power supply board information & wiring diagram · extension board or i/o controller c+...
TRANSCRIPT
MUD-SNet-UM-PC-003REG No. 749921389
LED Diagnostic
CASE
Before ApplicationExecute
HardwareInitialization
Memory ErrorDetected
Firmware Checking /Status Update
Erase Firmware
Erase Error Detected
Update Firmware
Update ErrorDetected
Verify Firmware
Verify Error Detected
Loading Application
No ApplicationDetected
Normal Operation
Normal Operation(Busy)
Remote Firmware Update
LEDRED GREEN YELLOW BLUEOff
Off
On
Off
Off
On
Off
On
Off
On
Off
Off
Off
On
Off
Continuesblinking
Off
Off
Continuesblinking
Off
Continuesblinking
Off
Continuesblinking
On
Continuesblinking
Continuesblinking(slowly)
On
Off
Continuesblinking
On
On
Blink x 1(3 sec. interval)
Continuesblinking
Blink x 2(3 sec. interval)
Off
Blink x 3(3 sec. interval)
Off
-
-
On
Off
-
Off
On
-
Off
-
Continuesblinking
-
On
Continuesblinking
(1 sec. interval)
Continuesblinking
(1 sec. interval)
Blue, Yellow, Green, and Red blink sequentially
CASE
Memory ErrorDetected
Erase ErrorDetected
Update ErrorDetected
Verify ErrorDetected
No ApplicationDetected
No ServerConnection
Fire Alarm Trigger
Setup Mode
Web Diagnostic On
Door Forced Open,Door Left Open,Tamper Triggered,Main Power Fail
On
On
On
On
Off
Continuesblinking
Error
LEDRED GREEN YELLOW BLUE
Continuesblinking
Continuesblinking
Continuesblinking
Continuesblinking
Off
Continuesblinking
Continuesblinking
Blink x 1(3 sec. interval)
Blink x 2(3 sec. interval)
Blink x 3(3 sec. interval)
Off
-
-
-
-
-
Continuesblinking
(1 sec. interval)
Continuesblinking
(1 sec. interval)
Blue, Yellow, Green, and Red blink sequentially
Please refer to UPLINK STAT LED
Buzzer beeps every 10 secs.
Buzzer beeps once
Controller Web Diagnostic
Connect network cable to RJ45 socket.Note: SNet controller supports both directand crossover cables.
Pre-Configuration
SNet’s default setting after ColdStart:Host IP = 192.168.1.200Ethernet IP = 192.168.1.210
ColdStart2
Open Internet Explorer browser > Typehttp://192.168.1.210 in the address box >Key in 'admin' for username > Key in'password10' for password.
Login to Controller WebDiagnostic3
Click System Info > Monitor system status(Server Status, Main Power Status,Tamper Status, Fire Alarm Status,Controller ID, DIPS Setting (HEX), RS485Reader Status)
Monitoring System Status4
Click Device Info > Confirm Date Time,Device Version, Description, Internal ID,Date Time Released, Date Time Loaded,Boot Loader Version & Board Serial No.
Checking Device Info6
Click Configuration > Enter new username> Enter new password > Retype newpassword > Click Confirm Change Password .
Changing Login Details7
Click Configuration > Click Confirm Reset .
Resetting Controller8
Click Log Out > Log Out message will be displayed.
Log Out from Web Diagnostic9
*Note:After changing Ethernet IP, the Web Diagnostic of the controller will only accessible through the newcustomised Ethernet IP.
Click Network Setting > Refer to the table below for detailed descriptions > Perform neccessary changes> Click Save Setting .
Configuring Network Setting5
FIELD DESCRIPTION
Host IP
Ethernet IP
Ethernet Subnet
Ethernet Gateway
Ethernet Pri DNS
Ethernet Sec DNS
MAC Address
Enhanced NetworkEncryption (AES 128)
IP address of server PC Default: 192.168.1.200
IP address of controller Default: 192.168.1.210
Subnet mask of the controller network setting Default: 255.255.255.0
Gateway of the controller network setting Default: 192.168.1.1
Primary DNS setting
Secondary DNS setting
MAC address of controller
Network encryption setting of controller Note: In order to use AES 128, please ensure that this is available in the application.
Reader (RS485)OR Reader
Interface Unit
RS485 Uplink
C+
C-
C+
C-
Multi-PurposeRelay Outputs
CO
N37
D3+
D3-
+12V (O
UTP
UT O
NLY
)
LAN
CO
N21
Buzzer
C+
C-Extension Boardor I/O Controller
C+
C-Extension Boardor I/O Controller
C+
C-Extension Boardor I/O Controller
DC Input Terminal
RS485 COM PortInterfaces
External WatchdogTimer Jumper(Always shorted)
Bootloader Jumper(Always opened)
JTAG Interface Control Signal Jumper(Always opened)
Output Power Terminal for ExternalBoard (e.g.: Extension Board, I/OController, RS485 Uplink, ReaderInterface Unit, RS485 Reader)
Note:3A Fuse Protection for CON53 &CON54
Battery:To supply power toSRAM and RTC
CPU boardpower status LED
RJ45 Socket:10 Base-T / 100 Base-TXEthernet Network Interface
Fire Alarm Input(Normally closed)
Tamper Input(Normally closed)
- +
CO
N18
ADDRESS SETTINGS
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
00 01 02 03 04 05 06 07
08 09 10 11 12 13 14 15
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
CONTROLLER SETTINGS
SETTINGController Type
Internal Door I/OMonitoring Function
Internal I/O Configuration
RS485 Uplink Baud Rate
ONLift Controller
(Max. 128 relay output points)
Enable
Configurable I/O(via xPortal)
19200 bps(Please confirm that the RS485
Uplink used supports this baud rate)
OFFDoor Controller
(Max. 10 alarm boards)
Disable(All internal I/O usedfor alarm function)
Fixed Door I/O
9600 bps
1
2
3
4
ReaderConnector 1-5ABA / Wiegand
Reader12V0V
CLK / Data 0Data / Data 1
LED 1LED 2Buzzer
RS232 / RS485 SELECTORJUMPER SETTING
Short 1 & 2RS232 port
Short 2 & 3RS485 port
RS485J26/J28J25/J27
RS232J27 J28
321
321
SNET
Board Information & Wiring Diagram
Door RelayOutput 1-5
(If set to FixedDoor I/O)
Multi-PurposeInputs
CO
N51
+-
CO
N52
+-
CO
N53
+-
CO
N54
+-
+12V (M
AX
3A)
DOWNLINK
CO
N36
D3+
D3-
CO
N35
D3+
D3-
CO
N34
D2+
D2-
CO
N33
D1+
D1-
CO
N32
D0+
D0-
UP
LINK
PC
+P
C-
COLDSTARTRUN STAT CPU
M1 M2 M3
ERR
M0SW1
RELAY / DRY CONTACT OUTPUT SELECTION
J1
123
J2
123
RE
LAY 1
LEFT JUMPERS: J1, J3, J5, J7, J9, J11, J13, J15
Short 1 & 2: Short 2 & 3:Use as dry contact Use as relay output
RIGHT JUMPERS: J2, J4, J6, J8, J10, J12, J14, J16
Short 1 & 2: Short 2 & 3:Use as NO (Normally Opened) Use as NC (Normally Closed)
RS485 INTERFACES CAPACITY
Extension Board & I/O Controllera) Door (5 Doors)SNet-E5D
b) Lift (Max. 128 Outputs)SNet-E32Rc) Alarm (Max. 10 Boards)SNet-E32R, SNet-E32S, SNet-E248SMiO-L32, MiO-S168, MiO-R16
Reader Interface UnitMK800 / MK801
Reader (RS485)MicroEngine Readers
Note: SNet supports total of 10 units of readerinterfaces together with RS485 readers.
RELAY OUTPUT CONNECTOR INFO
12VDC
GND
12V+G
ND
NO
/NC
CO
M
NO / NC
COM
12V+G
ND
NO
/NC
CO
M
WET OUTPUT DRY CONTACT OUTPUT
TYPICAL DOOR I/O
DoorSensor
PushButton
S1+ S1-DS1
S2+PB1
0V
EM Lock
EBG
COMNO NC
12V
12V+
GNDNO/NCCOM S2-
Power Supply
ON
1 2 3 4
ADDRESS
ON
1 2 3 4
SETTING
J16J15
Relay 1(Door 1)
Relay 2(Door 2)
Relay 3(Door 3)
Relay 4(Door 4)
Relay 5(Door 5)
Relay 6
Relay 7
Relay 8
CON31
C+
C-Reader (RS485)RS485
RS232
J27
J28
CO
M1
RS485
RS232
J25
J26
CO
M0
COM SEL
CO
N38
TXRX
GNDCOM0
RS232
RS232COM PortInterfaces
RS232 /RS485
SelectorJumper
J30
J31
J32
J33
PROG
WDT
DIAG
TEST
UPLINK STAT
UPLINK STATUSServer PC not foundServer PC foundConnected to xPortal
OffBlinkOn
Test ModeJumper
WDT Disabled(Always opened)
*BLOAD(Always opened)
RESET
SW4
RESET:Press the button toreset the controller
12V G
ND
+ NO
/NC
CO
M12V
GN
D + N
O/N
C C
OM
12V G
ND
+ NO
/NC
CO
M12V
GN
D + N
O/N
C C
OM
12V G
ND
+ NO
/NC
CO
M12V
GN
D + N
O/N
C C
OM
12V G
ND
+ NO
/NC
CO
M12V
GN
D + N
O/N
C C
OM
CO
N22
CO
N23
CO
N24
CO
N25
CO
N26
CO
N27
CO
N28
J14J13
J12J11
J10J9
J8J7
J6J5
J4J3
J2J1
RE
LAY8
RE
LAY1
RE
LAY2
RE
LAY3
RE
LAY4
RE
LAY5
RE
LAY6
RE
LAY7
COLDSTART1. Press & hold COLDSTART button2. Press & release RESET button3. Wait for STAT & CPU LED light up together4. Release COLDSTART button
DIAGNOSTIC MODE1. Short Diagnostic jumper (J32) Network setting temporary reset to default2. Remove Diagnostic Jumper (J32) when finish network setup
CO
N50
12V
GN
D
MA
IN
POWER BATTSTAT
Power status LED
Battery status LED
LEFT RIGHT
WEB DIAGNOSTIC JUMPER SETTINGWeb Diagnostic On : All IP setup and web login willtemporarily reset to default
Short
Web Diagnostic Off: Return to normal operationOpen
Buzzer will be beepingevery 10 secs.
RESET
SW
1
RESET:Press the button toreset the controller
BLO
AD
J1E-W
DT
J2
RTC
KJ4
PW
RC
PU
VPPGND
D0D1L1L2
BUZ
READER 1
VPPGND
D0D1L1L2
BUZ
READER 2
VPPGND
D0D1L1L2
BUZ
READER 3
VPPGND
D0D1L1L2
BUZ
READER 4
VPPGND
D0D1L1L2
BUZ
READER 5
Door Sensor &Push Button 1-5(If set to FixedDoor I/O)
Input 1DoorSensor 1
CON1S1- S
1+
Input 2PushButton 1
CON2S2- S
2+
Input 3DoorSensor 2
CON3S3- S
3+
Input 4PushButton 2
CON4S4- S
4+
Input 5DoorSensor 3
CON5S5- S
5+
Input 6PushButton 3
CON6S6- S
6+
Input 7DoorSensor 4
CON7S7- S
7+
Input 8PushButton 4
CON8S8- S
8+
Input 9DoorSensor 5
CON9S9- S
9+
Input 10PushButton 5
CON10S10- S
10+
Input 11CON11S
11- S11+
Input 12CON12S
12- S12+
Input 13CON13S
13- S13+
Input 14CON14S
14- S14+
Input 15CON15S
15- S15+
Input 16CON16S
16- S16+
CON17
-FIRE
+
FIRE ALARM
TAMPER
CONFIGURATION OF CONNECTION TO READER
CON32 Plato / Plato KL (Door 0 to 4, Entry & Exit)Plato / Plato KL (Door 5 to 9, Entry & Exit)ORMK800 / MK801 (Door 0 to 9)
Plato / Plato KL (Lift 0 to 9, Entry)Plato / Plato KL (Lift 0 to 9, Exit)ORMK800 / MK801 (Lift 0 to 9)
CON33
DOOR CONTROLLER LIFT CONTROLLER
L N COM BAT COM V V(ADJ)(AC)
AC Input BackupBattery
DC OutputMain FailSignal
+ +- -