Power Protection Handbook for IBM System i and System p Applications Powerware 9910 UPS

International

July 2008

Page 2: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 1

Table of Contents

Resources and Sales Tools on the Web: powerware.com/ibm .........................................................2

9 Power Problems and Their UPS Solutions.....................................................................................3

UPS Topologies: Online, Line-Interactive, and Standby....................................................................4

Frequently Asked Questions .............................................................................................................5

Preventing UPS Problems.................................................................................................................6

RoHS Compliant and pre-RoHS Part Number Cross Reference Chart .............................................7

Glossary of Power Terms..................................................................................................................8

Commonly-Used Acronyms.............................................................................................................10

Recommended Powerware 9910 UPS by Application.....................................................................11

How Much Battery Runtime Do You Need? ....................................................................................12

Powerware 9910 UPS Models

Attributes at a Glance......................................................................................................................13

Powerware 9910-P14......................................................................................................................14

Powerware 9910-P16......................................................................................................................17

Powerware 9910-E30......................................................................................................................20

Powerware 9910-E33......................................................................................................................23

Powerware 9910-E64......................................................................................................................26

Powerware 9910-E65......................................................................................................................30

Powerware 9910-E83......................................................................................................................33

Powerware Software and Connectivity............................................................................................37

Note: Due to continuing product improvement programs, all specifications are subject to change without notice. For the latest information, go to www.powerware.com/ibm.

Eaton, Powerware, ABM, LanSafe, ConnectUPS, and X-Slot are trade names, trademarks and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective owners.

Page 3: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 2

Resources and Sales Tools on the Web: powerware.com/ibm

The following information is available to you on the web or from your Eaton® representative. Please note that the web site is updated more frequently than this handbook. Download the latest information from www.powerware.com/ibm.

Sales Tool/ Reference Chart Description

9910 UPS Validator Verify your IBM 9910 UPS e-config solution and ensure that you have the complete list of components and options

e-Config Updates See the latest release dates for the most recent versions of the e-config tool and their respective changes

i5 Rack UPS Chart Configure the appropriate Powerware 9910 UPS for your POWER (IBM i (i5/os)) and System i rack applications

p5 Rack UPS Chart Configure the appropriate Powerware 9910 UPS for your POWER (AIX and Linux), and System p rack applications

How to determine what parts are included with your 9910 UPS

What to know what components are included with your 9910 UPS kit? Find out the various components and options available for the 9910 UPS models

How much battery runtime do you need

Calculate how much runtime you require and find out how many minutes of battery back up time Powerware 9910 UPS models provide

IBM UPS Support Knowledge Base? Have an application, product or power configurator question? Check out this data base of frequently asked questions

IBM Feature Codes and Powerware Part Number Cross Reference Chart

Wondering what an IBM Part Number, IBM Feature Code or Powerware part number is? Find out with this cross-reference chart

Eaton Contact Information Want to know how to contact your local Eaton representative? View the regional Eaton Representative information

Page 4: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 3

9 Power Problems and Their UPS Solutions

Page 5: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 4

UPS Topologies: Online, Line-Interactive, and Standby Online UPS Technology Online UPSs are designed to provide complete power protection. They isolate equipment from all types of power problems by continuously regulating the AC power for your systems. Online UPSs isolate equipment from harmonic distortions and are strongly recommended for critical applications that must meet the 5%maximum harmonic requirement (stated in major computer manufacturer specifications and installation guides). Battery conservation is an essential factor for a customer deciding to purchase an online UPS. An online UPS uses the battery less often than any other UPS technology, therefore increasing the life expectancy of the battery. Eaton’s robust, state-of-the-art online UPS provides superior protection for your communication and networking systems. Note: Online UPSs provide protection from all 9 power problems listed on page 5. Line-Interactive UPS Technology Line-interactive UPSs offer basic power protection at mid-range prices. In addition to protection against power failures, power sags and power surges, line-interactive UPSs protect against brownouts and electrical line noise. This design offers low-grade voltage regulation by “boosting” the utility voltage up or down before passing it through to your electronic system. Note: Line-interactive UPSs do not provide protection from power problems 6 – 9 (see page 5).

Standby UPS Technology Standby UPSs are intended to provide a low price solution for power failures, power sags and power surges. Utility power is provided during normal operation. Utility voltage and frequency changes are not regulated by the UPS and pass through to the equipment. When voltage or frequency changes become too severe, the UPS converts DC battery power to AC power to run the equipment. Standby UPSs provide protection from simple power problems as described in items 1, 2 & 3. Note: Standby UPSs do not provide protection from power problems 4 – 9 (see page 5).

Page 6: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 5

Frequently Asked Questions 1. What happens if the UPS is overloaded? For example, if the

protected equipment and/or load draws more current than the UPS can provide. The UPS transfers the load to bypass (for a few minutes) until the overload condition is reversed. If the overload condition continues, the UPS automatically shuts down.

2. What causes a UPS to be overloaded?

There are two possible answers: (1) the UPS was undersized (e.g. the load is rated at 1200 VA but a 1000 VA UPS was provided), or (2) the customer plugs more equipment into the UPS than it was designed to handle.

3. How do you convert watts to VA?

Multiply watts by the power factor 1.3.1000W = 1300 VA 4. How do you convert amps to VA?

Multiply amps by voltage (230 volts in Europe). 10A x 230V = 2300 VA

5. How long does it take for the UPS batteries to recharge?

On average it takes 10 times the discharge time for the UPS batteries to recover. (A 30-minute battery discharge requires about 300 minutes to recharge.) After each power outage, the recharge process begins immediately. It is important to note that the load is fully protected while the batteries are recharging. However, if the batteries are needed during the recharge time, the holdover time available will be less than it would have been if the batteries were fully charged.

6. Where can I get technical help?

Contact your territory representative, call the IBM® UPS Hotline at +44 (0) 845 177 3410, or visit powerware.com/ibm.

7. What is the average lifespan of the batteries used in the

UPS? The typical life of batteries in a Powerware UPS with ABM® technology is 4 to 6 years. Overall service life depends on a number of factors, including temperature and the number of battery discharges.

8. Does the UPS need to have a load on it to charge its

batteries? The UPS should have a minimum of 10% load for UPS to charge its batteries. Once connected to a standard supply of electricity (via input plug or hardwiring), your UPS should charge its batteries regardless of how much load, if any, is attached to it.

9. If my UPS is in storage, how often should I charge the

batteries? If a UPS is in storage, we recommend that you plug it in every 6 months to prevent the batteries from becoming fully discharged and significantly shortening their service life. We recommend that you follow the same guidelines for charging external batteries.

10. I came across a spare, unused Powerware UPS that we had

in storage. Is it still operable? If the UPS has been in storage for more than 6 months, the batteries inside your UPS may be bad. If your UPS has been in storage without any charge for longer than a year, it’s likely that the batteries need to be replaced.

11. How can you be sure UPS batteries are in good condition in order to insure they have maximum holdover in the event of a power failure? What preventive maintenance procedures should be done and how often should they be done? The batteries used in the UPS and associated battery modules and cabinets are sealed, lead-acid batteries often referred to as maintenance-free batteries. While this type of is sealed and you do not need to check the fluid level in the battery, they do require some attention to assure proper operation. You should inspect the UPS a minimum of once per year by initiating a self-test of the UPS.

12. I already have surge protection. Why do I need a UPS?

Surge protection will not keep your business and phones operational during a blackout. In addition, surge protectors do nothing to improve the quality of power feeding your sensitive and expensive telecom equipment. The Powerware UPS provides perfect, clean power to your equipment at all times. Over time, poor quality power will degrade your equipment.

13. What’s the difference between a surge protector and a UPS?

A surge protector provides just that—surge protection. In addition to surge protection, a UPS continually regulates incoming voltage and provides battery backup in the event of a power failure. You’ll often see surge protectors plugged into a UPS for added surge protection and additional output receptacles.

14. We have heard that UPS models greater than 750 VA cannot

be installed behind larger UPS models. Is this true? No. If you are connecting a UPS to a source other than directly to the utility, the source (such as another UPS or generator) must be 3 to 5 times larger than the smaller UPS.

15. How much capacity of a UPS should I use?

To allow for future expansion, we recommend that you install a UPS at approximately 75% capacity. In addition, the batteries degrade overtime so by over sizing you provide room for error. In the powerware.com/ibm sizing tool we have included a “capacity used” column.

16. How is battery runtime impacted if I reduce the load on the

UPS? There can be a significant increase in runtime. Generally speaking, a UPS that provides 5 minutes at full load will provide 15 minutes at half load.

17. Why is power quality such a problem today?

Today’s high-tech IT equipment and control units are much more sensitive to electrical disturbances and are more important to the critical functions of many businesses than in the past. As a result, power quality problems today are more frequent and more costly than ever.

18. Are power quality problems always noticeable?

No. In many cases, disturbances can cause imperceptible damage to circuits and other components, a major cause of premature equipment failure and problems like computer lockups. Many power quality problems go unresolved resulting in lost revenue and data.

Page 7: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 6

Preventing UPS Problems The following observations can help you avoid potential problems with the sale and installation of a UPS. Observation #1 alone will protect you from a large percentage of problems. If you have any questions about this information, please contact your Eaton consultant for IBM UPS sales. 1. Always be sure to advise the customer which wall receptacle

is required to plug in the UPS. Only UPSs with power ratings up to 1500 VA plug into a standard 15-amp wall outlet. All others require a larger receptacle, which must be installed by an electrician. Things will go more much more smoothly if your customers are not waiting for this to be done after all of their equipment has arrived.

2. Does your customer have the correct set of interconnecting

cords? For some applications, it’s as simple as plugging the UPS into the wall socket and plugging the loads into the UPS. However, IBM 9910 applications often require specific interconnecting cords in order to complete installation. We recommend that you make that determination before installation to avoid delays.

3. Be sure that the UPS has enough output receptacles.

If the UPS is not equipped with enough output receptacles, you may need to add a PowerPass Distribution Module or choose another UPS.

4. Adding batteries to the UPS provides additional battery

runtime only, not added capacity. If a customer adds equipment to the configuration, a higher rated UPS may be needed.

With larger UPS models particularly above 3 kVA and for 3-phase UPS solutions, it is extremely important to make sure that you review that site at which the UPS will be located. Here are a few general guidelines: 5. Make sure the UPS, batteries, and options will fit in the

allocated space. Is there enough room for a technician to service the UPS? Some customers have limited space.

6. Does the UPS have adequate ventilation?

Most UPS models incorporate internal fans to cool the UPS but they need to pull cooler air through the UPS to work effectively. You should not install the UPS in a sealed container or small, sealed room.

7. Ensure that the UPS can be placed in its final position.

Will the UPS components fit through any doors? Are there any stairs?

8. Is the floor strong enough?

The UPS and its battery cabinets can be heavy so make sure that the site has the proper floor loading capacity.

9. Check to see if there is an adequate electrical supply near

the UPS. Compare UPS fuse ratings (amps) and breaker types and whether any electrical work may be needed (i.e. cabling to the UPS terminal block input). The site may have its own electrical contractors.

Page 8: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 7

RoHS Compliant and pre-RoHS Part Number Cross Reference Chart The Restriction of Hazardous Substances Directive (RoHS) became European Law in February 2003. This directive restricts the use of six hazardous materials in the manufacture of various types of electronic and electrical equipment. It is closely linked with the Waste Electrical and Electronic Equipment Directive (WEEE), which sets collection, recycling and recovery targets for electrical goods and is part of a legislative initiative to solve the problem of huge amounts of toxic e-waste. RoHS restricts the use of the following 6 substances: Lead, Mercury, Cadmium, Chromium VI (Also known as hexavalent chromium), PBB, PBDE Throughout 2006 Eaton updated our domestic and international products to meet RoHS and WEEE standards. As part of this process, most Powerware product part numbers were changed.

9910 Machine Type Description

RoHS Compliant IBM Part Number

Pre-RoHS IBM Part Number

UPS

P14 UPS, 950W/1400 VA, 230 Vac 39J4810 39J2533

P16 UPS, 1050W/1500 VA, 230 Vac 39J4812 04N6374

E30 UPS, 2100W/3000 VA, 208-240 Vac 42R8069 38P9297

E33 UPS, 2700W/3000 VA, 208-240 Vac 42R8065 21P7219

E64 UPS, 4200W/6000 VA, 208-240 Vac 42R8073 38P9298

E65 UPS, 4500W5000 VA, 208-240 Vac 42R8077 39J2534

E83 UPS, 8000W/10000 VA, 220-240 Vac 44V3923 -

EBM

6605 Extended Battery Module for P16 39J4813 04N6626

6643 Extended Battery Module for E33 42R8067 39J4815

6644 Extended Battery Module for E30 42R8071 38P9299

6645 Extended Battery Module for E64 & E65 42R8075 38P9300

6646 Extended Battery Module for E83 & E82 44V3921 -

Communication Options

2934 SNMP Card 39J4824 53P4619

2939 X-Slot Relay/Serial Card 42R4332 39J2627

Power Distribution Module

6570 NEMA PowerPass Distribution Module for

E30

42R4320 38P9301

6571 NEMA PowerPass Distribution Module for

E64

42R4318 38P9302

6572 IEC PowerPass Distribution Module for E64 42R4319 38P9303

Other Options

2973 PDU to UPS Power Cord 42R4331

2974 PDU to UPS Power Cord 42R4333

2975 UPS Input (Mains) Power Cord 42R4335

2976 UPS Input (Mains) Power Cord 42R4336

Page 9: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 8

Glossary of Power Terms Ampere (A or Amp) – The unit of measure for the “rate of flow” of electricity, analogous to “gallons per minute.” VA x 0.7 (power factor) = Watts Alternating Current (AC) – An electric current that reverses its direction at regularly recurring intervals. Arc – Sparking that results when undesirable current flows between two points of differing potential. This may be due to leakage through the intermediate insulation or a leakage path due to contamination. Audible Noise – A measure of the noise emanating from a device at audible frequencies. Backup Time – The amount of time the battery in a UPS is designed to support the load. Blackout – A zero-voltage condition lasting for more than two cycles. BTU – British Thermal Unit. Used to measure heat dissipation. Energy required to raise one pound of water one degree Fahrenheit. One pound of water at 32 degrees F requires the transfer of 144 BTUs to freeze into solid ice. Brownout – A steady state of low voltage, but not zero voltage. Common Mode Noise – An undesirable voltage that appears between the power conductors and ground. Crest Factor – Usually refers to current. It is the mathematical relationship between RMS current and peak current. A normal resistive load will have a crest factor of 1.4142, which is the normal relationship between peak and RMS current. A typical PC will have a crest factor of 3. Critical Equipment – Equipment such as computers, communications systems or electronic process controls, whose continuous availability is imperative. Direct Current (DC) – An electric current in which the flow of electrons is in one direction, such as supplied by a battery. Double-Conversion – A UPS design in which the primary power path consists of a rectifier and inverter. Double con-version isolates the output power from all input anomalies such as low voltage surges and frequency variations. Downtime – The time during which a functional unit cannot be used because of a fault within the functional unit or within the environment. Electrical Line Noise – Radio frequency interference (RFI), electromagnetic interference (EMI) and other voltage or frequency disturbances.

Electromagnetic Interference (EMI) – Electrical interference that can cause equipment to work improperly. EMI can be separated into conducted EMI (interference conducted through cables out of the UPS) and radiated EMI (interference conducted through the air). Ground – A conducting connection, whether intentional or accidental, by which an electric circuit or equipment is connected to the earth, or to some conducting body of relatively large extent that serves in place of the earth. Harmonic – A sinusoidal component of an AC voltage that is multiple of the fundamental waveform frequency. Certain harmonic patterns may cause equipment problems. Harmonic Distortion – Regularly appearing distortion of the sine wave whose frequency is a multiple of the fundamental frequency. Converts the normal sine wave into a complex waveform. Hertz (Hz) – A unit of frequency equal to one cycle per second. High Voltage Spike – Rapid voltage peak up to 6,000 volts. Hot-Swappable – The ability to change a module without taking the critical load off the UPS. i5 Server – The most current generation of the IBM System i™ family of general-purpose systems that supports the i5/OS™ Operating System/400, AIX®, and Linux® operating systems and that provides application portability across all models. Input Voltage Range – The voltage range within which a UPS operates in “normal” mode and does not require battery power. Inverter – UPS assembly that converts internal DC power to output AC power to run user’s equipment. When the inverter is supporting 100% of the load at all times, as with an online UPS, there is no break from utility power to battery power. Kilovolt Ampere (kVA) – An approximation of available power in an AC system that does not take the power factor into account. Line-Interactive – An offline UPS topology in which the system interacts with the utility line in order to regulate the power to the load. Load – The equipment connected to and protected by a UPS. Logical Partition (LPAR) – (1) A set of key or RID pairs in a non-partitioning index that are associated with a particular partition. (2) A subset of a single system that contain resources (processors, memory, and input/output devices). A logical partition operates as an independent system. If hardware requirements are met, multiple logical partitions can exist within a system.

Page 10: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 9

Glossary of Power Terms (continued) Maintenance bypass – An external wiring path to which the load can be transferred in order to upgrade or perform service on the UPS without powering down the load. Make-Before-Break – Operational sequence of a switch or relay where the new connection is made prior to disconnecting the existing connection, also soft-load-transfer switching Noise – (1) A disturbance that affects a signal; it can distort the information carried by the signal. (2) Random variations of one or more characteristics of any entity such as voltage, current or data. (3) Loosely, any disturbance tending to interfere with normal operation of a device. Offline – Any UPS that does not fit the definition of online. Line-interactive and standby topologies are offline. Ohm – The unit of measurement for electrical resistance or opposition to current flow. Online – (1) A UPS that provides power to the load from its inverter 100% of the time, regulating BOTH voltage and frequency, usually double conversion topology. Orderly Shutdown – The sequenced shutdown of units comprising a computer system to prevent damage to the system and subsequent corruption or loss of data. Plug-and-Play – An electrical device that does not require extensive setup to operate. p5 Servers – The most current generation of the IBM System p® server family that uses IBM’s POWERt architecture designed for AIX and Linux. Power Factor (PF) – The ratio of real power to apparent power. Watts divided by VA. Most power supplies used in communication and computer equipment have a power factor of 0.7. (PF = 0.7) VA x PF = W W/PF = VA Power Sag – Low voltage (below nominal 230 volts). Power Surge – High voltage (above nominal 230 volts). Rackmount – Ability to mount an electrical assembly into a standardized rack. Rectifier – UPS component that converts incoming AC power to DC power for feeding the inverter and for charging the battery. Redundancy – Duplication or repetition of elements in electronic equipment to provide alternative functional channels in case of failure.

Relay Communication – Communication between a UPS and a computer through the opening and closing of solid-state relays which are pre-defined to indicate UPS status. RS-232 – The standard for serial interfaces (serial refers to the eight bits of each character successively sent down one wire) used by most computers, modems and printers; a 25-pin physical interface. Sine Wave – A waveform that represents periodic oscillations of a pure frequency. Single-Phase – Power system with one primary waveform. Standby – UPS technology where power is applied to the load directly from the utility under normal operation, but switched to the inverter and battery for emergency support (offline topology). System I™ Server – One of a family of general-purpose systems that supports IBM i5/OS and Operating System 400 and that provides application portability across all models. Formerly known as iSeries server. System p™ Servers – The IBM server family that uses IBM’s POWER architecture designed for AIX and Linux operating systems. Formerly known as pSeries server. System x™ Servers – The product name of an IBM eServer™ product that emphasizes industry-standard server scalability and self-managing server technologies. It is the successor to the Netfinity® family of servers. Formerly known as xSeries server. Three-Phase – A power system with three primary voltage waveforms spaced equally (in time) out of phase with each other. Total Harmonic Distortion (THD) – Describes how much the circuit voltage deviates from a perfect sine wave. A poor voltage THD is most often manifested in a “flat topped” waveform that comes from the inability of a power source to respond to the demands of highly non-linear loads. Uninterruptible Power System (UPS) – An electrical system designed to provide instant, transient-free back up power during power failure or fault. Some UPSs also filter and/or regulate utility power (line conditioning). Volt/voltage (V) – Electrical pressure that pushes current through a circuit. High voltage in a computer circuit is represented by 1; low (or zero) voltage is represented by 0. Volt Amps (VA) – Voltage x amps. Volts Direct Current (Vdc) Volts Alternating Current (Vac) Watts (W) – The rate of doing electrical work. W x 1.3 = VA.

Page 11: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 10

Commonly-Used Acronyms ABM Advanced Battery Management

AC Alternating Current

BBM Break-Before-Make (Bypass Switch)

BDM Bypass Distribution Module

BTU British Thermal Unit

CSA Canadian Standards Association

DC Direct Current

EBC Extended Battery Cabinet

EBM Extended Battery Module

EMEA Europe, Middle East, Africa

HW Hardwired

IEEE Institute of Electrical And Electronics Engineers

IP Internet Protocol

kVA Kilovolt ampere

LAN Local Area Network

MBB Make-Before-Break (bypass switch)

MTBF Mean Time Before Failure

MTTR Mean Time To Repair

NEMA National Electrical Manufacturers Association

NEC National Electrical Code

PBX Private Branch Exchange

PDM Power Distribution Module

PPDM PowerPass Distribution Module

PoE Power Over Ethernet

PUE Power Usage Efficiency

REPO Remote Emergency Power-off

RFI Radio Frequency Interference

RM Rackmount

RoHS Restriction of Hazardous Substances

SAN Storage Area Network

SNMP Simple Network Management Protocol

THD Total Harmonic Distortion

UL Underwriter’s Laboratory

UPS Uninterruptible Power System

USB Universal Serial Bus

VA Volt Amps

VoIP Voice Over IP

WAN Wide Area Network

Page 12: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 11

Recommended Powerware 9910 UPS by Application

Server (power draw) P16 P14 E30 E33 E64 E65 E83

POWER Systems Power 520 (750W) 8204-E4A (AIX, Linux) 9407-M15 (IBM i, (i5/OS)) 9408-M25 (IBM i, (i5/OS))

Power 550 (1,100W) 8204-E8A (AIX, Linux) 9409-M50 (IBM i, (i5/OS))

Power 570 (Watts vary) 9117-MMA (AIX, Linux) 9406-MMA (IBM i, (i5/OS)) 2-4 core (up to 1400W) 5-8 core (up to 2800W) 9-12 core (up to 4200W) 13-15 core (up to 5600W)

Power 575 (up to 20,300W)2

9125-F2A

Power 595 (up to 27,500W)2

9119-FHA CEC & 3 I/O Drawers

System p, p5 and OpenPower

9110-510 Rack (475W)

9111-520 Tower (750W)

9111-520 Rack (750W)

9113-550 Tower (1,100W)

9113-550 Rack (1,100W) 1

7047-185 Tower (450W)

7037-A50 Tower (450W)

p5 9110-51A Rack (625W)

p5 9115-505 Rack (500W)

p5 9111-285 Tower (750W)

p5 9116-561 Rack (1300W)

p5 9123-710 Rack (700W)

p5 9124-720 Tower (1592W) 1

p5 9124-720 Rack (1592W)

p5 9131-52A Tower (750W)

p5 9131-52A Rack (750W)

p5 9133-55A Tower (1100W) 1

p5 9133-55A Rack (1100W)

System i, i5

9405-510 Tower (600W)

9406-520 Tower (600W)

9406-520 Rack (600W)

9406-55x Tower (1,100W) 1

9406-55x Rack (1,100W)

9406-570 2–4 Way (1,300W)

9406-570 5–8 Way (2,600W)

9406-570 9–12 Way (3,900W)

9406-570 13–16 Way (5,200W)

9406 595 (up to 27,500W)2 1. Requires PDM FC 6572 for E64. 2. Contact +44(0) 845 177 3410 for UPS recommendation.

Page 13: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 12

How Much Battery Runtime Do You Need?

To meet customer needs of continued operation during power outages, Powerware 9910 UPS solutions offer options that can extend battery runtimes beyond 60 minutes. In today's 24x7 business environment, continued availability along with application and safety considerations must be taken into account and estimated when calculating UPS battery runtimes. For example, a typical battery runtime is 15 minutes. The recommended formula used to calculate runtime is: Runtime (calculated in minutes) = business + system application shutdown + safety

Example Business needs = 5 System (application) shutdown = 6 Safety margin = 4

Total battery runtime required = 15

Business needs: Approximately 80% of power outages are less than 5 minutes in duration. Using 5 minutes will ensure that if the typical power outage is less than 5 minutes, the application will not start a premature or unrecoverable shutdown. In the example, 5 minutes is used.

System shutdown: The National Power Laboratory (1990-1995) Power Quality Report indicates there may be consecutive power outages before power continuity is fully restored. By doubling the system/application time, you allow for two consecutive power outages to occur while providing an adequate reserve of battery runtime to initiate a safe system shutdown during the second power outage. In the example, it takes the application 3 minutes to shut down. Doubling the shutdown time results in 6 minutes.

Safety margin: Allows for natural battery charge cycles, temperature variations and aging. Also take into account variations in business needs. In the example, 4 minutes is used.

Find the correct UPS model then select the runtime required. If the power consumption of the equipment to be protected is unknown, use the maximum load (Watts) number given for the UPS.

For example, if the load requires less than 2,100 Watts and the runtime is 15 minutes, a valid UPS will be the E30 with one Extended Battery Module providing 25 minutes of battery backup (autonomy) runtime at the E30 maximum capacity of 2,100 watts.

Note: The runtime is total (standard internal batteries and optional EBMs), not additive.

Battery Runtime in Minutes

UPS Model

Maximum Watts

Supported

Standard (Internal) Battery +1 EBM +2 EBMs +3 EBMs +4 EBMs

EBM Feature Code

P14 950 5 - - - - None P16 1050 8 37 70 106 144 6605 E30 2100 5 25 38 54 70 6644 E33 2700 5 25 49 69 90 6643 E64 4200 10 30 52 76 102 6645 E65 4500 7 24 46 67 89 6645 E82 8000 5 12 27 36 45 6646

Page 14: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 13

Attributes at a Glance

Attribute P14 P16 E30 E33 E64 E65 E83

IBM Part Number 39J4810 39J4812 42R8069 42R8065 42R8073 42R8077 44V3923

Vac Input/Output 230 230 208-240 208-240 208-240 208-240 220-240

Maximum Output (Watts) 950 1050 2100 2700 4200 4500 8000

Maximum Output (VA) 1400 1500 3000 3000 6000 5000 10000

Level of Protection (Series) 5 9 9 5 9 5 9

Tower Form Factor 1

Rackmount Form Factor

Rack Height (U) 2 2 5 3 6

ABM Technology

Hot-Swappable Batteries

Hot-Swappable Electronics Module

Maintenance (Service) Bypass 1

Load Segments

Extended Battery Modules

EBM Feature Code — 6605 6644 6643 6645 6645 6646

EBM IBM p/n — 39J4813 42R8071 42R8067 42R8075 42R8075 44V3921

X-Slot™ Communication Cards 2

PowerPass FC 6572 (IEC Receptacle Sets)

1. Requires PowerPass Distribution Module FC 6572. 2. P16 have X-Slot Relay Card factory installed. Includes UPS to AS/400 communications cable.

Page 15: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 14

Powerware 9910-P14 950 Watt/1400 VA, 230 Vac UPS

Features and Benefits

• Low cost power protection for entry- to mid-level desk side servers • Extends battery service life and provides advanced warning of the end of

useful battery life with ABM technology • Regulates power fluctuations with Buck and Boost voltage regulation • Protects equipment connected by network or phone wiring from ”back door”

power surges with a network transient protector • Minimizes downtime with hot-swappable batteries • Single SKU supports POWER (AIX, Linux and IBM i (i5/OS)) and System i and System p • AS/400 (System I, i5) and serial connectivity enhances communication capability • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

P14 Model Guide

Model Number IBM Number Power Out

(Watts/VA) Input Connection

Output Connections

Dimensions (HxWxD, in/mm)

Unit Weight (lb/kg)

230 Vac1; 50/60 Hz auto-sensing

9910-P14 39J4810 950/1400 IEC-320-C14 (6) IEC-320-C13 7.6 x 5.9 x 15.4/ 193 x 150 x 390 37/16.8

1. 230V default, also user-selectable for 220 and 240V with rear panel DIP switches. P14 Battery Runtimes Chart (in Minutes)

Load UPS Internal Batteries 128W/200 VA 58 192W/300 VA 41 320W/500 VA 28 402W/600 VA 19 500W/750 VA 14 603W/900 VA 10 670W/1000 VA 8 804W/1200 VA 6 938W/1400 VA 5

Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.

Page 16: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 15

P14 Technical Specifications*

Electrical Input

Nominal Voltage 230 Vac (user selectable to 220 Vac)

Online Voltage Range ±20% for nominal voltage at full load

Nominal Input Frequency 45–65 Hz, 50/60 Hz; auto-sensing

Input Protection Reset-able circuit breaker

Connection IEC-320-C14

Electrical Output

Power Levels 950W/1400 VA

Online Regulation -10%, +6% of nominal voltage

On Battery Voltage Regulation ±5% of nominal voltage; -10% after low battery warning

On Battery Frequency Regulation ±0.1 Hz of nominal frequency

Voltage Wave Shape Sine wave (during normal and battery operation)

Connections (6) IEC-320-C13

Indicators and Controls

Front Panel LEDs Power on, on battery, overload, and battery fault

Front Panel Buttons On/off and alarm silence/self-test

Communication Port DB-9 female (UPS ships with communication cable); USB Interface Adapter is optional

Battery

Battery Type Sealed, maintenance-free lead-acid; starved electrolyte

Battery Description (3) 12V, 9 Ah

Battery Recharge <3 hours to 90% capacity

Battery Runtime See Battery Runtimes table

Start-On-Battery Startup with UPS batteries in absence of utility power

General

Topology Line-interactive

Diagnostics 0.68

Dimensions and Weight See Model Guide

Network Transient Protector In and out RJ-11 jack for telephone/modem protection or RJ-45 for 10BaseT network cable; UL497A tested

Environmental and Safety

Operating Temperature 0°C to 40°C (32°F to 104°F) UL tested at 25°C (77°F)

Transit/Storage Temp. -15°C to 55°C (5°F to 131°F)

Heat Dissipation 189 BTU/hr, maximum

Audible Noise <45 dBA typical

Relative Humidity 5% to 95% noncondensing

Safety Markings UL, cUL, and CSA

Safety Conformance UL 1778, CAN/CSA C22.2, No. 107.1

EMC Markings FCC Class B; 230V models also CE (EN50091-2) and C-Tick

Surge Suppression ANSI C62.41 Category A (formerly IEEE 587)

Immunity IEC 801-2, -3, -4 * Due to continuing product improvement programs, specifications subject to change without notice.

Page 17: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 16

What’s Included with the P14 UPS • 950W/1400 VA, 230V UPS • Serial Cable, DB-9 to DB-9 (6 ft/1.8m) • AS/400 Interface Cable (6 ft/1.8m) • USB Cable, DB-9 to USB (6 ft/1.8m) • Powerware 5115 UPS User’s Guide • Powerware (9910-P13 and P14) Communication Options for IBM Applications Manual • Powerware Software Suite CD • Service and Support Manual for IBM Applications

P14 Applications Matrix Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the P14 UPS.

IBM Server Watts Vac Expected Battery Runtime

(in Minutes)

i5, System i

9406-520, 9405-520 600 200-240 10

p5, System p and OpenPower

9111-520 600 200-240 10

9123-710 475 200-240 14

9110-510, 9123-705 400 200-240 19

7047-185 600 200-240 10

Page 18: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 17

Powerware 9910-P16 1050 Watt/1500 VA, 230 Vac UPS

Features and Benefits • Isolates connected equipment from all incoming power problems to provide

the highest degree of protection with rugged, online design • Significantly increases battery service life and gives you advanced warning of

the end of useful battery life with ABM technology • Prolongs backup time with Extended Battery Modules • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

P16 Model Guide

Model Number IBM Number Power Out

(Watts/VA) Input Connection

Output Connections

Dimensions (HxWxD, in/mm)

Unit Weight (lb/kg)

230 Vac; 50/60 Hz auto-sensing

9910-P16 39J4812 1050/1500 IEC-320-C141 (6) IEC-320-C13 3.5 x 17 x 19.4/ 89 x 432 x 493 50/23

Extended Battery Module (EBM)

9910-6605 39J4813 — — — 3.5 x 17 x 19.4/ 89 x 432 x 493 65/29.5

1. P16 includes (3) IEC-320-C13 to IEC-320-C14 interconnecting cords. P16 Battery Runtimes Chart (in Minutes)

Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs 280W/400 VA 46 177 331 501 682 490W/700 VA 25 96 180 272 370 585W/850 VA 21 76 142 214 292 700W/1000 VA 16 61 115 174 237 875W/1250 VA 11 46 87 131 179 1050W/1500 VA 8 37 70 106 144

Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.

Page 19: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 18

P16 Technical Specifications*

Electrical Input

Nominal Voltage 230 Vac

Input Voltage Ranges 150–288V (without using batteries)

Input Power Factor >0.95 typical

Frequency 50/60 Hz, auto-sensing

Frequency Range 46–65 Hz

Electrical Output

On Utility Voltage Regulation ±3% of nominal

On Battery Voltage Regulation ±3% of nominal

Efficiency 89–92% depending on load

Frequency Regulation ±3 Hz online; ±1 Hz on battery

Load Crest Factor 3 to 1 ratio

Communications

Communication Port Relay port standard; optional X-Slot cards available

Communication Cable 6-ft AS/400 communication cable included

Battery

UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid

UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid

Battery Runtime See Battery Runtime Chart

Battery Replacement Hot-swappable UPS internal batteries and external batteries modules

Recharge Time <2 hours from complete discharge to 80% capacity at nominal line conditions

Start-On-Battery Allows start of UPS without utility input

General

Topology True online, double-conversion

Diagnostics Full system self-test on power up

UPS Bypass Automatic on overload or UPS failure

Dimensions and Weight See Model Guide

Environmental and Safety

Ambient Operating Temperature 0°C to 40°C (32°F to 104°F) 0°C to 25°C (32°F to 77°F)

Heat Dissipation 645 BTU/hr maximum

Leakage Current <0.6 mA typical

Storage Temperature 0°C to 25°C (32°F to 77°F)

Relative Humidity 0% to 90% noncondensing

Audible Noise <45 dBA typical

Safety Markings CSA, VDE, CE, S, D, N, FI, B NOM, R

EMC Compliance FCC Class B and VCCI Class II, 3000 FCC Class A

Surge Suppression IEEE/ANSI C62.41 Category B (formerly 587)

REPO Port Meets NEC code 645-11 intent and UL requirements

Network Transient Protector In and out jack for models only or 10BaseT network cable protection. UL497A tested * Due to continuing product improvement programs, specifications subject to change without notice.

Page 20: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 19

What’s Included with the P16 UPS • 1050W/1500 VA, 230V UPS • Powerware 9125 UPS User’s Guide • Powerware 9125 Installation Guide for IBM Applications • X-Slot Relay Interface Adapter Card User’s Guide • X-Slot RIA Quick Start Guide • AS/400 Interface Cable (6 ft/1.8m) • (3) IEC-320-C13 to IEC-320-C14 Equipment Power Cords • (2) Pedestals (Black)

P16 Options Various options are available depending on application. For POWER (IBM i, i5/OS)), System i applications, consult chart below to select appropriate feature codes to order with the P16 UPS.

Description IBM Feature Code

IBM Part Number

POWER (IBM i, i5/OS),

i5-System i Tower Worldwide

Extended Battery Module (EBM) (up to 4 EBMs) 6605 39J4813 Yes

Page 21: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 20

Powerware 9910-E30 2100 Watt/3000 VA, 208-240 Vac UPS

Features and Benefits • Isolates connected equipment from all incoming power problems to provide

the highest degree of protection with rugged, online design • Conserves valuable rack space with compact 2U form factor • Significantly increases battery service life and gives you advanced warning

of the end of useful battery life with ABM technology • Prolongs backup time with 2U Extended Battery Modules • Optional interface/communication cards expand control of application • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

E30 Model Guide

Model Number

IBM Number

Power Out (Watts/VA)

Input Connection Output Connections Dimensions

(HxWxD, in/mm) Unit Weight (lb/kg)

208-240 Vac; 50/60 Hz auto-sensing

9910-E30 42R8069 2100/3000 Varies1 (4) IEC-320-C13, (1) IEC-320-C19

3.5 x 17 x 19.4/ 89 x 432 x 493 34/15

9910-E30 + FC 6570

42R8069 + 42R4 320 2100/3000 Varies

(4) 6-20R, (2) 5-20R, (2) L6-15R

7 x 17 x 19.4/ 178 x 432 x 493 68/31

Extended Battery Module

9910-6644 42R8071 — — — 3.5 x 17 x 19.4/ 89 x 432 x 493 65/29.5

1. E30 input (mains) connection varies by country. Optional input (mains) connection type IEC-309 P+N+G 32 Amp (FC 2976) available. See Line Cord Options table. E30 Battery Runtimes Chart (in Minutes)

Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs 875W/1250 VA 16 57 90 150 200 1050W/1500 VA 13 55 72 120 160 1750W/2000 VA 7 28 48 68 88 2100W/3000 VA 5 25 38 54 70

Note:This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc. E30 UPS Rear Panel

Page 22: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 21

What’s Included with the E30 UPS • 2100W /3000 VA, 208-240V UPS • E30 Accessory Kit (IBM Part Number 42R8070)

- UPS Safety Manual - Powerware 9125 (2500–3000 VA) UPS User’s Guide - Powerware 9125 (9910 E30) Installation Guide for IBM Applications - Powerware Software Suite CD - Serial Cable, DB-9 to DB-9 (6 ft/1.8m) - Serial Cable, RJ-45 to DB-9 (6 ft/1.8m) - Four IEC 320-C13 to C14, 10A equipment power cords (6.6ft/2m) - One IEC 320-C19 to C20, 16A equipment power cord (14.8ft/4.5m) - (4) Pedestals - (4) Pedestal Mounting Screws (M4 x 10 mm) - (2) Chrome Rack Handles - (4) Rack Handle Screws (#8-32 x 0.5”) - Rail hardware kit

E30 Options Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the E30 UPS.

Description IBM Feature Code

IBM Part Number

POWER (IBM i),

System i Tower IEC

POWER (IBM i),

System i Tower NEMA

POWER (AIX,

Linux), System p Tower IEC

POWER (AIX,

Linux), System p

Tower NEMA

POWER (AIX,

Linux), System p Rack WW

POWER (IBM i),

System i Rack WW

ConnectUPS-X Web/SNMP Card 29341 39J4824 No No Yes2 Yes2 Yes No

X-Slot Relay/Serial Card Kit 29391 42R4332 Yes Yes No No No Yes Extended Battery Module (EBM) (up to 4 EBMs) 66442 42R8071 Yes Yes Yes Yes Yes Yes

EBM Accessory Kit (1 per FC 6644) — 42R8072 Yes Yes Yes Yes Yes Yes

PDU to UPS Power Cord 2974 42R4333 No No No No Yes Yes 1. Maximum one FC 2934 or 2939 per E30 UPS. 2. ConnectUPS-X Web/SNMP Card required if implementing Logical Partitions (LPARs) on POWER Systems (AIX or Linux), p5 or System p.

E30 Line Cord Options

Feature Code Description 9866 C19 to CEE 7 VII (16 Amp) 9867 C19 to SABS 164 (16 Amp) 9868 C19 to CEI 23-16 (16 Amp) 9871 C19 to IEC-309 P+N+G (16 Amp) 9872 C19 to SII 32-1971 (16 Amp) 9874 C19 to SAA-AS 3112 (16 Amp) 9875 C19 to IEC 60083-A5 (16 Amp)

Page 23: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 22

E30 Technical Specifications*

Electrical Input

Nominal Voltage 208, 220, 230 and 240 Vac

Input Voltage Ranges 160–288V (without using batteries)

Input Power Factor >0.95 typical

Frequency 50/60 Hz, auto-sensing

Frequency Range 46–65 Hz

Electrical Output

On Utility Voltage Regulation ±3% of nominal

On Battery Voltage Regulation ±3% of nominal

Efficiency 89–92% depending on load

Frequency Regulation ±3 Hz online; ±1 Hz on battery

Load Crest Factor 3 to 1 ratio

Communications

Communication Port RS-232 communication port standard; optional X-Slot cards available

Communication Cable 6-ft Serial (DB-9 to DB-9) and 6-ft (RJ-45 to DB-9) cables included

Battery

UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid

UPS Internal Battery Type 9 Ah, sealed, maintenance-free lead-acid

Battery Runtime See Battery Runtime Chart

Battery Replacement Hot-swappable UPS internal batteries and external batteries modules

Recharge Time <2 hours from complete discharge to 80% capacity at nominal line conditions

Start-On-Battery Allows start of UPS without utility input

General

Topology True online, double-conversion

Diagnostics Full system self-test on power up

UPS Bypass Automatic on overload or UPS failure

Dimensions and Weight See Model Guide

Environmental and Safety

Ambient Operating Temperature 0°C to 40°C (32°F to 104°F)

Storage Temperature 0°C to 25°C (32°F to 77°F)

Relative Humidity 0% to 90% noncondensing

Heat Dissipation 186666 BTU/hr, maximum

Leakage Current <0.6 mA typical

Audible Noise <45 dBA typical

REPO Port Meets NEC code 645-11 intent and UL requirements

Network Transient Protector In and out jack for models only or 10BaseT network cable protection. UL497A tested

Safety Markings CSA, VDE, CE, S, D, N, FI, B, NOM, R

EMC Compliance FCC Class B and VCCI Class II, 3000 FCC Class A

Surge Suppression IEEE/ANSI C62.41 Category B (formerly 587) * Due to continuing product improvement programs, specifications subject to change without notice.

Page 24: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 23

Powerware 9910-E33 2700 Watt/3000 VA, 208-240 Vac UPS

Features and Benefits • 0.9 power factor delivers more real output power in order to power more servers than another UPS

of equivalent VA rating • Conservers valuable space with 2U rack height • Hot-swappable batteries and power module allow you to service or replace batteries and

electronics without interrupting power to protected loads or removing the UPS from the rack • Significantly increases battery service life and gives you advanced warning of the end of useful

battery life with ABM technology • Prolongs backup time with Extended Battery Modules • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

E33 Model Guide

Model Number IBM Number Power Out

(Watts/VA) Input Connection

Output Connections

Dimensions (HxWxD, in/mm)

Unit Weight (lb/kg)

208-240 Vac; 50/60 Hz auto-sensing

9910-E331 42R8065 2700/3000 varies2 (9) IEC-320-C13, (1) IEC-320-C19

3.5 (2U) x 17.5 x 24.5/ 89 x 440 x 610 89/40.4

Extended Battery Module (EBM)

9910-6643 42R8067 — — — 3.5 (2U) x 17.5 x 24.5/ 89 x 440 x 610 100/45.5

1. E33 includes (4) IEC-320-C13 to IEC-320-C14 and (1) IEC-320-C19 to C20 interconnecting cords. 2. E33 input (mains) connection varies by country. Optional input (mains) connection type IEC-309 P+N+G 32 Amp (FC 2976) available. See Line Cord Options table. E33 Battery Runtimes Chart (in Minutes)

Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs 1350W/1500 VA 15 61 103 146 190 2700W/3000 VA 5 25 49 69 90

Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.

Page 25: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 24

E33 Technical Specifications*

Electrical Input

Nominal Voltage 208, 220, 230, and 240 Vac

Input Voltage Ranges 154–288V

Frequency 50/60 Hz, auto-sensing

Frequency Range 46–65 Hz

Electrical Output

On Utility Voltage Regulation -10% to +6% of nominal

On Battery Voltage Regulation ±5% RMS

Voltage Wave Shape (on battery Sine wave

Output Protection Short circuit protection

Battery

Battery Type Sealed, maintenance-free lead-acid

Battery Runtime See Battery Runtime Chart

Battery Replacement Hot-swappable UPS internal batteries and external batteries modules

Recharge Time <3 hours to 90% usable capacity

Start-On-Battery Allows start of UPS without utility input

General

Diagnostics Full system self-test on power up

UPS Bypass No bypass, internal bypass

Transfer Time 2-4 ms typical

Dimensions and Weight See Model Guide

Communications

User Interface Front control panel

Audible Alarms For UPS alarm conditions, including: On Battery, Low Battery, Overload, & UPS fault

Network Transient Protector UL497A, in/out jacks RJ-45

REPO Port Meets NEC code 645-11 intent and UL requirements

X-Slot Interface RS-232 Single-Port Serial Card (standard); other options available

Cable 6-ft communication (DB-9 to DB-9) cable included

Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)

Environmental and Safety

Operating Temperature 0 to 40°C (32 to 104°F)

Storage Temperature -15 to 50°C (5 to 122°F)

Relative Humidity 0% to 95% noncondensing

Heat Dissipation 695 BTU/hr, maximum

Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5

Surge Energy Rating 480 Joules

Audible Noise <40 dBA typical

Altitude 3000m (10,000 ft) without derating

Safety Certifications UL; cUL; NOM; C-Tick; CE mark

EMC Compliance FCC Part 15, EN50091-2, Class A * Due to continuing product improvement programs, specifications subject to change without notice.

Page 26: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 25

What’s Included with the E33 UPS • 2700W/3000 VA, 208–240V UPS • E33 Accessory Kit (IBM Part Number 42R8066) • Powerware 5125 (2500–3000 VA) UPS User’s Guide • Powerware 5125 (9910 E33) Installation Guide for IBM Applications • (4) IEC-320-C13 to IEC-320-C14, 10A Equipment Power Cords (6 ft/1.8m) • (1) IEC-320-C19 to IEC-320-C20, 16A Equipment Power Cord (14.8ft/4.5m) • (1) IBM PDU (FC types supported: #7188, #9188, #5889 or #7109) to IEC-320-C20 [formerly FC 2974]

Power Cord (6ft/1.8m) • Powerware Software Suite CD • Serial Cable, DB-9 to DB-9 (6 ft/1.8m) • Bag of Cord Retention Clips • Mounting handle and screws • Rail hardware kit E33 Options Matrix Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the E33 UPS.

Description IBM Feature Code

IBM Part Number

POWER (AIX, Linux),

System p Rack Worldwide

POWER (IBM i), System i Rack

Worldwide

ConnectUPS-X Web/SNMP Card 29341 39J4824 Yes No

X-Slot Relay/Serial Card Kit 29391 42R4332 No Yes Extended Battery Module (EBM) (up to 4 EBMs) 6643 42R8067 Yes Yes

1. Maximum one FC 2934 or 2939 per E33 UPS. ConnectUPS-X Web/SNMP Card required if implementing Logical Partitions (LPARs) on POWER Systems (AIX or Linux), p5 or System p. E33 Line Cord Options

Feature Code Description 9866 C19 to CEE 7 VII (16 Amp) 9867 C19 to SABS 164 (16 Amp) 9868 C19 to CEI 23-16 (16 Amp) 9871 C19 to IEC-309 P+N+G (16 Amp) 9872 C19 to SII 32-1971 (16 Amp) 9874 C19 to SAA-AS 3112 (16 Amp) 9875 C19 to IEC 60083-A5 (16 Amp)

Page 27: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 26

Powerware 9910-E64 4200 Watt/6000 VA, 208-240 Vac UPS

Features and Benefits • Isolates connected equipment from all incoming power problems to

provide the highest degree of protection with rugged, online design • Conservers valuable space with compact design • Significantly increases battery service life and gives you advanced warning of the end of useful

battery life with ABM technology • Prolongs backup time with 3U Extended Battery Modules • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

E64 Model Guide

Model Number

IBM Number

Power Out (Watts/VA)

Input Connection2

Output Connection

Dimensions (HxWxD, in/mm)

Unit Weight (lb/kg)3

208-240 Vac; 50/60 Hz auto-sensing

9910-E641 42R8073 4200/6000 L6-30AR (1) L6-30R 8.75 (5U) x 17 x 24.9/ 219 x 432 x 633 206/93.6

Extended Battery Module (EBM)

9910-6645 42R8076 — — — 5.25 (2U) x 17 x 24.75/ 133 x 432 x 628 169/76.8

1. Base configuration of the E64 consists of E64 Accessory Kit (IBM p/n 42R8074) and two UPS internal battery trays (IBM p/n 42R4316). 2. Input power cord is 1.5 ft/0.5m. Requires input power cord supplied by IBM. Types vary. See Line Cord Options table. 3. Weight includes batteries. E64 Battery Runtimes Chart (in Minutes)

Load in Watts UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs 1400 38 108 186 271 362 2100 34 70 122 178 237 2800 19 49 86 125 168 3500 13 37 65 96 128 4200 10 30 52 76 102

Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc. E64 UPS Rear Panel

Page 28: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 27

What’s Included with the E64 UPS • 4200W/6000 VA, 208–240V UPS • (2) UPS Internal Battery Trays (IBM Part Number 42R4316) • E64 Accessory Kit (IBM Part Number 42R8074)

- UPS Safety Manual - UPS Lower Front Panel (Bezel) Black - Powerware 9125 (5000/6000 VA) UPS User’s Guide - Powerware 9125 (9910 E64) Installation Guide for IBM Applications - Powerware Software Suite CD - Serial Cable, RJ-45 to DB-9 (6 ft/1.8m) - Serial Cable, DB-9 to DB-9 (6 ft/1.8m) - Battery Retaining Bracket - (2) Battery Retaining Bracket Screws (M4 x 10 mm) - (4) Pedestals - (4) Pedestal Mounting Screws (M4 x 10 mm)

E64 Line Cord Options

Feature Code Description 1424 L6-30R to IEC-309 P+N+G (32 Amp) 1426 L6-30R to PDL Australia (30 Amp) 1427 L6-30R to PDL New Zealand (30 Amp)

Page 29: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 28

E64 Technical Specifications*

Electrical Input

Nominal Voltage 208, 220, 230, and 240 Vac

Input Voltage Ranges 160–288V (without using batteries)

Frequency 50/60 Hz, auto-sensing

Input Power Factor >0.96 in any mode

Frequency Range 50 Hz: 47–53 Hz; 60 Hz: 57–63 Hz

Electrical Output

On Utility Voltage Regulation ±3% of nominal

On Battery Voltage Regulation ±3% of nominal

Efficiency >85% online mode; >90% high-efficiency mode

Frequency Regulation ±3 Hz online; +1 Hz on battery; +3 Hz high-efficiency mode

Load Crest Factor 3 to 1 ratio

Communications

Communication Port RS-232 communication port standard; optional X-Slot cards available

Communication Cable Two (2) 6-ft communication cable included (DB-9 to DB-9 and RJ-45 to DB-9) included

Battery

UPS Internal Battery Type 7 Ah, sealed, maintenance-free lead-acid

EBM Battery Type 9 Ah, sealed, maintenance-free lead-acid

Battery Type Sealed, maintenance-free lead-acid

Battery Runtime See Battery Runtime Chart

Battery Replacement Hot-swappable UPS internal batteries and external batteries modules

Recharge Time <2 hours from complete discharge

Start-On-Battery Allows start of UPS without utility input

General

Topology True online, double-conversion

Diagnostics Full system self-test on power up

UPS Bypass Automatic on overload or UPS failure

Dimensions and Weight See Model Guide

Environmental and Safety

Ambient Operating Temperature 0°C to 40°C (32°F to 104°F)

Storage Temperature 0°C to 25°C (32°F to 77°F)

Relative Humidity 5% to 90% noncondensing

Heat Dissipation 2066 BTU/hr, maximum

Audible Noise <45 dBA typical; <50 dBA (on battery)

REPO Port Meets NEC code 645-11 intent and UL requirements

Safety Markings UL, cUL, VDE, CE, NOM, NYCE, GS

EMC Compliance FCC-A, VCCI-A, BSMI-A, C-Tick, CE Compliance

Surge Suppression ANSI C62.41 Category B3, and EN61000-4-5 Level 3 Criteria B * Due to continuing product improvement programs, specifications subject to change without notice.

Page 30: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 29

E64 Applications Matrix Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the E64 UPS.

Description IBM Feature Code

IBM Part Number

POWER (IBM i),

System i Tower

IEC

POWER (IBM i),

System i Tower NEMA

POWER (AIX,

Linux), System p

Tower IEC

POWER (AIX,

Linux), System p

Tower NEMA

POWER (AIX,

Linux), System p Rack WW

POWER (IBM i),

System i Rack WW

NEMA PowerPass Distribution Module 6571 42R4318 No Yes No Yes No No

IEC PowerPass Distribution Module 65723 42R4319 Yes No Yes No No No

#7188, #9188, #5889 or #7109 PDU to UPS power cord 14-feet of 4-feet (respectively)

2972 or 2973

25R2555 or 42R4331 No No No No Yes Yes

UPS Input Power Cord Varies Varies Yes Yes Yes Yes Yes Yes

Options

ConnectUPS-X Web/SNMP Card 29341 39J4824 No No Yes Yes Yes2 No

X-Slot Relay/Serial Card Kit 29391 42R4332 Yes Yes No No No Yes Extended Battery Module (EBM) (up to 4 EBMs) 6645 42R8075 Yes Yes Yes Yes Yes Yes

EBM Accessory Kit (1 per FC 6645) — 42R8076 Yes Yes Yes Yes Yes Yes

1. Maximum one FC 2934 or 2939 per E64 UPS. 2. ConnectUPS-X Web/SNMP Card required if implementing Logical Partitions (LPARs) on POWER Systems (AIX or Linux), p5 or System p. 3. Used with 6572 EMA Power Cord Kit consists of two IEC-320-C13 to NEMA 5-15P power cords (6 ft/1.8m), four IEC-320-C13 to NEMA 6-15P power cords (6 ft/1.8m), and two IEC-320-C19 to NEMA 6-20P power cords (14 ft/4.4m).

Page 31: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 30

Powerware 9910-E65 4500 Watt/5000 VA, 208-240 Vac UPS

Features and Benefits • High power, low profile design ideal for dense i5, p5,

System i, System p and Power configurations • Supports multiple PDUs (1–3 PDUs in a non-redundant power configuration and

2–6 PDUs in a dual-redundant power configuration) • Maximizes 32A 1-phase input (mains) power connection capacity by providing 4500

watts of output power • Single SKU supports System i and System p • Optional interface/communication cards expand control of application • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

E65 Model Guide1

Model Number IBM Number Power Out

(Watts/VA) Input Connection2

Output Connections

Dimensions (HxWxD, in/mm)

Unit Weight (lb/kg) 3

208-240 Vac; 50/60 Hz auto-sensing

9910-E651 42R8077 4500/5000 L6-30P (1) L6-30R, (4) IEC-320-C13, (4) IEC-320-C19

5.25 x 17.5 x 26/ 133.5 x 444 x 660 161/67

Extended Battery Module (EBM)

9910-6645 42R8075 — — — 5.25 x 17.5 x 24.75/ 133.5 x 444 x 620 169/76

1. Base configuration for the E65 consists of the E65 Accessory Kit (IBM p/n 42R8078) and two UPS Internal Battery Trays (IBM p/n 39J2536). 2. Input power cord is 1.5ft/0.5 m. Requires input power cord supplied by IBM. Types vary. See Line Cord Options table. 3. Weight includes batteries. E65 Battery Runtimes Chart (in Minutes)

Load in Watts UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs 900 59 169 303 452 612 1800 26 79 138 204 274 2250 19 61 106 156 210 2700 15 49 85 125 168 3150 13 43 73 110 142 4050 8 27 52 76 89 4500 7 24 46 67 80

Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.

Page 32: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 31

E65 Technical Specifications*

Electrical Input

Nominal Voltage 200/208, 220, 230, and 240 Vac

Input Voltage Ranges 160–288V

Frequency 50/60 Hz, auto-sensing

Frequency Range 46–54 Hz for 50 Hz; 56–64 Hz for 60 Hz

Electrical Output

On Utility Voltage Regulation -10% to +6% of nominal

On Battery Voltage Regulation ±5% RMS

Voltage Wave Shape (on battery Sine wave

Output Protection Short circuit protection

Battery

Battery Type Sealed, maintenance-free lead-acid

Battery Runtime See Battery Runtime Chart

Battery Replacement Hot-swappable UPS internal batteries and external batteries modules

Recharge Time <3 hours to 90% usable capacity

Start-On-Battery Allows start of UPS without utility input

General Electrical Power Module Replacement Yes, hot-swap

Diagnostics Full system self-test on power up

UPS Bypass Internal bypass

Transfer Time 4 ms typical, 6 ms max

Overload (normal operation) 100-102% indefinite, 103-112% 2 minutes and >112% 12 line cycles

Dimensions and Weight See Model Guide

Communications

User Interface Front control panel

Audible Alarms For various UPS alarm conditions, including: On Battery, Low Battery, Overload, and UPS Fault

REPO Port Meets NEC code 645-11 intent and UL requirements

Communication Ports Native USB and serial port

X-Slot Interface Empty; other X-Slot options available

Cable 6-ft communication cable included

Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)

Environmental and Safety

Operating Temperature 10 to 40°C (50 to 104°F)

Storage Temperature -25 to 55°C (-13 to 131°F)

Relative Humidity 0% to 95% noncondensing

Heat Dissipation 2730 BTU/hr, maximum

Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5

Surge Energy Rating High-energy 6500A peak

Audible Noise <45 dBA typical

Altitude 3000m (10,000 ft) without derating

Safety Certifications UL; cUL; NOM; C-Tick; CE marking, TUV/VDE, GS

EMC Compliance FCC Part 15, EN50091-2, Class A * Due to continuing product improvement programs, specifications subject to change without notice.

Page 33: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 32

What’s Included with the E65 UPS • 4500W/5000 VA, 208–240V UPS • (2) Battery Trays (IBM Part Number 39J4828) • Accessory kit (IBM Part Number 42R8078) consisting of

- UPS Front Panel (Bezel) Black - Powerware 5125 (5000/6000 VA) User’s Guide - Powerware 5125 (9910 E65) Installation Guide for IBM Applications - UPS Safety Manual - Powerware Software Suite CD - Serial Cable, RJ-45 to DB-9 (6 ft/1.8m) - Serial Cable, DB-9 to DB-9 (12 ft/3.6m) - Rail Hardware Kit - REPO Connector Plug 10A, 2-pin

E65 Options Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the E65 UPS.

Description IBM Feature Code

IBM Part Number

POWER (AIX, Linux),

System p Rack

Worldwide

POWER (IBM i),

System i Rack

Worldwide Rack Mounting Bracket Kit — 42R4322 Yes Yes

ConnectUPS-X Web/SNMP Card 29341 39J4824 Yes No

X-Slot Relay/Serial Card Kit 29391 42R4332 No Yes #7188, #9188, #5889 or #7109 PDU to UPS power cord 14-feet or 4-feet (respectively) 2972 or 2973 25R2555 or

42R4331 Yes Yes

UPS Input Power Cord2 Varies Varies Yes Yes Extended Battery Module (EBM) (up to 4 EBMs) 66453 42R8075 Yes Yes

EBM Accessory Kit (1 per FC 6645) - 42R8076 Yes Yes

PDU to UPS Power Cord 29743 42R4333 Yes Yes 1. Maximum one FC 2934 or 2939 per E65 UPS. 2. UPS input power cord varies according to country requirements. 3. Used to connect a 7188/9188/5889/7109 PDU to the C19 outlet. E65 Line Cord Options

Feature Code Description 1424 L6-30R to IEC-309 P+N+G (32 Amp) 1426 L6-30R to PDL Australia (30 Amp) 1427 L6-30R to PDL New Zealand (30 Amp)

Page 34: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 33

Powerware 9910-E83 8000 Watt/10000 VA, 220-240 Vac UPS

Features and Benefits • High power, low profile design ideal for dense i5, p5 or Blades • System i, System p and Power configurations • Supports multiple PDUs (1–5 PDUs in a non-redundant power

configuration and 2-10 PDUs in a dual-redundant power configuration)

• Maximizes 63A input (mains) power connection capacity by providing 8000 watts of output power

• Single SKU supports System i and System p • Optional interface/communication cards expand control of application • Tested and approved by IBM to assure out-of-box usability • Includes premium IBM warranty

E83 Model Guide

Model Number

IBM Number

Power Out (Watts/VA)

Input Connection2

Output Connections

Dimensions (HxWxD, in/mm)

Unit Weight (lb/kg) 3

220-240 Vac; 50/60 Hz auto-sensing

9910-E831 44V3923 8000/10000 IEC309 P+N+G 63A

(1) IEC309 P+N+G 63A, (4) IEC-320-C19

10.5 x 17.2 x 30/ 266 x 437 x 762 254/115

Extended Battery Module (EBM)

9910-6646 44V3921 — — — 5.25 x 17.2 x 23.9/ 133.5 x 437 x 607 179/81

1. Base configuration for the E83 consists of the E82/E83 Accessory Kit (IBM p/n 44V3919) and four UPS Internal Battery Trays (IBM p/n 44V3920). 2. Input power cord is 9.9ft/3m. 3. Weight includes batteries. E83 Battery Runtimes Chart (in Minutes)

Load in Watts UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs

1000 80 137 189 275 365 2000 31 61 99 138 181 3000 18 38 68 92 121 4000 12 27 52 69 90 5000 9 21 42 55 72 6000 7 17 35 46 60 7000 6 14 31 40 51 8000 5 12 27 35 45

Note: This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.

Page 35: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 34

E83 Rear Panel

What’s Included with the E83 UPS • 8000W/10000 VA, 220V nominal, optional 208, 230–240V UPS • (4) Battery Trays (IBM Part Number 44V3920) • (Internal) Accessory Kit (no IBM PN)

- Mounting Brackets front and rear - Rails (left, right) and hardware

• (External) Accessory kit (IBM Part Number 44V3919) consisting of: - Powerware 9140 (9910 E82 & E83) Installation Guide for IBM Applications - User’s Guide CD (in Nine languages) - Powerware Software Suite CD - Serial Cable, RJ-45 to DB-9 (6 ft/1.8m) - Serial Cable, DB-9 to DB-9 (12 ft/3.6m) - REPO Connector Plug 10A, 2-pin

E83 Options Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the E83 UPS.

Description IBM Feature Code

IBM Part Number

POWER (AIX, Linux),

System p Rack Worldwide

POWER (IBM i),

System i Rack

Worldwide ConnectUPS-X Web/SNMP Card 29341 39J4824 Yes No

X-Slot Relay/Serial Card Kit 29391 42R4332 No Yes Extended Battery Module (EBM) (up to 4 EBMs) 6646 44V3921 Yes Yes

EBM Accessory Kit (1 per FC 6646) - 44V3922 Yes Yes

PDU to UPS Power Cord 29742 42R4333 Yes Yes 1. Maximum one FC 2934 or 2939 per E83 UPS. ConnectUPS-X Web/SNMP Card required if implementing Logical Partitions (LPARs) on POWER Systems (AIX or Linux), p5 or System p. 2. Used to connect a 7188/9188/5889/7109 PDU to the C19 outlet.

Page 36: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 35

E83 Technical Specifications*

Electrical Input

Nominal Voltage 220 default, optional; 200, 208, 230, and 240 Vac

Input Voltage Ranges 220/230/240; 174-288V or 200/208; 160–253V,

Frequency 50/60 Hz, auto-sensing

Frequency Range 45-65Hz

Default Frequency 60Hz Maximum Input Current at Nominal Utility Voltage 48A

Noise Filtering MOVs and line filter for normal and common mode noise

Connections 9.9ft/3-meter IEC309 P+N+G 63A (363P6W) power cord

Input Power Factor >0.99

Input Mode Single-phase with input power cord. Three-phase input available when input power cord removed.

Electrical Output

Regulation Nominal output voltage +/- 2% Static, +/- 10% Dynamic

Nominal Outputs

200/208/220/230/240 (voltage configurable or auto-sensing) 45/48/45/43/41A 9/10/10/10/10 kVA 7.2/8/8/8/8 kW

Output Overload

100-110%: Activates Overload alarm 110-130%: load transfers to Bypass mode after 1 minute 130-150%: load transfers to Bypass mode after 1 second >150%: load transfers to Bypass mode after 100 ms

Voltage Waveform Normal mode: Sine wave; <3% THD with linear load; <5% with nonlinear load

Output Receptacles (4) IEC-320-C19, 16A (1) IEC309 P+N+G 63A (363C6W)

Battery

Battery Type Sealed, maintenance-free, valve-regulated, lead-acid

Monitoring Advanced monitoring for earlier failure detection and warning

Configuration (32) 12V, 5 Ah

Battery Runtime See Battery Runtime Chart

Battery Replacement Hot-swappable UPS internal batteries and external batteries modules Charging (in minutes) to 80% usable capacity at nominal line voltage after full load discharge

UPS Internal Batts +1 EBM +2 EBMs +3 EBMs +4 EBM 266 336 368 398 419

Start-On-Battery Allows start of UPS without utility input

General

Battery Module Replacement Yes, hot-swap

Diagnostics Full system self-test on power up

UPS Bypass Internal bypass

Dimensions and Weight See Model Guide

Communications

User Interface Front control panel, with two-line graphical LCD with backlight

Languages User selectable

Audible Alarms For various UPS alarm conditions, including: On Battery, Low Battery, Overload, and UPS Fault

REPO Port Meets NEC code 645-11 intent and UL requirements

Communication Ports Native USB and serial port (DB-9)

X-Slot Interface Empty; other X-Slot options available

Cable Two (2) 6-ft communication cables (DB-9 to DB-9 and RJ-45 to DB-9) included

Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)

Page 37: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications 36

Environmental and Safety

Operating Temperature 0 to 40°C (32 to 104°F)

Storage Temperature -20 to 50°C (-4 to 122°F)

Relative Humidity 0% to 95% noncondensing

Heat Dissipation 2066 BTU/hr (605.5W) maximum

Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5

Surge Energy Rating High-energy 6500A peak

Audible Noise <55 dBA at 5 feet with battery fully charged, without horn

Altitude 3000m (10,000 ft) without derating

Leakage Current <3.5 mA

Surge Suppression ANSI C62.41 Category B3

Safety Certifications UL 1778; CSA C22.2, No. 107.3; EN and IEC 62040-2; NOM-019-SCFI-1993;

Agency Markings cULus, cUL, NOM, CE

EMC Compliance FCC Part 15, EN 50091-2, ICES-003

Seismic Uniform Building Code (UBC) and Bellcore for Zone 4 Earthquake * Due to continuing product improvement programs, specifications subject to change without notice.

Page 38: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

www.powerware.com/ibm +44 (0) 845 177 3410 37

Powerware Software and Connectivity

Power management software unifies and centralizes UPS management Bundled with every Powerware 9910 UPS, Powerware LanSafe power management software gives you control and visibility over all your UPS systems, using an intuitive, graphical interface and SNMP (Simple Network Management Protocol). You can securely monitor UPS and battery performance over your LAN or the Web, establish prioritized shutdown of network devices and client/server applications, test all networked UPS systems from one node, analyze trends and network conditions, and stay informed of potential power problems by pager and e-mail. Seamlessly integrate UPSs into the IBM Director Management Console with Powerware Extensions for IBM Director Management System Powerware Extensions allow administrators to monitor UPSs in the network, in real-time and obtain advance notice on critical elements of server power management, such as UPS battery status, load level, temperature and alarms for battery replacement. Monitor, diagnose, configure, set alarms, schedule self-tests, check battery, gather inventory information, and control Powerware UPSs network wide from a single console within IBM Director. Connectivity options offer maximum flexibility Connectivity options are available to suit nearly any communication requirement. The Powerware are equipped with an RS-232 serial communication port, some with built-in USB port to interface with power management software. You can customize your UPS by adding any of the following X-Slot interface options for other types of communication:

ConnectUPS Web/SNMP Interface Card (FC 2934) enables direct control and monitoring in SNMP-based networks, plus the ability to monitor UPS status and meters through a Web browser (includes built-in switch hub). Use with IBM POWER Systems (AIX, Linux), p5/System p server, OpenPower, or System x server with virtualization LPARs and/or Network (Web server) connection (UPS as a node). Relay-Serial Card and Cable Kit (FC 2939) provides DB-9 and DB-25 serial interface between the UPS and IBM POWER Systems (IBM i (i5/OS)), System i (AS/400) server and Serial Server (Microsoft Windows, Linux, AIX, or other operating systems). Includes: One (1) UPS to Server (i, i5, System i, iSeries, AS/400 type) communication cable DB-25 to DB-9 (30’/9.1m). Requires IBM provided #1827 interface cable. One (1) UPS to Server (serial) communication cable DB-9 to DB-9 (6’/1.8m).

Page 39: Power Protection Handbook for IBM System i and System …lit.powerware.com/ll_download.asp?file=9910INT_July08.pdf · 6 Powerware Power Protection Handbook for IBM 9910 International

UNITED STATES 8609 Six Forks RoadRaleigh, NC 27615 U.S.A.Toll Free: 1.800.925.4426 or 919.872.3020

www.powerware.com/ibm

Eaton, Powerware, ABM, LanSafe, ConnectUPS, and X-Slot are trade names, trademarks and/or service marks of Eaton Corporation or its sub-sidiaries and affiliates. All other trade-marks are property of their respective owners.

©2008 Eaton CorporationAll Rights ReservedPrinted in USA9910INT July 2008