    Why Be Concerned With Power Quality?Why Be Concerned With Power Quality?Why Be Concerned With Power Quality?Why Be Concerned With Power Quality?

    Protects The Integrity Of Your DataProtects The Integrity Of Your Data

    Maximizes Equipment LifeMaximizes Equipment Life

    Provides For Orderly System Shut Down.Provides For Orderly System Shut Down.

    CLEAN POWER KEEPSYOUR SYSTEM RUNNING

    CLEAN POWER KEEPSYOUR SYSTEM RUNNING

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    3/63

    1997 CLARY CORPORATION

    Power Quality ProblemsPower Quality ProblemsPower Quality ProblemsPower Quality Problems

    SurgesSurges

    SagsSags

    BrownoutsBrownouts

    BlackoutsBlackouts

    Ground LoopsGround Loops

    Noise TransientsNoise Transients

    Harmonic Distortion.Harmonic Distortion.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    4/63

    1997 CLARY CORPORATION

    Poor Power Quality SymptomsPoor Power Quality SymptomsPoor Power Quality SymptomsPoor Power Quality Symptoms

    Corrupted FilesCorrupted Files Intermittent LockupsIntermittent Lockups

    Hardware Component FailureHardware Component Failure

    Power Supply FailurePower Supply Failure

    Complete System Shut Down.Complete System Shut Down.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    5/63

    1997 CLARY CORPORATION

    Sources of Power Line ProblemsSources of Power Line ProblemsSources of Power Line ProblemsSources of Power Line Problems

    Weather InducedWeather Induced Utility CompanyUtility Company

    Neighborhood InducedNeighborhood Induced

    Internal CausesInternal Causes

    I n t e r n a l

    E n v i r o n m e n t a lU t i l i t y

    N e i g h b o r

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    6/63

    1997 CLARY CORPORATION

    Typical Office PowerTypical Office PowerTypical Office PowerTypical Office Power

    Typical Office PowerTypical Office Power(Time Elapsed - About 20 minutes)(Time Elapsed - About 20 minutes)

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    7/63

    1997 CLARY CORPORATION

    Power Protection StrategiesPower Protection StrategiesPower Protection StrategiesPower Protection Strategies

    Transient Voltage Surge Suppression (TVSS)Transient Voltage Surge Suppression (TVSS)Surge SuppressorsSurge Suppressors

    Grounding SystemsGrounding Systems

    Power Conditioners & Voltage RegulatorsPower Conditioners & Voltage Regulators

    Back-up GeneratorsBack-up Generators

    Uninterruptible Power Systems (UPS)Uninterruptible Power Systems (UPS)

    Continuous Power Systems (CPS).Continuous Power Systems (CPS).

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    8/63

    1997 CLARY CORPORATION

    TVSS - TRANSIENTTVSS - TRANSIENTVOLTAGE SURGEVOLTAGE SURGE

    SUPPRESSIONSUPPRESSION

    TVSS - TRANSIENTTVSS - TRANSIENTVOLTAGE SURGEVOLTAGE SURGE

    SUPPRESSIONSUPPRESSIONSurge SuppressorsSurge Suppressors

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    9/63

    1997 CLARY CORPORATION

    TVSS - Transient Voltage SurgeTVSS - Transient Voltage SurgeSuppressionSuppression

    TVSS - Transient Voltage SurgeTVSS - Transient Voltage SurgeSuppressionSuppression

    TVSS ComponentsTVSS ComponentsAre Activated By AAre Activated By A

    Rise In Line VoltageRise In Line Voltage

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    10/63

    1997 CLARY CORPORATION

    TVSS ConceptTVSS ConceptTVSS ConceptTVSS Concept

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    11/63

    1997 CLARY CORPORATION

    Inline Surge Suppressers Most CommonInline Surge Suppressers Most CommonInline Surge Suppressers Most CommonInline Surge Suppressers Most Common

    Typical DepartmentTypical DepartmentStore SurgeStore Surge

    SuppressersSuppressers

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    12/63

    1997 CLARY CORPORATION

    Other Forms of TVSSOther Forms of TVSSOther Forms of TVSSOther Forms of TVSS

    Installed At or Near Main PowerInstalled At or Near Main PowerPanelPanel

    Embedded Into Equipment.Embedded Into Equipment.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    13/63

    1997 CLARY CORPORATION

    TVSS TECHNOLOGIESTVSS TECHNOLOGIESTVSS TECHNOLOGIESTVSS TECHNOLOGIES

    Most Common /Most Common /Least EffectiveLeast Effective

    MOVs -Metal OxideMOVs -Metal Oxide

    VaristorsVaristors

    (Degrade with use)(Degrade with use)

    Less Common / MoreLess Common / MoreEffectiveEffective

    Avalanche DiodesAvalanche Diodes

    Gas Tube ArrestersGas Tube Arresters

    Series Mode InductorsSeries Mode Inductors

    (none of the above(none of the above

    degrade with normaldegrade with normal

    use)use)

    Many new innovative systems are a combination of the abovetechnologies.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    14/63

    1997 CLARY CORPORATION

    TVSS and NetworksTVSS and NetworksTVSS and NetworksTVSS and Networks

    Use Care When Equipment isUse Care When Equipment isInterconnected such as printers andInterconnected such as printers and

    network componentsnetwork components

    Some TVSS Devices Can ActuallySome TVSS Devices Can ActuallyIntroduce New Problems - GroundIntroduce New Problems - Ground

    Contamination.Contamination.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    15/63

    1997 CLARY CORPORATION

    TVSS Mode 1TVSS Mode 1TVSS Mode 1TVSS Mode 1

    Uses a single surge device betweenUses a single surge device between

    hot and neutral. Protects againsthot and neutral. Protects against

    normal mode disturbances.normal mode disturbances.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    16/63

    1997 CLARY CORPORATION

    TVSS Mode 2TVSS Mode 2TVSS Mode 2TVSS Mode 2

    Mode 2 uses additional surgeMode 2 uses additional surgedevices to ground. Also protectsdevices to ground. Also protects

    against common modeagainst common mode

    disturbancesdisturbances

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    17/63

    1997 CLARY CORPORATION

    TVSS Ground ContaminationTVSS Ground ContaminationTVSS Ground ContaminationTVSS Ground Contamination

    Diverting a Surge to Ground Can BeDiverting a Surge to Ground Can BeDangerous for InterconnectedDangerous for Interconnected

    Equipment!Equipment!

    Contaminated GroundContaminated Ground

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    18/63

    1997 CLARY CORPORATION

    U.S. Government TVSS ClassificationsU.S. Government TVSS ClassificationsU.S. Government TVSS ClassificationsU.S. Government TVSS Classifications

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    19/63

    1997 CLARY CORPORATION

    TVSS SummaryTVSS SummaryTVSS SummaryTVSS Summary

    Surge Suppressors are NOT PowerSurge Suppressors are NOT Power

    ConditionersConditioners

    Avoid cheap, unrated devicesAvoid cheap, unrated devices

    Observe classificationsObserve classifications

    Do not connect protected devices to un-Do not connect protected devices to un-protected devicesprotected devices

    Do not connect protected devices to un-Do not connect protected devices to un-

    protected networksprotected networks Replace degradable components.Replace degradable components.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    20/63

    1997 CLARY CORPORATION

    GROUNDINGGROUNDINGGROUNDINGGROUNDING

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    21/63

    1997 CLARY CORPORATION

    GroundingGroundingGroundingGrounding

    All Electrical Systems Must Have a GoodAll Electrical Systems Must Have a GoodGroundGround

    Safety - Reduces Shock HazardsSafety - Reduces Shock Hazards

    Equipment ProtectionEquipment Protection

    System Ground Generally Provided BySystem Ground Generally Provided By

    Electrical Contractor.Electrical Contractor.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    22/63

    1997 CLARY CORPORATION

    Grounding in a Typical BuildingGrounding in a Typical BuildingGrounding in a Typical BuildingGrounding in a Typical Building

    Grounding is generally done at mainGrounding is generally done at mainelectrical service entranceelectrical service entrance

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    23/63

    1997 CLARY CORPORATION

    Methods of GroundingMethods of GroundingMethods of GroundingMethods of Grounding

    Pipes or Plumbing in the EarthPipes or Plumbing in the Earth Special Electrodes in the EarthSpecial Electrodes in the Earth

    Method Varies with Size of ElectricalMethod Varies with Size of Electrical

    Service and Soil CompositionService and Soil Composition Only 1 Neutral-Ground BondOnly 1 Neutral-Ground Bond

    Allowed in a System After EachAllowed in a System After Each

    Transformer.Transformer.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    24/63

    1997 CLARY CORPORATION

    Neutral-Ground BondNeutral-Ground BondNeutral-Ground BondNeutral-Ground Bond

    Connection between neutral and groundConnection between neutral and ground

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    25/63

    1997 CLARY CORPORATION

    Summary On GroundingSummary On GroundingSummary On GroundingSummary On Grounding

    Good Grounding is Important -Good Grounding is Important -Particularly With InterconnectedParticularly With Interconnected

    EquipmentEquipment

    Have a Qualified ElectricalHave a Qualified ElectricalContractor Check Your BuildingsContractor Check Your Buildings

    Ground if You Suspect a Problem.Ground if You Suspect a Problem.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    26/63

    POWER CONDITIONERSPOWER CONDITIONERSPOWER CONDITIONERSPOWER CONDITIONERS

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    27/63

    1997 CLARY CORPORATION

    Power ConditionersPower ConditionersPower ConditionersPower Conditioners

    Controls Many Forms of Noise &Controls Many Forms of Noise &InterferenceInterference

    Can Provide Isolation From Utility LineCan Provide Isolation From Utility Line

    Provides Some Voltage RegulationProvides Some Voltage Regulation Relatively CheapRelatively Cheap

    Generally Passive.Generally Passive.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    28/63

    1997 CLARY CORPORATION

    Disadvantages of Power ConditioningDisadvantages of Power ConditioningDisadvantages of Power ConditioningDisadvantages of Power Conditioning

    Does Not Replace EmergencyDoes Not Replace EmergencyGenerator or UPSGenerator or UPS

    Large / BulkyLarge / Bulky

    Still Requires Good TVSS System.Still Requires Good TVSS System.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    29/63

    1997 CLARY CORPORATION

    Power Conditioning EquipmentPower Conditioning EquipmentPower Conditioning EquipmentPower Conditioning Equipment

    Tap Switching AutotransformersTap Switching Autotransformers Isolation TransformersIsolation Transformers

    Electronic Voltage RegulatorsElectronic Voltage Regulators

    Motor Generators.Motor Generators.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    30/63

    1997 CLARY CORPORATION

    Tap Switching AutotransformersTap Switching AutotransformersTap Switching AutotransformersTap Switching Autotransformers

    Provides Some Form of VoltageProvides Some Form of VoltageRegulationRegulation

    Boost Low Voltage by Switching TapsBoost Low Voltage by Switching Taps

    Cheaper Then Isolation TransformersCheaper Then Isolation Transformers

    Do Not Isolate From Utility.Do Not Isolate From Utility.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    31/63

    1997 CLARY CORPORATION

    Isolation TransformersIsolation TransformersIsolation TransformersIsolation Transformers

    Advantages:Advantages:

    Isolates Load FromIsolates Load From

    All Other CircuitsAll Other Circuits

    Recreates Neutral-Recreates Neutral-

    Ground BondGround Bond

    Rejects CommonRejects Common

    Mode Noise OnMode Noise On

    LineLine

    Disadvantages:Disadvantages:

    LargeLarge

    HeavyHeavy

    Little RegulationLittle Regulation

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    32/63

    1997 CLARY CORPORATION

    Ferroresonant TransformersFerroresonant TransformersFerroresonant TransformersFerroresonant Transformers

    All of the advantages of IsolationAll of the advantages of IsolationTransformersTransformers

    Much better at voltage regulationMuch better at voltage regulation

    Inefficient, hot & noisy.Inefficient, hot & noisy.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    33/63

    1997 CLARY CORPORATION

    Motor-Generator SetMotor-Generator SetMotor-Generator SetMotor-Generator Set

    Advantages:Advantages:

    High Quality Sine WaveHigh Quality Sine Wave

    IsolatedIsolated

    Good Ride-ThroughGood Ride-Through

    Disadvantages:Disadvantages:MechanicalMechanical

    Large, Heavy,Large, Heavy,

    NoisyNoisyCost Effective forCost Effective for

    Larger LoadsLarger Loads

    OnlyOnly

    M O T O R

    A C I N A C O U T

    G E N E R A T O R

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    34/63

    1997 CLARY CORPORATION

    UNINTERRUPTIBLE POWERUNINTERRUPTIBLE POWERSYSTEMSSYSTEMS

    UNINTERRUPTIBLE POWERUNINTERRUPTIBLE POWERSYSTEMSSYSTEMS

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    35/63

    1997 CLARY CORPORATION

    UPS - Uninterruptible PowerUPS - Uninterruptible PowerSystemsSystemsUPS - Uninterruptible PowerUPS - Uninterruptible PowerSystemsSystems

    Provide AC Power Generated FromProvide AC Power Generated FromEnergy Stored in BatteriesEnergy Stored in Batteries

    Most UPSs Include Varying Levels ofMost UPSs Include Varying Levels of

    TVSSTVSS Some Provide Full Isolation From UtilitySome Provide Full Isolation From Utility

    Many Allow Graceful Shutdown ofMany Allow Graceful Shutdown of

    Computer Systems.Computer Systems.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    36/63

    1997 CLARY CORPORATION

    Concept of UPSsConcept of UPSsConcept of UPSsConcept of UPSs

    Energy is Stored as DC in BatteriesEnergy is Stored as DC in Batteries Inverter Converts DC Back Into AC.Inverter Converts DC Back Into AC.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    37/63

    1997 CLARY CORPORATION

    Grades Of UPSsGrades Of UPSsGrades Of UPSsGrades Of UPSs

    Small Office / Desktop (Department Store)Small Office / Desktop (Department Store) Mission Critical (Servers, Workstations)Mission Critical (Servers, Workstations)

    Scientific/Medical (Lab Equipment)Scientific/Medical (Lab Equipment)

    Industrial/Ruggedized (Process Control)Industrial/Ruggedized (Process Control)

    Military (Data & Communications).Military (Data & Communications).

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    38/63

    1997 CLARY CORPORATION

    Power Ratings of UPSsPower Ratings of UPSsPower Ratings of UPSsPower Ratings of UPSs

    Power handling capacity stated inPower handling capacity stated inVA (Volt/Amps)VA (Volt/Amps)

    VA not exactly the same as WattsVA not exactly the same as Watts

    Ratio between VA and Watts is calledRatio between VA and Watts is calledthe Power Factorthe Power Factor

    Better UPSs include Power FactorBetter UPSs include Power Factor

    Correction.Correction.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    39/63

    1997 CLARY CORPORATION

    UPS Basics - Off LineUPS Basics - Off LineUPS Basics - Off LineUPS Basics - Off Line

    2 Basic UPS design topologies:2 Basic UPS design topologies:1. Off Line (Line Interactive, Standby)1. Off Line (Line Interactive, Standby)

    Single ConversionSingle Conversion

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    40/63

    1997 CLARY CORPORATION

    UPS Basics - True On LineUPS Basics - True On LineUPS Basics - True On LineUPS Basics - True On Line

    2 Basic UPS design topologies:2 Basic UPS design topologies:2. TRUE ON-LINE - Double Conversion2. TRUE ON-LINE - Double Conversion

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    41/63

    1997 CLARY CORPORATION

    Line-Interactive or Single ConversionLine-Interactive or Single ConversionUPSUPSLine-Interactive or Single ConversionLine-Interactive or Single ConversionUPSUPS

    Quiet and InexpensiveQuiet and Inexpensive Inverter is off-line - Passes AC Line DirectlyInverter is off-line - Passes AC Line Directly

    Through to Load During Normal OperationThrough to Load During Normal Operation

    Inverter powers load only when there is aInverter powers load only when there is adisturbance on input AC supplydisturbance on input AC supply

    Cannot Offer Power Factor Correction.Cannot Offer Power Factor Correction.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    42/63

    1997 CLARY CORPORATION

    Off Line DiagramOff Line DiagramOff Line DiagramOff Line Diagram

    Off Line system runs on utility power untilOff Line system runs on utility power untilinverter is neededinverter is needed

    No Power Factor CorrectionNo Power Factor Correction Can provide some voltage boostCan provide some voltage boost

    Output is usually a step wave.Output is usually a step wave.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    43/63

    1997 CLARY CORPORATION

    Step Wave UPS - ProblemsStep Wave UPS - ProblemsStep Wave UPS - ProblemsStep Wave UPS - Problems

    Never Connect a Surge Suppresser Downstream of aNever Connect a Surge Suppresser Downstream of a

    Step-Wave UPSStep-Wave UPS

    This can cause premature aging of TVSS devices.This can cause premature aging of TVSS devices.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    44/63

    1997 CLARY CORPORATION

    True On-Line / Double Conversion UPSTrue On-Line / Double Conversion UPSTrue On-Line / Double Conversion UPSTrue On-Line / Double Conversion UPS

    Critical load powered by inverter at all timesCritical load powered by inverter at all times

    Load protected from variations at all timesLoad protected from variations at all times

    Boosts low voltage w/o discharging batteryBoosts low voltage w/o discharging battery

    Better systems have Power Factor CorrectionBetter systems have Power Factor Correction

    Better systems produce clean sine wave outputBetter systems produce clean sine wave output Battery conservation and management are optimized.Battery conservation and management are optimized.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    45/63

    1997 CLARY CORPORATION

    True On Line DiagramTrue On Line DiagramTrue On Line DiagramTrue On Line Diagram

    Inverter Powers Load ContinuouslyInverter Powers Load Continuously

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    46/63

    1997 CLARY CORPORATION

    Input Voltage vs. Output VoltageInput Voltage vs. Output VoltageInput Voltage vs. Output VoltageInput Voltage vs. Output Voltage

    True On-Line Systems AlwaysTrue On-Line Systems Always

    Regenerate PowerRegenerate Power

    OFF-LINE TRUE ON-LINE

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    47/63

    1997 CLARY CORPORATION

    Power Ratings of UPSsPower Ratings of UPSsPower Ratings of UPSsPower Ratings of UPSs

    UPSs are rated by VA (not Watts)UPSs are rated by VA (not Watts)Typical Desktop PC - 200VATypical Desktop PC - 200VA

    Small Server - 200VA to 800VASmall Server - 200VA to 800VA

    Large Servers 800VA to 2KVA.Large Servers 800VA to 2KVA. Power rating must be equal to orPower rating must be equal to or

    larger than the load (cheaper systemslarger than the load (cheaper systems

    should have an even greater margin)should have an even greater margin)

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    48/63

    1997 CLARY CORPORATION

    Power Factor Correction (PFC)Power Factor Correction (PFC)Power Factor Correction (PFC)Power Factor Correction (PFC)

    Power Factor is the ratio of Watts to Volt-Amps(VA)Power Factor is the ratio of Watts to Volt-Amps(VA)

    Watts = True energy NEEDED by loadWatts = True energy NEEDED by load

    VA = Energy ABSORBED by loadVA = Energy ABSORBED by load

    Off Line UPSs incapable of PF Correction - Only TrueOff Line UPSs incapable of PF Correction - Only True

    On-Line UPSs Provide PFC.On-Line UPSs Provide PFC.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    49/63

    1997 CLARY CORPORATION

    Power Factor in ComputersPower Factor in ComputersPower Factor in ComputersPower Factor in Computers

    Computer power supplies distort powerComputer power supplies distort power

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    50/63

    1997 CLARY CORPORATION

    Good and Bad Power FactorGood and Bad Power FactorGood and Bad Power FactorGood and Bad Power Factor

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    51/63

    1997 CLARY CORPORATION

    Why is PFC Important?Why is PFC Important?Why is PFC Important?Why is PFC Important?

    Computer Power Supplies Distort Input ACComputer Power Supplies Distort Input AC Poor PF Can Cause Certain Wiring in OlderPoor PF Can Cause Certain Wiring in Older

    Buildings to Overheat.Buildings to Overheat.

    Higher Electricity Bills - Utilities Charge forHigher Electricity Bills - Utilities Charge for

    VA, Not Watts!VA, Not Watts! Interaction With Other EquipmentInteraction With Other Equipment

    PFC Now a Requirement in Europe and willPFC Now a Requirement in Europe and will

    soon be in USA.soon be in USA.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    52/63

    1997 CLARY CORPORATION

    CONTINUOUS POWERCONTINUOUS POWERSYSTEMSSYSTEMS

    CONTINUOUS POWERCONTINUOUS POWERSYSTEMSSYSTEMS

    Next Generation Of UninterruptibleNext Generation Of Uninterruptible

    Power SystemsPower Systems

    N t tiN t tiN t tiN t ti

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    53/63

    1997 CLARY CORPORATION

    Next-generation:Next-generation:On-Line Triple Conversion UPSOn-Line Triple Conversion UPSNext-generation:Next-generation:On-Line Triple Conversion UPSOn-Line Triple Conversion UPS

    All digital - digitally recreated sine waveAll digital - digitally recreated sine waveThird step of DC to DC conversionThird step of DC to DC conversion

    for extended voltage regulationfor extended voltage regulation

    Better Power Factor CorrectionBetter Power Factor Correction

    High Frequency IsolationHigh Frequency Isolationno bulky transformersno bulky transformers

    Higher efficiency - less heat, less coolingHigher efficiency - less heat, less cooling

    Greater connectivityGreater connectivity

    Better battery management.Better battery management.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    54/63

    1997 CLARY CORPORATION

    SOFTWARE / CONNECTIVITYSOFTWARE / CONNECTIVITYSOFTWARE / CONNECTIVITYSOFTWARE / CONNECTIVITY

    Why Monitor Your PowerWhy Monitor Your PowerWhy Monitor Your PowerWhy Monitor Your Power

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    55/63

    1997 CLARY CORPORATION

    Why Monitor Your PowerWhy Monitor Your PowerSystem?System?Why Monitor Your PowerWhy Monitor Your PowerSystem?System?

    Use as Problem Analysis and SolvingUse as Problem Analysis and SolvingToolTool

    Shutdown Software Safely ClosesShutdown Software Safely Closes

    Files and ApplicationsFiles and Applications

    Remote Management SavesRemote Management Saves

    Administration Costs.Administration Costs.

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    56/63

    1997 CLARY CORPORATION

    Network Monitoring CapabilitiesNetwork Monitoring CapabilitiesNetwork Monitoring CapabilitiesNetwork Monitoring Capabilities

    Set alarms for problem conditionsSet alarms for problem conditions Remote alarm notificationRemote alarm notification

    Local and remote system shutdownLocal and remote system shutdown

    Remote rebooting and load controlRemote rebooting and load control

    Instantaneous power status -Instantaneous power status -

    input/output voltage and powerinput/output voltage and power

    Record power and event histories.Record power and event histories.

    Power System Monitoring &Power System Monitoring &Power System Monitoring &Power System Monitoring &

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    57/63

    1997 CLARY CORPORATION

    Power System Monitoring &Power System Monitoring &ControlControlPower System Monitoring &Power System Monitoring &ControlControl

    2 ways to connect:2 ways to connect:Direct local connection (serialDirect local connection (serial

    cable)cable)

    Network connection (SNMP)Network connection (SNMP)

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    58/63

    1997 CLARY CORPORATION

    Direct UPS ConnectivityDirect UPS ConnectivityDirect UPS ConnectivityDirect UPS Connectivity

    UPS Connects Directly toUPS Connects Directly toWorkstation via Serial CableWorkstation via Serial Cable

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    59/63

    1997 CLARY CORPORATION

    Network ConnectivityNetwork ConnectivityNetwork ConnectivityNetwork Connectivity

    SNMP Connectivity on NetworksSNMP Connectivity on Networks

    Monitoring Over a Network UsingMonitoring Over a Network UsingMonitoring Over a Network UsingMonitoring Over a Network Using

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    60/63

    1997 CLARY CORPORATION

    Monitoring Over a Network UsingMonitoring Over a Network UsingSNMPSNMPMonitoring Over a Network UsingMonitoring Over a Network UsingSNMPSNMP

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    61/63

    1997 CLARY CORPORATION

    POWER PROTECTION SUMMARYPOWER PROTECTION SUMMARYPOWER PROTECTION SUMMARYPOWER PROTECTION SUMMARY

    Transient Voltage Surge SuppressionTransient Voltage Surge Suppression(TVSS)(TVSS)

    Surge SuppressorsSurge Suppressors

    Grounding SystemsGrounding Systems

    Power Conditioners & Voltage RegulatorsPower Conditioners & Voltage Regulators

    Back-up GeneratorsBack-up Generators

    Uninterruptible Power Systems (UPS)Uninterruptible Power Systems (UPS)

    Continuous Power Systems (CPS).Continuous Power Systems (CPS).

    WHY BE CONCERNED WITH POWERWHY BE CONCERNED WITH POWERWHY BE CONCERNED WITH POWERWHY BE CONCERNED WITH POWER

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    62/63

    1997 CLARY CORPORATION

    WHY BE CONCERNED WITH POWERWHY BE CONCERNED WITH POWERQUALITY?QUALITY?

    WHY BE CONCERNED WITH POWERWHY BE CONCERNED WITH POWERQUALITY?QUALITY?

    CLEAN POWER KEEPSYOUR SYSTEM RUNNING

    CLEAN POWER KEEPSYOUR SYSTEM RUNNING

  • 8/8/2019 POWER QUALITY=Clary-PowerQualityBasics2 MOD 033010

    63/63

    Thank YouThank YouThank YouThank You

    When it absolutely, positively has to keep running!When it absolutely, positively has to keep running!