power engineering international - article on swas

Upload: rikumohan

Post on 14-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Power Engineering International - Article on SWAS

    1/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    1 of 7 6/9/09 7:46 PM

    SAVE THIS | EMAIL THIS | Close

    A measure of success in the fight against corrosion

    Dissolved impurities in water and steam can cause damaging corrosion and deposition in modern powerplants operating at increasingly high temperatures and pressures. To control these impurities, it is first

    necessary to measure them accurately.

    Nitin Kirloskar, Forbes Marshall Pvt Ltd, India

    In countries such as India and China, which are still growing despite the economic slowdown, power

    generation or, to be more precise, the quality of power generation matters a lot.

    One way to improve power generation would be to increase generation capacity. Another would be to

    save power by operating power plants more efficiently, reducing outages and loss of capacity. The latterstrategy sounds more economical, as the cost of maintaining the health of a power plant is far lower thanthat of continually adding capacity.

    Click here to enlarge image

    A steam and water analysis system isvital in the battle to maintain steamand water purity, and keep corrosion

    at bay.

    Corrosion and deposition play a major role in destabilizing power plants, reducing both power generationefficiency, leading to reduced output, and the effective life of a power plant.

    Maintaining water and steam quality at ultra-pure levels is one of the best ways to reduce the effects ofcorrosion and deposition. A water quality management system is therefore vital for any power plant

    running on steam.

    In such a plant, impurities such as dissolved oxygen, silica, phosphate, sodium, chlorides and many

    others, slowly eat into the boiler tubes/super-heaters and, more importantly, the turbines. Theseimpurities ultimately result in corrosion and deposition, which can lead to turbine failures and boiler

    shutdowns, and, in extreme cases, permanent damage to equipment. The cost of unplanned shutdownscan be high. In fact, more than 50 per cent of unplanned shutdowns are due to inadequate analysis andcontrol of impurities, and the corrosion and deposition resulting from it.

    Corrosion, if not monitored properly, can result in a loss in turbine efficiency of 10 per cent. This means arecurring loss of 10 per cent of revenue. If not enough attention is paid to the corrosion/deposition

  • 7/27/2019 Power Engineering International - Article on SWAS

    2/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    2 of 7 6/9/09 7:46 PM

    problem, this loss can be compounded by damages to the turbine or even turbine failure.

    Corrosion and deposition have similar effects to those of cholesterol levels in our bodies. Our cholesterol

    levels need to be controlled, and to do this a proven, reliable and accurate method of measuring andmonitoring cholesterol levels is required. It is the same with deposition and corrosion. More specifically a

    reliable and accurate method of online analysis is needed. Good online analyzers supported by awell-engineered sample conditioning system is the ideal solution. A sample conditioning system andonline analyzer system is called a steam and water analysis system (SWAS). With a well-engineered

    SWAS, it is possible to monitor various dissolved impurities that damage the turbines and other steamequipment to parts per billion (ppb) levels continuously and online.

    Forbes Marshall is one of the largest manufacturers of SWAS packages. The companys integratedsample conditioning and analysis system includes conditioning equipment and world class onlineanalyzers.

    Any good SWAS package depends on expertise in steam engineering as well as control instrumentation.Forbes Marshall can provide this expertise. With an installed base of over 350 SWAS packages, the

    company has solutions for the most complex steam and water analysis requirements.

    Water quality improvements

    In the power industry, control of water purity is a prerequisite for the safe and efficient operation of the

    boiler plant. Typically, up to 20 different samples per boiler unit are taken from various parts of thesteam/water cycle.

    Sample conditions in todays supercritical boilers and plant, with capacities of 800 - 1000 MW, can be assevere as 200 bar at 560 C, and equipment must be of highest quality and integrity. The equipmentused varies in complexity from a single sample probe with cooler, pipe work and valves for manual

    sampling, to fully automatic multi-stream sample conditioning consoles for centralized monitoring.

    Water and steam samples are

    analyzed using a dry-panel analyzer.

    In todays power industry, online monitoring of various boiler parameters has become common. In the

    past, these parameters were monitored in laboratories using grab samples, a method that was errorprone due to contamination. However, online analyzers have eliminated most of these errors.

    With the advent of online analyzers, it became essential to condition the sample, because the sensorsused for online analysis were not able to handle the water/steam sample at high temperatures orpressures. To maintain consistency, it was made mandatory to cool the sample to 25-40 C.

    The next development in analyzers was temperature compensation. With this, it became easier tomonitor a parameter at any temperature and interpret it as if it was at a particular temperature, say 25

  • 7/27/2019 Power Engineering International - Article on SWAS

    3/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    3 of 7 6/9/09 7:46 PM

    C.

    Today we have state-of-the-art equipment to take care of sampling, sample conditioning and sample

    analysis. The most popular equipment for online analysis is the SWAS. The SWAS package consists oftwo parts: the sample conditioning unit and the analysis system. Most of the sample is handled in the

    former. The analysis of the samples is done in the latter, which mostly handles the signals and givesvarious outputs, for controls or alarms, for example.

    Sample conditioning system

    The online analyzers used for analyzing steam or water only work with the required accuracy andreliability if the input conditions are stable. The sensors are delicate and can only handle the water/steamsamples at particular temperatures and pressures. This means we need to control and stabilize the

    temperature, pressure and flow conditions of the sample using a well-engineered sample conditioningsystem.

    To accurately and reliably analyze a steam sample, it is important that the sample is withdrawn from theprocess, transported, conditioned, analyzed and disposed of properly all without changing itscomposition.

    Probably the most common problem in sample system design is the lack of realistic information aboutthe properties of the process at the sampling point. Also, while the sample is being conditioned, utmost

    care has to be taken to see that the sample does not become contaminated and is truly representative.The condition of the sample reaching the analyzer should match exactly with that at the tapping point.

    Unless this condition is met, we might end up with highly accurate analysis of the wrong sample.

    The design of a sampling system depends on a variety of factors, such as conditions to which thesampling system will be exposed. Materials selection, mechanical design, thermodynamic calculations

    and so on greatly depend on these conditions. Similarly, the end users requirements, space constraints,and the consultants design philosophy have design implications. Systems can be completely enclosed or

    placed in walk-in cabinets, or arranged in open-frame, free-standing configurations.

    Sample extraction

    An important aspect of accurate steam analysis is sample extraction. It is vital to choose the correct

    sample extraction probe. The validity of the analysis will undermined if representative samples are nottaken. Being directly attached to the process pipe work, the probe may be subject to severe conditions,and for most applications, this item is manufactured to the stringent codes applicable to high-pressure,

    high-temperature pipework.

    The precise type of probe to be used will depend on the process stream parameter to be measured, the

    required sample flow rate and the position of the sampling point in the system. The guiding principle insample extraction probe design is that the steam must enter the probe at the same velocity as thesteam flowing in the pipe from where steam is extracted.

    Generally, when sampling from pipes for suspended solids an isokinetic probe is used. This class of probeis designed to ensure that the sample enters the port(s) at the same velocity as the main process

    stream, reducing kinetic segregation of suspended particles to a minimum. A more important factor in

    obtaining representative samples is the maintenance of a sufficiently high transport velocity in thesample line to prevent hideout of the suspended species. The isokinetic probe is the right choice forthese applications. Isokinetic probes may be of single port, multiport or capillary types, and should beinstalled with the port(s) facing upstream into the oncoming flow.

    Sample cooling

    The sample coolers form the heart of the sampling system. The preferred design these days is a doublehelix coil-in-shell-type design, as this provides the required compactness, good approach temperature

    and optimum cooling water consumption. Forbes Marshall provides an optimized cooler that offers thebest combination of low-approach temperature and minimal cooling water consumption, and thus thebest performance. The design and performance of the cooler is validated by the Indian Institute of

    Technology.

  • 7/27/2019 Power Engineering International - Article on SWAS

    4/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    4 of 7 6/9/09 7:46 PM

    Click here to enlarge image

    A chiller provides cooling, bringing

    analysis samples down to atemperature where they can be

    analyzed.

    Safety is another important aspect of good sample cooler design. The traditional stainless steel AISI 316

    coils are susceptible to failure if the cooling water is not of the required quality and contains chlorides.

    Forbes Marshall provides a built-in shell pressure relief valve on its coolers, making it extremely safe foroperators.

    Sample filtering

    The sample conditioning system delivers the sample under controlled temperature, pressure and flowconditions to the online analyzers. The majority of online analyzers are for dissolved solids or volatile

    species, and the presence of unwanted particulate matter can damage the instrumentation and certaincomponents in the sampling system. To avoid blockages in the sample path, a small high-pressure filterwith a sintered stainless steel element is required. However, for plants with a high particulate burden,

    larger stainless or alloy steel high-pressure Y-filters may be necessary. These can be supplied withintegral valves to permit regular cleaning without disassembly.

    Pressure conditioning

    An important aspect of sample conditioning design is ensuring that analyzers are never subjected to apressure higher than the safe limit. With inlet pressures conditions as high as 250 bar, this is a serious

    safety consideration. Pressure reduction is not enough, as sample pressures may fluctuate, andregulation is required.

    A pressure regulator that can maintain the downstream pressure at a constant set limit, irrespective ofupstream fluctuations, is ideal. On closing fully, the regulator should ensure zero flow condition and beable to withstand the total upstream pressure. A safety valve built into this pressure regulator makes

    the unit safe for operators as well as analyzers downstream. For high-pressure reduction and regulation,piston-type pressure regulators are needed. For low-pressure reduction and regulation, spring-loadeddiaphragm-type pressure regulators should be considered.

    Back-pressure regulation

    Just as the pressure regulator regulates the downstream pressure constant, irrespective of upstreamfluctuations, the back-pressure regulator maintains the upstream pressure constant. This is needed to

    maintain the flow characteristics of sample flowing to the analyzers. One of the important requirementsof sampling system design is sample flow regulation. The back-pressure regulator ensures priority flow to

    all analyzers and maintains the flow characteristics of the sample at a constant level.

    High temperature and pressure protection

    During the operation of a sample conditioning system, high temperature and/or high pressure alarm

    conditions may be encountered. For example, there can be a cooling water failure or for some reasonsample flow may increase, leading to a high temperature/pressure sample reaching the components and

  • 7/27/2019 Power Engineering International - Article on SWAS

    5/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    5 of 7 6/9/09 7:46 PM

    coolers downstream. As explained earlier, online analyzers have very delicate sensors and must beprotected from high-temperature samples by a reliable shut-off and alarm system. Temperature sensing

    can be done with electrical contacts on the outlet temperature gauge or using a dedicated samplethermo switch. Pressure sensing can be achieved using a pressure switch. The electrical output of bothcan be used for sample shut off, using a solenoid valve. This arrangement should be able to withstand

    the high temperatures of a sample in alarm condition, which can be as high as 250 C.

    Cation column

    The principle of cation exchange is the same as any ion exchange process. This process is used in any

    water demineralization plant. The demineralization plant uses anion exchanger and cation exchangers toremove anions and cations from the water, leaving it free from salts and dissolved impurities.

    The cation exchange principle alone is used to eliminate the masking effects of chemicals such asammonia or dissolved amines, as explained in detail below.

    The conductivity measurement is a blind method of crosschecking whether dissolved impurities arepresent in a water sample or whether it is ultra-pure. The ultra-pure water is poorly ionized and, hence,has extremely low conductivity. The moment one adds even a small amount of salt (say NaCl), the

    conductivity shoots up drastically. This can even happen with the addition of desired chemicals. Thetypical reaction on the cation column will be:

    1) Na(+) + Cl(-) => H(+) ions => HCl + Na(+) ions2) NH4(+) + OH (-) => H(+) ions => H2O + NH4(+) ions

    In the cation columns, resins are present, charged with H(+) ions. These ions replace the +ve ions ofany salt or dissolved impurity as it dissociates in water.

    In case (1), the cations replace Na ions and the outcome is HCl, that is the corresponding acid. In case(2), the cations replace NH4 ions and the outcome is pure water (H2O). The conductivity in case (1) isthree times that imparted by the salt (here NaCl), while in case (2), the conductivity imparted by the

    chemical (here NH4OH) gets eliminated, as the outcome is pure H2O. Thus the cation conductivitymeasurement eliminates the masking effects of known/desired chemicals.

    The cooling question

    Systems are designed to condition samples to the temperature required by the analyzers. The questionis: what is this temperature? The temperature should be 25+1 C, as analysis needs to be done at this

    temperature.

    There are two ways of approaching this issue. One way is to cool the sample with the available cooling

    water temperature (cooling water is generally available at 32-36 C if it is coming from cooling towers).With this cooling water, one can cool the sample to (say) 40 C. This sample can be fed to analyzers,which in turn sense it and interpret the results as if the sample was at 25 C. A temperature

    compensation algorithm is used for this purpose inside the analyzer.

    An alternative option is to cool the sample to 25+1 C. Some users and consultants believe in this

    method. But if we are investing in a sampling system for conditioning the sample, why not do the wholejob in the sampling system itself? Chilled water becomes necessary in such a case. This is becausecooling water available onsite is not capable of cooling the sample to 25+1 C. Normal practice is to use

    available cooling water to extract as much heat as possible from the sample and use chilled water toremove the remaining fraction of heat. Thus it becomes two-stage sample cooling. In the first stage,

    available cooling water is used, and in the second stage, chilled water.

    A chiller with an isothermal bath is a compact unit. The chiller provides the chilled water to a container,

    the isothermal bath, where the sample coils are immersed, thus avoiding the use of individual heatexchangers. A SWAS vendor who can manufacture chillers/isothermal baths units is an ideal choice forbuyers looking for a single point of responsibility arrangement.

    Reliable and accurate analysis

    The ultimate purpose of buying any sampling system is to achieve reliable and accurate analysis. Theanalyzers are therefore the most important elements of any SWAS package. The analysis parameters

    that are most commonly monitored in power stations are conductivity, pH, dissolved oxygen, silica,

  • 7/27/2019 Power Engineering International - Article on SWAS

    6/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    6 of 7 6/9/09 7:46 PM

    hydrazine and sodium. Others include alkalinity, hardness, calcium, chloride, phosphate, dissolved ozoneand so on. Let us look the significance of some of these parameters.

    The power of hydrogen

    The steam that goes into the power generating turbines has to be ultra-pure. Thus the water used forgenerating this steam should be in its purest form. Monitoring the pH value of the feed water gives a

    direct indication of the alkalinity or acidity of this water. The pH scale goes from zero to 14: zeroindicating strong acidity and 14 indicating strong alkalinity. The ultra-pure water is pH7; this issupposed to be neutral. Unfortunately, it never remains neutral and tends to become acidic, due to the

    ingress of various impurities. Acidic water causes corrosion, especially under high temperatures andpressures. In a steam circuit it is normal practice to keep the pH value of the feed water slightly alkalineto prevent corrosion of pipework and other equipment. In the steam circuit, pH should be monitored in

    the drum water, high-pressure heaters, make-up condensate, plant effluent, condenser and coolingwater.

    Conductivity test

    Conductivity measurements can detect salt contamination from the atmosphere or due to leakages inheat exchangers in water and steam. The conductivity of ultra-pure water is close to zero (say 1-2

    microsiemens/cm), but with the addition of even 1ppm of salt, the conductivity can shoot up to morethan 100 microsiemens/cm. Thus conductivity can give a quick indication of a plant malfunctioning orleakages. Typical points in the steam circuit where conductivity should be monitored include the drum

    steam, drum water, high-pressure heaters, low-pressure heaters, condenser, plant effluent,demineralization plant, and the make-up water to the demineralization plant.

    The biggest enemy

    The presence of silica in the steam and water circuits of power generation plant is associated with anumber of problems in the superheater and turbine sections. Silica present in water or steam neverexists in a completely dissolved form. Some part of it is always undissolved. The solubility of silica in

    stream increases with pressure. The presence of silica in the steam can lead to deposition in superheatertubes and on the turbine blades. Small deposits on the turbine blades can result in a loss of efficiency,

    while larger deposits can cause permanent mechanical damage.

    To ensure that the turbines operate at maximum performance, continuous monitoring of silica in steam,boiler water and feed water is highly recommended. The monitoring of anion and mixed-bed ion

    exchanges safeguards and optimizes the operation of demineralization plant. Silica analysis is required atthis stage also.

    The typical points in steam circuits where silica analysis is required, are the high-pressure andlow-pressure turbines, drum steam, drum water, CEP discharge, make-up water, demineralization plant

    and the supply water to the demineralization plant.

    The silica that may appear at the boiler drum can be eliminated by Blowdown action in the case of

    subcritical boilers. Unfortunately, with supercritical boilers, which are of once-through type, there is noboiler drum. Hence, controlling silica and removing it at the demineralization plant level becomes of the

    utmost importance.

    Oxygen control

    Within a temperature range of 200-250 C (feed water), dissolved oxygen causes corrosion incomponents and piping (condensers, low-pressure preheaters, feed-water tanks, high-pressure

    preheaters and economizers. The resulting pitting may eventually cause puncturing and failures.Dissolved oxygen also promotes electrolytic action between dissimilar metals, causing corrosion andleakage at joints and gaskets.

    To minimize corrosion under alkaline operating conditions, mechanical de-aeration and chemicalscavenger additives are used to remove the dissolved oxygen. An analytical check of process efficiency is

    then essential.

    Dissolved oxygen monitoring is imperative in power stations using neutral or combined operating

    conditions (pH7.0-7.5 or 8.0-8.5). The typical points in steam circuit where dissolved oxygen monitoring

  • 7/27/2019 Power Engineering International - Article on SWAS

    7/7

    Power Engineering International - A measure of success in the figh... http://pe.articles.printthis.clickability.com/pt/cpt?action=cpt&titl...

    7 of 7 6/9/09 7:46 PM

    is required are the condenser outlet, low-pressure heaters and economizer inlet.

    Hydrazine measurement

    The use of hydrazine as an oxygen scavenger and a source of feed water alkalinity has well-known

    advantages: it prevents frothing in the boiler and minimizes deposits on metal surfaces.

    As well as scavenging oxygen, hydrazine helps maintain a protective magnetite layer over steel surfaces

    and controls feed water alkalinity to prevent acidic corrosion. The nominal dosage rate for hydrazine infeed water is about three times its oxygen level. Underdosing of hydrazine leads to increased corrosion.

    The monitoring of dissolved oxygen levels is insufficient to control the optimum concentration, because itcant measure excess hydrazine. Typical points in steam circuit where hydrazine monitoring is requiredare the re-heaters, economizer inlet and low-pressure heaters.

    Sodium attack

    The measurement of sodium is an effective way of assessing the condition of a high-purity water/steamcircuit. The presence of sodium signals contamination with potentially corrosive anions, (chlorides,

    sulphates etc.). Under conditions of high pressure and temperature, neutral sodium salts exhibitconsiderable steam solubility. NaCl and NaOH, in particular, are associated with stress corrosion crackingof boiler and superheater tubes.

    The measurement of sodium, acting as a carrier of potentially corrosive anions, is now recognized as aneffective means of monitoring steam purity.

    The ubiquitous character of sodium in the environment makes it useful in spotting leak conditions in thecircuit, particularly in the condenser section. Typical points where sodium monitoring is required, are the

    demineralization plant, condensate pump, condenser, drum steam and demineralization plant output.The monitoring of other parameters, such as alkalinity, hardness, calcium, chloride, phosphate anddissolved ozone, is also required, depending on the size of the plant and the quality of water and steam

    equipment.

    Measurement and control

    With increasingly high temperatures and pressures it is important to control key dissolved impurities inthe feed water online. To get effective, reliable and accurate measurements, select a supplier who hasexpertise, a proven track record, the required manufacturing and testing set-up, plus domain knowledge

    in both steam engineering and control instrumentation.

    Power Engineering InternationalMay, 2009

    Find this article at:http://pepei.pennnet.com/display_article/362115/17/ARTCL/none/none/1/A-measure-of-success-in-the-fight-against-corrosion

    SAVE THIS | EMAIL THIS | Close

    Check the box to include the list of links referenced in the article.

    Copyright PennWell Corporation.