Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada 1 , T. Koseki 1 & K. Hisatomi 2 1 The University of Tokyo, Japan 2 Shin-Keisei Electric Railway Co. Ltd., Japan Abstract Most electric trains in DC-electrified railways are presently equipped with a regenerative braking system. On braking, the traction controller of a train can convert kinetic energy into electrical energy during deceleration of the train only when other powering trains consume the electrical energy as electrical loads for the regenerating train in the electrical circuit. Therefore, the traction controller of the braking train must reduce the electrical power following squeezing control of regenerative power when the electrical loads are too small in the electrical circuit, because there are, typically, no other devices to absorb the regenerated energy in the electrical circuit. However, actual traction controllers have often reduced regenerative power excessively because they do not recognize the states of the electrical circuit, which include positions of other trains and substations and power consumption/regeneration of other trains in the electrical circuit. In this paper, the authors discuss an improvement of the squeezing control of regenerative power based on information of the electric circuit. The information includes voltage at the pantograph, estimated positions and power consumption/regeneration of other trains etc. 1 Regenerative braking in DC-electrified railway Fig.1 shows the typical power flow on braking in a DC-electrified circuit. The black solid arrows show the typical power flow in the present system, in which only the powering train consumes the power regenerated from a braking train. Therefore, the braking train must reduce the electrical power following squeezing control of regenerative power when the power consumption of powering trains is too small since there is, typically, no other device to absorb Energy Management in the Train Operation 13 www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press 10 doi:10.2495/978-1-84564- -/ 498 7 02

Upload: phamhanh

Post on 01-May-2018

220 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

Power management control in DC-electrified railways for the regenerative braking systems of electric trains

Y. Okada1, T. Koseki1 & K. Hisatomi2 1The University of Tokyo, Japan 2Shin-Keisei Electric Railway Co. Ltd., Japan

Abstract

Most electric trains in DC-electrified railways are presently equipped with a regenerative braking system. On braking, the traction controller of a train can convert kinetic energy into electrical energy during deceleration of the train only when other powering trains consume the electrical energy as electrical loads for the regenerating train in the electrical circuit. Therefore, the traction controller of the braking train must reduce the electrical power following squeezing control of regenerative power when the electrical loads are too small in the electrical circuit, because there are, typically, no other devices to absorb the regenerated energy in the electrical circuit. However, actual traction controllers have often reduced regenerative power excessively because they do not recognize the states of the electrical circuit, which include positions of other trains and substations and power consumption/regeneration of other trains in the electrical circuit. In this paper, the authors discuss an improvement of the squeezing control of regenerative power based on information of the electric circuit. The information includes voltage at the pantograph, estimated positions and power consumption/regeneration of other trains etc.

1 Regenerative braking in DC-electrified railway

Fig.1 shows the typical power flow on braking in a DC-electrified circuit. The black solid arrows show the typical power flow in the present system, in which only the powering train consumes the power regenerated from a braking train. Therefore, the braking train must reduce the electrical power following squeezing control of regenerative power when the power consumption of powering trains is too small since there is, typically, no other device to absorb

Energy Management in the Train Operation 13

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

doi:10.2495/978-1-84564- - /498 7 02

Page 2: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

the regenerated energy in the electrical circuit. However, there are many possible solutions for effective usage of regenerative braking. For example, brake choppers with resistances on board or in the electrical circuit contribute to maintenance reduction of trains. Another method is to install energy storage devices which include flywheels, batteries and double layer capacitors on board or in the electrical circuit, and commutated rectifiers at substations contribute to efficient energy usage. In addition, reduction of voltage regulation at substations and of feeding resistance can contribute to effective regenerative braking. However these methods require additional hardware, which mean additional cost. The other solution, which does not cause excessive cost, is to improve the squeezing control of regenerative power, which can enhances the performance of regenerative braking.

Powerconverter

M otorPow er

converterM otor

Pow ering trainRegenerating train

Energy storage by fly w heels, batteriesand double layer capacitors

Pow er consum ption w ith brake chopperand resistance

Substation

Pow er systemLoads

Im provem ent ofsqueezing control ofregenerative pow er

Reduction ofline resistance

Reduction ofvoltage regulation

Introduction ofcom m utated rectifier

Typical pow er flow in present system

System s for efficient energy usage andm aintenam ce reduction

System s for only m aintenance reduction

Energy storage by fly w heels, batteriesand double layer capacitorsPow er consum ption w ith D C chopperand resistance

Figure 1: Typical power flow on braking.

In this paper, the authors discuss improvement of the squeezing control of regenerative power with information of the electrical circuit and brake choppers with resistances.

2 Problems of squeezing control of regenerative power

On braking, the braking train converts kinetic energy to electrical energy. And other powering trains consume the electrical energy as electrical loads in the electrical circuit. Therefore, when electrical loads are too small in the circuit, the braking trains must reduce regenerative power following the characteristic shown by the solid line in Fig.2 to avoid excessive voltage at the pantograph. This control is called squeezing control of regenerative power.

Computers in Railways IX, J. Allan, C. A. Brebbia, R. J. Hill, G. Sciutto & S. Sone (Editors)© 2004 WIT Press, www.witpress.com, ISBN 1-85312-715-9

14 Power Supply, Energy Management and Catenary Problems

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 3: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

1650 1750Voltage of pantograph[V]

Motor current

1900

C onventional characteristic

M axim al line voltage

0

Figure 2: Typical characteristic of squeezing control.

However, actual traction controllers often reduce regenerative power excessively [1]. The reasons for the excessive reduction are as follows; 1. traction controllers reduce regenerative power excessively in low-speed

range because they reduce AC motor current directly instead of their DC current,

2. traction controllers reduce motor current at lower voltage than maximal voltage limit of feeding circuit as shown by the solid line in Fig.2 and,

3. actual traction controllers often reduce motor current at lower voltage than the conservative voltage limit shown by the solid line in Fig.2.

In these problems, squeezing DC current of traction controller instead of AC motor current can solve the problem in 1(above). However, a traction controller needs to recognize the state of the electrical circuit in which braking trains exist to solve the problems in 2 and 3. When the traction controller cannot recognize the states of the electrical circuit, it must control regenerative power with statically conservative characteristic shown by the solid line in Fig.2 to avoid excessive voltage at the pantograph, because the voltage at the pantograph rises when a powering train, which exists in the electrical circuit, reduces its power consumption. The faster the reduction of power consumption is, the higher the voltage of the pantograph rises. Therefore, the traction controller must squeeze regenerative power regarding reduction of power consumption of register-controlled trains, which reduce their power consumption faster than any other train, in the electrical circuit. However, the reduction of power consumption of trains controlled by VVVF-inverters, armature choppers or a field chopper is slower than that of resistor-controlled trains. Traction controller squeezes, consequently, regenerative power excessively when powering trains controlled by these methods to reduce their power consumption.

3 Improvement of squeezing control

The improvement of electrical circuits, power management with data communication in an electrical circuit etc. are proposed to improve squeezing control of regenerative power [1], [2], [3]. In this paper, the authors propose squeezing control of regenerative power whose characteristics vary according to states of the electrical circuit. It is necessary to know the behaviour of the

Energy Management in the Train Operation 15

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 4: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

pantograph voltage rising quickly at the stop of the power consumption of powering trains in the same electric circuit for improving the squeezing control of the braking train. For that purpose, the traction controller must have the following information; 1. the position and velocity of the trains, voltage at pantograph, DC current of

traction controller and power regeneration of the regenerating train, 2. running profile of the line on which the regenerating train exists, 3. control method of every train on the line, 4. the time when powering trains in the electrical circuit reduce their power

consumption and 5. distance between the braking train and the powering trains.

In the above, the information in 1 can easily be measured, and the information in 2 and 3 can be stored on board as data of traction controller. However, the information given in 4 and 5 needs to be estimated from the information in 1, 2 and 3. And, the characteristics of squeezing control of regenerative power must be determined, based on the information. One must propose how to estimate the information in 4 and 5 and how to determine the characteristics of squeezing control of regenerative power. The voltage regulation at the pantograph in the case of powering trains with various control methods, reduce their power consumption for determining characteristics of squeezing control of regenerative power in the following part of this paper.

Filtercapacitor

FilterreactorInternal

resistance

Feeder line(variable)

Substation Feeder line(1km ) Braking train

Efc

I0

Es

Powering train

Squeezing control ofregenerative pow er

Tractioncontroller

Il

Is Ir

Efc

I0 : C urrent operation from braking operation

Ich

Efc

B rake chopper operation

Brakingresistor

Ich

Ir

Figure 3: Electrical circuit for examination.

4 Voltage regulation at the pantograph

4.1 Electrical circuit for examination of voltage regulation

Fig.3 shows the electrical circuit to calculate voltage regulation at the pantograph. The electrical circuit consists of a substation, a powering train and a braking train controlled by VVVF-inverter. The powering train is controlled by

16 Power Supply, Energy Management and Catenary Problems

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 5: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

VVVF-inverters, field-current choppers or resistor controllers. Fig.4 shows the equivalent circuits of the powering train and Fig.5 shows characteristics at reduction of power consumption at the powering train. The line voltage at the electrical circuit is limited up to 1900V. The authors will monitor the voltage at a filter capacitor of a braking train instead of that at pantograph.

Filter reactor

Filter capacitor

Tractioncontroller

Tractioncontroller

(b) Field chopper control Resistor control

(a) VVVF-inverter control

Ia

Il

Il

Ia

Figure 4: Equivalent circuits of a powering train.

Ia[A]

1600 1600

Tim e[s] Tim e[s]

50

0 2.5 3.5 5

800

50

0 2.5 2.55 2.60 2.65

(a)VVVF-Inverter control (c)Resistor control

5

1600

Tim e[s]

50

0 2.5 3.1 5

(b)Field chopper control

Ia[A] Ia[A]

1.0s 0.6s 50m s

Figure 5: Characteristics at reduction of power consumption.

Efc

Characteristic ofsqueezing control

I0

I00 >I0 → I =I00

I00 <I0 → I =I0

I00

I

10V

Emax

Efc[V]I00[A]

-2000

011+Ts

(T=30[m s])

Ir

(a) O peration logic for squeezing control of regenerative power (b) C haracteristic of squeezing control

Figure 6: Squeezing control for VVVF-inverter and chopper controlled train.

4.2 Voltage regulation at pantograph of the braking train

4.2.1 Case of VVVF-inverter controlled powering train Fig.6 (a) shows the operation logic of how to reduce the regenerative power when the powering train controlled by VVVF-inverter stops its power consumption. In this logic, the V-I characteristic in Fig.6 (b) is assumed as the “characteristic of squeezing control” in Fig.6 (a). The first order delay, the time constant of which is assumed T=30[ms], represents the response of the traction

Energy Management in the Train Operation 17

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 6: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

motor current. In addition, the distance between the powering and the braking trains is 2 km. Fig.7 shows voltage at the filter capacitor of the braking train. It also shows that the braking train can keep electric braking action by reducing its regenerative power continuously for avoiding excessive pantograph voltage, even if the other train stops its powering in various cases from Emax=1600[V] up to 1850[V]. In addition, Fig.8 demonstrates the relation between the voltage at the filter capacitor and the DC current from the braking train while the powering train reduces its power consumption in the case that Emax is 1850V. And Fig.8 illustrates that the traction controller of the braking train can reduce its regenerative power following the design of its squeezing control.

Figure 7: Voltage at the filter capacitor (VVVF-inverter).

Figure 8: Following characteristic of squeezing control (VVVF-inverter).

4.2.2 Case of powering train controlled by field-current chopper Fig.6 (a) shows operation logic for squeezing control of regenerative power when a powering train controlled by a field-current chopper stops its power consumption. In addition, the distance between the powering and the braking trains is 2 km.

18 Power Supply, Energy Management and Catenary Problems

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 7: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

Fig.9 shows voltage at the filter capacitor of the braking train. It also shows that the braking train can keep electric braking action by reducing its regenerative power continuously for avoiding excessive pantograph voltage, even if the other train stops its powering in various cases from Emax=1600[V] up to 1850[V]. In addition, Fig.10 illustrates the relation between voltage at the filter capacitor and the DC current of the traction controller of the braking train while the powering train reduces its power consumption in case that Emax is 1850V. And Fig.10 illustrates that traction controller of the braking train can reduce its regenerative power following the design of its squeezing control.

Figure 9: Voltage at the filter capacitor (Chopper).

Figure 10: Following characteristic of squeezing control (Chopper).

4.2.3 Case of resister-controlled powering train Fig.11 shows operation logic for squeezing control of regenerative power in case the powering train, which is resister-controlled, reduces its power consumption. In addition, the first order delay, whose time constant is 1.0 ms, is used to suppress vibration of I00 and the other first order delay, whose time constant is 30 ms, indicates characteristic of response of current at traction motor. Moreover,

Energy Management in the Train Operation 19

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 8: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

the limiter 1 makes its output zero when its input is negative and the Limiter 2 makes its output zero when its input is positive.

Efc

I0

I00 I

ddt

Proportional gain0.3

Lim iter 1

Lim iter 2

+

+

C haracteristic ofsqueezing control I00 >I0 → I =I00

I00 <I0 → I =I0

Ir

11+T1s

(T1=1[m s])1

1+T2s(T2=30[m s])

I00

Figure 11: Operation logic for squeezing control (2).

Fig.12 shows voltage at the filter capacitor of braking train when the Emax indicated in Fig.6 (b) is 1600V and the distance between the powering and the braking trains is 2km. Fig.12 also illustrates that the filter capacitor of braking train rises drastically because the powering train spontaneously reduces its power consumption in several milliseconds. Therefore, Emax must be less than 1600V so that traction controller can reduce regenerative power conservatively when resister-controlled train, instead of a VVVF-inverter controlled train or a field-chopper controlled one, cuts off its power.

Figure 12: Voltage at the filter capacitor (3).

In addition, Fig.13 shows maximal voltage at the filter capacitor of the braking train when the distance between the powering and the braking trains varies if Emax is 1600V. This figure means that the longer the between the powering and the braking trains is, the lower the maximal voltage at the filter capacitor of the braking train is, since the line resistance proportional to the distance between the two trains restricts the power to be transferred from the braking to the powering train. Fig.13 also demonstrates that the longer the distance between the powering and the braking trains is, the higher the Emax can be. Fig.14 shows maximal Emax to avoid excessive voltage at the filter capacitor of the braking train. This figure means the longer distance between the powering and the braking trains allows

20 Power Supply, Energy Management and Catenary Problems

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 9: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

higher Emax, since the influence from the action of the powering train is substantially smaller when the distance between the two trains is longer. The logic indicated by Fig.14 (b) determines the possible Emax to avoid excessive voltage at the filter capacitor of the braking train.

Figure 13: Voltage rise.

STARTEmax=1600[V]

C ircuit sim ulation

M axim al Efc < 1900V(during sim ulation)

Emax = Emax-10

End

Emax = Emax+10

No

Yes

(a) The possible Emax to avoid excessive voltage (b) The logic to determ ine the possible Emax

Figure 14: Possible Emax to avoid excessive voltage.

18500 1860

Ich[A]

Efc[V]

150

Figure 15: V-I characteristic for a chopper-control of a braking resistor.

If the braking train has supplemental braking resistor, whose characteristic for operation is assumed as Fig.15, Emax=1850[V] is possible for all the investigated

Energy Management in the Train Operation 21

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 10: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

train distance, since the braking resistor can effectively absorb the power deviation from the spontaneous action of the powering train. In this case, maximal power consumption of the braking resistor at all the investigated train distance is 220kW, which is approximately 7% of maximal power consumption of typical electric train on powering.

5 Conclusion

In this paper, the authors have proposed squeezing control of regenerative power whose characteristics vary according to states of electrical circuit. They have examined the voltage at the filter capacitor of the braking train when the different three kinds of powering trains stop their power consumption. They have concluded: 1. when a powering train, which is controlled by VVVF inverter or field

chopper, stops its power consumption, braking train can successfully reduce its regenerative power with squeezing control whose Emax is close to maximal voltage limitation,

2. the controller of the braking train must reduce its regenerative power conservatively when a resister-controlled powering train close to the braking train stops its power consumption,

3. longer distance between the powering and the braking trains allows higher Emax, since the influence from the action of the powering train is substantially smaller when the distance between the two trains is longer, and

4. the braking resistor, whose power consumption approximately 7% of the maximal power consumption of typical electric train on powering enables Emax to be 1850[V] for all the investigated train distance.

6 Future work

The authors have studied only the squeezing control of regenerative power on board. However, they must also investigate how to estimate and use the following information to introduce a better squeezing control of regenerative power whose characteristics vary according to the states of electrical circuit; 1. the time when powering trains in electrical circuit stop their power

consumption, and 2. distance between the braking train and the powering train which cuts off its

power consumption.

Acknowledgements

and cooperation in the investigation in this paper. Mr. Hideki Iida at Shin-Keisei Electric Railway Co., Ltd. for their assistance The authors are grateful to Prof. Satoru Sone at Kogakuin University and

22 Power Supply, Energy Management and Catenary Problems

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 11: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

References

[1] S. Sone, Re-examination of Feeding Characteristics and Squeezing Control of Regenerative Trains, Joint Technical Meeting Transportation and Electric Railway and Linear drives, TER-02-49/LD-02-64, 2002.

[2] Y. Okada, T. Koseki, Evaluation of maximal reduction of electric energy consumed by DC-fed electric trains, NATIONAL CONVENTION RECORD I.E.E. JAPAN, 5-219, pp307-308, 2003.

[3] Y. Okada, T. Koseki, S. Sone, Energy Management for Regenerative Brakes on a DC Feeding System, STECH’03, pp 376-380, 2003.

Energy Management in the Train Operation 23

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10

Page 12: Power management control in DC-electrified railways for ... · Power management control in DC-electrified railways for the regenerative braking systems of electric trains Y. Okada1,

www.witpress.com, ISSN 1755-8336 (on-line) WIT Transactions on State of the Art in Science and Engineering, Vol 39, © 20 WIT Press10