Power System Protection
Dr. Lionel R. Orama Exclusa, PEWeek 1
![Page 2: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/2.jpg)
Jan 18/2006 Copyright L.R. Orama 2006 2
Philosophy of Protective Relaying
Readings-Mason Chapter 1• Relay function• What exactly is a relay?• CT’s and PT’s• Abnormal conditions-faults• Desirable relay characteristics• Zones of protection
– Primary and backup protection
![Page 3: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/3.jpg)
Copyright L.R. Orama 2006 3
Relay function
• Causes fast disconnection of equipment from power system during abnormal conditions– Minimizes damage– Minimizes effects on the system operation– Maximizes power transfer
![Page 4: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/4.jpg)
Copyright L.R. Orama 2006 4
Relay function• Power transfer (from C.R. Mason page 13)
![Page 5: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/5.jpg)
Copyright L.R. Orama 2006 5
What exactly is a relay?
• Measuring device-receives a signal from the Power System (PS) & determines if the condition is abnormal
• Control device-for abnormal conditions, it signals Circuit Breakers (CB) to disconnect equipment– It kind of “relays” a signal from the PS to the CB– Relay & CB is a system protection team– Fuses are simpler system
![Page 6: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/6.jpg)
Copyright L.R. Orama 2006 6
What exactly is a relay?
![Page 7: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/7.jpg)
Copyright L.R. Orama 2006 7
What exactly is a CB?
![Page 8: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/8.jpg)
Copyright L.R. Orama 2006 8
What exactly is a relay?
![Page 9: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/9.jpg)
Copyright L.R. Orama 2006 9
Current Transformers (CT’s)
• Device that produces current proportional to current in the power system conductor
• Ideal CT has current of:
• Rated ICT is aprox. 5A, typically (called CT secondary current)
CT
SYSCT N
II =
![Page 10: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/10.jpg)
Copyright L.R. Orama 2006 10
Current Transformers (CT’s)
40020005
2001000:5
120600:5
80400:5
40200:5
20100:5
1050:5
TurnsCurrent
Common ratios
Polarity dot convention
![Page 11: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/11.jpg)
Copyright L.R. Orama 2006 11
Potential Transformers (PT’s)
• Device that produces voltage proportional to voltage in the power system bus
• Ideal PT has voltage of:
• Rated VPT is aprox. 120V, typically (called PT secondary voltage)
1
2
N
NVV SYSPT =
![Page 12: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/12.jpg)
Jan 20/2006 Copyright L.R. Orama 2006 12
Relaying Diagram
![Page 13: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/13.jpg)
Copyright L.R. Orama 2006 13
Simple Contacts Diagram
• Short hand notation for the trip circuit
• Control Relaying & Instrumentation Diagram (CR&I)
![Page 14: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/14.jpg)
Copyright L.R. Orama 2006 14
Relay Contacts• “a” Contact
– Open when relay that controls it is not picked up, or when CB that controls it is open
– Closed when relay that controls it is picked up, or when CB that controls it is closed
• “b” Contact– Closed when relay that controls it is
not picked up, or when CB that controls it is open
– Open when relay that controls it is picked up, or when CB that controls it closed
![Page 15: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/15.jpg)
Copyright L.R. Orama 2006 15
Contacts• A relay is said to be picked up
when its:– Its “a” contacts are closedor– Its “b” contacts are open
![Page 16: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/16.jpg)
Copyright L.R. Orama 2006 16
Faults (Short Circuits)
• Most common type of abnormal condition• Often Abnormally high currents flow IF>>IL• Flow of current in a path not intended for it• To interrupt IF, circuit must be opened• Relays often set based on calculated IF
![Page 17: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/17.jpg)
Copyright L.R. Orama 2006 17
Faults (Short Circuits)• Cause high current
– mechanical stress
• Cause high temperature arcs– destroy equipment, cause fires
• Alter system voltage• Cause system unbalance• Block the flow of power• Cause generator overspeed
– Instability, loss of synchronism
![Page 18: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/18.jpg)
Copyright L.R. Orama 2006 18
Fault Current Interruption
• No current flow when breakers open
![Page 19: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/19.jpg)
Copyright L.R. Orama 2006 19
Desirable Relay Characteristics
• Speed (time to make decision 1/60sec)– Minimizes damage from current– Maximizes power transfer and stability
• Security– Relay should not cause CB to open during
normal conditions
• Dependability (reliability)– Relay should cause CB to open during
abnormal operation
![Page 20: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/20.jpg)
Copyright L.R. Orama 2006 20
Desirable Relay Characteristics
• Sensitivity – Ability to detect all faults for the expected limiting
system and fault conditions• Selectivity
– Ability to discriminate between faults internal and external to its intended zone of protection
![Page 21: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/21.jpg)
Copyright L.R. Orama 2006 21
Primary & Backup Protection
• Relays, CB’s, CT’s & PT’s located at substations
• Substation is a point of– Interconnection– Switching– Voltage
transformation
![Page 22: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/22.jpg)
Jan 23/2006 Copyright L.R. Orama 2006 22
Primary & Backup Protection
• Every equipment should be protected by at least two independent protection systems
• Equipment– Lines, busses, transformers, generators
• Protection system– Primary and backup
![Page 23: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/23.jpg)
Copyright L.R. Orama 2006 23
Primary Protection
• Primary– To do it, zones are drawn on the system’s
one-line diagram– Zones are defined by CT location and include
equipment & CB’s that isolate equipment
![Page 24: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/24.jpg)
Copyright L.R. Orama 2006 24
Primary Protection• Primary protective zones
– CB’s located in connection to each PS equipment
– Zones configured so the fault within the zone causes all CB’s in the zone to open
– CB’s open simultaneously & instantaneously (no intentional delay)
– If primary zone is successful, minimum effect on the system (power transfer ability)
![Page 25: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/25.jpg)
Copyright L.R. Orama 2006 25
Primary Protection• Primary
protective zones– Zones defined
by the CT’slocated in the bushings of the CB’s
– Zones overlap to avoid uncovered areas and CB failure
![Page 26: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/26.jpg)
Copyright L.R. Orama 2006 26
Primary & Backup Protection
Causes of Relay Failure• CT’s and circuits• PT’s and circuits• Loss of DC supply
– Short circuit– Open circuit– Failure of auxiliary switches
• Relay failure
![Page 27: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/27.jpg)
Copyright L.R. Orama 2006 27
Primary & Backup Protection
Causes of CB failure• Loss of DC supply• Open trip coil• Short circuit trip coil• Mechanical failure• Failure of main contacts
![Page 28: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/28.jpg)
Copyright L.R. Orama 2006 28
Backup Protection• Provided in case of:
– Primary relay failure– Circuit breaker failure
• Ideally primary & backup must be independent– Relay, CB’s, CT’s, PT’s– However, duplicity of CB’s is not practical & causes
other problems
• Backup is slower than primary• Opens more CB’s than necessary to clear a fault• Provides primary protection when primary
equipment is out of service
![Page 29: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/29.jpg)
Copyright L.R. Orama 2006 29
Backup ProtectionTypes of backup protection• Remote backup
– Clears fault one substation away from where the failure has occured
• Local backup– Clears fault in the same substation where the
fault has occured
![Page 30: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/30.jpg)
Copyright L.R. Orama 2006 30
Remote Backup
• CB’s P and O opens• CB M stay closed• Then B, C and I has to open • Load is lost in this case
![Page 31: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/31.jpg)
Copyright L.R. Orama 2006 31
Remote Backup
• Trips more system than necessary to clear the fault
• Long backup times from 50-60 cycles (0.8-1.0 sec)
• Difficult to set remote relays• Initially, more economical• In the long run is more expensive
![Page 32: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/32.jpg)
Copyright L.R. Orama 2006 32
Local Backup
• Primary relay op. & energizes timer
• If CB relays remain picked up & timer times out– Opens all CB’s on
the bus (trips all CB’s)
![Page 33: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/33.jpg)
Copyright L.R. Orama 2006 33
Local Backup
• J opens• H closed• G and I opens• Load is operating
![Page 34: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/34.jpg)
Copyright L.R. Orama 2006 34
Local Backup
• P and O open• M closed• G and I opens• L trips locally• I tripped by
communicated signal (Transfer Trip)
• A special kind of backup keeps Z closed
![Page 35: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/35.jpg)
Copyright L.R. Orama 2006 35
Local Backup
When a CB does not work• Trips least amount of system in clearing a
fault• Fastest backup times are 9-20 cycles
(0.15-0.33 sec)• Simple relay settings• Initially has a higher cost
![Page 36: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/36.jpg)
Copyright L.R. Orama 2006 36
Remote vs. Local Backup
• Remote
• Local
![Page 37: Power System Protection - Electrical and Computer Engineering](https://reader035.vdocuments.net/reader035/viewer/2022071600/613d191a736caf36b7594a0f/html5/thumbnails/37.jpg)
Copyright L.R. Orama 2006 37
Remote vs. Local Backup
• Remote
• Local