MUD-SNet-UM-PC-003 REG No. 749921389 LED Diagnostic CASE Before Application Execute Hardware Initialization Memory Error Detected Firmware Checking / Status Update Erase Firmware Erase Error Detected Update Firmware Update Error Detected Verify Firmware Verify Error Detected Loading Application No Application Detected Normal Operation Normal Operation (Busy) Remote Firmware Update LED RED GREEN YELLOW BLUE Off Off On Off Off On Off On Off On Off Off Off On Off Continues blinking Off Off Continues blinking Off Continues blinking Off Continues blinking On Continues blinking Continues blinking (slowly) On Off Continues blinking On On Blink x 1 (3 sec. interval) Continues blinking Blink x 2 (3 sec. interval) Off Blink x 3 (3 sec. interval) Off - - On Off - Off On - Off - Continues blinking - On Continues blinking (1 sec. interval) Continues blinking (1 sec. interval) Blue, Yellow, Green, and Red blink sequentially CASE Memory Error Detected Erase Error Detected Update Error Detected Verify Error Detected No Application Detected No Server Connection Fire Alarm Trigger Setup Mode Web Diagnostic On Door Forced Open, Door Left Open, Tamper Triggered, Main Power Fail On On On On Off Continues blinking Error LED RED GREEN YELLOW BLUE Continues blinking Continues blinking Continues blinking Continues blinking Off Continues blinking Continues blinking Blink x 1 (3 sec. interval) Blink x 2 (3 sec. interval) Blink x 3 (3 sec. interval) Off - - - - - Continues blinking (1 sec. interval) Continues blinking (1 sec. interval) Blue, Yellow, Green, and Red blink sequentially Please refer to UPLINK STAT LED Buzzer beeps every 10 secs. Buzzer beeps once Controller Web Diagnostic Connect network cable to RJ45 socket. Note: SNet controller supports both direct and crossover cables. Pre-Configuration SNet’s default setting after ColdStart: Host IP = 192.168.1.200 Ethernet IP = 192.168.1.210 ColdStart 2 Open Internet Explorer browser > Type http://192.168.1.210 in the address box > Key in 'admin' for username > Key in 'password10' for password. Login to Controller Web Diagnostic 3 Click System Info > Monitor system status (Server Status, Main Power Status, Tamper Status, Fire Alarm Status, Controller ID, DIPS Setting (HEX), RS485 Reader Status) Monitoring System Status 4 Click Device Info > Confirm Date Time, Device Version, Description, Internal ID, Date Time Released, Date Time Loaded, Boot Loader Version & Board Serial No. Checking Device Info 6 Click Configuration > Enter new username > Enter new password > Retype new password > Click Confirm Change Password . Changing Login Details 7 Click Configuration > Click Confirm Reset . Resetting Controller 8 Click Log Out > Log Out message will be displayed. Log Out from Web Diagnostic 9 *Note: After changing Ethernet IP, the Web Diagnostic of the controller will only accessible through the new customised Ethernet IP. Click Network Setting > Refer to the table below for detailed descriptions > Perform neccessary changes > Click Save Setting . Configuring Network Setting 5 FIELD DESCRIPTION Host IP Ethernet IP Ethernet Subnet Ethernet Gateway Ethernet Pri DNS Ethernet Sec DNS MAC Address Enhanced Network Encryption (AES 128) IP address of server PC Default: 192.168.1.200 IP address of controller Default: 192.168.1.210 Subnet mask of the controller network setting Default: 255.255.255.0 Gateway of the controller network setting Default: 192.168.1.1 Primary DNS setting Secondary DNS setting MAC address of controller Network encryption setting of controller Note: In order to use AES 128, please ensure that this is available in the application. Reader (RS485) OR Reader Interface Unit RS485 Uplink C+ C- C+ C- Multi-Purpose Relay Outputs CON37 D3+ D3- +12V (OUTPUT ONLY) LAN CON21 Buzzer C+ C- Extension Board or I/O Controller C+ C- Extension Board or I/O Controller C+ C- Extension Board or I/O Controller DC Input Terminal RS485 COM Port Interfaces External Watchdog Timer Jumper (Always shorted) Bootloader Jumper (Always opened) JTAG Interface Control Signal Jumper (Always opened) Output Power Terminal for External Board (e.g.: Extension Board, I/O Controller, RS485 Uplink, Reader Interface Unit, RS485 Reader) Note: 3A Fuse Protection for CON53 & CON54 Battery: To supply power to SRAM and RTC CPU board power status LED RJ45 Socket: 10 Base-T / 100 Base-TX Ethernet Network Interface Fire Alarm Input (Normally closed) Tamper Input (Normally closed) - + CON18 ADDRESS SETTINGS ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 ON 1 2 3 4 CONTROLLER SETTINGS SETTING Controller Type Internal Door I/O Monitoring Function Internal I/O Configuration RS485 Uplink Baud Rate ON Lift Controller (Max. 128 relay output points) Enable Configurable I/O (via xPortal) 19200 bps (Please confirm that the RS485 Uplink used supports this baud rate) OFF Door Controller (Max. 10 alarm boards) Disable (All internal I/O used for alarm function) Fixed Door I/O 9600 bps 1 2 3 4 Reader Connector 1-5 ABA / Wiegand Reader 12V 0V CLK / Data 0 Data / Data 1 LED 1 LED 2 Buzzer RS232 / RS485 SELECTOR JUMPER SETTING Short 1 & 2 RS232 port Short 2 & 3 RS485 port RS485 J26/J28 J25/J27 RS232 J27 J28 3 2 1 3 2 1 SNET Board Information & Wiring Diagram Door Relay Output 1-5 (If set to Fixed Door I/O) Multi-Purpose Inputs CON51 + - CON52 + - CON53 + - CON54 + - +12V (MAX 3A) DOWNLINK CON36 D3+ D3- CON35 D3+ D3- CON34 D2+ D2- CON33 D1+ D1- CON32 D0+ D0- UPLINK PC+ PC- COLD START RUN STAT CPU M1 M2 M3 ERR M0 SW1 RELAY / DRY CONTACT OUTPUT SELECTION J1 1 2 3 J2 1 2 3 RELAY 1 LEFT JUMPERS: J1, J3, J5, J7, J9, J11, J13, J15 Short 1 & 2: Short 2 & 3: Use as dry contact Use as relay output RIGHT JUMPERS: J2, J4, J6, J8, J10, J12, J14, J16 Short 1 & 2: Short 2 & 3: Use as NO (Normally Opened) Use as NC (Normally Closed) RS485 INTERFACES CAPACITY Extension Board & I/O Controller a) Door (5 Doors) SNet-E5D b) Lift (Max. 128 Outputs) SNet-E32R c) Alarm (Max. 10 Boards) SNet-E32R, SNet-E32S, SNet-E248S MiO-L32, MiO-S168, MiO-R16 Reader Interface Unit MK800 / MK801 Reader (RS485) MicroEngine Readers Note: SNet supports total of 10 units of reader interfaces together with RS485 readers. RELAY OUTPUT CONNECTOR INFO 12VDC GND 12V + GND NO/NC COM NO / NC COM 12V + GND NO/NC COM WET OUTPUT DRY CONTACT OUTPUT TYPICAL DOOR I/O Door Sensor Push Button S1+ S1- DS1 S2+ PB1 0V EM Lock EBG COM NO NC 12V 12V + GND NO/NC COM S2- Power Supply ON 1 2 3 4 ADDRESS ON 1 2 3 4 SETTING J16 J15 Relay 1 (Door 1) Relay 2 (Door 2) Relay 3 (Door 3) Relay 4 (Door 4) Relay 5 (Door 5) Relay 6 Relay 7 Relay 8 CON31 C+ C- Reader (RS485) RS485 RS232 J27 J28 COM1 RS485 RS232 J25 J26 COM0 COM SEL CON38 TX RX GND COM0 RS232 RS232 COM Port Interfaces RS232 / RS485 Selector Jumper J30 J31 J32 J33 PROG WDT DIAG TEST UPLINK STAT UPLINK STATUS Server PC not found Server PC found Connected to xPortal Off Blink On Test Mode Jumper WDT Disabled (Always opened) *BLOAD (Always opened) RESET SW4 RESET: Press the button to reset the controller 12V GND + NO/NC COM 12V GND + NO/NC COM 12V GND + NO/NC COM 12V GND + NO/NC COM 12V GND + NO/NC COM 12V GND + NO/NC COM 12V GND + NO/NC COM 12V GND + NO/NC COM CON22 CON23 CON24 CON25 CON26 CON27 CON28 J14 J13 J12 J11 J10 J9 J8 J7 J6 J5 J4 J3 J2 J1 RELAY8 RELAY1 RELAY2 RELAY3 RELAY4 RELAY5 RELAY6 RELAY7 COLDSTART 1. Press & hold COLDSTART button 2. Press & release RESET button 3. Wait for STAT & CPU LED light up together 4. Release COLDSTART button DIAGNOSTIC MODE 1. Short Diagnostic jumper (J32) Network setting temporary reset to default 2. Remove Diagnostic Jumper (J32) when finish network setup CON50 12V GND MAIN POWER BATT STAT Power status LED Battery status LED LEFT RIGHT WEB DIAGNOSTIC JUMPER SETTING Web Diagnostic On : All IP setup and web login will temporarily reset to default Short Web Diagnostic Off: Return to normal operation Open Buzzer will be beeping every 10 secs. RESET SW1 RESET: Press the button to reset the controller BLOAD J1 E-WDT J2 RTCK J4 PWR CPU VPP GND D0 D1 L1 L2 BUZ READER 1 VPP GND D0 D1 L1 L2 BUZ READER 2 VPP GND D0 D1 L1 L2 BUZ READER 3 VPP GND D0 D1 L1 L2 BUZ READER 4 VPP GND D0 D1 L1 L2 BUZ READER 5 Door Sensor & Push Button 1-5 (If set to Fixed Door I/O) Input 1 Door Sensor 1 CON1 S1- S1+ Input 2 Push Button 1 CON2 S2- S2+ Input 3 Door Sensor 2 CON3 S3- S3+ Input 4 Push Button 2 CON4 S4- S4+ Input 5 Door Sensor 3 CON5 S5- S5+ Input 6 Push Button 3 CON6 S6- S6+ Input 7 Door Sensor 4 CON7 S7- S7+ Input 8 Push Button 4 CON8 S8- S8+ Input 9 Door Sensor 5 CON9 S9- S9+ Input 10 Push Button 5 CON10 S10- S10+ Input 11 CON11 S11- S11+ Input 12 CON12 S12- S12+ Input 13 CON13 S13- S13+ Input 14 CON14 S14- S14+ Input 15 CON15 S15- S15+ Input 16 CON16 S16- S16+ CON17 -FIRE+ FIRE ALARM TAMPER CONFIGURATION OF CONNECTION TO READER CON32 Plato / Plato KL (Door 0 to 4, Entry & Exit) Plato / Plato KL (Door 5 to 9, Entry & Exit) OR MK800 / MK801 (Door 0 to 9) Plato / Plato KL (Lift 0 to 9, Entry) Plato / Plato KL (Lift 0 to 9, Exit) OR MK800 / MK801 (Lift 0 to 9) CON33 DOOR CONTROLLER LIFT CONTROLLER L N COM BAT COM V V (ADJ) (AC) AC Input Backup Battery DC Output Main Fail Signal + + - -

Upload: hadien

Post on 25-Apr-2018

231 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Power Supply Board Information & Wiring Diagram · Extension Board or I/O Controller C+ C-Extension Board or I/O Controller C+ C- ... Board Information & Wiring Diagram Door Relay

MUD-SNet-UM-PC-003REG No. 749921389

LED Diagnostic

CASE

Before ApplicationExecute

HardwareInitialization

Memory ErrorDetected

Firmware Checking /Status Update

Erase Firmware

Erase Error Detected

Update Firmware

Update ErrorDetected

Verify Firmware

Verify Error Detected

Loading Application

No ApplicationDetected

Normal Operation

Normal Operation(Busy)

Remote Firmware Update

LEDRED GREEN YELLOW BLUEOff

Off

On

Off

Off

On

Off

On

Off

On

Off

Off

Off

On

Off

Continuesblinking

Off

Off

Continuesblinking

Off

Continuesblinking

Off

Continuesblinking

On

Continuesblinking

Continuesblinking(slowly)

On

Off

Continuesblinking

On

On

Blink x 1(3 sec. interval)

Continuesblinking

Blink x 2(3 sec. interval)

Off

Blink x 3(3 sec. interval)

Off

-

-

On

Off

-

Off

On

-

Off

-

Continuesblinking

-

On

Continuesblinking

(1 sec. interval)

Continuesblinking

(1 sec. interval)

Blue, Yellow, Green, and Red blink sequentially

CASE

Memory ErrorDetected

Erase ErrorDetected

Update ErrorDetected

Verify ErrorDetected

No ApplicationDetected

No ServerConnection

Fire Alarm Trigger

Setup Mode

Web Diagnostic On

Door Forced Open,Door Left Open,Tamper Triggered,Main Power Fail

On

On

On

On

Off

Continuesblinking

Error

LEDRED GREEN YELLOW BLUE

Continuesblinking

Continuesblinking

Continuesblinking

Continuesblinking

Off

Continuesblinking

Continuesblinking

Blink x 1(3 sec. interval)

Blink x 2(3 sec. interval)

Blink x 3(3 sec. interval)

Off

-

-

-

-

-

Continuesblinking

(1 sec. interval)

Continuesblinking

(1 sec. interval)

Blue, Yellow, Green, and Red blink sequentially

Please refer to UPLINK STAT LED

Buzzer beeps every 10 secs.

Buzzer beeps once

Controller Web Diagnostic

Connect network cable to RJ45 socket.Note: SNet controller supports both directand crossover cables.

Pre-Configuration

SNet’s default setting after ColdStart:Host IP = 192.168.1.200Ethernet IP = 192.168.1.210

ColdStart2

Open Internet Explorer browser > Typehttp://192.168.1.210 in the address box >Key in 'admin' for username > Key in'password10' for password.

Login to Controller WebDiagnostic3

Click System Info > Monitor system status(Server Status, Main Power Status,Tamper Status, Fire Alarm Status,Controller ID, DIPS Setting (HEX), RS485Reader Status)

Monitoring System Status4

Click Device Info > Confirm Date Time,Device Version, Description, Internal ID,Date Time Released, Date Time Loaded,Boot Loader Version & Board Serial No.

Checking Device Info6

Click Configuration > Enter new username> Enter new password > Retype newpassword > Click Confirm Change Password .

Changing Login Details7

Click Configuration > Click Confirm Reset .

Resetting Controller8

Click Log Out > Log Out message will be displayed.

Log Out from Web Diagnostic9

*Note:After changing Ethernet IP, the Web Diagnostic of the controller will only accessible through the newcustomised Ethernet IP.

Click Network Setting > Refer to the table below for detailed descriptions > Perform neccessary changes> Click Save Setting .

Configuring Network Setting5

FIELD DESCRIPTION

Host IP

Ethernet IP

Ethernet Subnet

Ethernet Gateway

Ethernet Pri DNS

Ethernet Sec DNS

MAC Address

Enhanced NetworkEncryption (AES 128)

IP address of server PC Default: 192.168.1.200

IP address of controller Default: 192.168.1.210

Subnet mask of the controller network setting Default: 255.255.255.0

Gateway of the controller network setting Default: 192.168.1.1

Primary DNS setting

Secondary DNS setting

MAC address of controller

Network encryption setting of controller Note: In order to use AES 128, please ensure that this is available in the application.

Reader (RS485)OR Reader

Interface Unit

RS485 Uplink

C+

C-

C+

C-

Multi-PurposeRelay Outputs

CO

N37

D3+

D3-

+12V (O

UTP

UT O

NLY

)

LAN

CO

N21

Buzzer

C+

C-Extension Boardor I/O Controller

C+

C-Extension Boardor I/O Controller

C+

C-Extension Boardor I/O Controller

DC Input Terminal

RS485 COM PortInterfaces

External WatchdogTimer Jumper(Always shorted)

Bootloader Jumper(Always opened)

JTAG Interface Control Signal Jumper(Always opened)

Output Power Terminal for ExternalBoard (e.g.: Extension Board, I/OController, RS485 Uplink, ReaderInterface Unit, RS485 Reader)

Note:3A Fuse Protection for CON53 &CON54

Battery:To supply power toSRAM and RTC

CPU boardpower status LED

RJ45 Socket:10 Base-T / 100 Base-TXEthernet Network Interface

Fire Alarm Input(Normally closed)

Tamper Input(Normally closed)

- +

CO

N18

ADDRESS SETTINGS

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

00 01 02 03 04 05 06 07

08 09 10 11 12 13 14 15

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

CONTROLLER SETTINGS

SETTINGController Type

Internal Door I/OMonitoring Function

Internal I/O Configuration

RS485 Uplink Baud Rate

ONLift Controller

(Max. 128 relay output points)

Enable

Configurable I/O(via xPortal)

19200 bps(Please confirm that the RS485

Uplink used supports this baud rate)

OFFDoor Controller

(Max. 10 alarm boards)

Disable(All internal I/O usedfor alarm function)

Fixed Door I/O

9600 bps

1

2

3

4

ReaderConnector 1-5ABA / Wiegand

Reader12V0V

CLK / Data 0Data / Data 1

LED 1LED 2Buzzer

RS232 / RS485 SELECTORJUMPER SETTING

Short 1 & 2RS232 port

Short 2 & 3RS485 port

RS485J26/J28J25/J27

RS232J27 J28

321

321

SNET

Board Information & Wiring Diagram

Door RelayOutput 1-5

(If set to FixedDoor I/O)

Multi-PurposeInputs

CO

N51

+-

CO

N52

+-

CO

N53

+-

CO

N54

+-

+12V (M

AX

3A)

DOWNLINK

CO

N36

D3+

D3-

CO

N35

D3+

D3-

CO

N34

D2+

D2-

CO

N33

D1+

D1-

CO

N32

D0+

D0-

UP

LINK

PC

+P

C-

COLDSTARTRUN STAT CPU

M1 M2 M3

ERR

M0SW1

RELAY / DRY CONTACT OUTPUT SELECTION

J1

123

J2

123

RE

LAY 1

LEFT JUMPERS: J1, J3, J5, J7, J9, J11, J13, J15

Short 1 & 2: Short 2 & 3:Use as dry contact Use as relay output

RIGHT JUMPERS: J2, J4, J6, J8, J10, J12, J14, J16

Short 1 & 2: Short 2 & 3:Use as NO (Normally Opened) Use as NC (Normally Closed)

RS485 INTERFACES CAPACITY

Extension Board & I/O Controllera) Door (5 Doors)SNet-E5D

b) Lift (Max. 128 Outputs)SNet-E32Rc) Alarm (Max. 10 Boards)SNet-E32R, SNet-E32S, SNet-E248SMiO-L32, MiO-S168, MiO-R16

Reader Interface UnitMK800 / MK801

Reader (RS485)MicroEngine Readers

Note: SNet supports total of 10 units of readerinterfaces together with RS485 readers.

RELAY OUTPUT CONNECTOR INFO

12VDC

GND

12V+G

ND

NO

/NC

CO

M

NO / NC

COM

12V+G

ND

NO

/NC

CO

M

WET OUTPUT DRY CONTACT OUTPUT

TYPICAL DOOR I/O

DoorSensor

PushButton

S1+ S1-DS1

S2+PB1

0V

EM Lock

EBG

COMNO NC

12V

12V+

GNDNO/NCCOM S2-

Power Supply

ON

1 2 3 4

ADDRESS

ON

1 2 3 4

SETTING

J16J15

Relay 1(Door 1)

Relay 2(Door 2)

Relay 3(Door 3)

Relay 4(Door 4)

Relay 5(Door 5)

Relay 6

Relay 7

Relay 8

CON31

C+

C-Reader (RS485)RS485

RS232

J27

J28

CO

M1

RS485

RS232

J25

J26

CO

M0

COM SEL

CO

N38

TXRX

GNDCOM0

RS232

RS232COM PortInterfaces

RS232 /RS485

SelectorJumper

J30

J31

J32

J33

PROG

WDT

DIAG

TEST

UPLINK STAT

UPLINK STATUSServer PC not foundServer PC foundConnected to xPortal

OffBlinkOn

Test ModeJumper

WDT Disabled(Always opened)

*BLOAD(Always opened)

RESET

SW4

RESET:Press the button toreset the controller

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

12V G

ND

+ NO

/NC

CO

M12V

GN

D + N

O/N

C C

OM

CO

N22

CO

N23

CO

N24

CO

N25

CO

N26

CO

N27

CO

N28

J14J13

J12J11

J10J9

J8J7

J6J5

J4J3

J2J1

RE

LAY8

RE

LAY1

RE

LAY2

RE

LAY3

RE

LAY4

RE

LAY5

RE

LAY6

RE

LAY7

COLDSTART1. Press & hold COLDSTART button2. Press & release RESET button3. Wait for STAT & CPU LED light up together4. Release COLDSTART button

DIAGNOSTIC MODE1. Short Diagnostic jumper (J32) Network setting temporary reset to default2. Remove Diagnostic Jumper (J32) when finish network setup

CO

N50

12V

GN

D

MA

IN

POWER BATTSTAT

Power status LED

Battery status LED

LEFT RIGHT

WEB DIAGNOSTIC JUMPER SETTINGWeb Diagnostic On : All IP setup and web login willtemporarily reset to default

Short

Web Diagnostic Off: Return to normal operationOpen

Buzzer will be beepingevery 10 secs.

RESET

SW

1

RESET:Press the button toreset the controller

BLO

AD

J1E-W

DT

J2

RTC

KJ4

PW

RC

PU

VPPGND

D0D1L1L2

BUZ

READER 1

VPPGND

D0D1L1L2

BUZ

READER 2

VPPGND

D0D1L1L2

BUZ

READER 3

VPPGND

D0D1L1L2

BUZ

READER 4

VPPGND

D0D1L1L2

BUZ

READER 5

Door Sensor &Push Button 1-5(If set to FixedDoor I/O)

Input 1DoorSensor 1

CON1S1- S

1+

Input 2PushButton 1

CON2S2- S

2+

Input 3DoorSensor 2

CON3S3- S

3+

Input 4PushButton 2

CON4S4- S

4+

Input 5DoorSensor 3

CON5S5- S

5+

Input 6PushButton 3

CON6S6- S

6+

Input 7DoorSensor 4

CON7S7- S

7+

Input 8PushButton 4

CON8S8- S

8+

Input 9DoorSensor 5

CON9S9- S

9+

Input 10PushButton 5

CON10S10- S

10+

Input 11CON11S

11- S11+

Input 12CON12S

12- S12+

Input 13CON13S

13- S13+

Input 14CON14S

14- S14+

Input 15CON15S

15- S15+

Input 16CON16S

16- S16+

CON17

-FIRE

+

FIRE ALARM

TAMPER

CONFIGURATION OF CONNECTION TO READER

CON32 Plato / Plato KL (Door 0 to 4, Entry & Exit)Plato / Plato KL (Door 5 to 9, Entry & Exit)ORMK800 / MK801 (Door 0 to 9)

Plato / Plato KL (Lift 0 to 9, Entry)Plato / Plato KL (Lift 0 to 9, Exit)ORMK800 / MK801 (Lift 0 to 9)

CON33

DOOR CONTROLLER LIFT CONTROLLER

L N COM BAT COM V V(ADJ)(AC)

AC Input BackupBattery

DC OutputMain FailSignal

+ +- -