power control agc1

Upload: surya892

Post on 13-Apr-2018

239 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Power Control AGC1

    1/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC)

    1

    Power System Control and Operation:

    Automatic Generation Control (AGC)

  • 7/27/2019 Power Control AGC1

    2/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 2

    Outline

    Read chapter 11: 11.0-11.6.

    Homework: 11.2, 11.6

    Automatic Generation Control (AGC)

    System modeling: control block diagram

    AGC for single generator

    AGC for 2 generators

    AGC for multi generators

    Area Control Error (ACE)

  • 7/27/2019 Power Control AGC1

    3/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 3

    Purpose of AGC

    To maintain power balance in the system.

    Make sure that operating limits are not

    exceeded:-

    Generators limit

    Tie-lines limit

    Make sure that system frequency is constant

    (not change by load).

  • 7/27/2019 Power Control AGC1

    4/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 4

    Overview of AGC

    Load is always changing.

    To maintain power balance, generators need to

    produce more or less to keep up with the load.

    When Gen < Load (Gen > Load), generatorspeed and frequency will drop (rise).

    => We use this generator speed and frequency

    as control signals!

  • 7/27/2019 Power Control AGC1

    5/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 5

    3 Components of AGC

    Primary control

    Immediate (automatic) action to sudden change of load.

    For example, reaction to frequency change.

    Secondary control

    To bring tie-line flows to scheduled.

    Corrective actions are done by operators.

    Economic dispatch

    Make sure that the units are scheduled in the most economical

    way.

    This presentation covers only primary and secondary

    control of AGC.

  • 7/27/2019 Power Control AGC1

    6/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 6

    AGC for Single Area

    System Modeling

    Single Generator

    Multi Generators, special case: two

    generators

  • 7/27/2019 Power Control AGC1

    7/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 7

    System Modeling: Turbine-Governor Model

    Small signal analysis model, relating mechanical powerto the control power and the generator speed.

    Where = Small change in control setting power

    = Small change in governor synchronous speed

    = Small change in mechanical output power

    = Regulation constant

    = Transfer function relating mechanical power to control signals

    CP MP

    TG

    sTsT 11

    1

    sGM

    R

    1

    +

    -

    C

    P

    MP

    sGM

    R

  • 7/27/2019 Power Control AGC1

    8/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 8

    Speed-Power Relationship

    From synchronous turbine-governor: small

    signal analysis model,

    At steady state (s 0, 1), we have

    RPsGPCMM

    1

    R

    PPCM

    1

    sGM

  • 7/27/2019 Power Control AGC1

    9/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 9

    Static Speed-Power Curve

    From,

    Primary control: Immediate

    change corresponding tosudden change of load

    (frequency)

    Secondary control: Change in

    setting control power to

    maintain operating frequency. The higher R (regulation), the

    better.

    R

    PPCM

    1

    Slope = -R

    1MP 2MP1CP 2CP

    MP

    = =

    1

    2

    0

  • 7/27/2019 Power Control AGC1

    10/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 10

    System Modeling: Generator Model

    This model relates mechanical power to power

    angle, ignore change of voltage.

    Note that power angle is not voltage angle ( )

    TDsMs 21

    MP

    G iiV +

    -ii

    E

    sjX iiV

    ii

  • 7/27/2019 Power Control AGC1

    11/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 11

    AGC for Single Generator

    Since , we can draw

    closed loop power control system as below. 0

    CP

    TG sTsT 11

    1

    R

    1

    +

    -

    TDsMs 2

    1MP

    s

  • 7/27/2019 Power Control AGC1

    12/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 12

    AGC for Multi Generators

    Consider effect of

    power flows in transmission lines, and

    loads at each bus

    to mechanical power of each generator. This analysis assumes that every bus is a

    generator bus.

  • 7/27/2019 Power Control AGC1

    13/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 13

    Power Balance Equation at Each Bus

    At each bus,

    Where = Generator i power

    = Load power at bus I

    = Power flow from bus i

    Consider small changes,

    iDiGi PPP

    GiP

    DiP

    iP

    iDiGi PPP

    2GP

    G1 G2

    1GP

    3DP

    1DP

    2V

    1V

    3V

    G3

    2DP

    3GP

    2P1P

  • 7/27/2019 Power Control AGC1

    14/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 14

    Load Power Equation ( )

    Assume that

    Where = Small change of load input

    = Small change of load power

    = Small change of voltage angle

    Substitute in power balance equation,

    We have

    LiiLiLiiLiDi PDPDP

    DiP

    i

    LiP

    DiP

    iLiiLiGi PPDP

    iDiGi PPP

  • 7/27/2019 Power Control AGC1

    15/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 15

    Mechanical Power of Each Generator ( )

    Linearized equation relating mechanical power

    to generator power and generator speed.

    Where = Small change in mechanical power of generator i

    = Small change in electric power of generator i

    = small change in internal voltage angle of generator i

    From,

    We have

    GiiiiiMi PDMP

    MiP

    GiP

    i

    GiP

    iLiiLiGi PPDP

    iLiiLiiiiiMi PPDDMP

  • 7/27/2019 Power Control AGC1

    16/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 16

    Generator Block Diagram

    From,

    We can write

    where

    iLiMi

    ii

    i PPP

    DsM

    ~

    1

    iLiiLiiiiiMi PPDDMP

    Liii DDD

    ~

    ii DsM

    1

    s

    1+-

    -

    MiP

    LiP

    i

    i

    iP

  • 7/27/2019 Power Control AGC1

    17/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 17

    AGC for Multi Generators: Block Diagram

    sGMi

    iR

    1

    +

    -

    sGPi

    iMiP

    LiP

    CiP

    iP

    +

    -

    -

    ii

    Pi

    DsMsG ~

    1

    TiGi

    Mi

    sTsTsG

    11

    1

    Change in tie-line

    power flow

  • 7/27/2019 Power Control AGC1

    18/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 18

    Tie-line Model ( )

    From power flow equation,

    Approximate at normal operating condition, we

    have

    Then, for small change,

    Where is called stiffness or synchronizing power coefficient

    iP

    n

    k

    kiikkii BVVP

    1

    sin

    n

    k

    kiiki BP

    1

    n

    k

    kiik

    n

    k

    kiiki TBP

    11

    ikT

  • 7/27/2019 Power Control AGC1

    19/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 19

    Tie-Line Block Diagram

    From and

    We have,

    n

    k

    kiiki TP

    1

    s

    1

    n

    k

    ki

    ik

    i

    s

    TP

    1

    s1

    ++

    +

    ikT

    iP

    ii

    +

    - +

    - +

    -

    k

  • 7/27/2019 Power Control AGC1

    20/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 20

    AGC for 2-Generator: Block Diagram

    sGM2

    2

    1

    R

    +-

    sGP222MP

    2LP

    2CP212 PP

    +

    -

    -2

    s

    -

    sGM1

    1

    1

    R

    +

    -

    sGP1

    1

    1MP1LP

    1CP

    121 PP

    +

    -

    -

    1

    s

    +

    -1

    12T

    Load

    Frequency 2

    Different phase angle Transfer power 12

    Frequency 1

    Governor 2 sense

    speed , try to

    mechanical power

    Governor 1 sensespeed , try to

    mechanical power

    Steady state: New

    (lower) system

    Frequency

  • 7/27/2019 Power Control AGC1

    21/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 21

    AGC for 2-Generator:

    Static Speed-Power Curve

    Load increases.

    Frequency drops.

    Steady state is reached

    when frequency of bothgenerators is the same.

    1MP 2MP

    MP

    1

    2

    0

    + = Change in

    total load

    1MP 2MP

  • 7/27/2019 Power Control AGC1

    22/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 22

    Steady State Frequency Calculation:

    2 generators

    From

    Consider the frequency at steady state,

    But, , ,and

    Then,

    iLiiiiLiiiiiMi PPDPPDMP ~~

    linetieLM PPDP 1111

    ~

    linetieLM PPDP 2222 ~

    21 1

    1

    1

    RPM

    2

    2

    1

    RPM

    21

    21

    21

    11~~

    RRDD

    PP LL

  • 7/27/2019 Power Control AGC1

    23/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 23

    Note that

    In single area- multi generators case, we have

    not discuss how to systematically bring back the

    new steady state frequency by adjusting control

    power. We will discuss this in the following section.

  • 7/27/2019 Power Control AGC1

    24/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 24

    AGC for Multi Areas

    Simplified Control Model

    Area Control Error (ACE) Example 11.5

  • 7/27/2019 Power Control AGC1

    25/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 25

    Simplified Control Model

    Generators are grouped into control areas.

    Consider An area as one generator in single area, and,

    Tie-lines between areas as transmission linesconnecting buses in single area.

    We can apply the same analysis to multi-area!!

    However, we have to come up with frequency-

    power characteristics of each area. Actual application of this model is for power pool

    operation.

  • 7/27/2019 Power Control AGC1

    26/35

    ELEN 460:Power System Control and Operation:Automatic Generation Control (AGC) 26

    Power Pool Operation

    Power pool is an interconnection of the powersystems of individual utilities.

    Each company operates independently, BUT,

    They have to maintain contractual agreement about power exchange of

    different utilities, and,

    same system frequency.

    Basic rules Maintain scheduled tie-line capacities.

    Each area absorbs its own load changes.

  • 7/27/2019 Power Control AGC1

    27/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 27

    AGC for Multi Areas

    During transient period, sudden change of load causes

    each area generation to react according to its frequency-

    power characteristics.

    This is called primary control.

    This change also effects steady state frequency and tie-

    line flows between areas.

    We need to

    Restore system frequency,

    Restore tie-line capacities to the scheduled value, and,

    Make the areas absorb their own load.

    This is called secondary control.

  • 7/27/2019 Power Control AGC1

    28/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 28

    Area Control Error (ACE)

    Control setting power of each area needs to be

    adjusted corresponding to the change of

    scheduled tie-line capacity and change of

    system frequency. ACE measures this balance, and is given by,

    for two area case.Where = Frequency bias setting of area i (>0) and

    1121 BPACE

    2212 BPACE

    iB

    i

    Lii

    RDB

    1

  • 7/27/2019 Power Control AGC1

    29/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 29

    ACE: Tie-Line Bias Control

    Use ACE to adjust setting control power, , of

    each area.

    Goal:

    To drive ACE in all area to zero. To send appropriate signal to setting control power,

    Use integrator controller so that ACE goes to

    zero at steady state.

    CiP

    CiP

  • 7/27/2019 Power Control AGC1

    30/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 30

    AGC for 2-Area with Tie-line Bias Control:

    Block Diagram

    sGM2

    2

    1

    R

    + -

    sGP2

    22MP

    2LP

    2CP212 PP

    +

    -

    - 2s

    -

    sGM1

    1

    1

    R

    +-

    sGP1

    1

    1MP1LP

    1CP

    121 PP

    +

    -

    -

    1

    s

    +

    -112T

    -1

    +

    +

    +

    +

    s

    K2

    s

    K1

    1

    2

    12P

    21P

    1B

    2B

    1ACE

    2ACE

    Load 2

    Frequency 2

    Different phase angle Transfer power 12

    Frequency 1

    Governor 2 sense

    speed , try to

    mechanical power

    Governor 1 sense

    speed , try to

    mechanical power

    ACE 2 < 0

    ACE 1 = 0

    Setting control power 2

    Frequency 2

    Different phase angle

    Governor 2 sense

    speed , try to

    mechanical power

    Transfer power 12

    Governor 1 sense

    speed , try to

    mechanical powerFrequency 1

    Steady state:

    Maintain Frequency

    Set control power 2 > 0

  • 7/27/2019 Power Control AGC1

    31/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 31

    AGC for 2-Area with Tie-line Bias Control :

    Static Speed-Power Curve

    Load in area 2 increases.

    Frequency of both area

    drops.

    ACE makes Control

    power of area 2

    increases.

    Steady state is reached

    when frequency is back

    at the operating point andgenerator in area 2 take

    its own load.

    1MP 2MP

    MP

    1

    2

    0

    + = Change in load 2

    1MP 2MP

    2

    1MP

    2MP

  • 7/27/2019 Power Control AGC1

    32/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 32

    Example 11.5

    Two-area system,

    Find change in frequency, ACE, and appropriatecontrol action.

    A B

    MW100000 A

    L

    A

    G PP MW000,1000

    B

    L

    B

    G PP

    sec/MWperrad015.0A

    R sec/MWperrad0015.0B

    R0 BL

    A

    L DD

    MW10 ALP

  • 7/27/2019 Power Control AGC1

    33/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 33

    Example 11.5: Frequency Calculation

    From,

    And,

    And,

    We have,

    21

    AB

    A

    LAB

    A

    LA

    A

    L

    A

    M PPPPDP

    BABA

    B

    LB

    B

    L

    B

    M PPPDP

    A

    A

    MR

    P1

    B

    B

    MR

    P1

    secperrad0136.0

    0015.0

    1

    015.0

    1

    10

    11

    BA

    AL

    RR

    P

  • 7/27/2019 Power Control AGC1

    34/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 34

    Example 11.5: ACE Calculation

    First, find from

    Then,

    MW9091.00136.0015.0

    11

    A

    A

    M

    RP

    MW091.9 A

    L

    A

    MABAB

    A

    L

    A

    M PPPPPP

    MW091.9 ABBA PP

    ABP

    MW100136.0015.01091.91

    A

    ABA

    RPACE

    MW00136.00015.0

    1091.9

    1

    B

    BAB

    RPACE

  • 7/27/2019 Power Control AGC1

    35/35

    ELEN 460:Power System Control and Operation:

    Automatic Generation Control (AGC) 35

    Example 11.5: Control Action

    ACE indicates each area action to the change of

    load.

    ACE of area B is zero, this means that nothing

    should be done in area B. ACE of area A < 0, this means that area A

    should increase the setting control power by

    (-10) = 10 MW to cover its own load.