Products Solutions Services Application / Function Overview Technical data Dimensions Electrical connection Go to shop Contact Accessories Price table Technical Datasheet TD 00029E/24/EN/01.13 Flush-mounted process connections with metal diaphragm Up to four times overload resistant and longterm stability FDA compliant fill oil Materials in contact with process made of 316L SS with a surface finish of Ra ≤ 0.8 µm Complete product information: www.e-direct.us/pmp135 Specs at a glance: Product: Liquids, vapors and gases in the food industry Output: 4 to 20 mA Accuracy: < 0.5 % Product temperature: -13 to +212 °F (-25 to +100 °C), +275 °F (135 °C ) for 1 h Measuring range (limits): 0 to 15 psi (1 bar), 0 to 600 psi (40 bar) Hygienic pressure transmitter Cerabar T PMP135 $ 383.00

Upload: e-direct-division-of-endresshauser

Post on 14-Jul-2015

42 views

Category:

Devices & Hardware


2 download

TRANSCRIPT

Products Solutions Services

Application / FunctionOverview Technical data Dimensions

Electrical connectionGo to shopContactAccessories Price table

Technical DatasheetTD 00029E/24/EN/01.13

• Flush-mounted process connections with metal diaphragm

•Up to four times overload resistant and longterm stability

• FDA compliant fill oil•Materials in contact with process

made of 316L SS with a surface finish of Ra ≤ 0.8 µm

Complete product information:www.e-direct.us/pmp135

Specs at a glance:

•Product: Liquids, vapors and gases in the food industry

•Output: 4 to 20 mA•Accuracy: < 0.5 % •Product temperature:

-13 to +212 °F (-25 to +100 °C), +275 °F (135 °C ) for 1 h

•Measuring range (limits): 0 to 15 psi (1 bar), 0 to 600 psi (40 bar)

Hygienic pressure transmitter

CerabarTPMP135

$ 383.00

4 to 20 mA

Power supply(e.g. RN221N)

p

CerabarTPMP135 2Contact

Overview Technical data Dimensions

Electrical connection Accessories Price tableGo to shop

Application / Function

Application The Cerabar T PMP135 is a pressure transmitter designed for measuring absolute and gauge pressures in hygienic applications within in the food processing and pharmaceutical industries.

ApplicationexampleFunction The process pressure acting on the metallic separating diaphragm of the sensor is transmitted to a resistance bridge via a fill fluid. The change in the output voltage of the bridge is proportional to the pressure and can be measured directly.

Cerabar T pressure transducer with 4 to 20 mA output and auxiliary power supply, such as RN221N.

CerabarTPMP135 3Contact

Application / FunctionOverview Dimensions

Electrical connection Accessories Price tableGo to shop

Technical data

Technicaldata

OutputOutput signal 4 to 20 mALoad RB ≤ (US - 12 V)/0.02 A (US = power supply)

AccuracyNon-linearity ≤ 0.5 % including hysteresis and non-

reproducibilityReference operating conditions

As per DIN IEC 60770, T = 77 °F (25 °C)

Effect of ambient temperature

In relation to nominal valuezero point: typ. 0.2 % of URL/10 K;Range: typ. 0.2 % of URL/10 K

Long-term drift ≤ 0.15 % per year

Operating conditionsMaterial temperature -13 to +212 °F (-25 to +100 °C),

+275 °F (135 °C) for 1 hAmbient temperature -13 to +158 °F (-25 to +70 °C)

Ex i: -13 to +149 °F (-25 to +65 °C)Storage temperature -40 to +185 °F (-40 to +85 °C)Climate class 4 Z: with Z = 158 °F (70 °C) as per VDI/VDE

3540Mounting position Any orientation. Orientation dependent zero

shift can be corrected using potentiometer adjustments

Degree of protection Plug PG 11 or ½" NPT: IP 65Plug M12×1 when using gauge pressure sensors: IP 65Plug M12×1 when using absolute pressure sensors: IP 68 (1 m (3.3 ft) water column)Cable: IP 68 (1 m (3.3 ft) water column)

Limiting medium pressure range

Maximum overload resistance, refer to measuring range Vacuum resistance up to 10 mbarabs

Vibration resistance 4M5 as per DIN EN 60721-3EMC According to EN 61326

Mechanical constructionProcess connection ½", 1" Clamp; G1A with tapered metallic seal

or with sealing surface for flush-mounted installation

Materials Process connections and diaphragm: 316L SS; wetted surface smoothness: Ra ≤ 0.8 µm; Transmitter housing: 304 SS Cable outer covering: polyurethane (PUR) Fill fluid: Neobee M20

Power supply Ub

Supply voltage 12 to 30 V DCResidual ripple Max. 5 %

ApprovalsEx approval ATEX II 1/2 G EEx ib IIC T6

ATEX II 2 G EEx ib IIC T63A

CerabarTPMP135 4Contact

Application / FunctionOverview Technical data

Price tableGo to shopAccessoriesElectrical connection

Dimensions

Dimensions(ininches) Electricalconnection Accessory:DisplayPHX20 / PHX21

12...30 V

4...20 mA

1+ 2–

1

2

+

Plug ISO 4400/M16 or ½" NPT

1.65

1.65

(Dimensions in inches)

1.89

Technical dataDisplay 4 digits, red LED, loop powered to use in

4 to 20 mA loops, angular connector DIN 43650 7.62 mm (0.3") display height, turnable in angle of 90°

Display range -1 999 to +9 999, programmable via two keysProtection class IP 65Material Plastic PA6 GF30, front screen PMMAVoltage drop ≤ 5 V (equivalent burden of max. 250 Ω)Approval PHX21: ATEX II 2G

1.46

3.11

Ø 1.08

2.05

Plug M16,IP 65

Housing

Installation according to instruction manual.

1.30

1.30

Ø 0.68Ø 0.68

Ø 2.00

Ø 1.71

Ø 2.52

Tri-Clamp 1" to 1½" (ISO 2852)

Process connections

Tri-Clamp 2" (ISO 2852)

M

Ø 2.22

CerabarTPMP135 5Contact

Application / FunctionOverview Technical data Dimensions

Electrical connection AccessoriesGo to shopPrice table

Pricetable

*

Moreproductstocompleteyourmeasuringpoint…

Cerabar T PMP135; Output: 4-20mA SIL Order no. Price/pcs. in USDElectrical Connection Process Connection 1 to 5 6 to 10 11 to 35Plug ISO4400 NPT½, IP65 NEMA4X

Tri-Clamp ISO2852 DN25-38 (1...1½"), 316L, DIN32676 DN25-40, EHEDG, 3A

PMP135-A2G01 435.00 405.00 383.00

Tri-Clamp ISO2852 DN40-51 (2"), 316L, DIN32676 DN50, EHEDG, 3A

PMP135-A2H01 435.00 405.00 383.00

Plug and cable to be ordered as ‘accessory’* Please add code for measuring range.

Accessories Order no. Price/pcs. in USDDisplay PHX20 52022914 222.00Display PHX21 52022915 265.00Weld-in adapter G1, d=60, 316L 52001051 88.00Prices valid until 09.30.2013 in U.S. dollars per unit (not including shipping and applicable sales tax).See Endress+Hauser, Inc. Terms and Conditions of Sale for shipping, tax, and payment terms.

Complete product information:www.e-direct.us/pmp135

Measuring Range

Code Gauge pressure OverloadA1G 0 to 1 bar, 0 to 100 kPa 4 bar, 400 kPaA1H 0 to 1.6 bar, 0 to 160 kPa 6.4 bar, 640 kPaA1N 0 to 2.5 bar, 0 to 250 kPa 10 bar, 1 MPaA1Q 0 to 4 bar, 0 to 400 kPa 16 bar, 1.6 MPaA1R 0 to 6 bar, 0 to 600 kPa 24 bar, 2.4 MPaA1S 0 to 10 bar, 0 to 1 MPa 40 bar, 4 MPaA1T 0 to 16 bar, 0 to 1.6 MPa 64 bar, 6.4 MPaA1W 0 to 25 bar, 0 to 2.5 MPa 100 bar, 10 MPaA1X 0 to 40 bar, 0 to 4 MPa 160 bar, 16 MPaQ4H 0 to 15 psi 60 psiQ4K 0 to 30 psi 150 psiQ4N 0 to 50 psi 240 psiQ4R 0 to 150 psi 600 psiQ4S 0 to 300 psi 1500 psiQ4T 0 to 500 psi 2400 psi

Code Absolute pressure OverloadA2G 0 to 1 bar, 0 to 100 kPa 4 bar, 400 kPaA2H 0 to 1.6 bar, 0 to 160 kPa 6.4 bar, 640 kPaA2N 0 to 2.5 bar, 0 to 250 kPa 10 bar, 1 MPaA2Q 0 to 4 bar, 0 to 400 kPa 16 bar, 1.6 MPaA2R 0 to 6 bar, 0 to 600 kPa 24 bar, 2.4 MPaA2S 0 to 10 bar, 0 to 1 MPa 40 bar, 4 MPaA2T 0 to 16 bar, 0 to 1.6 MPa 64 bar, 6.4 MPaA2W 0 to 25 bar, 0 to 2.5 MPa 100 bar, 10 MPaA2X 0 to 40 bar, 0 to 4 MPa 160 bar, 16 MPaR4H 0 to 15 psi 60 psiR4K 0 to 30 psi 150 psiR4N 0 to 50 psi 240 psiR4R 0 to 150 psi 600 psiR4S 0 to 300 psi 1500 psiR4T 0 to 500 psi 2400 psi

*

CompactthermometerEasytemp TMR35

PointlevelswitchLiquiphant T FTL20H

FieldindicatorRIA16

Application / FunctionOverview Technical data Dimensions

Electrical connectionGo to shopContactAccessories Price table

Contact

E-directEndress+Hauser, Inc.2350 Endress PlaceGreenwood, IN 46143

Direct order

Internet www.e-direct.usby phone 888- EH-DIRECT

(343-4732)per Fax 317-535-8498E-Mail [email protected]