Power HT

Floor standing gas high efficiency condensing boilers

Page 2: Power Ht 0910

are Baxi strategic aims and

the awarded certifications

ensure compliance with the

specific regulations

The Company assumes no responsibility for any possible contents mistakes, and reserves the right to make changes in products, due to technical or commercial demands, at any time without notice. Baxi S.p.A. 09-10 (E)

36061 BASSANO DEL GRAPPA (VI) Italy Via Trozzetti, 20Tel. +39 0424 517111 - Fax: +39 0424 [email protected] www.baxi.it

Power HT 1.230 Power HT 1.280 Power HT 1.320

Nominal heat output kW 215,0 260,0 305,0

Maximum heating heat output (80/60°C) kW 210,5 254,8 294,0

Maximum heating heat output (50/30°C) kW 229,8 278,2 321,3

Minimum heat output (80/60°C) kW 33,5 40,2 45,9

Minimum heat output (50/30°C) kW 37,4 44,9 51,4

Energetic efficiency 92/42/CEE

Average efficiency (DIN 4702-T8) (75/60°C) % 106,6 106,7 106,7

Average efficiency (DIN 4702-T8) (40/30°C) % 109,6 109,7 109,7

Nominal efficiency (80/60°C) % 97,9 98,0 98,0

Nominal efficiency (50/30°C) % 106,9 107,0 107,1

Efficiency at 30% % 105,4 105,6 105,7

Minimum flow on the exchanger (80/40°C) l/h 4555 5515 6360

NOx Class (EN 483) 5 5 5

Minimum working temperature °C -5 -5 -5

Water content lt 34,0 42,5 51,0

Condensation quantity (50/30°C) l/h 25,3 30,7 35,4

Maximum working pressure bar 6 6 6

Maximum flow temperature °C 90 90 90

Flue ducts max length m 40 (Ø200) 40 (Ø200) 40 (Ø200)

Maximum flue mass flow rate kg/s 0,097 0,118 0,136

Minimum flue mass flow rate kg/s 0,015 0,018 0,0207

Maximum flue temperature (80/60°C) °C 61 60 60

Residual fan prevalence Pa 100 100 100

Supply air flow @ Qn m³/h 272,7 329,7 380,5

Dimensions (hxwxd) mm 1410x692x1269 1410x692x1362 1410x692x1452

Net weight kg 240 295 345

Gas type Natural Gas / LPG

Power consumption W 330 380 450

Reduced power consumption W 40 45 50

Power consumption in stand-by W 3,5 3,5 3,5

Possible maximum length of the outdoor sensor cable m < 20m (0,8mm²) < 80m (1,0mm²) < 120m (1,5mm²)

Baxi presents the extension of the high efficiency condensing boilers Power HT: a range that is the result of the combination of leading edge technology and high efficiency. It is suitable for large buildings (from multi-dwellings buildings to an office complex or a shopping centre) for single and cascade installations.

FEATURES• Aluminium silicon water/flue exchanger with glass-wool insulation: high efficiency, compact dimensions, reliability and long life • Low NOx emissions premixing burner • Digital control panel with advanced electronics to manage single and cascade installations (flue and hydraulic accessories to manage the installation up to 2 boilers)• Modulation ratio 1: 6,5• Complete range of thermoregulation accessories• Flue pipes completely separated from the installation place• Low operation noise

Power HT

QualityEnvironment

SafetyISO

900

1 - I

SO 14001 - OHSAS

18001