supply Installation,testing & commissioning of Submersible single stage single entry
pumps with C.I.body and C.I. two vane enclosed type impeller connected to TEFC
submersible motor for 415 volts, 3 phase, 50 cycles A.C. power supply with
mechanical seal, pump connector unit with rubber diaphram and bend, vt.
discharge pipe, in built level controller with operational moded as one pump working
at low level, both pumps at high level with a hooter alarm and cut off at dry level as
determined with in built MCC panel with auto cut in/off with sequential change over
facility incuding all connecting cables,controllers etc all complete as required.The
pump shall also be provided with a lifting devise of pull chain/guide rail as per
requirement complete in all respects.
a) For Drainage
(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 12mm)
Capacity- 225 lpm (Each)
Head - 15 m Set 1
b) For Drainage(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 12mm)
Capacity- 570 lpm (Each)
Head - 18 m Set 1
c) For sewage(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 40 mm)
Capacity- 180 lpm (Each)
Head - 15 m Set RO
3 Domestic Dual Media FilterSupply,Installation, testing and commissioning of multi media with activated carbon
layer vertical water pressure filter fabricated from M.S plate with 8 mm shell and 10
mm thick dished ends complete with initial charge of filter media with Butterfly valve,
uPVC face piping, accessories as specified in the specifications,sand blasted inside
and outside, finished with primer and epoxy paint coating inside and one coat of primer
and two coats of high gloss enamel paintof approved shade outside, testing and
commisioning complete. (Thinner plates for shell and dished ends not
acce table)a) Workin ressure : 2-2.5 k /cm
2.
Test pressure : 4.5 kg/cm
2
.Flow rate per filter : 6000 lph
Filtration rate : 14500 lph/m2
Filter dia :800mm Each 1
4 Chlorination Pum
Supply and installation,testing and commissioning of chemical dosing pump capacity 0
10 lph mounted on a 100 lit capacity uPVC container with lid, injection fitting
assembly,suction and delivery hose upto the point of injectionincluding supports
complete in all respects.
a) For chlorination of raw water Each 1
5 Hydroneunatic System for domestic water supply
Confidential Page 9 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
10/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
Supply,Installation, testing and commissioning of Vertical/horizontal monoblock
centrifugal hydroneumatic pressurised pumping set with SS body and S.S impeller,
S.S shaft mechanical seal, connected to a TEFC induction motor suitable for 415 volts
% 3 phase 50 cycles A.C supply with a common suction header of 100 mm dia with
valves on main connecting & pumps inlet and a common delivery header with valves,
including water shock absorber, non return valves with built in MCC panel with controlcable ,controllers , sequential change over ,auto/manual control including M.S.
galvanized supports and painting with one coat of primer and two coats of synthetic
enamel paint including a 100mm dia pressure gauge , Vibration eliminating pads under
foundation, all mounted on a common base plate of MS 80x40mm I section bolted to
RCC foundation complete complete in all respects.
Each Set ( 1working + 1 stand by)
Capacity Each Pump : 100 lpm
Head Each Pump : 35 m Set 1
7 Providing and fixing MS (heavy class) puddle flanges fabricated and painting with
epoxy paint of approved colour as per standard design to water tanks.
a) 50 mm dia Each 8
b) 65 mm dia Each 4
c) 80 mm dia Each 1
d) 100 mm dia Each 1
e) 150 mm dia Each 1
TOTAL FOR P.08
P.09 PLUMBING PANEL
1.0 Providing and fixing of internal piping with valves,fittings, controllers for low/high level
for auto fill in/cut in/cut off , dry level protection,for all pumps including controls with
supporting clamps, brackests etc. as required within pump room complete in all
respects.
2 Providing and fixing of MCC panel with incoming and ougoing controls. Connecting
cables for auto control with manual ride over , sequential,change over facility , cable
glands with supporting clamps, brackests etc. as required within pump room complete
in all respects.
A INCOMING :1 No. of 100A, ATP- HCCB of 25 KA with 50% heavy duty neutral link with On/ Off
Indicating Lamps with 2A SP MCB back-up.
B METERING FOR INCOMING :
i 1 No. Voltmeter of range 0-500V, selector switch and 2 Amps SP MCB back up.
ii 1 No. Ammeter of range 0-300 A, selector switch and 3 Nos. of associated CT's of
ratio 300/5 A.
iii One set of phase indicating lamps with 2 Amps SP MCB back up.
C BUS BAR :
i Electrolytic high conductivity aluminium, 4P, busbars rated at 100Amps,
insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for
oints.
ii The busbar sizing calculations shall be sumitted for approval, considering all derating
factors.
D OUTGOINGS :
(All MCB/ MCCB shall be suitable for motor duty & with heavy duty detachable
solid neutral link):
i 6 Nos. TP MPCB of Suitable breaking capacity with Single Phase Preventor of suitable
rating, Suitable for 3 HP motor with ON / OFF indication lamps, Auto/ Manual/ Off
selector switch. (Type - II, Co-ordination)
ii 6 Nos. DOL starter suitable for 3 HP motor and A/M selector switch.
iii Plumbing Panel as described as above & complete in all respects Set 1
3. Power CablesSupplying and laying of following 1100 volt grade PVC insulated sheathed copper
conductor armoured cables clamped to wall/in tray/in ground with suitable clamps,
Saddles fixing bolts including double compression glands, cable socket connecting
testing and commissioning for all interconnecting for sizes as required within plant
room complete in all respects. Lot 1
4 Providing and fixing MS painted slotted cable trays supported from ceiling at intervals
of 60cms on both ends including cable clips with nuts and bolts of support rods with
ceiling inserts or by drilling and installing expandable fasteners, cutting and making
good for laying of all cables within plant room of required sizes complete in all
respects.complete. Lot 1
Confidential Page 10 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
11/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
5 Supplying, installation and jointing of MS conduits on surface or concealed complete
with MS junction boxes, cover plates, MS bends, GI saddles, base and other
accessories all made in MS with Giscrews as required to complete the job. Exposed
conduiting shall be painted with red enamel paint for identification.
a) 25 mm dia. Lot 1
6 Supply and fixing of 8 SWG bare copper wires of required sizes including all necessary
and effecting proper connections as required complete in all respects. RM 10
7 Cable Termination:
Supply & making end termination with brass double compression glands for the
following PVC insulated, PVC sheathed & armoured 1100 V grade Aluminium cable of
required sizes within oplant room including cost of crimping lugs/ferrules, compression
glands, solder, cable sockets, insulation tape etc complete as required.
Lot 2
8 Level Control cum Indicating Panel
Providing and fixing, installation, testing and commissioning of console type control
cum indicating light panel and all internal wiring. All push buttons shall be provided with
slip-on type lockable arrangement. The panel to house all level and indicating
controllers.
8.1 Raw water filter pumpsTo start pump when low level in the domestic water ground tank and to stop pump
when water tank is full. Each 1
8.2 Domestic dual media filter pumpTo start pump when low level in the domestic water over head tank and to stop pump
when water tank is full. Each RO
8.3 Tubewell PumTo start pump when low level in the raw water tank and to stop pump when raw water
tank is full. Each RO
TOTAL FOR P.09
B FIRE SUPRESSION WORKS
F.01 FIRE HYDRANT SYSTEM (Wet-Riser)
1 Providing and fixing M.S. Pipes to I.S.1239 (Heavy C class) painting with one coat of
zinc chromate primer and two or more coats of synthetic enamel P.O Red paint.
Including all fittings like anchor fastners, couplings, bends, elbows, tees, flanges and
epoxy coated structural supports where required etc. welded or screwed joints as
required, cutting holes and chases in brick or RCC walls and making good complete.
a) 25 mm dia m 10
b) 50 mm dia m RO
c) 80 mm dia m 25
d) 100 mm dia m 10
e) 150 mm dia m 125
f) 200 mm dia (pump room) m 10
1a Providing , fixing including as required cutting holes ,chasees in RCC walls road
cutting ,exacavation trenches of required width , and repairing etc. for ,M.S. Pipes to
I.S.1239 (Heavy C class) with two coats of bitumastic paint, wrapping with one
layer of polythene tape 400 micron thickness and applying a final coat of bitumastic
paint.Including all fittings epoxy coated structural supports where required etc. welded
or screwed joints making good complete.
a) 150 mm dia m 15
2 Providing and fixing gunmetal Hydrant Valve 80 mm inlet with 1 no. single headed
gunmetal landing valve, 63 mm dia instantaneous female coupling on the outlet
complete with orifice flange as required, blank cap and chain locations as per
drawings (inlet flanged to I.S. 5290-1969 Class C ). Nos. 7
3 Providing and fixing first aid Fire Hose Reel wall mounting swinging type fitted with 25
mm dia 30 m long high pressure hose to IS 5132 with 5 mm outlet gunmetal nozzle
with shut off valve (IS 884-1969). Nos. 7
4 Providing and fixing 38mm x 63 mm dia 15 m long RRL (rubberized fabric lined) Hose
including gunmetal male and female instantaneous type coupling machine, wound with
Copper wire complete in all respects. Hose shall be permaline hose and coupling to IS
903 - 1975 with ISI certification. (Two er h drant station) Nos. 14
5 Providing and fixing gunmetal Short Branch Pipe with gunmetal nozzle 16 mm dia
outlet with standard instantaneous type 63 mm dia coupling. Nos. 7
6 Providing & fixing gunmetal Fire Brigade draw out connection and 150 mm dia
flanged outlet to underground tanks complete with 150mm dia foot valve. Nos. 1
7 Providing & fixing gunmetal Fire Brigade Inlet 4 way collecting head with 63 mm dia
instantaneous type inlet and 150 mm dia flanged outlet with builtin check valve for fire
brigade connection to underground tanks (I.S. 904-1965) Nos.a) Four way Nos. 1
b) Two way Nos. 1
Confidential Page 11 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
12/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
8 Providing and fixing single acting Air Release Valve with screwed inlet 25 mm dia.Nos. 2
9 Providing and fixing SS/GM fullway Ball Valve, with screwed female ends for hose
reels. (Imported)
a) 25 mm dia Nos. 10
10 Providing and fixing C.I. double flanged horizontal type Non Return Valves to IS: 5312
including nuts, bolts, 1.5 mm thick compressed asbestos gasket complete.
a) 100 mm dia Nos. 1
b) 150 mm dia Nos. 2
c) 200 mm dia Nos. 1
11 Providing and fixing cast iron double flanged Butterfly Valves complete with bolts,
nuts, washers 3 mm thick insertion neo rene asket.a) 100 mm dia Nos. 2
b) 150 mm dia Nos. 2
c) 200 mm dia Nos. 2
12 Providing and fixing suction Bucket Strainer with MS flanged connection
a) 100mm dia. Each 2
b) 150 mm dia. Each RO
c) 200 mm dia. Each 1
13 Providing and fixing partly glazed single/double hung lockable Aluminium Shutter
fabricated from aluminium angle of size 400x400x5 mm and aluminium sheet 4 mm
thick glass for fire station enclosing landing valve, first aid hose reel, 2 rolls of 63 mm
dia hose 15 m long and fire extinguisher etc. complete with aluminium angle frame of
size 50x50x6 mm complete including stove enamelled painting of door and frame and
words "Fire H drant" written on lass front.a) Size 2100x900x600 mm deep. Nos. 7
14 Providing and fixing Fire Hose Cabinet fabricated from 16 gauge M.S. sheet with
single or double glazed front door and locking arrangement, painted "Fire Red" with
stove enamelled paint "Fire Hose" written on front including necessary supports
approximate size 900x600x600 mm deep (to house two lengths of canvas hose with
couplings, branch pipe and nozzle for external hydrants) Nos. RO
15 Providing and laying non-pressure NP2 class RCC Hume pipes for Crossing road
plumbing and fire sericed services
a) 400 mm dia R.C.C. pipe RM RO
b) 500mm dia R.C.C. pipe RM RO
TOTAL FOR F.01
F.02 AUTOMATIC SPRINLER SYSTEM
Note: Contractor to give alternate price for supply of sprinkler head if client
arranges for CT3 Form & exemption of Custom Duty.
1 Providing. Fixing and testing M.S. pipe confirming to IS 1239 (Heavy class) complete
with necessary malleable M.S. f it tings and clamps, f ixing pipes on epoxy painted
structrual support at 2-3 metres intervals, painting of pipes with epoxy paint over a
prime coat of primer, cutting holes in brick /RCC walls etc. and making good the same
com lete includin cost of su orts, of nominal dia
b) 32 mm dia m 21
c) 40 mm dia m 3
d) 50 mm dia m 6
e) 65 mm dia m 9
f) 80 mm dia m 40
m
1a Providing , fixing including as required cutting holes ,chasees in RCC walls road
cutting ,exacavation trenches of required width , and repairing etc. for ,M.S. Pipes to
I.S.1239 (Heavy C class) with two coats of bitumastic paint, wrapping with one
layer of polythene tape 400 micron thickness and applying a final coat of bitumastic
paint.Including all fittings epoxy coated structural supports where required etc. welded
or screwed joints making good complete.
a) 100 mm dia m 15
2 Providing and fixing 15 mm dia gunmetal Sprinkler Head (UL listed) with quartzoid
bulb and set to operate at 68 deg. C
a) Pendent type (For exposed location) Nos. 35
b) Side wall type Nos. RO
3 Providing and fixing C.I. double flanged Butterfly Valves conforming to IS 13095 PN
1.6 complete with bolts, nuts, washers 3 mm thick insertion neoprene gasket.
a) 80 mm dia Nos. 2
4 Providing and fixing electrically operated Flow Switches with threaded connection for
a minimum flow of 900 lpm for indicating water flow in sprinkler branch line on each
floor with necessary junction box installed in an accessible place.
a) 80 mm dia Nos. 1
Confidential Page 12 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
13/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
5 Providing and fixing copper conductor PVC covered Control Cables from individual
flow switches on each floor to annunciation panel installed in fire control room in
basement including sleeves,cable clips, supports for horizontal runs making
connection to each switch complete.a) 2 core 1.5 mm
2 m 150
6 Providing and fixing C.I. double flanged horizontal Non Return Valves to IS 5312
including nuts, bolts 1.5 mm thick compressed asbestos gasket complete.a) 80 mm dia Nos. 1
TOTAL FOR F.02
Confidential Page 13 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
14/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
F.03 FIRE PUMPS & ACCESSORIES
Note :- 1. Valves, headers and vibration eliminators etc. have been taken in
Subhead I of this section
2. Contractor to quote separately for Supply of Pumps & Installation works.
1 Providing and fixing Horizontal Split Casing Fire Pump, (electric motor driven) single
stage, single outlet with bronze impeller and C.I. body, SS shaft and connected by a
flexible coupling to a totally enclosed fan cooled Induction motor of 2900 RPM
mounted on a common structural base plate including foundation with all pump
accessor ies complete as per specifications motor to be suitable for 415 volts, 3
phase, 50 cycles A/C supply (main pump motors to be provided with inbuilt heating
arran ement).
a) Main Fire Pump:
Capacity 1620 lpm.
Head 60 m
H.P. 35 (approx)
RPM 1500
Supply Set 1
Installation Set 1
b) Jockey Pump:
Capacity 180 lpm
Head 60 m
H.P. 5 (approx.)
RPM 2900
Supply Set 1
Installation Set 1
2 Providing and fixing Horizontal Split Casing (Standby) Fire Pump (Diesel engine
driven)single stage, single out let pumping set with C.I. body and bronze impeller, SS
shaft, connected by a flexible coupling to a water cooled diesel engine, (with cooling
water drawn from the discharge side of the pump and with pressure reducing valve,
pressure gauge strainer and all accessories) mounted on a common structural base
plate with resilient pads and foundation bolts, nuts, washers complete with electric
panel with all annunciations, with built in logic for manual start/ auto start, battery
(including one spare battery), exhaust pipe of required length to discharge outside
building with muffler , and expansion joint with isolation day oil tank mounted on
suitable structural supports complete in all respects, ready for use including a battery
charger as per specification.
Fully Automatic Diesel engine starting system complete with battery charger, 8 window
annunciator, indicating lights, transformer, rectifier, timer, voltmeter ammeter, selector
switches, push buttons, auxiliary relay etc. complete as required as per TAC rules
Pump: Kirloskar or equivalent
Engine: Kirloskar Cummins or equivalent
Pump capacity 1800 lpm
-Engine H.P. as per BS : 5514
Supply Nos. 1
Installation Nos. 1
3 Providing and fixing double flanged vertical Air Vessel fabricated from 12 mm thick
M.S.plate with dished ends 450 mm dia and 2.0 m high common for fire and jockey
pumps complete with four pressure switches to operate jockey and main pumps at
drop of pressure as given in the specifications. Set 1
4 Providing and fixing dust and vermin proof cubicle type motor Fire Pump Control
Panel fabricated from 14 g M.S. sheet with stove enamelled finish and comprising of:-
a) One incoming main MCCB unit of matching rating.
b) One fully insulated aluminium bus bar of 400 amp. capacity in separate bus bar
chamber.
c) Two MCCBs of 300 amps with HRC fuses for main electrical & sprinkler pumps.
d) One MCCB units with HRC fuses of 63 amps rating for 30 H.P. jockey pump (fire).
e) Three fully automatic star delta starters with push buttons and on/off indicating lights
for fire & sprinkler pumps.
f) Three rotary type auto/ manual/off selector witches.
g) Three single phasing preventors of suitable rating one for each motor.
h) One 150 mm square panel type voltmeter reading 0-500 V with rotary selector switch
for reading voltage between phases.
Confidential Page 14 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
15/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
i) Two 100 mm square panel type ampere meter reading 0-400 amps for fire/sprinkler
pumps.
j) Two 100 mm square panel type ampere meter reading 0-100 amps for jockey/Diesel
pumps.
k) Appropriate eteched plastic identification plate
l) Colour coded internal wiring from incoming main to bus bar, switchgear, starters,
meters indicating lamps complete in all respect
(Note: The rating of all switchgear & HRC fuses must match the HP of all pump
motors offered).
Supply Set 1
Installation Set 1
5 Providing and fixing heavy duty PVC insulated, PVC Armoured Conductor Cables
1100V grade including necessary support clamps and connection lugs complete in all
res ects.a) Power cable 3 core 240 mm
2aluminium conductor armoured cable m RO
b) Power cable 3 core 16 mm2
aluminium conductor armoured cable. m 25
6 Providing and fixing Copper Earthing 25mm x 3 mm tapes from all motors and MCC
panel to be connected in an approved manner to the general earthing system .m 10
7 Providing Earthing Station for pumps and M.C.C. panel including excavation, C.I.
manhole cover and frame com lete as er s ecifications and IE rules. Nos. 1
8 Providing and fixing dial type pressure gauge with isolation cock and pipe at hydrant
station.
a) dial diameter 100 mm, calibration 0-15 kg Nos. 3
TOTAL FOR F.03
Confidential Page 15 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
16/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
F.04 HAND APPLIANCES1 Providing and fixing CO2 fire extinguishers consisting of welded M.S. cylindrical
body, squeeze grip lever discharge valve fitted with pressure indicating gauge internal
discharge tube, 30cms long high pressure discharge hose, discharge nozzle,
suspension bracket, confirming to IS:2878 finished externally with red enamel paint andfixed to wall with brackets complete with internal charge.
Capacity 4.5 kg.(I.S. 2878) Nos. 9
2 Providing and fixing stored pressure type Water CO2 fire extinguishers complete
with cylinder hose, discharge nozzle, suspension bracket and externally finished with
red enamel paint and fixed to wall with brackets complete with initial charges.
Capacity 9 ltrs(I.S. 940) Nos. 9
TOTAL FOR F.04
Confidential Page 16 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
17/94
DLF Phase 3 Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
QuantityRate
(Rs.)
Amount
(Rs.)Sl No. Description Unit
F.05 CO2 PANEL FLOODING SYSTEM
1.0 Supply, f ixing, testing and commissioning of Polymer Tube Detection based CO2
System for Electrical Panels (Firetrace Tube Panel Protection System), consisting of
the following components:
(a1) CO2 Cylinder, 8 kg capacity, complete with all necessary CO2 Gas, fittings, support
and accessories, connected with Valve (with manual release facility).No. 2
(a2) CO2 Cylinder, 4.5 kg capacity, complete with all necessary CO2 Gas, fittings, support
and accessories, connected with Valve (with manual release facility).No. 1
(b) Filling Adapter Each 3
(c) Outlet adapter Each 3
(d) End of Line adapter Each 3
(e) Pressure switch Each 3
(f) Flexible Polymer Detection Tube with all necessary fittings & supports. M 10
(g) Master Control Unit for controlling each system, complete with pressure switches,
buzzers and electronic hooters, including all necessary accessories + electrical wiring
to make each entire system functional.
Each 3
(h) Auto weight measuring Unit for Cylinders with automatic audio/visual alarm. Each 3
Note: The items indicated above are notable items. The vendor to include all allied and
implid items in required quantity at no extra cost.
TOTAL FOR F.05
Confidential Page 17 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
18/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
PART-3 PLUMBING & FIRE FIGHTING
A PLUMBING SYSTEM
P.01 SANITARY FIXTURES
1 Providing and Fixing white/coloured vitreous china European type water closet with
concealed 'P' or 'S' trap ,C.P.Bolts, nuts, C.I. Chair or other hanging/fixing arrangement
with mult i f lexi connector to mains, solid plastic seat with lid, C.P. brass hinges and
rubber buffers with wall mounted dual low volume flushing cistern , C.P. brass screws
and washers complete, including cutting holes in walls,f loors and making good the
same complete in all respects. (Hindware or eq.)
a) Supply Each 1
b) Installation Each 1
2 Providing and Fixing vitreous china wash basin Under Water Counter round/oval
with waste coupling fitting,32mm CP cast brass bottle trap and pipe to wall with CP wall
flange and rubber adopter for waste connection, CP deck mounted mixer with battery
operated and built in sensor for auto cut in/cut off operation complete including cutting
and making good the walls where required complete in all respects.(Hindware or eq.)
a) Supply Each 1
b) Installation Each 1
3 Providing and Fixing 15 mm C.P. brass long body bib cock with C.P.brass flange
complete including cutting and making good the walls where required.
a) Supply (Jaguar continental or eq.) Each RO
b) Installation Each RO
4 Providing and Fixing C.P brass ablution health faucet assembly with 1.2 m long
braided PVC hose with mounting bracket fixed on wall complete.a) Supply (Jaguar continental or eq.) Each 1
b) Installation Each 1
5 Providing and fixing Stainless Steel finish toilet paper holder with stainless steel roller
complete, including cutting and making good the walls where required.
a) Supply (utec or eq.) Each 1
b) Installation Each 1
6 Providing &fixing 15 mm dia angle valve with flanges including 450 mm long copper
connecting pipe with nuts complete.a) Supply (Jaguar continental or eq.) Each 2
b) Installation Each 2
7 Providing and Fixing Stainless steel twin coat hooks f ixed on toilet door with C.P.
brass screws.
a) Supply (Utec or eq.) Each 1
b) Installation Each 1
8 Providing and fixing wall mounted auto aerosol dispenser with digital display fixed
with brackets and rowl plug complete in all respects.
a) Supply (Utec UT 650 or eq.) Each 1
b) Installation Each 1
9 Providing &Fixing 15 mm C.P. brass wall mounting single lever mixing fitting for
kitchen sink with swinging and Swivel spout complete including cutting and making
ood the walls wherever re uired.a) Supply (Jaguar Savoy 11163 ) Each RO
b) Installation Each RO
TOTAL FOR P.01
Rate
(Rs.)
Amount
(Rs.)
RAPID METRO RAIL GURGAON LIMITED
TENDER FOR E & M WORKS
SCHEDULE OF QUANTITY
ELEVATED METRO STATION - BELVEDERE
Sl No. Description Unit Quantity
Confidential Page 18 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
19/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.02 SOIL, WASTE,VENT & FITTINGS
1 Providing, fixing & testing uPVC pipes confirming to IS 13592 (Type B) alongwitF all
required fittings like tees, bends, crosses witF or witFout access doors jointed witF
approved solvent cement as per manufacturer's recommendations, fixed to walls and
ceilings witF clamps complete including cutting and making good tFe floors and wallswFere required complete of outer diameter. ( price to be inclusive of fire rated UPVC
wFerever crossing from one floor to anotFer floor occurs.)
I Vertical Pipe
a) 75 mm OD m RO
b) 110 mm OD m 25
II Pipe at Ceiling
a) 110mm OD m RO
b) 160mm OD m RO
III Pipe at Floor
a) 110mm OD m 5
2 Providing, fixing & testing uPVC pipes, conforming to IS 4985 class 3 (6 kg/cm2)
including injection moulded fittings, jointing with solvent cement, cutting and making
good the floors and walls and jointing to trap/waste pipe, complete of outer dia.
a) 40 mm OD m 2
b) 50 mm OD m RO
c) 63 mm OD m RO
3 Providing and laying cement concrete 1:2:4 mix (1 cement:2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) 75 mm in bed and alround uPVC soil & waste
pipes including excavation, refil ling where required complete in all respect as per
standard desi n.a) Pipe 90 to 110 mm OD m 5
b) Pipe 40 to 63 mm OD m 2
4 Providing, fixing and testing of uPVC P or S trap including jointing with solvent cement
and making good the walls, floors etc., complete of nominal size.
a) 110x 110mm Each 1
5 Providing, fixing and testing of uPVC SWR inlet fittings with two or three saddle inlets
of 40, 50 or 63 mm size, fabr icated from 110 mm outer dia uPVC pipes and fixed to
uPVC traps with solvent cement joint complete. Each
1
6 Providing and fixing uPVC reducing elbow as floor drain in cement concrete 1:2:4
float with floor com lete in all res ects.
a) 110 x63 mm outlet Each RO
7 Providing and fixing 125 mm dia, 1 mm thick Stainless steel grating with frame for
floor traps or drains of required pattern including cutting and making good the floors
com lete.a) 125mm dia over Floor Trap Each 2
TOTAL FOR P.02
Confidential Page 19 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
20/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.03 RAIN WATER PIPES & FITTINGS
1 Providing, fixing testing uPVC pipes, conforming to IS 4985 class III (6 kg per sqcm)
including injection moulded fittingswitF bosses like bents tee's adopters etc. suitable for
rubber ring jointing witF solvent cement including cutting, fixing to walls /ceiling witF
supporting clamps etc. all complete in all respects.
a) 110 mm OD m RO
b) 160 mm OD m 180
c) 210 mm OD m RO
d) 260 mm OD m RO
2 Providing & fixing dura coating cast iron hopper with cast aluminium ring and dome
grating with S.S screw for rain water outlet including making joint to uPVC rain water
pipe as per manufacturer's recommendations, complete making good the walls and
floors wherever re uiered.a) Flat type with 110 mm dia outlet Nos. RO
b) Flat type with 160 mm dia outlet Nos. 12
c) Flat type with 210 mm dia outlet Nos. RO
d) Flat type with 260 mm dia outlet Nos. RO
3 Providing and fixing floor drain with supporting clamp ceiling or in sunken portion
including cutting and making good the walls and floors wherever required complete in
all respects.(Basement Drainage)a) 150 x150 mm Greating Each RO
4 Providing and fixing cast iron grating in lengths of 0.6 to 1 metre with angle iron
frame with hold fasts (25 mm wide 3 mm thick M.S. f lat) welded to frame, setting with
cement mortar 1:3 (1 cement : 3 coarse sand) true to level as required by the
Engineer-in-Charge
a) 300 mm wide 40 mm thick including 50x50x5 mm angle iron frame for basement car
parking areas. m RO
5 300 mm wide 25 mm thick including 30x30x50 mm angle iron frame and M.S. hold
fasts as required for plant rooms. m 7
TOTAL FOR P.03
Confidential Page 20 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
21/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.04 INTERNAL WATER SUPPLY SYSTEM
1 Providing and fixing CPVC (Chlorinated Poly Vinyl Chloride) water supply pipes with
pipe as per CTS SDR-13.5 at a working pressure of 22.5 kg/sqcm PSI at 23 deg C &
80 PSI at 82 deg. C, using solvent welded CPVC fittings ie. Tees, Elbows, Couplers,
Unions, Reducers, brushings etc. including transition fittings connection between CPVC& metal pipe /GI) ie. Brass Adaptors (both Male & Female threaded) conforming to
ASTM D-2846 with only CPVC solvent cement conforming to ASTM F-493 with
fabricated & subssequently epoxy painted clamps/ structural steel supports as required
for directed at site including cutting chases and fitting the same with cement concrete
/cement mortar as required or exposed in shaft/ ceiling as required with all supports
clamps etc. complete. All termination points for installation of faucets shall have brass
termination fittings.
a) 15 mm nominal bore m 3
b) 20 mm nominal m 2
c) 25 mm nominal m RO
d) 32 mm nominal m RO
2 Providing, laying, jointing and testing, GI medium class pipes conforming to IS:1239,
including all fittings couplings, adapters & two or more coats of synthetic
enamel paint over a coat of primer of approved quality and shade (shade as per pipe
colour code)complete in all respect as directed by the Engineer-in-Charge.
i) For Toilet
a) 15 mm nominal boe m 8
b) 20 mm nominal bore m 20
c) 25 mm nominal bore m RO
ii) In Pum room
a) 32 mm nominal bore m 10
b) 40 mm nominal bore m 5
c) 50 mm nominal bore m 10
d) 65 mm nominal bore m 10
e) 80 mm nominal bore m 15
f) 100 mm nominal bore m 5
3 Providing & fixing stainless steel ball valve with wheel & female screwed ends of
approved quality to I complete in all respects.a) 15 mm nominal bore Nos. 1
b) 20 mm nominal bore Nos. 1
c) 25 mm nominal bore Nos. 1
d) 32 mm nominal bore Nos. 1
e) 40 mm nominal bore Nos. RO
4 Providing and fixing C.I. double flanged butterfly valves complete with bolts, nuts,
washers 3 mm thick insertion neo rene asket.a) 50 mm nominal bore Nos. 3
b) 65 mm nominal bore Nos. 1
c) 80 mm dia Nos. 6
d) 100 mm dia Nos. 2
5 Providing and fixing float valve (brass) with copper float of approved quality suitable
for high or low pressure complete in all respects.a) 32mm dia Nos. 1
b) 40 mm dia Nos. RO
c) 50 mm dia Nos. RO
TOTAL FOR P.04
Confidential Page 21 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
22/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.05 EXT. WATER SUPPLY
1 Excavating trencFes of required width for pipes, cables etc. including road cutting
,excavation for sockets and dressing of sides, ramming of bottom deptF upto 1.5 M
including getting out tFe excavated soil and tFen returning tFe soil as required
in layers not exceeding 20 cms in deptF including filling jamuna sand alround,consolidating eacF deposited layer by ramming, watering etc. and road reparing ,
disposing of surplus excavated soil outside tFe site.
a) Pipes, cables etc.not exceeding 80 dia. m 30
b) Pipes, cables etc.exceeding 80 dia but not exceeding 150 mm dia. m RO
2 Providing, laying, jointing and testing, GI Medium class pipes conforming to IS:1239,
including all fittings with expansion loop at intervals with flanged joints including all
couplings, adapters etc., complete, including excavation, trenching and back filling
complete in all respect.a) 32 mm dia m 5
b) 40 mm dia m 25
c) 50 mm dia m RO
d) 80 mm dia m RO
3 Painting G.I. pipes with two coats of bitumastic paint, wrapping with one layer of
polythene tape 400 micron thickness and applying a final coat of bitumastic paint.
a) 32 mm dia m 5
b) 40 mm dia m 25
c) 50 mm dia m RO
d) 80 mm dia m RO
4 Providing and fixing water meter with direct reading dial in KL with all internal
parts in gunmetal or brass, strainer, flanged distance piece for easy removal in
future, 100 mm dia. Bourden type Municipal pressure guage and isolation cock
including necessary isolation cock including necessary test certificate for the meter
from Local Authorities (For Municipal Connection & tubewell outlets).
50 mm nominal bore Each 1
5 Constructing brick valve chamber 600x450x750mm, inside with 75 class designation
brick work in cement mortar 1 : 5 (1 cement : 5 coarse sand) for sluice/butterfly
valve,with C.I. surface box 100mm. top diameter,160mm bottom diameter and 180mm
deep (inside) with chained lid and RCC top slab1:2:4 mix (1 cement : 2 coarse sand : 4
graded stone aggregate 20mm nominal depth, refilling and disposal of surplus earthas
directed, foundation concrete 1 : 5 : 10 (1cement : 5 coarse sand : 10 graded stone
aggregate 40 mm nominal size) and inside plastering with cement mortar 1 : 3 (1
cement : 3 coarse sand) 12 mm thickfinished with a floating coat of neat cement
outside plaster ing with 1 : 3 cement mortar (1 cement : 3 coarse sand) 12 mm thick
complete as per standard design.Each 1
6 Making connection from municipal /borewell exising line to water meter including
required pipe length up to water meter including pipe corrosion treatment,trench,road
cuttingand complete with all respect Each 1
TOTAL FOR P.05
Confidential Page 22 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
23/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.06 EXTERNAL SEWERAGE SYSTEM
Note -quantity measured up to first manhole . Piping from first manhole as per
site not included .
1 Exacavation trencFes of required width for pipes, cables etc. including excavation for
sockets and dressing of sides, ramming of bottom deptF of 1.5 m including getting out
of tFe excavated soil and tFen returning tFe soil as required in layers by ramming,watering,road cutting and repairing etc. and disposing of surplus excavated soil as
directed witFin a lead of 200 m in Dense soil .
a) Pipes, cables etc.exceeding 80 dia but not exceeding 300 mm dia. m 10
b) Pipes cables etc. exceeding 300 mm m RO
2 Extra for excavating trenches pipes, cables etc. for depth exceeding1.5 m. but not
exceedin 3m.a) Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. Dia m RO
b) Pipes cables etc. exceeding 300 mm dia. m RO
3 Providing and laying PVC socketed Pipes to IS 15328 class-SN-4 KN/sqm with
solvent cement joints laid on 150 mm thick concrete base over 300 mm thick stone dry
soling 150 mm concrete all around of 1:3:6 mix ( 1 cement:3 coarse sand:6 aggreagte
20 mm nominal size ) including testing of joints etc. complete:
a) 160 mm OD pipe m 5
b) 210 mm OD pipe m 5
4 Constructing brick masonry Rectunglar manhole with Ist class bricks in cement
mortar 1:5 (1 cement : 5 fine sand) RCC top slab with 1:2:4 mix (1 cement: 2 coarse
sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1
cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside and
outside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand)
finished with a floating coat of neat cement inside and rough plaster on outside and
making channels in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) neatly finished including PVC foot rests @ 300
mm spacing complete as per standard design including excavation, refil ling, and
disposal of surplus earth and PVC coated M.S. foot rest at 300 mm spacing.
a) Inside size 90 x 80x 60 cms deep including heavy duty SFRC manhole cover and
frame complete in all respects. Each 1
5 Extra for additional depth of manholes
a) Size 90x80 cms beyond 60 cms depth m RO
6 Constructing brick masonry circular type manhole with 75 class designation bricks in
cement mortar 1:4 mix (1cement: 4 coarse sand) inside and outside cement
plaster 12 mm thick with cement mortar 1:3 (1cement : 3 coarse sand) inside with
a floating coat of neat cement, and outside with water proofing compound,225 - 300
mm thick P.C.C.base concrete 1:3:6 mix (1 cement:3 coarse sand: 6 graded stone
aggregate 20 mm nominal size) including excavation, back fil ling and disposal of
surplus earth, providing and embedding 12mm dia M.S polypropylene coated manhole
steps embedded in cement concrete block 1:2:4 at 300 mm apart neatly finished
complete as per CPWD specification/design.
a) 0.91m. internal bottom dia * 1.67 m deep with steel fibre reinforced concrete (SFRC)
manhole cover with frame (heavy duty) 560mm internal dimeter, total weight of
cover and frame to be not less than 182 kg. (weight of cover 80 kg and weight of
frame 102 kg) fixed in Cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone
aggregate 20 mm nominal size) including centring & shuttering
Each RO
7 Providing and fixing square mouth SW gully trap grade 'A' complete with C.I. grating
brick masonry chamber and water tight C.I. cover with frame of 300x300 mm size
(inside) the weight of cover to be not less than 4.53 kg and frame to be not less than
2.72 k as er standard desi n.150x100 mm size P type F.P.S. bricks of class designation 75. Each 2
8 Making connection of sewer line with existing manhole including breaking into and
making good the walls,floors with cement concrete branch sewer line to main sewer
sewer manhole including cement concrete 1:2:4(1 cement :2 fine sand :4 graded
stone aggrigate 20 mm nominal size ) cement plastered on both sides with1:3 (1
cement : 3 coarse sand) inside with a floating coat of neat cement, and outside
required channels complete as per standred design and specifications.Each 1
TOTAL FOR P.06
Confidential Page 23 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
24/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.07 EXTERNAL DRAINAGE SYSTEM
Note -Extenal Drainage pipe up to propoded recharge pit
1 Exacavation trenches of required width for pipes, cables etc. including excavation for
sockets and dressing of sides, ramming of bottom depth of 1.5 m including getting out
of the excavated soil and then returning the soil as required in layers by ramming,
watering,road cutting and repairing etc. and disposing of surplus excavated soil asdirected within a lead of 200 m in Dense soil .
a) Pipes, cables etc.exceeding 80 dia but not exceeding 300 mm dia. m 170
b) Pipes, cables etc. exceeding 300mm m RO
2 Extra for excavating trenches pipes, cables etc. for depth exceeding1.5 m. but not
exceedin 3.5m.a) Pipes, cables etc. exceeding 80mm dia but not exceeding 300mm. Dia m RO
b) Pipes, cables etc. exceeding 300mm m RO
3 Providing and laying non-pressure NP2 class S/S RCC pipes with collars joined with
stiff mixture of cement mortar in the proportion of 1:2(1 cement :2 fine sand) including
testin of oints etc. com lete
a) 150 mm dia R.C.C. pipe m 10
b) 250 mm dia R.C.C. pipe m RO
c) 300 mm dia R.C.C. pipe m 160
d) 400 mm dia R.C.C. pipe m RO
4 Providing and laying cement concrete 1:4:8 (1 cement : 4 coarse sand: 8
aggregate 40 mm nominal size) alround R.C.C pipes including in bed concrete 150
mm thick ,alround or haunching etc. as per standard design.
a) 150 mm dia m 10
b) 250 mm dia m RO
c) 300 mm dia m 160
5 Constructing brick masonry road gully chamber 50x45x60 cm wtth bricks of class
designation 75 in cement mortar 1:5 (1cement : 5 fine sand) including 500x450 mm
precast RCC horizontal grating wilh frame complete as per standard design. With
F.P.S. bricks Each 14
6 Constructing brick masonry Rectunglar manhole with Ist class bricks in cement
mortar 1:5 (1 cement : 5 fine sand) RCC top slab with 1:2:4 mix (1 cement: 2 coarse
sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1
cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside and
outside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand)
finished with a floating coat of neat cement inside and rough plaster on outside and
making channels in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded
stone aggregate 20 mm nominal size) neatly finished including PVC foot rests @ 300
mm spacing complete as per standard design including excavation, refil ling, and
disposal of surplus earth and PVC coated M.S. foot rest at 300 mm spacing.
a) Inside size 90 x 80x 60 cms deep including heavy duty SFRC manhole cover and
frame com lete in all res ects. Each 2
7 Extra for additional depth of manholes
a) Size 90x80 cms beyond 60 cms depth m RO
8 Constructing brick masonry circular type manhole with 75 class designation bricks in
cement mortar 1:4 mix (1cement: 4 coarse sand) inside and outside cement
plaster 12 mm thick with cement mortar 1:3 (1cement : 3 coarse sand) inside with
a floating coat of neat cement, and outside with water proofing compound,225 - 300
mm thick P.C.C.base concrete 1:3:6 mix (1 cement:3 coarse sand: 6 graded stone
aggregate 20 mm nominal size) including excavation, back fil ling and disposal of
surplus earth, providing and embedding 12mm dia M.S polypropylene coated manhole
steps embedded in cement concrete block 1:2:4 at 300 mm apart neatly finished
complete as per CPWD specification/design.
a) 0.91m. internal bottom dia * 1.67 m deep with steel fibre reinforced concrete
(SFRC) manhole cover with frame (heavy duty) 560mm internal dimeter, total weight
of cover and frame to be not less than 182 kg. (weight of cover 80 kg and weight of
frame 102 kg) fixed in Cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone
aggregate 20 mm nominal size) including centring & shutteringEach RO
9 Making connection of drainage line with existing drain / manhole including breaking
into and making good the walls,floors with cement concrete branch sewer line to main
sewer sewer manhole including cement concrete 1:2:4(1 cement :2 fine sand :4
graded stone aggrigate 20 mm nominal size ) cement plastered on both sides with1:3
(1 cement : 3 coarse sand) inside with a floating coat of neat cement, and
outside required channels complete as per standred design and specifications.Each RO
10 Construction of ground water re-charge pit 5m X 1M wide and 4m effictive depth
s ecifications and com lete as er drawin .
a) Peripherial brick masonry in cement mortar 1:4 (1 cement: 4 coarse sand)
b) Foundation concrete 1:5:10
c) 300mm thick dry stone aggregate bed (40 to 65mmnominal grade)
d) 200mm depth thick R.C.C. (1:3:4) slab to cover the well
at top including necessary reinforcement.
Confidential Page 24 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
25/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
e) 2*160 mm dia PVC perforated pipe upto 5 mtr above water. depth Rate to include
excavation, back filling and all other operations necessary for complete the job
including obtaining approval from local and other Govt. bodies Each 2
f) 1*160 mm dia PVC perforated pipe upto 5 mtr above water. depth Rate to include
excavation, back filling and all other operations necessary for complete the job
including obtaining approval from local and other Govt. bodies Each RO
TOTAL FOR P.07
Confidential Page 25 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
26/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
P.08 WATER SUPPLY PUMPS & WTP EQUIPMENTS
A Water Supply & Drainage Pumps
Supply,Installation, testing and commissioning of Vertical monoblock centrifugal
transfer pumping set with SS body and S.S impeller, S.S shaft mechanical seal,
connected to a TEFC induction motor suitable for 415 volts % 3 phase 50 cycles A.C
supply with a common suction header of 100 mm dia with valves on main connecting &
pumps inlet and a common delivery header with valves, includingt water shockabsorber, non return valves with M.S. galvanized supports and painting with one coat
of pr imer and two coats of synthetic enamel paint including a 80mm dia pressure
gauge , Vibration eliminating pads under foundation, all mounted on a common base
plate of MS 80x40mm I section bolted to RCC foundation complete complete in all
respects. (For detail refer tender drawing ).
1 Raw Water filter PumOne Set
(1 working + 1 stand by)
Capacity : 100 lpm
Head :35 m
Each 1
2 Submersible pumps for drainage /Sewage
Supply Installation,testing & commissioning of Submersible single stage single entry
pumps with C.I.body and C.I. two vane enclosed type impeller connected to TEFC
submersible motor for 415 volts, 3 phase, 50 cycles A.C. power supply with
mechanical seal, pump connector unit with rubber diaphram and bend, vt.
discharge pipe, in built level controller with operational moded as one pump working
at low level, both pumps at high level with a hooter alarm and cut off at dry level as
determined with in built MCC panel with auto cut in/off with sequential change over
facility incuding all connecting cables,controllers etc all complete as required.The
pump shall also be provided with a lifting devise of pull chain/guide rail as per
requirement complete in all respects.
a) For Drainage(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 12mm)
Capacity- 225 lpm (Each)
Head - 15 m Set 1
b) For Drainage(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 12mm)
Capacity- 570 lpm (Each)
Head - 18 m Set RO
c) For sewage
(one working + one standby/both working in high flow conditions)
(Solid handiling capacity 40 mm)
Capacity- 180 lpm (Each)
Head - 15 m Set RO
3 Domestic Dual Media FilterSupply,Installation, testing and commissioning of multi media with activated carbon
layer vertical water pressure filter fabricated from M.S plate with 8 mm shell and 10
mm thick dished ends complete with initial charge of filter media with Butterfly valve,
uPVC face piping, accessories as specified in the specifications,sand blasted inside
and outside, finished with primer and epoxy paint coating inside and one coat of primer
and two coats of high gloss enamel paintof approved shade outside, testing and
commisioning complete. (Thinner plates for shell and dished ends not
acce table)a) Workin ressure : 2-2.5 k /cm
2.
Test ressure : 4.5 k /cm2.
Flow rate per filter : 6000 lph
Filtration rate : 14500 l h/m2
Filter dia :800mm Each 1
4 Chlorination PumpSupply and installation,testing and commissioning of chemical dosing pump capacity 0-
10 lph mounted on a 100 lit capacity uPVC container with lid, injection fitting
assembly,suction and delivery hose upto the point of injectionincluding supportscomplete in all respects.
a) For chlorination of raw water Each 1
5 Hydroneunatic System for domestic water su ly
Supply,Installation, testing and commissioning of Vertical/horizontal monoblock
centrifugal hydroneumatic pressurised pumping set with SS body and S.S impeller,
S.S shaft mechanical seal, connected to a TEFC induction motor suitable for 415 volts
% 3 phase 50 cycles A.C supply with a common suction header of 100 mm dia with
valves on main connecting & pumps inlet and a common delivery header with valves,
including water shock absorber, non return valves with built in MCC panel with control
cable ,controllers , sequential change over ,auto/manual control including M.S.
galvanized supports and painting with one coat of primer and two coats of synthetic
enamel paint including a 100mm dia pressure gauge , Vibration eliminating pads under
foundation, all mounted on a common base plate of MS 80x40mm I section bolted to
RCC foundation complete complete in all respects.
Each Set ( 1working + 1 stand by)
Capacity Each Pump : 100 lpm
Head Each Pump : 35 m Set 1
Confidential Page 26 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
27/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
7 Providing and fixing MS (heavy class) puddle flanges fabricated and painting with
epoxy paint of approved colour as per standard design to water tanks.
a) 50 mm dia Each 8
b) 65 mm dia Each 4
c) 80 mm dia Each 1
d) 100 mm dia Each 1
e) 150 mm dia Each 1TOTAL FOR P.08
P.09 PLUMBING PANEL
1.0 Providing and fixing of internal piping with valves,fittings, controllers for low/high level
for auto fill in/cut in/cut off , dry level protection,for all pumps including controls with
supporting clamps, brackests etc. as required within pump room complete in all
respects.
2 Providing and fixing of MCC panel with incoming and ougoing controls. Connecting
cables for auto control with manual ride over , sequential,change over facility , cable
glands with supporting clamps, brackests etc. as required within pump room complete
in all respects.
A INCOMING :1 No. of 100A, ATP- HCCB of 25 KA with 50% heavy duty neutral link with On/ Off
Indicating Lamps with 2A SP MCB back-up.
B METERING FOR INCOMING :
i 1 No. Voltmeter of range 0-500V, selector switch and 2 Amps SP MCB back up.
ii 1 No. Ammeter of range 0-300 A, selector switch and 3 Nos. of associated CT's of
ratio 300/5 A.
iii One set of phase indicating lamps with 2 Amps SP MCB back up.
C BUS BAR :
i Electrolytic high conductivity aluminium, 4P, busbars rated at 100Amps,
insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for
oints.
ii The busbar sizing calculations shall be sumitted for approval, considering all derating
factors.
D OUTGOINGS :
(All MCB/ MCCB shall be suitable for motor duty & with heavy duty detachable
solid neutral link):
i 6 Nos. TP MPCB of Suitable breaking capacity with Single Phase Preventor of suitable
rating, Suitable for 3 HP motor with ON / OFF indication lamps, Auto/ Manual/ Off
selector switch. (Type - II, Co-ordination)
ii 6 Nos. DOL starter suitable for 3 HP motor and A/M selector switch.
iii Plumbing Panel as described as above & complete in all respects Set 1
3. Power Cables
Supplying and laying of following 1100 volt grade PVC insulated sheathed copper
conductor armoured cables clamped to wall/in tray/in ground with suitable clamps,
Saddles fixing bolts including double compression glands, cable socket connecting
testing and commissioning for all interconnecting for sizes as required within plant
room complete in all respects. Lot 1
4 Providing and fixing MS painted slotted cable trays supported from ceiling at intervals
of 60cms on both ends including cable clips with nuts and bolts of support rods with
ceiling inserts or by drilling and installing expandable fasteners, cutting and making
good for laying of all cables within plant room of required sizes complete in all
respects.complete. Lot 1
5 Supplying, installation and jointing of MS conduits on surface or concealed complete
with MS junction boxes, cover plates, MS bends, GI saddles, base and other
accessories all made in MS with Giscrews as required to complete the job. Exposed
conduiting shall be painted with red enamel paint for identification.
a) 25 mm dia. Lot 1
6 Supply and fixing of 8 SWG bare copper wires of required sizes including all necessary
and effecting proper connections as required complete in all respects. RM 10
7 Cable Termination:Supply & making end termination with brass double compression glands for the
following PVC insulated, PVC sheathed & armoured 1100 V grade Aluminium cable of
required sizes within oplant room including cost of crimping lugs/ferrules, compression
glands, solder, cable sockets, insulation tape etc complete as required.Lot 2
8 Level Control cum Indicating Panel
Confidential Page 27 of 92 December 2010
-
8/3/2019 Plumbing & Firefighting Enq. for Rapid Metro at Gurgaon.
28/94
Belvedere Station Rapid Metro Rail Gurgaon Limited
Schedule of Qunatity- Elevated Stations
Rate
(Rs.)
Amount
(Rs.)Sl No. Description Unit Quantity
Providing and fixing, installation, testing and commissioning of console type control
cum indicating light panel and all internal wiring. All push buttons shall be provided with
slip-on type lockable arrangement. The panel to house all level and indicating
controllers.
8.1 Raw water filter pumps
To start pump when low level in the domestic water ground tank and to stop pump
when water tank is full. Each 1
8.2 Domestic dual media filter pumpTo start pump when low level in the domestic water over head tank and to stop pump
when water tank is full. Each RO
8.3 Tubewell PumTo start pump when low level in the raw water tank and to stop pump when raw water
tank is full. Each RO
TOTAL FOR P.09
B FIRE SUPRESSION WORKS
F.01 FIRE HYDRANT SYSTEM (Wet-Riser)
1 Providing and fixing M.S. Pipes to I.S.1239 (Heavy C class) painting with one coat of