www.elim.si Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèiAutomatic Power Factor Correction Equipment for Low Voltage

PREVOD FEBRUAR 2006

PQM – POWER QUALITY MANAGEMENT®

Page 2: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

Moduli za vgradnjo / Sistemi za vgradnjoAssemblies / Modular Packaging Systems

Pregled izdelkov Overview of Products

Dinamiène kompenzacijske napraveDynamic Power Factor Correction Equipment

Avtomatske kompenzacijske napraveAutomatic Power Factor Correction Equipment

Naprave z uglašenimi filtriTuned Filter Circuits Equipment

Sistemi aktivnih filtrovActive Filter Systems

Page 3: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

Vsebina Table of content

Izbor kompenzacijskih naprav 4 Selection of power factor correction equipment (PFC) 4Teoretiène osnove 5 Theoretical fundamentals 5Priporoèila za tonfrekvenèno krmiljenje 6 Recommendations for audio frequency control signals 7

Avtomatske kompenzacijske naprave Automatic power factor correction equipment Tehnièna pojasnila 8 Technical comments 8Podatki za projektiranje 9 Configuration data 9Majhne naprave v kovinskem ohišju, IP 54 10 Small equipment in steel sheet cubicle, IP 54 10Kompaktne naprave v kovinskem ohišju, IP 54 10 Compact equipment in steel sheet cubicle, IP 54 10Velike naprave 400 V 11 Large equipment 400 V 11Velike naprave 690 V 11 Large equipment 690 V 11

Avtomatske kompenzacijske naprave s kondenzatorji z dušilkami Reactor protected automatic power factorcorrection equipment

Teoretiène osnove 12 Theoretical fundamentals 12Podatki za projektiranje 14 Configuration data 14Kompaktne naprave v kovinskem ohišju 15 Compact equipment in steel sheet cubicle 15Velike naprave 400 V, 690 V, p=7 % 16 Large equipment 400 V, 690 V, p=7 % 16Velike naprave 400 V, 690 V, p=5,67 % 17 Large equipment 400 V, 690 V, p=5.67 % 17Velike naprave 400 V, 690 V, p=12,5 % 18 Large equipment 400 V, 690 V, p=12,5 % 18Velike naprave 400 V, 690 V, p=14 % 19 Large equipment 400 V, 690 V, p=14 % 19

Dinamiène kompenzacijske naprave Dynamic power factor correction equipmentSplošno, uporaba 20 General information, application 20Tehnièni podatki 22 Configuration data 22Velike naprave 400 V 23 Large equipment 400 V 23

Naprave z uglašenimi filterskimi krogi Tuned filter circuits equipmentPojasnitev pojmov, tehnièna pojasnila 24 Explanation of terms, technical comments 24Izvedba 25 Specification 25Podatki za projektiranje 26 Configuration data 26Velike naprave, 400 V, 690 V 27 Large equipment, 400 V, 690 V 27

Aktivni filterski sistemi Active filter systemsSplošno, uporaba 28 General information, application 28Lastnosti, princip delovanja 29 Features, working principle 29Tipski program 30 Range of types 30Podatki za projektiranje 31 Configuration data 31

Regulator jalove moèi Power factor controllersCX, CM 32 CX, CM 32Pro-Con 34 Pro-Con 34

Moduli za vgradnjo / Sistemi za vgradnjo Assemblies / modular packaging systemsPribor za modularne kompenzacijske naprave 35 Accessories for modular PFC-equipment 35Podatki za projektiranje 36 Configuration data 36Moduli za vgradnjo 400 V, 690 V 37 Assemblies 400 V, 690 V 37Moduli za vgradnjo 400 V, z dušilkami, raster 300 mm 38 Assemblies 400 V, reactor-protected, grid 300 mm 38Moduli za vgradnjo 690 V, z dušilkami, raster 300 mm 39 Assemblies 690 V, reactor-protected, grid 300 mm 39Moduli za vgradnjo 400 V, z dušilkami, raster 400 mm 40 Assemblies 400 V, reactor-protected, grid 400 mm 40Moduli za vgradnjo 400 V, tiristorsko krmiljeni, raster 300 mm 41 Assemblies 400 V, thyristor-controlled, grid 300 mm 41

Dimenzijske skice 42 Dimension drawings 42

Principelna prikljuèna shema naprav za kompenzacijo Schematic circuit diagram for automatic power factor jalove moèi 45 correction equipment 45

Razno MiscellaneousPrikljuèni kabel in varovalke 46 Connection cable and fuse protection 46

Page 4: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

4

Izbor kompenzacijskih naprav Selection of compensation equipment

Obremenitev z višjimi Stanje bremena, dinamika bremena / Load situation, dynamic of load changes harmonikiHarmonic stress

veliko jalovo breme majhno jalovo breme

High reactive load Low reactive load

statièno breme pogoste spremembe fliker velik nièelni tokbremena

Static load Frequent load changes Flicker High neutral current

< 15 % bremena usmernikav glavnem linearna bremena,brez paralelne resonance< 15 % converter load primarily linear load no parallel resonance

< 50 % bremena usmernika linearna in nelinerna bremena razred mreže 2 po EN61000-2-4 je prisoten < 50 % converter load linear and nonlinear loads, net class 2 acc. to EN61000-2-4 is adhered to

> 50 % bremena usmernikapretežno nelinearna bremena velika obremenitev s harmoniki> 50 % converter loadprimarily nonlinear load,high harmonic load

Kompenzacija brez dušilk ..... strani 8 – 11Compensation without reactorprotection ......................................... Pages 8 – 11

ali or

ali or

in and

Dinamièna kompenzacijaz dušilkami ..................................... strani 20 – 23Dynamic compensation withreactor protection ..................... Pages 20 – 23

Kompenzacija z dušilkami . strani 12 – 19Compensation with reactorprotection ....................................... Pages 12 – 19

Uglašeni filterski krogi ........... strani 24 – 27Tuned filter circuits ................ Pages 24 – 27

Aktivni harmonski filtri ........... strani 28 – 31Active harmonic filters.......... Pages 28 – 31

Page 5: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

5Slika 1: Vsota aktivne in jalove komponenteFig. 1: Sum of active and reactive component

Theoretiène osnove

Elektrièna moè P, ki teèe iz elektriène mreže, je enaka pro-duktu iz napetosti U, toka I in kosinusa kota zakasnitve ϕ

P = U x l x cos ϕ

Èisto aktivno moè pri periodiènih velièinah sinusne oblike do-bimo samo, èe sta tok in napetost v fazi, to je, èe imata istoè-asen prehod skozi nièlo. To je res pri ohmskih porabnikih,npr. žarnicah na nitko in elektriènem ogrevanju. Ker se dove-dena moè v veliki veèini pretvarja v drugo obliko, govorimo oaktivni moèi.

Delovanje elektriènih motorjev in transformatorjev pa zahtevamagnetna polja. Za to potrebnega dela energije pa ni mogo-èe pretvoriti v aktivno moè, zato govorimo o jalovi moèi Q.

Pri prenosu moèi naj bo nekoristen jalovi del èim manjši. Kerpa porabnik jalovo moè potrebuje, mu jo skušamo preskrbetina drug naèin kot z dobavo iz elektriène mreže. Pri tem po-maga dejstvo, da v kondenzator teèe tok, ki napetost po faziprehiteva. Èe je kapacitivna upornost kondenzatorjev enakaupornosti induktivnosti, se oba uèinka kompenzirata.

Na ta naèin je mogoèe zmanjšati jalovo moè, ki jo dobivamo(in plaèamo) od dobavitelja elektriène moèi (Slika 2). Energi-ja, ki jo vsebujeta elektrièni kondenzator in magnetna polja(induktivnosti) sta izenaèeni. Ta proces imenujemo kompen-zacija moènostnega faktorja (jalovega toka), s cos ϕ oznaèu-jemo razmerje med aktivno moèjo P in navidezno moèjo S:

cos ϕ = P_S

Theoretical fundamentals

The power P drawn from the electrical network is equal tothe product of the voltage U, the current l and the phase dis-placement angle ϕ.

P = U x l x cos ϕ

However, pure active power can only be created with sinu-soidal alternating changes when current and voltage are inphase (i.e., have their zero crossing at the same time). Thisis the case with ohmic loads (e.g., incandescent lamps andelectric heaters). Since most of the power can be used this iscalled active power. Operation of motors and transformers requires magneticfields. Since the energy required here cannot be convertedto active power, it is called reactive power Q.This useless reactive power component should be kept aslow as possible. Since such reactive power is needed by theconnected equipment, an attempt is made to supply thispower from a source other than the power network. It is help-ful that capacitors have a leading reactive current. When itscapacitive resistance is just as great as that of the inductivi-ties, the effects are cancelled out.

This can be used to reduce the reactive power obtained from(and must be paid for) power providers (Fig. 2). The power ofthe electrical (capacitor) and the magnetic fields (inductivity)cancel each other out. This procedure is called power factorcompensation. Cos ϕ is the ratio of active power P to appar-ent power S:

cos ϕ = P_S

elekrodistribucije in tudi plaèaPower input from the power providerto be paid by the customer

Moè, ki jo daje kompenzacijski kondenzatorPower input fromcompensating capacitor

Jalovamoè Q

Reactivepower Q

Potrebna navideznamoè S

Aktivnamoè PActive

power P

Jalovi tokReactive current

Jalova moèReactive power

Aktivni tokActive currentAktivna moèActive power

Navidezni tokApparent currentNavidezna moèApparent power

ϕ

cos ϕ =P/Ssin ϕ =Q/Stan ϕ =Q/P

Slika 2: Bilanca moèiFig. 2: Power balance

Page 6: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

6

Priporoèila za tonfrekvenèno centralnokrmiljenje

Naprave za tonfrekvenèno centralno krmiljenje (TFK) delujejona frekvencah med ca. 100 Hz in 1350 Hz. Odvisno od krmil-ne frekvence imajo lahko kondenzatorji brez dušilk in konde-zatorji z dušilkami nedopustne povratne vplive na TFK napra-ve. Zato je pri naèrtovanju kondenzatorske naprave potebnoupoštevati lokalno uporabljeno frekvenco centralnega krmil-jenja. Merilo za zmanjšanje tonfrekvenène impedance je faktor im-pedance α. Pri lastnem mrežnem transformatorju velja:

α = ZS–ZA

0,4 (Priporoèila za prepreèevanje nedopustnihpovratnih vplivov na centralno tonfrekvenènokrmiljenje)

ZS = Impedanca mreže pri konkretni tonski frekvenci

ZA = Impedanca mreže pri osnovni frekvenci (50 Hz)

Za doseganje faktorja impedance α 0,4 so pri naèrtovanjukondenzatorskih naprav na razpolago sledeèe možnosti: - Uporaba tonfrekvenènih zapornih krogov - Uporaba kondenzatorjev z dušilkami in s posebnimi dušil-

kami (kombinirane dušilke) - Uporaba kondenzatorjev brez dušilk

Pri stalno veèji obremenitvi mrež z usmerniki in podobnimiporabniki z nelinearnimi karakteristikami je pri vseh ukrepihza zapiranje (kondenzatorjev) potrebno paziti, da harmonskitokovi, ki jih povzroèajo ti porabniki, na elementih za zapiran-je ne povzroèajo nedopustnih obremenitev. Do teh na zapor-nih vezjih pride zaradi neizogibne resonance med kondenza-torjem in zapornim elementom. Pri projektiranju kompenza-cijske naprave, zaprte proti tonskim frekvencam, je potrebnopaziti na prisotne višje harmonike. Slika 3 podaja pregled, s kakšnimi ukrepi je pri kompenza-cijskih napravah mogoèe doseèi zadosten zaporni uèinek.Uporaba kondenzatorjev brez tonfrekvenènih zapornih kro-gov je možna. Medtem ko je uporaba kondenzatorjev brezdušilk možna samo pri krmilnih frekvencah nižjih od 250 Hzin pri majhnem deležu usmerniškega toka, je mogoèe s siste-mi z vgrajenimi dušilkami v pravi kombinaciji mogoèe doseèizadosten zaporni uèinek pri vseh frekvencah.

Tonfrekvenèni zaporni sistemi, povezani s kondenzatorskiminapravami z dušilkami oziroma s filterskimi sistemi, zahteva-jo poseben pristop pri naèrtovanju in so projektirani individu-alno ob upoštevanju strukture harmonikov v mreži višjega re-da in kratkostiène reaktance na mestu prikljuèitve naprave.

Slika 5: Nadomestna slika (1-polna)

Slika 3: Projektiranje kompenzacijskih naprav (Izvleèek DEW 5/93)

Slika 4: Prikljuèna shema

Javna distribucijska

mreža

M

SN Vozlišce

Mrežnitransformator

Kompenzacijska naprava, po potrebi

z dodatnimi elementi (dušilke,

zaporni krogi)

Staticno breme

Motorsko breme

NN

Mrežna frekvencafn= 50 Hz

Un VozlišceKrmilna

frekvenca fs

Enopolna nadomestna shema

Za= Un/PA2

Zs

Statiènobreme

Page 7: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

7

Fig. 3: Configuration of compensation equipment (excerpt fromVDEW 5/93)

Recommendations for audio frequencycontrol systems

Ripple control systems (TRA) use frequencies from approx.100 Hz to 1350 Hz. Depending on this frequency, capacitorswith or without reactor protection can cause excessive per-turbations on the ripple control systems.

When a capacitor system is designed, the audio frequencysignal used by the local power utility must be considered.

A guide to the decrease in audio frequency impedance is theimpedance factor a for which the following applies, for exam-ple, for the separate power transformer:

α = ZS–ZA

0.4 (Recommendations for the avoidance of ex-cessive perturbations on the audio frequencycontrol system)

ZS = Network impedance of the particular audio frequency ZA = Network impedance of the basic frequency (50 Hz)

To achieve an impedance factor of α 0.4, the followingpossibilities exist when planning capacitor systems: - Use of audio frequency blocking circuits - Use of reactor-protected and special reactor-protected ca-

pacitors (combination reactor-protection) - Use of capacitors without reactor protection

Due to the increasing load on the power networks caused bycurrent converters and similar loads with non-linear charac-teristics, remember when executing blocking measures thatthe harmonic currents generated by these loads do notcause excessive stress on the blocking elements. This is dueto the unavoidable series resonance between capacitor andblocking element which occurs in all blocking circuits. Duringconfiguration of a compensation system blocked against au-dio frequencies, existing harmonics must be considered.

Fig. 3 gives an overview of which measures can be used incompensation equipment to achieve sufficient blocking ef-fects. While use of non-reactor-protected capacitors withoutaudio frequency blocking circuits is only possible for audiofrequencies of less than 250 Hz and low current converterportion, reactor-protected systems in suitable combinationare able to achieve sufficient blocking effects for all regularaudio frequencies. Audio frequency blocking systems combined with reactor-protected capacitor systems or filter circuits under considera-tion of the harmonics content of the higher-level network andthe short-circuit reactance at the connection point can be in-dividually configured on request.

Fig. 5: Equivalent circuit. (Single-pole)

Fig. 4: Connection diagram

Page 8: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

8

Tehnièna pojasnila

Avtomatske kompenzacijske naprave se uporabljajo za cen-tralno kompenzacijo jalove moèi v trifaznih sistemih brez pri-sotnosti višjih harmonikov. Regulacijske naprave in razširitve-ne enote se dobavljajo v zaprtih kovinskih ohišjih, primernihza montažo na steno ali kot prosto stojeèa izvedba.

Regulacijske naprave do 75 kvar so narejene v obliki plošèe za vgradnjo, kompletno sestavljenein povezane, opremljene z regulatorjem in NN varovalkami,kondenzatorskimi kontaktorji z vgrajenimi predupori za dušenjevklopnega toka, praznilnimi upori, nizkoizgubnimi kondenzatorjiz vrstnimi sponkami za prikljuèitev vodnikov za krmiljenje in na-pajanje tokovnega transformatorja. Naprave so dobavljene vobliki kovinske omare za montažo na steno. Regulacijske naprave nad 75 kvar vsebujejo: - Kondenzatorske module, sestavljene iz 3 NN varovalk z

deli zbiralk, kondenzatorskega kontaktorja z vgrajenimpreduporom za dušenje vklopnega toka, nizkoizgubnihkondenzatorjev in praznilne dušilke za hitro praznjenje.

- Regulator jalove moèi z displejem in vgrajenim preklopni-kom roèno/avtomatsko.

- Kovinsko ohišje z regulatorjem v vratih omare, kjer se tudinadzira delovanje regulacijskih funkcij.

- Prikljuèek na PEN vodnik.

Prikljuèek Predviden je kabelski prikljuèek od spodaj. Za regulacijskoenoto in za vsako razširitveno enoto je potreben mrežni prikl-juèek in tripolno varovanje.

Razširitvene enote Razširitev regulacijske enote je možna s paralelno prikljuèit-vijo razširitvenih enot. Razširitvene enote so z regulacijskoenoto povezane z regulacijskim kablom. Pri tem ostane šte-vilo stopenj nespremenjeno, spremeni se samo moè posa-mezne stopnje. Razširitvene enote nimajo regulatorja na vra-tih.

Predpisi Avtomatske kompenzacijske naprave odgovarjajo predpisomDIN EN 61921 (VDE 0560 Teil 700), EN 60831-1 (VDE 0560Teil46) in EN 60439 Teil 1 (VDE 0660 Teil 500), IEC Publika-cijam 831 in 439 in VDE 0106, Teil 100.

Montaža Avtomatske regulacijske naprave in razširitvene enote so pri-merne za notranjo montažo. Naprave za zunanjo montažoso dobavljive na zahtevo.

Technical comments

Automatic power factor correction equipment is used for thecentral compensation of the reactive power in three-phasepower supply systems without harmonics.Equipment and extension modules are made of steel sheetencapsulated boxes for wall mounting or in free standingconstruction.Units up to 75 kvarconsist of a built-in module completely mounted and connec-ted with a power factor controller, capacitor contactors withintegrated resistors for damping of the inrush current, di-scharge resistors, lowloss power capacitors and terminalblocks for connection of the control and current transformerlines. The module is built into a prefabricated steel sheet boxfor wall mounting.Units over 75 kvar contain:- Capacitor modules, each consisting of 3 H.R.C. low-volta-

ge fuses with portions of bus bars, capacitor contactorwith integrated series resistors for attenuation of theswitch-on current, low-loss power capacitors and dischar-ge reactor for quick discharge.

- Power factor controller with display and integratedhand/automatic mode selector.

- Steel sheet standard panel with power factor controller inthe front door for observation of the function of the con-troller.

- Terminal for PEN-conductor.ConnectionThe cable entry for each equipment is provided from the bot-tom. One each power connection and one three-pole, low-voltage fuse protection are required for the unit and each ex-tension unit.Extension modulesThe unit can be expanded by parallel connection of exten-sion units. The extension units are connected to the unit withcontrol lines. The number of steps remains the same and on-ly the step size is increased. With extension units the con-troller in the cabinet door is omitted.StandardsAutomatic power factor compensation equipment complieswith EN 61921 (VDE 0560 Part 700), EN 60831-1 (VDE0560 Part 46) and EN 60439 Part 1 (VDE 0660 Part 500),and IEC Publications 831 and 439 as well as VDE 0106,Part 100.InstallationAutomatic power factor correction equipment and extensionmodules are designed for indoor installation. Equipment foroutdoor installation on request.

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV EA U T O M AT I C P O E R FA C T O R C O R R E C T I O N E Q U I P M E N T

Page 9: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

9

Podatki za projektiranje

Nadmorska višina: do 2000 m nadmorske višine pri nazivnih delovnih pogojihNazivna napetost in frekvenca:400 V, 50 Hz690 V, 50 Hzdruge nazivne napetosti oziroma 60 Hz na zahtevoMaksimalna dopustna delovna napetost:1,0 x UN trajno1,1 x UN do 8 ur na danMaksimalen dopusten delovni tok:1,3 x IN trajnoOblika mreže:TN-Cdruge oblike mreže na zahtevoKrmilna napetost in frekvenca:230 V, 50 Hz (60 Hz); pri drugaèni krmilni napetosti in frek-venci je potreben krmilni transformator (npr. 525 / 230 V ali 690 / 230 V)Nazivna moè in število stopenj:glej tabele v nadaljevanju.naèin regulacije 1 : 1 : 1… ; 1 : 2 : 2… in drugiPraznjenje: male naprave s praznilnimi upori t 3 minkompaktne in velike naprave z dušilkami t 8 sVrsta zašèite: glej tabele v nadaljevanjuIzgubna moè: kondenzatorji 0,4 W / kvar(merjeno na sponkah kondenzatorjev)avtomatske naprave 2,0 W/ kvarMejne temperature: omare: + 35° C srednja vrednost v 24 urah+ 20° C letno povpreèje + 40° C maksimalna vrednost, kratkotrajno– 10° C minimalna vrednostHlajenje: naravno hlajenjeBarva: lakiranje: gramozno siva barva RAL 7032velike naprave: profili ohišja, zadnja stena in strop: pocink-ano Prikljuèek tokovnega transformatorja;:normalno…/5 A;…/1 APreseki prikljuèkov: glej tabele v nadaljevanjuVarovalke: glej tabele v nadaljevanju

Configuration data

Operation altitudeUp to 2000 m above sea level for normal serviceRated voltage and frequency400 V, 50 Hz690 V, 50 HzOther rated voltages resp. 60 Hz on requestMax. permissible operating voltage1.0 x UN permanent1.1 x UN for 8 h dailyMax. permissible operating current1.3 x IN permanentNetwork configurationTN-COther configuration on requestControl voltage and frequency230 V, 50 Hz (60 Hz); a control transformeris required for other operating voltages and frequencies(for example 525 / 230 V or 690 / 230 V)Rated power and number of stepsSee selection tablesSwitching sequence 1 : 1 : 1… ; 1 : 2 : 2…DischargeSmall equipment with discharge resistors t 3 minCompact and large equipment with chokes t 8 sProtectionSee selection tablesPower dissipationCapacitors 0.4 W / kvar (measured at the capacitorterminals)Automatic equipment 2.0 W / kvar.Temperature limitsPanels:+ 35° C average in 24 hours+ 20° C annual average+ 40° C max., short time– 10° C low limitCoolingSelf coolingCoatingPanel: grey RAL 7032Large equipment: Panel profiles, back and top: galvanizedConnection for current transformerNormally …/5 A;…/1 AWire cross sectionsSee selection tablesFusesSee selection tables

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV EA U T O M AT I C P O W E R FA C T O R C O R R E C T I O N E Q U I P M E N T

Page 10: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

10

Majhne naprave v kovinskem ohišju Small equipment in steel sheet cubicle, IP 54, brez dušilk IP 54, without reactor-protection

Kompaktne naprave v ohišju iz Compact equipment in steel sheet cubicle, jeklene ploèevine IP 54, brez dušilk IP 54, without reactor-protection

Osnovna enota Razširitveni modulBasic module Extension module

15 3 x 5 1:2 MKK-54-400 / 3x5-CX06 MKK-54-400 / 3x5 34 600 x 210 x 600 620 4 x 5 1:1:2 MKK-54-400 / 4x5-CX06 MKK-54-400 / 4x5 35 600 x 210 x 600 625 5 x 5 1:2:2 MKK-54-400 / 5x5-CX06 MKK-54-400 / 5x5 36 600 x 210 x 600 630 3 x 10 1:2 MKK-54-400 / 3x10-CX06 MKK-54-400 / 3x10 36 600 x 210 x 600 630 6 x 5 1:1:2:2 MKK-54-400 / 6x5-CX06 MKK-54-400 / 6x5 37 600 x 350 x 600 640 4 x 10 1:1:2 MKK-54-400 / 4x10-CX06 MKK-54-400 / 4x10 38 600 x 350 x 600 650 5 x 10 1:2:2 MKK-54-400 / 5x10-CX06 MKK-54-400 / 5x10 42 600 x 350 x 600 650 4 x 12,5 1:1:2 MKK-54-400 / 4x12,5-CX06 MKK-54-400 / 4x12,5 40 600 x 350 x 600 660 6 x 10 1:2:3 MKK-54-400 / 6x10-CX06 MKK-54-400 / 6x10 45 600 x 350 x 600 662,5 5 x 12,5 1:2:2 MKK-54-400 / 5x12,5-CX06 MKK-54-400 / 5x12,5 46 600 x 350 x 600 675 6 x 12,5 1:2:3 MKK-54-400 / 6x12,5-CX06 MKK-54-400 / 6x12,5 48 600 x 350 x 600 6

50 4 x 12,5 1:1:1:1 MKK-54-690 / 4x12,5-CX06 MKK-54-690 / 4x12,5 41 600 x 350 x 600 662,5 5 x 12,5 1:2:2 MKK-54-690 / 5x12,5-CX06 MKK-54-690 / 5x12,5 47 600 x 350 x 600 675 6 x 12,5 1:1:2:2 MKK-54-690 / 6x12,5-CX06 MKK-54-690 / 6x12,5 49 600 x 350 x 600 6

Nazivna napetost 400 V/50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V/50 Hz, control voltage 230 V / 50 Hz

Nazivna napetost 690 V/50 Hz, krmilna napetost 230 V/50 HzRated voltage 690 V/50 Hz, control voltage 230 V/50 Hz

Nazivna napetost 400 V/50 Hz, krmilna napetost 230 V/50 HzRated voltage 400 V/50 Hz, control voltage 230 V/50 Hz

Nazivna napetost 690 V/50 Hz, krmilna napetost 230 V/50 HzRated voltage 690 V/50 Hz, control voltage 230 V/50 Hz

Moè Število Preklopno Koda za naroèilo Koda za naroèilo Teža prib. Dimenzije Slikastopenj zaporedje kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Fig.of steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

100 8 x 12,5 1:1:2:2:2 MKK-54-400 / 8x12,5-CX06 MKK-54-400 / 8x12,5 90 600 x 300 x 1200 7112,5 9 x 12,5 1:2:2:4 MKK-54-400 / 9x12,5-CX06 MKK-54-400 / 9x12,5 95 600 x 300 x 1200 7125 10 x 12,5 1:1:2:2:4 MKK-54-400 / 10x12,5-CX06 MKK-54-400 / 10x12,5 100 600 x 300 x 1200 7150 6 x 25 1:1:1:1:1:1 MKK-54-400 / 6x25-CX06 MKK-54-400 / 6x25 105 600 x 300 x 1200 7

100 8 x 12,5 1:1:2:2:2 MKK-54-690 / 8x12,5-CX06 MKK-54-690 / 8x12,5 90 600 x 300 x 1200 7112,5 9 x 12,5 1:2:2:4 MKK-54-690 / 9x12,5-CX06 MKK-54-690 / 9x12,5 95 600 x 300 x 1200 7125 10 x 12,5 1:1:2:2:4 MKK-54-690 / 10x12,5-CX06 MKK-54-690 / 10x12,5 100 600 x 300 x 1200 7150 6 x 25 1:1:1:1:1:1 MKK-54-690 / 6x25-CX06 MKK-54-690 / 6x25 105 600 x 300 x 1200 7

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV EA U T O M AT I C P O E R FA C T O R C O R R E C T I O N E Q U I P M E N T

Sl. 6

Fig. 6

Sl. 7Fig. 7

Page 11: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

11

Nazivna napetost 400 V/50 Hz, Krmilna napetost 230 V/50 HzRated voltage 400 V/50 Hz, control voltage 230 V/50 Hz

Nazivna napetost 690 V/50 Hz, krmilna napetost 230 V/50 HzRated voltage 690 V/50 Hz, control voltage 230 V/50 Hz

Osnovna enota Razširitveni modulBasic module Extension module

Moè Št. stopenj Preklop. zaporedje Koda za naroèilo Koda za naroèilo Teža Dimenzije Zašèita Slikaca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Pro- Fig.of steps sequence appr. kg W x D x H (mm) tection

(kvar) (kvar) degree

75 6 x 12,5 1:1:2:2 MKK-40-400 / 6x12,5-CX06 MKK-40-400 / 6x12,5 150 600 x 620 x 2000 IP40 2787,5 7 x 12,5 1:2:4 MKK-40-400 / 7x12,5-CX06 MKK-40-400 / 7x12,5 165 600 x 620 x 2000 IP40 27100 8 x 12,5 1:1:2:4 MKK-40-400 / 8x12,5-CX06 MKK-40-400 / 8x12,5 175 600 x 620 x 2000 IP40 27100 4 x 25 1:1:2 MKK-40-400 / 4x25-CX06 MKK-40-400 / 4x25 170 600 x 620 x 2000 IP40 27112,5 9 x 12,5 1:2:2:4 MKK-40-400 / 9x12,5-CX06 MKK-40-400 / 9x12,5 180 600 x 620 x 2000 IP40 27125 10 x 12,5 1:1:2:2:4 MKK-40-400 / 10x12,5-CX06 MKK-40-400 / 10x12,5 185 600 x 620 x 2000 IP40 27125 5 x 25 1:2:2 MKK-40-400 / 5x25-CX06 MKK-40-400 / 5x25 170 600 x 620 x 2000 IP40 27150 12 x 12,5 1:1:2:4:4 MKK-40-400 / 12x12,5-CX06 MKK-40-400 / 12x12,5 190 600 x 620 x 2000 IP40 27150 6 x 25 1:1:2:2 MKK-40-400 / 6x25-CX06 MKK-40-400 / 6x25 180 600 x 620 x 2000 IP40 27175 7 x 25 1:2:2:2 MKK-40-400 / 7x25-CX06 MKK-40-400 / 7x25 195 600 x 620 x 2000 IP40 27200 8 x 25 1:1:2:2:2 MKK-40-400 / 8x25-CX06 MKK-40-400 / 8x25 205 600 x 620 x 2000 IP40 27225 9 x 25 1:1:1:2:2:2 MKK-20-400 / 9x25-CX06 MKK-20-400 / 9x25 210 600 x 620 x 2000 IP20 28250 10 x 25 1:1:2:2:2:2 MKK-20-400 / 10x25-CX06 MKK-20-400 / 10x25 225 600 x 620 x 2000 IP20 28250 5 x 50 1:1:1:1:1 MKK-20-400 / 5x50-CX06 MKK-20-400 / 5x50 220 600 x 620 x 2200 IP20 28275 11 x 25 1:2:2:2:2:2 MKK-20-400 / 11x25-CX06 MKK-20-400 / 11x25 230 600 x 620 x 2200 IP20 28300 12 x 25 1:1:1:1:2:2:2:2 MKK-20-400 / 12x25-CX08 MKK-20-400 / 12x25 240 600 x 620 x 2200 IP20 28300 6 x 50 1:1:1:1:1:1 MKK-20-400 / 6x50-CX06 MKK-20-400 / 6x50 230 600 x 620 x 2200 IP20 28325 13 x 25 1:1:1:1:1:2:2:2:2 MKK-20-400 / 13x25-CX12 MKK-20-400 / 13x25 245 600 x 620 x 2200 IP20 28350 14 x 25 1:1:1:1:2:2:2:2:2 MKK-20-400 / 14x25-CX12 MKK-20-400 / 14x25 250 600 x 620 x 2200 IP20 28375 15 x 25 1:1:1:1:1:2:2:2:2:2 MKK-20-400 / 15x25-CX12 MKK-20-400 / 15x25 255 600 x 620 x 2200 IP20 28400 16 x 25 1:1:1:1:1:1:2:2:2:2:2 MKK-20-400 / 16x25-CX12 MKK-20-400 / 16x25 260 600 x 620 x 2200 IP20 28

75 6 x 12,5 1:1:2:2 MKK-40-690 / 6x12,5-CX06 MKK-40-690 / 6x12,5 150 600 x 620 x 2000 IP40 2787,5 7 x 12,5 1:2:4 MKK-40-690 / 7x12,5-CX06 MKK-40-690 / 7x12,5 165 600 x 620 x 2000 IP40 27100 8 x 12,5 1:1:2:4 MKK-40-690 / 8x12,5-CX06 MKK-40-690 / 8x12,5 175 600 x 620 x 2000 IP40 27100 4 x 25 1:1:2 MKK-40-690 / 4x25-CX06 MKK-40-690 / 4x25 170 600 x 620 x 2000 IP40 27112,5 9 x 12,5 1:2:2:4 MKK-40-690 / 9x12,5-CX06 MKK-40-690 / 9x12,5 180 600 x 620 x 2000 IP40 27125 10 x 12,5 1:1:2:2:4 MKK-40-690 / 10x12,5-CX06 MKK-40-690 / 10x12,5 185 600 x 620 x 2000 IP40 27125 5 x 25 1:2:2 MKK-40-690 / 5x25-CX06 MKK-40-690 / 5x25 170 600 x 620 x 2000 IP40 27150 12 x 12,5 1:1:2:4:4 MKK-40-690 /12x12,5-CX06 MKK-40-690 / 12x12,5 190 600 x 620 x 2000 IP40 27150 6 x 25 1:1:2:2 MKK-40-690 / 6x25-CX06 MKK-40-690 / 6x25 180 600 x 620 x 2000 IP40 27175 7 x 25 1:2:2:2 MKK-40-690 / 7x25-CX06 MKK-40-690 / 7x25 195 600 x 620 x 2000 IP40 27200 8 x 25 1:1:2:2:2 MKK-40-690 / 8x25-CX06 MKK-40-690 / 8x25 205 600 x 620 x 2000 IP40 27225 9 x 25 1:1:1:2:2:2 MKK-20-690 / 9x25-CX06 MKK-20-690 / 9x25 210 600 x 620 x 2000 IP20 28250 10 x 25 1:1:2:2:2:2 MKK-20-690 / 10x25-CX06 MKK-20-690 / 10x25 225 600 x 620 x 2000 IP20 28250 5 x 50 1:1:1:1:1 MKK-20-690 / 5x50-CX06 MKK-20-690 / 5x50 220 600 x 620 x 2200 IP20 28275 11 x 25 1:2:2:2:2:2 MKK-20-690 / 11x25-CX06 MKK-20-690 / 11x25 230 600 x 620 x 2200 IP20 28300 12 x 25 1:1:1:1:2:2:2:2 MKK-20-690 / 12x25-CX08 MKK-20-690 / 12x25 240 600 x 620 x 2200 IP20 28300 6 x 50 1:1:1:1:1:1 MKK-20-690 / 6x50-CX06 MKK-20-690 / 6x50 230 600 x 620 x 2200 IP20 28325 13 x 25 1:1:1:1:1:2:2:2:2 MKK-20-690 / 13x25-CX12 MKK-20-690 / 13x25 245 600 x 620 x 2200 IP20 28350 14 x 25 1:1:1:1:2:2:2:2:2 MKK-20-690 / 14x25-CX12 MKK-20-690 / 14x25 250 600 x 620 x 2200 IP20 28375 15 x 25 1:1:1:1:1:2:2:2:2:2 MKK-20-690 / 15x25-CX12 MKK-20-690 / 15x25 255 600 x 620 x 2200 IP20 28400 16 x 25 1:1:1:1:1:1:2:2:2:2:2 MKK-20-690 / 16x25-CX12 MKK-20-690 / 16x25 260 600 x 620 x 2200 IP20 28

Velike naprave v prostostojeèih Large equipment, free standing, ohišjih, brez dušilk without reactor-protection

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV EA U T O M AT I C P O W E R FA C T O R C O R R E C T I O N E Q U I P M E N T

Nazivna napetost 525 V / 50 Hz na zahtevo. Rated voltage 525 V/50 Hz: on request.Pri omarah z nazivno moèjo 250 kvar je pri montaži ob steni potrebna minimalna razdalja odstene 100 mm (montaža hrbet / hrbet na zahtevo).Equipment having a rated output 250 kvar has to be installed at a distance of more than 100mm from the wall (installation back to back on request).

Merske skice na strani 42.Prikljuèni preseki in varoval-ke, glej stran 46.

Dimensional drawings onpage 42. Cross sections forfeeding cables and fusingsee page 46.

Page 12: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

12

Naprave s kondenzatorji z dušilkami

Teoretiène osnove Kompenzacijski kondenzator in induktivnosti transformatorjater mreže tvorijo paralelen nihajni krog. Impedanca tega kro-ga ima pri resonanèni frekvenci zelo veliko vrednost (teoreti-èno neskonèno). Èe se resonanèna frekvenca nahaja v bliži-ni frekvenc, ki jih povzroèa usmernik, so ti harmonski tokovivsiljeni preko te visoke impedance nihajnega kroga. Pri temnastanejo zelo veliki tokovi nihajnega kroga, ki lahko imajoza napravo moteèe ali unièujoèe posledice. (Slika 8).Za prepreèitev teh resonanènih pojavov prikljuèimo dušilko vserijo s kompenzacijskim kondenzatorjem (Slika 9). Serijskinihajni krog, sestavljen iz dušilke in kondenzatorja, je ugla-šen na resonanèno frekvenco, ki leži pod najnižjim harmoni-kom. Pri tem podajamo moè dušilke v procentih moèi kon-denzatorja pri osnovni frekvenci. Kondenzatorje s takimi duš-ilkami imenujemo tudi razglašeni filterski krogi. Kako velik je ”sesalni uèinek” (stopnja filtracije), je odvisnood vsakokratne kratkostiène impedance napajalne mreže innadomestne impedance razglašenega kroga, podane z nje-govo kvaliteto. Skupen harmonski tok, ki ga proizvaja usmer-nik, je potrebno oceniti.

Orientacijske vrednosti5. harmonik l5 = 0,23 x l17. harmonik l7 = 0,12 x l111. harmonik l11 = 0,085 x l1

Te vrednosti veljajo pri idealnem glajenju. Èe pa imamoopravka za majhnim ali nikakršnim glajenjem, je potrebnozlasti pri 5. harmoniku raèunati z veèjimi vrednostmi (30 ...35 % osnovnega vala). Prednosti razglašenih krogov so oèit-ne: - kompenzacija reaktivne moèi pri osnovni frekvenci na

vnaprej doloèeno vednost cos ϕ- izloèanje (izognitev) mrežnih resonanc v napajalni mreži.

Reactor protected equipment

Theoretical fundamentals It is found that power factor compensation capacitors and theinductances of transformers and the power supply networkform a parallel resonant circuit whose impedance at the res-onant frequency of the oscillating circuit can be extremly high(theoretically infinite). If the resonant frequency approximatesany harmonic frequency generated by the rectifier, then theharmonic current concerned will be forced over this high os-cillatory impedance and the resultant voltage drop will lead tovery high harmonic current that could damage the plant (Fig.8).In order to prevent resonances, a reactor will be connectedin series with the compensation capacitor (Fig. 9). The re-sultant series resonant circuit is tuned to a resonant frequen-cy that is beneath the lowest harmonic frequency. The powerof the reactor concerned is specified as a percentage of thecapacitor impedance referred to the fundamental current.Such reactor protected capacitors are also referred to as de-tuned filter circuits. How great the “absorption effect” (degreeof filter) is, depends on the short-circuit impedance of thepower supply network and the residual resistance of the de-tuned filter which is determined by the filter quality. The har-monic current generated by the current converter has to besuitably dimensioned.Guide values 5th harmonic l5 = 0.23 x l17th harmonic l7 = 0.12 x l111th harmonic l11 = 0.085 x l1These values are valid for ideal smoothing. If no smoothingor only slight smoothing is provided, then higher amplitudesmust be anticipated, particulary in the case of the 5th har-monic (30 ... 35 % of the fundamental current). The advan-tages of detuned filter circuits are obvious: - Compensation of the reactive power fundamental to a spe-

cified cos ϕ- Avoidance of resonance in the power supply network

Slika 8: Ojaèanje toka pri paralelni resonanciFig. 8: Current amplification in case of parallel resonance

Slika 9: Kompenzacija s kondenzatorji z dušilkamiFig. 9: Compensation with reactor-protected capacitors

1ωC

ωLTR

ωLN

UsmernikDC-drive

IHarmonik

IHarmonic

IRES

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV E S K O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Page 13: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

13

Naprave s kondenzatorji z dušilkami

Teoretiène osnove Avtomatske kompenzacijske naprave s kondenzatorji z dušil-kami se uporabljajo kot centralna kompenzacija v trifaznihmrežah, kjer so prisotni višji harmoniki. Èe je vgrajena dušil-ka izbrana tako, da resonanèni krog obremenjuje samo mini-malen del višjih harmonikov, govorimo o “zelo razglašenemfilterskem krogu”.

= ... % moèi kondenzatorja pri osnovni frekvenciPri v praksi pogosto uporabljeni vrednosti p = 7%, je serijskaresonanca pri 189 Hz. Tako dimenzionirani “zelo razglašenifilterski krogi” posesajo zelo majhen del 5. oziroma 7.harmo-nika; veèji del je spušèen v mrežo višjega reda.Avtomatske kompenzacijske naprave s kondenzatorji z dušil-kami so sestavljene iz: - kondenzatorske grupe, vsaka je sestavljena iz 3 NN varo-

valk z deli zbiralk, kondenzatorskega stikala, nizkoizgubnihkondenzatorjev in praznilne dušilke za hitro praznjenje.

- trifaznih dušilk za vsako kondenzatorsko grupo.- regulatorja reaktivne moèi z displejem in vgrajenim preklo-

pom roèno/avtomatsko.- kovinskega ohišja za prosto stojeèo montažo z regulator-

jem v vratih omare.- prikljuèka za PEN vodnik.

Prikljuèek Predviden je kabelski prikljuèek od spodaj. Mrežni kabelskiprikljuèek za tripolno varovanje je potreben pri regulacijskemdelu naprave in za vsako razširitveno enoto.

Razširitvene enote Razširitev oziroma poveèanje moèi regulacijske naprave jemožno s paralelno prikljuètvijo razširitvenih enot. Razširitve-ne enote so s krmilnimi vodniki povezane z regulacijsko na-pravo. Pri tem število stopenj ostane nespremenjeno, poveèase samo moè posamezne stopnje. Razširitvene enote v vra-tih nimajo regulatorja.

Predpisi Avtomatske kompenzacijske naprave odgovarjajo sledeèimpredpisom: DIN EN 61921 (VDE 0560 Teil 700), EN 60831-1 (VDE 0560Teil 46) in EN 60439 Teil 1 (VDE 0660 Teil 500), IEC Publika-cijam 831 in 439 in VDE 0106, Teil 100.

Montaža Avtomatske regulacijske naprave in razšititvene enote so predvide-ne za notranjo montažo. Naprave za zunanjo montažo so dobavlji-ve na zahtevo.

Reactor protected equipment

Theoretical fundamentals Power factor correction equipment with reactor-protected ca-pacitors are used for the central compensation of the reac-tive power in three-phase power supply network with har-monic loads. If the series reactor is selected in such a waythat a minimum part of the harmonics is charging the reso-nance circuit, it is called a “highly detuned filter circuit”

= ... % of the capacitor rating related to the fundamental os-cillation

The often applied value p = 7 % results in a series resonanceof 189 Hz. This ”highly detuned filter circuit” absorbs only asmall part of the 5th respectively the 7th harmonic current,whereas the greater part is supplied to the power supply net-work.Reactor-protected automatic power factor correction equip-ment consist of:- Capacitor subassemblies each consisting of 3 H.R.C. low

voltages fuses, bus bars, capacitor contactors, low-losscapacitors and discharge choke for quick discharge.

- 3-phase reactor for each subassembly.- Power factor controller with display and integrated

hand/automatic mode selector.- Steel sheet standard panel with power factor controller in

the front door for observation of the function of the con-troller.

- Terminal for PEN-conductor.ConnectionThe cable entry for each equipment is provided from the bot-tom. One each power connection and one three-pole, low-voltage fuse protection are required for the unit and each ex-tension unit.Extension modulesThe unit can be expanded by parallel connection of exten-sion units. The extension units are connected to the unit withcontrol lines. The number of steps remains the same and on-ly the step size is increased. With extension units the control-ler in the cabinet door is omitted.StandardsAutomatic power factor compensation equipment complieswith EN 61921 (VDE 0560 Part 700), EN 60831-1 (VDE0560 Part 46) and EN 60439 Part 1 (VDE 0660 Part 500),and IEC Publications 831 and 439 as well as VDE 0106,Part 100.InstallationAutomatic power factor correction equipment and extensionmodules are designed for indoor installation. Equipment foroutdoor installation on request.

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV E S K O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

p=XL / XC × 100% .......Moè dušilk p=XL / XC × 100% .......Reactor value

Page 14: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

Naprave s kondenzatorji z dušilkami

Podatki za projektiranjeNadmorska višina:do 2000 m nad morjem pri nazivnem obratovanju.Nazivna napetost in frekvenca:400 V, 50 Hz690 V, 50 Hzdruge nazivne napetosti oziroma 60 Hz na zahtevoMaksimalno dopustna delovna napetost:1,0 x UN trajno1,1 x UN do 8 ur na danNazivni tok:glej tabele v nadaljevanjuMaksimalno dopustne harmonske napetosti:po EN 61000-2-4, razred 2Oblika mreže:TN-Cdruge oblike mreže na zahtevoKrmilna napetost in frekvenca:230 V, 50 Hz (60 Hz); pri drugaèni delovni napetosti in frek-venci je potrebne krmilni transformator (npr. 525 / 230 V ali690 / 230 V)Nazivna moè in število stopenj:glej tabele v nadaljevanjuvrsta regulacije 1 : 1 : 1 ...; 1 : 2 : 2... in druge.Praznjenje:kompaktne naprave s praznilnimi upori t 3 min.velike naprave z dušilkami t 8 sStopnja zašèite:IP 20Izgubna moè:kondenzatorji 0,4 W / kvar (merjeno na sponkah kondenza-torjev), regulacijske naprave 5,0 W / kvarMejne temperature:omare:+ 35° C srednja vrednost v 24 urah+ 20° C letno povpreèje+ 40° C maksimalna vrednost, kratkotrajno– 10° C minimalna vrednostHlajenje:kompaktne naprave: naravno hlajenjevelike naprave: glej tabele v nadaljevanjuBarva:lakiranje: gramozno siva barva RAL 7032velike naprave: profili ohišja, zadnja stena in strop: pocinkaniPrikljuèek tokovnega transformatorja:normalno .../5 A; ... /1 APrikljuèni preseki in varovalke:glej tabele v nadaljevanjuHrupnost naprav:

60 dB pri zaprtih napravah nazivnem obratovanju na raz-dalji 1 m.

Reactor-protected equipment

Configuration dataAltitudeUp to 2000 m above sea levelRated voltage and Frequency400 V, 50 Hz690 V, 50 HzOther rated voltages resp. 60 Hz on requestMax. permissible operating voltage1.0 x UN permanent1.1 x UN for 8 h dailyRated currentSee selection tablesMax. permissible harmonic voltage distortionAccording to EN 61000-2-4, class 2Network configurationTN-COther configuration on requestControl voltage and frequency230 V, 50 Hz (60 Hz); a control transformer is required for ot-her operating voltages and frequencies(for example 525 / 230 V or 690 / 230 V)Rated power and number of stepsSee selection tablesSwitching program 1 : 1 : 1 ...; 1 : 2 : 2...DischargeCompact equipment with discharge resistors t 3 minLarge equipment with chokes t 8 sProtectionIP 20Power dissipationCapacitors 0.4 W / kvar (measured at the capacitor termi-nals), Automatic equipment 5.0 W / kvarTemperature limitsPanels:+ 35° C average in 24 hours+ 20° C annual average+ 40° C max. short time– 10° C low limitCoolingCompact equipment: self coolingLarge equipment: see selection tablesCoatingPanel: grey RAL 7032Large equipment: Panel profiles, back and top: galvanizedCurrent transformer connectionNormally .../5 A; ... /1 AWire cross sections and fusesSee selection tablesNoise emission

60 dB in enclosed equipment at rated service in 1 m dis-tance

14

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV E SK O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Page 15: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

Kompaktne naprave v kovinskem Compact equipment in steel ohišju sheet cubicle Stopnja zašèite IP 20 s kondenzatorji Protection degree IP 20 with reactor-z dušilkami protected capacitors

Osnovna enota Razširitveni modulBasic module Extension module

z dušilko, uglašeno na 189 Hz (p = 7%) / With reactor, detuned to 189 Hz (p = 7%)15 3 x 5 1:2 MKK-DR7-400 / 3x5-CX06 MKK-DR7-400 / 3x5 97 600 x 300 x 120020 4 x 5 1:1:2 MKK-DR7-400 / 4x5-CX06 MKK-DR7-400 / 4x5 106 600 x 300 x 120025 5 x 5 1:2:2 MKK-DR7-400 / 5x5-CX06 MKK-DR7-400 / 5x5 110 600 x 300 x 120030 3 x 10 1:2 MKK-DR7-400 / 3x10-CX06 MKK-DR7-400 / 3x10 104 600 x 300 x 120030 6 x 5 1:2:3 MKK-DR7-400 / 6x5-CX06 MKK-DR7-400 / 5x6 110 600 x 300 x 120040 4 x 10 1:1:2 MKK-DR7-400 / 4x10-CX06 MKK-DR7-400 / 4x10 113 600 x 300 x 120050 5 x 10 1:2:2 MKK-DR7-400 / 5x10-CX06 MKK-DR7-400 / 5x10 120 600 x 300 x 120060 3 x 20 1:1:1 MKK-DR7-400 / 3x20-CX06 MKK-DR7-400 / 3x20 123 600 x 300 x 120075 3 x 25 1:1:1 MKK-DR7-400 / 3x25-CX06 MKK-DR7-400 / 3x25 149 600 x 300 x 1200

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

Moè Št. stopenj Prekl.zapored. Koda za naroèilo Koda za naroèilo Teža Dimenzijeca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensionsof steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

z dušilko, uglašeno na 210 Hz (p = 5,67%) / With reactor, detuned to 210 Hz (p = 5.67%)15 3 x 5 1:2 MKK-DR5,67-400 / 3x5-CX06 MKK-DR5,67-400 / 3x5 97 600 x 300 x 120020 4 x 5 1:1:2 MKK-DR5,67-400 / 4x5-CX06 MKK-DR5,67-400 / 4x5 106 600 x 300 x 120025 5 x 5 1:2:2 MKK-DR5,67-400 / 5x5-CX06 MKK-DR5,67-400 / 5x5 110 600 x 300 x 120030 3 x 10 1:2 MKK-DR5,67-400 / 3x10-CX06 MKK-DR5,67-400 / 3x10 104 600 x 300 x 120035 6 x 5 1:2:3 MKK-DR5,67-400 / 6x5-CX06 MKK-DR5,67-400 / 5x6 110 600 x 300 x 120040 4 x 10 1:1:2 MKK-DR5,67-400 / 4x10-CX06 MKK-DR5,67-400 / 4x10 113 600 x 300 x 120050 5 x 10 1:2:2 MKK-DR5,67-400 / 5x10-CX06 MKK-DR5,67-400 / 5x10 120 600 x 300 x 120060 3 x 20 1:1:1 MKK-DR5,67-400 / 3x20-CX06 MKK-DR5,67-400 / 3x20 123 600 x 300 x 120075 3 x 25 1:1:1 MKK-DR5,67-400 / 3x25-CX06 MKK-DR5,67-400 / 3x25 149 600 x 300 x 1200

z dušilko, uglašeno na 141 Hz (p = 12,5%) / With reactor, detuned to 141 Hz (p = 12.5%)16,5 3 x 5,5 1:2 MKK-DR12,5-400 / 3x5,5-CX06 MKK-DR12,5-400 / 3x5,5 101 600 x 300 x 120025 3 x 8,33 1:2 MKK-DR12,5-400 / 3x8,33-CX06 MKK-DR12,5-400 / 3x8,33 109 600 x 300 x 120033,3 4 x 8,33 1:1:2 MKK-DR12,5-400 / 4x8,33-CX06 MKK-DR12,5-400 / 4x8,33 125 600 x 300 x 120041,7 5 x 8,33 1:2:2 MKK-DR12,5-400 / 5x8,33-CX06 MKK-DR12,5-400 / 5x8,33 133 600 x 300 x 120050 3 x 16,7 1:1:1 MKK-DR12,5-400 / 3x16,7-CX06 MKK-DR12,5-400 / 3x16,7 147 600 x 300 x 1200

z dušilko, uglašeno na 133 Hz (p = 14%) / With reactor, detuned to 133 Hz (p = 14%)16,5 3 x 5,5 1:2 MKK-DR14-400 / 3x5,5-CX06 MKK-DR14-400 / 3x5,5 101 600 x 300 x120025 3 x 8,33 1:2 MKK-DR14-400 / 3x8,33-CX06 MKK-DR14-400 / 3x8,33 109 600 x 300 x120033,3 4 x 8,33 1:1:2 MKK-DR14-400 / 4x8,33-CX06 MKK-DR14-400 / 4x8,33 125 600 x 300 x120041,7 5 x 8,33 1:2:2 MKK-DR14-400 / 5x8,33-CX06 MKK-DR14-400 / 5x8,33 133 600 x 300 x120050 3 x 16,7 1:1:1 MKK-DR14-400 / 3x16,7-CX06 MKK-DR14-400 / 3x16,7 147 600 x 300 x1200

15

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV E SK O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Nazivna napetost 525 V/50 Hz: na zahtevo.Rated voltage 525 V/50 Hz: on request.Prikljuèni preseki dovodnih kablov in varovalke, glej stran 46.Cross sections for feeding cables and fusing see page 46.

Slika 10 Fig. 10

Page 16: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

16

Velike naprave v omarah v Large equipment, free standingprosto stojeèi izvedbiStopnja zašèite IP 20 B s kondenzatorji z Protection degree IP 20 B with reactor-protecteddušilkami, uglašene na 189 Hz (p=7 %) capacitors tuned to 189 Hz (p=7 %)

Nazivna napetost 400 V/50 Hz, krmilna napetost 230 V/50 Hz, nazivna moè do 300 kvarRated voltage 400 V/50 Hz, Control voltage 230 V/50 Hz, rated power up to 300 kvar

Osnovna enota Razširitveni modulBasic module Extension module

Moè Št. stopenj Prekl. zaporedje Koda za naroèilo Koda za naroèilo Težat Dimenzije Vent. Slikaca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Fan Fig.of steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

75 6 x 12,5 1:1:2:2 MKK-DR7-400 / 6x12,5-CX06 MKK-DR7-400 / 6x12,5 150 600 x 620 x 2200 2887,5 7 x 12,5 1:2:4 MKK-DR7-400 / 7x12,5-CX06 MKK-DR7-400 / 7x12,5 180 600 x 620 x 2200 28100 8 x 12,5 1:1:2:4 MKK-DR7-400 / 8x12,5-CX06 MKK-DR7-400 / 8x12,5 190 600 x 620 x 2200 28100 4 x 25 1:1:2 MKK-DR7-400 / 4x25-CX06 MKK-DR7-400 / 4x25 190 600 x 620 x 2200 28112,5 9 x 12,5 1:2:2:4 MKK-DR7-400 / 9x12,5-CX06 MKK-DR7-400 / 9x12,5 200 600 x 620 x 2200 28125 10 x 12,5 1:1:2:2:4 MKK-DR7-400 / 10x12,5-CX06 MKK-DR7-400 / 10x12,5 220 600 x 620 x 2200 28125 5 x 25 1:2:2 MKK-DR7-400 / 5x25-CX06 MKK-DR7-400 / 5x25 215 600 x 620 x 2200 28150 12 x 12,5 1:1:2:4:4 MKK-DR7-400 / 12x12,5-CX06 MKK-DR7-400 / 12x12,5 250 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR7-400 / 6x25-CX06 MKK-DR7-400 / 6x25 245 800 x 620 x 2200 33175 7 x 25 1:2:2:2 MKK-DR7-400 / 7x25-CX06 MKK-DR7-400 / 7x25 250 800 x 620 x 2200 33200 8 x 25 1:1:2:2:2 MKK-DR7-400 / 8x25-CX06 MKK-DR7-400 / 8x25 260 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR7-400 / 4x50-CX06 MKK-DR7-400 / 4x50 280 800 x 620 x 2200 33225 9 x 25 1:2:2:2:2 MKK-DR7-400 / 9x25-CX06 MKK-DR7-400 / 9x25 310 800 x 620 x 2200 33250 10 x 25 1:1:2:2:2:2 MKK-DR7-400 / 10x25-CX06 MKK-DR7-400 / 10x25 360 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR7-400 / 5x50-CX06 MKK-DR7-400 / 5x50 350 800 x 620 x 2200 33275 11 x 25 1:2:2:2:2:2 MKK-DR7-400 / 11x25-CX06 MKK-DR7-400 / 11x25 410 800 x 620 x 2200 33300 12 x 25 1:1:2:2:2:2:2 MKK-DR7-400 / 12x25-CX08 MKK-DR7-400 / 12x25 465 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR7-400 / 6x50-CX06 MKK-DR7-400 / 6x50 420 800 x 620 x 2200 33

Nazivna napetost 400 V/50 Hz, krmilna napetost 230 V/50 Hz, nazivna moè do 400 kvarRated voltage 400 V/50 Hz, control voltage 230 V/50 Hz, rated power up to 400 kvar

300 6 x 50 1:1:1:1:1:1 MKK-DR7-400 / 6x50-CX06-400 MKK-DR7-400 /6x50-400 410 800 x 620 x 2250 X 39350 7 x 50 1:1:1:1:1:1:1 MKK-DR7-400 / 7x50-CX08-400 MKK-DR7-400 /7x50-400 462 800 x 620 x 2250 X 39400 8 x 50 1:1:1:1:1:1:1:1 MKK-DR7-400 / 8x50-CX08-400 MKK-DR7-400 /8x50-400 491 800 x 620 x 2250 X 39

Nazivna napetost 690 V/50 Hz, krmilna napetost 230 V/50 HzRated voltage 690 V/50 Hz, control voltage 230 V/50 Hz

75 6 x 12,5 1:1:2:2 MKK-DR7-690 / 6x12,5-CX06 MKK-DR7-690 / 6x12,5 180 800 x 620 x 2200 33100 4 x 25 1:1:2 MKK-DR7-690 / 4x25-CX06 MKK-DR7-690 / 4x25 210 800 x 620 x 2200 33125 5 x 25 1:2:2 MKK-DR7-690 / 5x25-CX06 MKK-DR7-690 / 5x25 230 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR7-690 / 6x25-CX06 MKK-DR7-690 / 6x25 260 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR7-690 / 4x50-CX06 MKK-DR7-690 / 4x50 300 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR7-690 / 5x50-CX06 MKK-DR7-690 / 5x50 370 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR7-690 / 6x50-CX06 MKK-DR7-690 / 6x50 440 800 x 620 x 2200 33

Nazivna napetost 525 V/50 Hz: na zahtevo. Rated voltage 525 V/50 Hz: on request.Prikljuèni preseki dovodnih kablov in varovalke, glej stran 46. Dimenzijske skice na straneh 42 do44. Cross sections for feeding cables and fusing see page 46. Dimensional drawings on pages 42 to44.Pri omarah z nazivno moèjo 250 kvar je pri montaži ob steni potrebno omogoèiti minimalnorazdaljo 100 mm (montaža hrbet proti hrbtu na zahtevo).Equipment having a rated output 250 kvar has to be installed at a distance of more than 100mm from the wall (installation back to back on request).

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV ES K O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Page 17: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

17

Velike naprave v omarah v Large equipment, free standingprosto stojeèi izvedbi Stopnja zašèite IP 20 B s kondenzatorji z Protection degree IP 20 B with reactor protected dušilkami, uglasitev na 210 Hz (p = 5,67 %) capacitors detuned to 210 Hz (p = 5.67 %)

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz, nazivna moè do 300 kvarRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz, rated power up to 300 kvar

Osnovna enota Razširitveni modulBasic module Extension module

Moè Št. stopenj Prekl.zap. Koda za naroèilo Koda za naroèilo Teža Dimenzije Vent. Slik.ca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Fan Fig.of steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

75 6 x 12,5 1:1:2:2 MKK-DR5,67-400 / 6x12,5-CX06 MKK-DR5,67-400 / 6x12,5 150 600 x 620 x 2200 2887,5 7 x 12,5 1:2:4 MKK-DR5,67-400 / 7x12,5-CX06 MKK-DR5,67-400 / 7x12,5 180 600 x 620 x 2200 28100 8 x 12,5 1:1:2:4 MKK-DR5,67-400 / 8x12,5-CX06 MKK-DR5,67-400 / 8x12,5 190 600 x 620 x 2200 28100 4 x 25 1:1:2 MKK-DR5,67-400 / 4x25-CX06 MKK-DR5,67-400 / 4x25 190 600 x 620 x 2200 28112,5 9 x 12,5 1:2:2:4 MKK-DR5,67-400 / 9x12,5-CX06 MKK-DR5,67-400 / 9x12,5 200 600 x 620 x 2200 28125 10 x 12,5 1:1:2:2:4 MKK-DR5,67-400 / 10x12,5-CX06 MKK-DR5,67-400 / 10x12,5 220 600 x 620 x 2200 28125 5 x 25 1:2:2 MKK-DR5,67-400 / 5x25-CX06 MKK-DR5,67-400 / 5x25 215 600 x 620 x 2200 28150 12 x 12,5 1:1:2:4:4 MKK-DR5,67-400 / 12x12,5-CX06 MKK-DR5,67-400 / 12x12,5 250 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR5,67-400 / 6x25-CX06 MKK-DR5,67-400 / 6x25 245 800 x 620 x 2200 33175 7 x 25 1:2:2:2 MKK-DR5,67-400 / 7x25-CX06 MKK-DR5,67-400 / 7x25 250 800 x 620 x 2200 33200 8 x 25 1:1:2:2:2 MKK-DR5,67-400 / 8x25-CX06 MKK-DR5,67-400 / 8x25 260 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR5,67-400 / 4x50-CX06 MKK-DR5,67-400 / 4x50 280 800 x 620 x 2200 33225 9 x 25 1:2:2:2:2 MKK-DR5,67-400 / 9x25-CX06 MKK-DR5,67-400 / 9x25 310 800 x 620 x 2200 33250 10 x 25 1:1:2:2:2:2 MKK-DR5,67-400 / 10x25-CX06 MKK-DR5,67-400 / 10x25 360 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR5,67-400 / 5x50-CX06 MKK-DR5,67-400 / 5x50 350 800 x 620 x 2200 33275 11 x 25 1:2:2:2:2:2 MKK-DR5,67-400 / 11x25-CX06 MKK-DR5,67-400 / 11x25 410 800 x 620 x 2200 33300 12 x 25 1:1:2:2:2:2:2 MKK-DR5,67-400 / 12x25-CX08 MKK-DR5,67-400 / 12x25 465 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR5,67-400 / 6x50-CX06 MKK-DR5,67-400 / 6x50 420 800 x 620 x 2200 33

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz, nazivna moè 400 kvarRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz, rated power up to 400 kvar

300 6 x 50 1:1:1:1:1:1 MKK-DR5,67-400 / 6x50-CX06-400 MKK-DR5,67-400 / 6x50-400 420 800 x 620 x 2250 X 39350 7 x 50 1:1:1:1:1:1:1 MKK-DR5,67-400 / 7x50-CX08-400 MKK-DR5,67-400 / 7x50-400 480 800 x 620 x 2250 X 39400 8 x 50 1:1:1:1:1:1:1:1MKK-DR5,67-400 / 8x50-CX08-400 MKK-DR5,67-400 / 8x50-400 530 800 x 620 x 2250 X 39

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

75 6 x 12,5 1:1:2:2 MKK-DR5,67-690 / 6x12,5-CX06 MKK-DR5,67-690 / 6x12,5 180 800 x 620 x 2200 33100 4 x 25 1:1:2 MKK-DR5,67-690 / 4x25-CX06 MKK-DR5,67-690 / 4x25 210 800 x 620 x 2200 33125 5 x 25 1:2:2 MKK-DR5,67-690 / 5x25-CX06 MKK-DR5,67-690 / 5x25 230 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR5,67-690 / 6x25-CX06 MKK-DR5,67-690 / 6x25 260 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR5,67-690 / 4x50-CX06 MKK-DR5,67-690 / 4x50 300 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR5,67-690 / 5x50-CX06 MKK-DR5,67-690 / 5x50 370 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR5,67-690 / 6x50-CX06 MKK-DR5,67-690 / 6x50 440 800 x 620 x 2200 33

Nazivna napetost 525 V/50 Hz: na zahtevo. Rated voltage 525 V/50 Hz: on request.Prikljuèni preseki dovodnih kablov in varovalke, glej stran 46. Dimenzijske skice, glej strani 42 do44.Cross sections for feeding cables and fusing see page 46. Dimensional drawings on pages 42 to44.Pri napravah z nazivno moèjo 250 kvar je pri montaži ob steni potrebno zagotoviti minimalnorazdaljo 100 mm (montaža hrbet proti hrbtu na zahtevo).Equipment having a rated output 250 kvar has to be installed at a distance of more than 100mm from the wall (installation back to back on request).

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV E SK O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Page 18: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

18

Velike naprave v omarah v Large equipment, free standingprosto stojeèi izvedbi Stopnja zašèite IP 20 B s kondenzatorji z Protection degree IP 20 B with reactor-protected dušilkami, uglasitev na 141 Hz (p = 12,5 %) capacitors detuned to 141 Hz (p = 12.5 %)

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz, nazivna moè do 300 kvarRated voltage 400 V/50 Hz, control voltage 230 V/50 Hz, rated power up to 300 kvar

Osnovna enota Razširitveni modulBasic module Extension module

Moè Št. stopenj Prekl. zap. Koda za naroèilo Koda za naroèilo Teža Dimenzije Vent. Sl.ca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Fan Fig.of steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

75 6 x 12,5 1:1:2:2 MKK-DR12,5-400 / 6x12,5-CX06 MKK-DR12,5-400 / 6x12,5 180 600 x 620 x 2200 2887,5 7 x 12,5 1:2:4 MKK-DR12,5-400 / 7x12,5-CX06 MKK-DR12,5-400 / 7x12,5 180 600 x 620 x 2200 28100 8 x 12,5 1:1:2:4 MKK-DR12,5-400 / 8x12,5-CX06 MKK-DR12,5-400 / 8x12,5 210 600 x 620 x 2200 28100 4 x 25 1:1:2 MKK-DR12,5-400 / 4x25-CX06 MKK-DR12,5-400 / 4x25 200 600 x 620 x 2200 28112,5 9 x 12,5 1:2:2:4 MKK-DR12,5-400 / 9x12,5-CX06 MKK-DR12,5-400 / 9x12,5 220 600 x 620 x 2200 28125 10 x 12,5 1:1:2:2:4 MKK-DR12,5-400 / 10x12,5-CX06 MKK-DR12,5-400 / 10x12,5 240 600 x 620 x 2200 28125 5 x 25 1:2:2 MKK-DR12,5-400 / 5x25-CX06 MKK-DR12,5-400 / 5x25 230 600 x 620 x 2200 28150 12 x 12,5 1:1:2:4:4 MKK-DR12,5-400 / 12x12,5-CX06 MKK-DR12,5-400 /12x12,5 270 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR12,5-400 / 6x25-CX06 MKK-DR12,5-400 / 6x25 260 800 x 620 x 2200 33175 7 x 25 1:2:2:2 MKK-DR12,5-400 / 7x25-CX06 MKK-DR12,5-400 / 7x25 265 800 x 620 x 2200 33200 8 x 25 1:1:2:2:2 MKK-DR12,5-400 / 8x25-CX06 MKK-DR12,5-400 / 8x25 300 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR12,5-400 / 4x50-CX06 MKK-DR12,5-400 / 4x50 310 800 x 620 x 2200 33225 9 x 25 1:2:2:2:2 MKK-DR12,5-400 / 9x25-CX06 MKK-DR12,5-400 / 9x25 340 800 x 620 x 2200 33250 10 x 25 1:1:2:2:2:2 MKK-DR12,5-400 / 10x25-CX06 MKK-DR12,5-400 / 10x25 390 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR12,5-400 / 5x50-CX06 MKK-DR12,5-400 / 5x50 380 800 x 620 x 2200 33275 11 x 25 1:2:2:2:2:2 MKK-DR12,5-400 / 11x25-CX06 MKK-DR12,5-400 / 11x25 440 800 x 620 x 2200 33300 12 x 25 1:1:2:2:2:2:2 MKK-DR12,5-400 / 12x25-CX08 MKK-DR12,5-400 / 12x25 490 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR12,5-400 / 6x50-CX06 MKK-DR12,5-400 / 6x50 460 800 x 620 x 2200 33

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz, nazivna moè do 400 kvarRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz, rated power up to 400 kvar

300 6 x 50 1:1:1:1:1:1 MKK-DR12,5-400 / 6x50-CX06-400 MKK-DR12,5-400 / 6x50-400 460 800 x 620 x 2250 X 39350 7 x 50 1:1:1:1:1:1:1 MKK-DR12,5-400 / 7x50-CX08-400 MKK-DR12,5-400 / 7x50-400 500 800 x 620 x 2250 X 39400 8 x 50 1:1:1:1:1:1:1:1 MKK-DR12,5-400 / 8x50-CX08-400 MKK-DR12,5-400 / 8x50-400 590 800 x 620 x 2250 X 39

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

75 6 x 12,5 1:1:2:2 MKK-DR12,5-690 / 6x12,5-CX06 MKK-DR12,5-690 / 6x12,5 180 800 x 620 x 2200 33100 4 x 25 1:1:2 MKK-DR12,5-690 / 4x25-CX06 MKK-DR12,5-690 / 4x25 210 800 x 620 x 2200 33125 5 x 25 1:2:2 MKK-DR12,5-690 / 5x25-CX06 MKK-DR12,5-690 / 5x25 230 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR12,5-690 / 6x25-CX06 MKK-DR12,5-690 / 6x25 260 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR12,5-690 / 4x50-CX06 MKK-DR12,5-690 / 4x50 300 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR12,5-690 / 5x50-CX06 MKK-DR12,5-690 / 5x50 370 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR12,5-690 / 6x50-CX06 MKK-DR12,5-690 / 6x50 440 800 x 620 x 2200 33

Nazivna napetost 525 V/50 Hz: na zahtevo. Rated voltage 525 V/50 Hz: on request.Prikljuèni preseki dovodnih kablov in varovanja, glej stran 46. Dimenzijske skice na straneh 42 do44.Cross sections for feeding cables and fusing see page 46. Dimensional drawings on pages 42 to44.Pri omarah z nazivno moèjo 250 kvar je pri montaži ob steni potrebno zagotoviti razdaljo mi-nimalno razdaljo 100 mm (montaža hrbet proti hrbtu na zahtevo).Equipment having a rated output 250 kvar has to be installed at a distance of more than 100mm from the wall (installation back to back on request).

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV ES K O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Page 19: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

19

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz, nazivna moè do 400 kvarRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz, rated power up to 400 kvar

300 6 x 50 1:1:1:1:1:1 MKK-DR14-400 / 6x50-CX06-400 MKK-DR14-400 / 6x50-400 460 800 x 620 x 2250 X 39350 7 x 50 1:1:1:1:1:1:1 MKK-DR14-400 / 7x50-CX08-400 MKK-DR14-400 / 7x50-400 500 800 x 620 x 2250 X 39400 8 x 50 1:1:1:1:1:1:1:1 MKK-DR14-400 / 8x50-CX08-400 MKK-DR14-400 / 8x50-400 590 800 x 620 x 2250 X 39

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

75 6 x 12,5 1:1:2:2 MKK-DR14-690 / 6x12,5-CX06 MKK-DR14-690 / 6x12,5 180 800 x 620 x 2200 33100 4 x 25 1:1:2 MKK-DR14-690 / 4x25-CX06 MKK-DR14-690 / 4x25 210 800 x 620 x 2200 33125 5 x 25 1:2:2 MKK-DR14-690 / 5x25-CX06 MKK-DR14-690 / 5x25 230 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR14-690 / 6x25-CX06 MKK-DR14-690 / 6x25 260 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR14-690 / 4x50-CX06 MKK-DR14-690 / 4x50 300 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR14-690 / 5x50-CX06 MKK-DR14-690 / 5x50 370 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR14-690 / 6x50-CX06 MKK-DR14-690 / 6x50 440 800 x 620 x 2200 33

Nazivna napetost 525 V/50 Hz: na zahtevo.Rated voltage 525 V/50 Hz: on request.Prikljuèni preseki dovodnih kablov in varovanje, glej stran 46. Dimenzijske skice, strani 42 do 44.Cross sections for feeding cables and fusing see page 46. Dimensional drawings on pages 42 to44.Pri omarah z nazivno moèjo 250 kvar je pri montaži ob steni potrebno zagotoviti minimalnorazdaljo 100 mm (montaža hrbet proti hrbtu na zahtevo).Equipment having a rated output 250 kvar has to be installed at a distance of more than 100mm from the wall (installation back to back on request).

Velike naprave v prosto stojeèi Large equipment, free standingizvedbi v omarahStopnja zašèite IP 20 B s kondenzatorji z Protection degree IP 20 B with reactor protected dušilkami, uglasitev na 133 Hz (p = 14 %) capacitors detuned to 133 Hz (p = 14 %)

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz, nazivna moè do 300 kvarRated voltage 400 V/50 Hz, control voltage 230 V/50 Hz, rated power up to 300 kvar

Osnovna enota Razširitveni modulBasic module Extension module

Moè Št. stopenj Prekl. zap. Koda za naroèilo Koda za naroèilo Teža Dimenzije Vent. Sl.ca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Fan Fig.of steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

75 6 x 12,5 1:1:2:2 MKK-DR14-400 / 6x12,5-CX06 MKK-DR14-400 / 6x12,5 180 600 x 620 x 2200 2887,5 7 x 12,5 1:2:4 MKK-DR14-400 / 7x12,5-CX06 MKK-DR14-400 / 7x12,5 180 600 x 620 x 2200 28100 8 x 12,5 1:1:2:4 MKK-DR14-400 / 8x12,5-CX06 MKK-DR14-400 / 8x12,5 210 600 x 620 x 2200 28100 4 x 25 1:1:2 MKK-DR14-400 / 4x25-CX06 MKK-DR14-400 / 4x25 200 600 x 620 x 2200 28112,5 9 x 12,5 1:2:2:4 MKK-DR14-400 / 9x12,5-CX06 MKK-DR14-400 / 9x12,5 220 600 x 620 x 2200 28125 10 x 12,5 1:1:2:2:4 MKK-DR14-400 / 10x12,5-CX06 MKK-DR14-400 / 10x12,5 240 600 x 620 x 2200 28125 5 x 25 1:2:2 MKK-DR14-400 / 5x25-CX06 MKK-DR14-400 / 5x25 230 600 x 620 x 2200 28150 12 x 12,5 1:1:2:4:4 MKK-DR14-400 / 12x12,5-CX06 MKK-DR14-400 /12x12,5 270 800 x 620 x 2200 33150 6 x 25 1:1:2:2 MKK-DR14-400 / 6x25-CX06 MKK-DR14-400 / 6x25 260 800 x 620 x 2200 33175 7 x 25 1:2:2:2 MKK-DR14-400 / 7x25-CX06 MKK-DR14-400 / 7x25 265 800 x 620 x 2200 33200 8 x 25 1:1:2:2:2 MKK-DR14-400 / 8x25-CX06 MKK-DR14-400 / 8x25 300 800 x 620 x 2200 33200 4 x 50 1:1:1:1 MKK-DR14-400 / 4x50-CX06 MKK-DR14-400 / 4x50 310 800 x 620 x 2200 33225 9 x 25 1:2:2:2:2 MKK-DR14-400 / 9x25-CX06 MKK-DR14-400 / 9x25 340 800 x 620 x 2200 33250 10 x 25 1:1:2:2:2:2 MKK-DR14-400 / 10x25-CX06 MKK-DR14-400 / 10x25 390 800 x 620 x 2200 33250 5 x 50 1:1:1:1:1 MKK-DR14-400 / 5x50-CX06 MKK-DR14-400 / 5x50 380 800 x 620 x 2200 33275 11 x 25 1:2:2:2:2:2 MKK-DR14-400 / 11x25-CX06 MKK-DR14-400 / 11x25 440 800 x 620 x 2200 33300 12 x 25 1:1:2:2:2:2:2 MKK-DR14-400 / 12x25-CX08 MKK-DR14-400 / 12x25 490 800 x 620 x 2200 33300 6 x 50 1:1:1:1:1:1 MKK-DR14-400 / 6x50-CX06 MKK-DR14-400 / 6x50 460 800 x 620 x 2200 33

AV T O M AT S K E K O M P E N Z A C I J S K E N A P R AV E SK O N D E N Z AT O R J I Z D U Š I L K A M IR E A C T O R - P R O T E C T E D A U T O M AT I C P O W E R FA C T O RC O R R E C T I O N E Q U I P M E N T

Page 20: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

20

u,i Mrežna napetostKondenzatorski tokKondenzatorska napetostNetwork voltageCapacitor currentCapacitor voltage

Regulator jalove moèi v realnem èasu

Real-time powerfactor controlle

Dinamièna kompenzacija

Dynami Compensation

MR

EŽA

NET

WO

RK

Tiristorji1 ... n

BREM

EL1L2L3

Dinamiène kompenzacijske naprave

SplošnoV številnih industrijskih obratih je danes vgrajena zelo dina-mièna pogonska oprema. Poleg nespornih prednosti te tehni-ke pa je prisotna tudi njena slaba stran namreè, da so napa-jalne mreže obremenjene s hitrim spreminjanjem bremena inz višjimi harmoniki. To ima za posledico nestabilne napetost-ne razmere, flikerje, povišanja napetosti in poveèane izgubev distribucijski mreži. Zaradi tega ne pride samo do zmanjš-anja koristne moèi mreže ampak tudi do vplivov na obèutljivaelektronska krmiljenja.Obièajne kompenzacijske jalove moèi so narejene tako, dapoleg èistega optimiranja moènostnega faktorja znižajo tudinivo višjih harmonikov. Vendar pa ne morejo slediti hitrimspremembam bremen in za opisano problematiko ne pred-stavljajo zadovoljive rešitve. Podroèje uporabe teh naprav jekompenzacija statiènih oziroma poèasi se spreminjajoèih bre-men, kjer so preklopni cikli v podroèju minut. DynamiC- stalno optimalen moènostni faktor ϕ- preklapljanje brez tranzientov- odstranjevanje flikerjev

Dinamièna kompenzacija reaktivne moèiPomoè predstavljajo dinamiène naprave s kompenzacijo vrealnem èasu.DynamiC. Pri tej tehnologiji sta obièajna elementa regulatorreaktivne moèi in kondenzatorski kontaktor zamenjana skombinacijo hitrega regulatorja in tiristorsko krmiljenih pre-klopnikov Thyro-C. Ta sistem reagira na spremembo breme-na z minimalno zamudo v eni periodi mreže in prepreèujeskoke reaktivne moèi v napajalni mreži. Moènostni faktor jeoptimiran v vsakem trenutku, obremenitev mreže je reducir-ana na mimimum. Za popolno eliminiranje reakcijskega èasaje krmiljenje kompenzacijskih stopenj mogoèe alternativno iz-vesti direktno preko krmilne elektronike velikih posamiènihporabnikov.

Dynamic compensation equipment

General Many industrial plants today use highly dynamic drive tech-nology. In addition to the undisputed advantages of this mod-ern technology, however, there is the disadvantage that thepower networks are stressed by frequent changes in load aswell as harmonics. This causes unstable voltage conditions,flickering, excessive currents and greater losses in powerdistribution. This in turn not only decreases the amount ofuseable network power but also affects the functions of sen-sitive electronic controllers. Conventional reactive power compensation systems are de-signed for the pure optimization of the power factor and alsoto reduce the harmonics level but are not able to keep upwith fast load changes and do not provide a satisfactory solu-tion to the problem described above. The application area ofthese systems is the compensation of static, or slowly chang-ing loads with switching cycles in the minutes range. DynamiC- At each moment optimized cos ϕ- Soft switching without transients- Flicker eliminated

ApplicationThe real-time power factor compensation equipment in theDynamiC series offers a solution. In these assemblies theclassic components controller and air contactor are substitut-ed by a combination ofcorresponding high speed controllerand thyristor power modules Thyro-C. This system reacts im-mediately to load fluctuation and reactive power surges willbe neutralised in the supply network. The power factor is op-timised at each moment, the negative effects describedabove are reduced to a minimum. This gives the consumernot only the advantage of a stable supply ratio, but the abilityto minimise energy distribution and reduce costs. To increasethe switching performance to an optimum, the control signalfor the control of the capacitor banks can alternatively be giv-en directly by the logic control of bigger loads.

D I N A M I È N E K O M P E N Z A C I J S K E N A P R AV ED Y N A M I C C O M P E N S AT I O N E Q U I P M E N T

Slika 11: Poteki tokov in napetostiFig. 11: Voltage and current curves

Slika 12: Shematièna vezalna shemaFig. 12: Schematic circuit diagram

Page 21: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

21

Dinamiène kompenzacijske naprave

Mehko preklapljanje brez vplivov na mrežoNaslednja pozitivna lastnost tega principa je “mehko” pre-klapljanje kondenzatorjev. Obièajne naprave povzroèajo tran-zientne preklopne konice, ki ne obremenjujejo samo elemen-tov kompenzacije, ampak lahko povzroèajo tudi motnje priporabnikih v mreži. DynamiC v splošnem kondenzatorjevklaplja in tudi izklaplja pri prehodu toka skozi nièlo, s èemerso motnje zaradi tranzientov prepreèene.

Malo vzdrževanjaŠtevilo prekopov naprav z DynamiC je neomejeno, praktiènoni pojavov obrabe. Zaradi preklopv brez tranzientov so varo-valke razbremenjene in imajo znatno daljšo življensko dobo.

Podroèja uporabe:- gradbena in hišna dvigala- mreže z varilnimi napravami- linije s stiskalnicami- testne naprave- energetske vetrne naprave

Regulator jalove moèi v realnem èasu

DynamiC T3, T6, T12

- LCD-multifunkcijski displej- vgrajen analizator mreže- razne možnosti programiranja- opcija: prikljuèek RS485

za Modbus / Profibus - elektronski izhodi za preklapljanje

Dynamic compensation equipment

Smooth switching without perturbationsAnother positive effect of this principle is the ”soft“ switchingof the capacitors. Conventional equipment with air contactorscreates transient inrush currents which not only affect thecompensation components, but can also lead to damagesand interferences of consumers. DynamiC generally switcheson and off during zero current crossing, so avoiding transientinterference completely.

Low-maintenanceThe number of switching operations of DynamiC systems isunlimited. They are almost wear-free. Transient-free switch-ing relieves the backup fuses so that they then have a muchlonger standby period.

Application areas:- Crane systems / elevators- Welding networks - Press lines- Testing stands- Wind power systems

Real-time power factor controller

DynamiC T3, T6, T12

- LCD-multifunction display- Power-analyser integrated- Multiple parameter settings available- Option: Interface RS485

for Modbus or Profibus- Electronic control ports

D I N A M I È N E K O M P E N Z A C I J S K E N A P R AV ED Y N A M I C C O M P E N S AT I O N E Q U I P M E N T

Slika 13: Prikazi na krmilnem modulu Fig. 13: Display of control module

Page 22: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

22

Dinamiène kompenzacijske napravePodatki za projektiranjeNadmorska višina:do 1000 m nad morjem pri nazivnem obratovanjuNazivna napetost in frekvenca:400 V, 50 Hz525 V, 50 Hzdruge napetosti oziroma 60 Hz na zahtevoMaksimalno dopustna delovna napetost:1,0 x UN trajno1,1 x UN do 8 ur na danMaksimalno dopusten delovni tok (brez dušilk):1,3 x IN trajnoMaksimalno dopustne harmonske napetosti:po EN 61000-2-4, razred 2Oblika mreže:TN-C, druge oblike mreže na zahtevoKrmilna napetost in frekvenca:230 V, 50 Hz (60 Hz); pri drugaèni delovni napetosti in frek-venci je potreben krmilni transformator (npr. 525 / 230 V )Preklopna frekvenca po stopnji:10 preklopov na sekundoNazivna moè in število stopenj:glej tabele v nadaljevanjuzaporedja preklopov 1:1:1...; 1:2:2...Praznjenje:s praznilnimi upori (t 3 min)Stopnja zašèite:IP 20 (višje stopnje zašèite na zahtevo)Izgubna moè:kondenzatorji 0,4 W / kvar (merjeno na sponkah kondenzatorjev)dinamiène regulacijske naprave, brez dušilk 5 W / kvardinamiène regulacijske naprave, z dušilkami 8 W / kvarMejne temperatureomare:+ 35° C povpreèje v 24 urah+ 20° C letno povpreèje+ 40° C maksimalna vrednost, kratkotrajno- 10° C minimalna vrednostHlajenje:naravno hlajenje oziroma naravno hlajenje z dodatnimi venti-latorji s filtriBarva:lakiranje: struktura - svetlosiva RAL 7032profili ohišij, zadnja stena in strop: pocinkanoPrikljuèek tokovnega transformatorja:x / 5 A in x / 1 APrikljuèni preseki:glej tabele v nadaljevanjuVarovalke:glej tabele v nadaljevanju

Dynamic compensation equipmentConfiguration dataOperation altitudeUp to 1000 m above sea levelRated Voltage and frequency400 V, 50 Hz525 V, 50 HzOther rated voltages resp. 60 Hz on requestMax. permissable operating voltage1.0 x UN permanent1.1 x UN for 8 h dailyMax. permissable operating current (without reactor-protec-tion)1.3 x IN continuouslyMax. permissible harmonic voltage distortionAccording to EN 61000-2-4, class 2Network configuration: TN-C, other configuration on requestControl voltage and frequency230 V, 50 Hz (60 Hz); a control transformer is required forother operating voltages and frequencies (e. g. 525 / 230 V )Switching frequency per step10 cycles / sRated power and number of stepsSee selection tablesSwitching sequences 1:1:1...; 1:2:2...DischargeWith resistors (t 3 min)Protection levelIP 20 (Higher protection levels upon request)Power dissipationCapacitors 0.4 W / kvar (measured at the capacitor terminals)Dynamic equipment, without reactor protection 5 W / kvarDynamic equipment, with reactor protection 8 W / kvarTemperature limitsPanels:+ 35° C average in 24 hours+ 20° C annual average+ 40° C max., short time- 10° C low limitCoolingSelf-cooling or self-cooling supported by additional fanCoatingPanel: structure-grey RAL 7032Panel profiles, back and top: galvanizedConnection for current transformerx / 5 A and x / 1 AWire cross sectionsSee selection tablesFusesSee selection tables

D I N A M I È N E K O M P E N Z A C I J S K E N A P R AV ED Y N A M I C C O M P E N S AT I O N E Q U I P M E N T

Page 23: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

23

Dinamiène kompenzacijske Dynamic compensation naprave, IP 20 B equipment, IP 20 B

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz – s kondenzatorji z dušilkami*Rated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz – with reactor-protected capacitors*

Osnovna enota Razširitveni modulBasic module Extension module

Moè Št. stopenj Prekl. zap. Koda za naroèilo Koda za naroèilo Teža Dimenzije Vent. Sl.ca. kg B x T x H (mm)

Power Number Switching- Order code Order code Weight Dimensions Fan Fig.of steps sequence appr. kg W x D x H (mm)

(kvar) (kvar)

75 6 x 12,5 1:1:2:2 DyC-20-400 / 6x12,5-T06 DyC-20-400 / 6x12,5 160 600 x620 x 2250 X 3487,5 7 x 12,5 1:2:4 DyC-20-400 / 7x12,5-T06 DyC-20-400 / 7x12,5 168 600 x620 x 2250 X 34100 8 x 12,5 1:1:2:4 DyC-20-400 / 8x12,5-T06 DyC-20-400 / 8x12,5 175 600 x620 x 2250 X 34100 4 x 25 1:1:2 DyC-20-400 / 4x25-T06 DyC-20-400 / 4x25 185 600 x620 x 2250 X 34125 5 x 25 1:2:2 DyC-20-400 / 5x25-T06 DyC-20-400 / 5x25 190 600 x620 x 2250 X 34150 6 x 25 1:1:2:2 DyC-20-400 / 6x25-T06 DyC-20-400 / 6x25 190 600 x620 x 2250 X 34175 7 x 25 1:2:2:2 DyC-20-400 / 7x25-T06 DyC-20-400 / 7x25 195 600 x620 x 2250 X 34200 8 x 25 1:1:2:2:2 DyC-20-400 / 8x25-T06 DyC-20-400 / 8x25 205 800 x620 x 2250 X 34200 4 x 50 1:1:1:1 DyC-20-400 / 4x50-T06 DyC-20-400 / 4x50 200 800 x620 x 2250 X 34225 9 x 25 1:2:2:2:2 DyC-20-400 / 9x25-T06 DyC-20-400 / 9x25 220 800 x620 x 2250 X 34250 10 x 25 1:1:2:2:2:2 DyC-20-400 / 10x25-T06 DyC-20-400 / 10x25 230 800 x620 x 2250 X 34250 5 x 50 1:1:1:1:1 DyC-20-400 / 5x50-T06 DyC-20-400 / 5x50 230 800 x620 x 2250 X 34275 11 x 25 1:2:2:2:2:2 DyC-20-400 / 11x25-T06 DyC-20-400 / 11x25 250 800 x620 x 2250 X 34300 6 x 50 1:1:1:1:1:1 DyC-20-400 / 6x50-T06 DyC-20-400 / 6x50 260 800 x620 x 2250 X 34

75 6 x 12,5 1:1:2:2 DyC-DR..-400 / 6x12,5-T06 DyC-DR..-400 / 6x12,5 180 600 x620 x 2250 X 3487,5 7 x 12,5 1:2:4 DyC-DR..-400 / 7x12,5-T06 DyC-DR..-400 / 7x12,5 190 600 x620 x 2250 X 34100 8 x 12,5 1:1:2:4 DyC-DR..-400 / 8x12,5-T06 DyC-DR..-400 / 8x12,5 210 600 x620 x 2250 X 34100 4 x 25 1:1:2 DyC-DR..-400 / 4x25-T06 DyC-DR..-400 / 4x25 200 600 x620 x 2250 X 34125 5 x 25 1:2:2 DyC-DR..-400 / 5x25-T06 DyC-DR..-400 / 5x25 220 600 x620 x 2250 X 34150 6 x 25 1:1:2:2 DyC-DR..-400 / 6x25-T06 DyC-DR..-400 / 6x25 250 600 x620 x 2250 X 34175 7 x 25 1:2:2:2 DyC-DR..-400 / 7x25-T06 DyC-DR..-400 / 7x25 255 600 x620 x 2250 X 34200 8 x 25 1:1:2:2:2 DyC-DR..-400 / 8x25-T06 DyC-DR..-400 / 8x25 270 800 x620 x 2250 X 34200 4 x 50 1:1:1:1 DyC-DR..-400 / 4x50-T06 DyC-DR..-400 / 4x50 260 800 x620 x 2250 X 34225 9 x 25 1:2:2:2:2 DyC-DR..-400 / 9x25-T06 DyC-DR..-400 / 9x25 275 800 x620 x 2250 X 34250 10 x 25 1:1:2:2:2:2 DyC-DR..-400 / 10x25-T06 DyC-DR..-400 / 10x25 360 800 x620 x 2250 X 34250 5 x 50 1:1:1:1:1 DyC-DR..-400 / 5x50-T06 DyC-DR..-400 / 5x50 350 800 x620 x 2250 X 34275 11 x 25 1:2:2:2:2:2 DyC-DR..-400 / 11x25-T06 DyC-DR..-400 / 11x25 410 800 x620 x 2250 X 34300 6 x 50 1:1:1:1:1:1 DyC-DR..-400 / 6x50-T06 DyC-DR..-400 / 6x50 420 800 x620 x 2250 X 34300 5 x 60 1:1:1:1:1 DyC-DR..-400 / 5x60-T06 DyC-DR..-400 / 5x60 400 800 x620 x 2250 X 34360 6 x 60 1:1:1:1:1:1 DyC-DR..-400 / 6x60-T06 DyC-DR..-400 / 6x60 450 800 x620 x 2250 X 34

* Naprave z dušilkami so dobavljive z:dušilkami uglašenimi na fr = 189 Hz (p = 7 %)dušilkami uglašenimi na fr = 210 Hz (p = 5,67%)dušilkami uglašenimi na fr = 141 Hz (p = 12,5 %)dušilkami uglašenimi na fr = 133 Hz (p = 14 %)Detajlne informacije o kondenzatorjih z dušilka-mi se nahajajo na straneh 12 in 13.Merske skice so na straneh 42, 43. Prikljuènepreseke za dovodne kable in varovanje, glejstran 46. Druge nazivne napetosti in 60 Hz na zahtevo.Naprave so opremljene s tiristorskimi preklop-niki Thyro-C. Tehnièni podatki za te preklopnikese nahajajo v posebnem katalogu.

* Reactor-protected equipment is availablewith:reactors tuned to fr = 189 Hz (p = 7 %)reactors tuned to fr = 210 Hz (p = 5,67 %)reactors tuned to fr = 141 Hz (p = 12,5 %)reactors tuned to fr = 189 Hz (p = 14 %)Detailed information about reactor-protectedcapacitors see pages 12 and 13.Dimensional drawings on pages 42, 43. Crosssections for feeding cables and fusing see pa-ge 46. Other rated voltages and 60 Hz on re-quest.These assemblies are equipped withthyristor power modules Thyro-C. Technicaldata of these devices are defined in a separa-te documentation.

D I N A M I È N E K O M P E N Z A C I J S K E N A P R AV ED Y N A M I C C O M P E N S AT I O N E Q U I P M E N T

Thyro-C / Thyro-C

Tu: desno odpiranje vrat;

Standardna izvedb: levo od-

piranje vrat

Here: Door hinges on right;

Standard model: Door hin-

ges on left

Page 24: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

24

Naprave z uglašenimi filtri

SplošnoNaprave s filterskimi krogi se uporabljajo v mrežah z velikimdeležem višjih harmonikov. Te naprave opravljajo nalogokompenzacije prisotne induktivne jalove moèi in istoèasnoizboljšujejo kakovost mrežne napetosti. V številnih industrijs-kih mrežah je mogoèe vzdrževati obremenitve z višjimi har-moniki znotraj mejnih vrednosti po EN 61000-2-2 samo zuporabo teh specialnih uglašenih filterskih krogov (imenova-nih tudi pasivni filterski krogi). Naèin delovanja filterskih kro-gov je prikazan na slikah 14 in 15.

UporabaFilterske naprave so (podobno kot naprave s kondenzatorji zdušilkami) sestavljene iz posameznih modulov. Število mo-dulov in moè posameznega modula sta odvisna od potrebnemoèi za kompenzacijo, še bolj pa od velikosti posameznihharmonikov.

Kar zadeva moè kompenzacije ima izbor frekvenc uglasitvepodrejen pomen, veliko bolj je pomemben izbor uglasitveglede na delovanje naprave z uglašenimi filtri v zvezi z izbol-jšanjem kakovosti mrežne napetosti. V tem pogledu je pose-ben pomen naprav z uglašenimi filtri v primerjavi z naprava-mi s kondenzatorji z dušilkami. Za doseganje optimalnegauèinka pri istoèasno stroškovno ugodni izvedbi morajo biti fil-terski krogi natanèno prilagojeni na konkretne pogoje mreže.Krogi so sestavljeni iz modulov, ki imajo resonanène frekven-ce skladne s frekvencami povratnih mrežnih vplivov usmerni-kov. Pri usmernikih v nizkonapetostnih mrežah, kjer so us-merniki najveèkrat 6 in 12 pulzni, so to moduli za 5., 7., 11.in 13. harmonik. Izraèun prièakovanih harmonskih tokov je potrebno doslednonarediti za najtežje delovne pogoje (worst case). Za ocenoharmonskih tokov je mogoèe uporabiti sledeèe izkustvenevrednosti:

- 5. harmonik I5 = 0,30 … 0,35 I1- 7. harmonik I7 = 0,10 … 0,12 I1- 11. harmonik I11 = 0,08 … 0,10 I1- 13. harmonik I13 = 0,06 … 0,08 I1

Te orientacijske vrednosti veljajo za 6 pulzne usmernike infrekvenène pretvornike z diodnim mostièkom na mrežni stra-ni, sicer pa je potrebno upoštevati podatke dobaviteljev us-mernikov. Optimalno prilagoditev filterskih krogov na konkret-ne pogoje mreže in obremenitve je mogoèe doseèi s pomoè-jo analize harmonikov (meritve mreže).

N A P R AV E Z U G L A Š E N I M I F I LT R IT U N E D F I LT E R C I R C U I T S E Q U I P M E N T

Tuned filter circuits equipment

GeneralFilter circuit systems are used in very harmonics-stressednetworks. They compensate existing inductive reactive powerand, at the same time, improve the quality of the system volt-age. Adherence to the limit values for the harmonic load inaccordance with EN 61000-2-2 can only be accomplished inmany industrial power networks by using these especiallytuned filter circuits (also called passive filter circuits). Figures14 and 15 illustrate how the filter circuits work.

ApplicationFilter systems are (similar to reactor protected compensationsystems) made up of modules. The number and capacity ofthe individual modules depends on both the amount of com-pensation capacity needed and, much more importantly, onthe amount of discrete harmonic currents.

Regarding the compensation capacity, the selection of thetuning frequencies only plays a minor role but not with regardto the effect of the filter circuit system for improvement of thequality of the network voltage. This is the special significanceof the systems with tuned filter circuits in comparison to thesystems with reactor-protected capacitors. To obtain optimumefficiency at the same time as inexpensive design, the filtercircuits must be precisely tuned to the existing network con-ditions. They are made up of modules whose resonance fre-quencies correspond to the frequencies of the power con-verter perturbations. With the 6 and 12-pulse power convert-ers which usually exist in the low voltage network, these aremodules for the 5th, 7th, 11th and 13th harmonics.

Calculation of the harmonic currents to be expected must al-ways be performed for the greatest load (worst case). Thefollowing values derived from experience can be used to esti-mate the harmonic currents.

- 5th harmonics I5 = 0.30 … 0.35 I1- 7th harmonics I7 = 0.10 … 0.12 I1- 11th harmonics I11 = 0.08 … 0.10 I1- 13th harmonics I13 = 0.06 … 0.08 I1

These standard values apply to 6-pulse power convertersand frequency converters with network-side diode bridge.Otherwise the specifications of the power converter suppliersapply. An optimal tuning of the filter circuits to the existingpower and load conditions can be achieved with a harmonicsanalysis (network measurement).

Page 25: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

25

Izvedba

Filterski krogi so na razpolago v obliki omar za mrežne nape-tosti 400 V in 690 V. Na zahtevo so dobavljive posebne iz-vedbe (eno in dvofazne, posebne napetosti in frekvence). Vposamièno omaro so vgrajeni maksimalno 4 filterski moduli.Vsak modul je sestavljen iz sledeèih bistvenih elementov :

- NN - moènostno loèilno stikalo z varovalkami- moènostni kondenzatorji z veliko tokovno obremenljivostjo

in veliko stabilnostjo kapacitivnosti- filterske dušilke v posebni izvedbi za velike harmonske to-

kove- termistorska zašèita s tipko za resetiranje za nadzor tem-

perature filterskih dušilk- zraèni kontaktor za preklapljanje modula- praznilne dušilke za hitro praznjenje modulov- preèna povezava k modulom z enako frekvenco uglasitve

s kontaktorjem in tokovnim relejem za nadzor modula inza lineariziranje tokov posameznih modulov.

Vklapljanje filterskih krogov se v skladu s projektom napraveizvede z roènim krmiljenjem in / ali z daljinskim krmiljenjem spomoèjo zunanjih krmilnih ukazov npr. preko SPS pogona, kiga kompenziramo. Pri tem je priporoèeno, da je filterska na-prava vklopljena prej kot pogon. V ta namen je npr. sprosti-tev regulacije kompenziranega usmernika mogoèe nareditiodvisno od stanja vklopa potrebne filterske naprave, za karje na razpolago brezpotencialen kontakt (doveden na sponè-no letev).

V splošnem je potrebno paziti na pravilno vklapljanje in izklapl-janje filterskih krogov. Za prepreèitev resonanènih problemovje potrebno dosledno najprej vklopiti filterski krog z najnižjofrekvenco uglasitve, nato z naslednjo višjo itd. Izklop je potreb-no izvesti v obratnem vrstnem redu. Pri tem je nujno potrebnoizklopiti kroge z višjimi frekvencami uglasitve, kadar so krogi znižjimi frekvencami uglasitve izklopljeni. Notranja zapora pre-preèuje morebitno napaèno manipulacijo take vrste in je zato vnobenem primeru ne smemo izklopiti.

f 5 f 7 f 5

f

Z

Induktivna Inductive

Kapacitivna Capacitive

MInduktivno

bremeRectifier

drive

ElektoenergetskoomrežjeNetwork

v=5 v=7 v=11

V mrežoInto thenetwork

V filterski krog

Into thefilter

circuits

Harmonski tokHarmonic current

N A P R AV E Z U G L A Š E N I M I F I LT R IT U N E D F I LT E R C I R C U I T S E Q U I P M E N T

Slika 14: Potek impedanceFig. 14: Impedance curves

Slika 15: Pretok harmonskih tokovFig. 15: Flow of harmonic currents

Design

Filter circuits in cabinet construction are offered for rated net-work voltages of 400 V and 690 V. Special models (single ortwo-phase, special voltages and frequencies) are availableon request. A maximum of 4 filter circuit modules are in-stalled per cabinet. Each module consists of the following pri-mary components.

- H.R.C. fuse load breaker- Power capacitors with high current carrying capability and

high capacity constancy- Filter circuit reactors in special models for high harmonic

currents - Thermistor protection with reset key for temperature moni-

toring of the filter circuit reactors- Air contactor for switching the module- Discharge reactors for fast discharge of the modules- Cross connection to the modules of the same tuning fre-

quency with contactor and current relay for monitoring themodule and for linearization of the currents of the individu-al modules

Depending on the particular project, the filter circuits areswitched on via manual control and/or via remote control viaexternal control commands (e.g., by the PLC of the drive tobe compensated). We recommend switching the filter systemthrough before the drive. For instance, the control enable ofthe current converter to be compensated can be made de-pendent on the switching through of the filter system forwhich a potential-free contact (on terminals) is then provided. In general it must be ensured that the switching on and off ofthe filter circuits is correct. To avoid resonance problems, thefilter circuit with the lowest tuning frequency must always beswitched on first, followed by the next highest, and so on.Switching off must then take place in reverse order. This en-sures that operation of the filter circuits of the higher tuningfrequencies is impossible when circuits of the lower tuningfrequencies are switched off. An internal block which mustnot be cancelled prevents operator mistakes regarding this.

impedanca flterskega vezja vodvisnosti od fekvenceFilter circuit impendancedepending on the frequency

Harmosnki tokovi v bremeFlow of harmonic currents

Page 26: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

26

Naprave z uglašenimi filterskimi krogi

Podatki za projektiranje

Nadmorska višina:do 2000 m nad morjem pri nazivnem obratovanjuNazivna napetost in frekvenca:400 V, 50 Hz690 V, 50 Hzdruge nazivne nazivne napetosti oziroma 60 Hz na zahtevoMaksimalno dopustna delovna napetost:1,0 x UN trajno1,1 x UN do 8 ur na danNazivni tok:glej tabele v nadaljevanjuOblika mreže:TN-Cdruge oblike mreže na zahtevoKrmilna napetost in frekvenca:230 V, 50 Hz (60 Hz); pri drugaèni delovni napetosti in frek-venci je potreben krmilni transformator (npr. 525 / 230 V ali690 / 230 V)Nazivna moè in število stopenj:glej tabele v nadaljevanjuPraznjenje:z dušilkami t 8 sStopnja zašèite:IP 20Izgubna moè:kondenzatorji 0,4 W / kvar (merjeno na sponkah konden-zatorjev)filterske naprave 8,0 W / kvar (instalirana moè)Mejne temperature:omare:+ 35° C povpreèje v 24 urah+ 20° C letno povpreèje+ 40° C maksimalna vrednost, kratkotrajno– 10° C minimalna vrednostHlajenje:naravno hlajenje, z dodatnimi ventilatitorji s filtriBarva:lakiranje: gramozno siva RAL 7032profili ohišja, zadnja stena in strop: pocinkanoPrikljuèni preseki in varovanje:glej stran 46Hrupnost naprave:

60 dB pri zaprtih napravah pri nazivnem obratovanju narazdalji1 m

Tuned filter circuits equipment

Configuration data

AltitudeUp to 2000 m above sea levelRated voltage and frequency400 V, 50 Hz690 V, 50 HzOther rated voltages resp. 60 Hz on requestMax. permissible operating voltage1.0 x U permanent1.1 x U for 8h dailyRated currentSee selection tablesNetwork configurationTN-COther configuration on requestControl voltage and frequency230 V, 50 Hz (60 Hz); a control transformer is required forother operating voltages and frequencies(for example 525 / 230 V or 690 / 230 V)Rated power and number of stepsSee selection tablesDischargeWith chokes t 8 sProtectionIP 20Power dissipationCapacitors 0.4 W / kvar (measured at the capacitor termi-nals)Filter circuit equipment 8.0 W / kvarTemperature limitsPanels:+35° C average in 24 hours+20° C annual average+40° C max. short time–10° C low limitCoolingSelf cooling, supported by fanCoatingPanel: grey RAL 7032Panel profiles, back and top: galvanizedCross sections und fusesSee page 46Noise emission

60 dB in enclosed equipment at rated servicein 1m distance

N A P R AV E Z U G L A Š E N I M I F I LT R IT U N E D F I LT E R C I R C U I T S E Q U I P M E N T

Page 27: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

27

Uglašeni filterski krogi Tuned filter circuits equipmentVelike naprave v prosto stojeèih omarah Large equipment, free standing

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

Moè Nazivni tokovi Št. omar kroga Koda za naroèilo Teža Dimenzije Vent./naprava. ca. kg B x T x H (mm)

Power Rated current Number of fc Order code Weight Dimensions Fan50 Hz 250 Hz 350 Hz 550 Hz cub. / assembl. appr. kg W x D x H (mm)

(kvar) (A) (A) (A) (A)

97 140 130 – – 1/2 MKK-FK200-400 / 97 220 800 x 620 x 2250 X144 209 130 65 – 1/3 MKK-FK210-400 / 144 260 800 x 620 x 2250 X145 210 195 – – 1/3 MKK-FK300-400 / 145 260 800 x 620 x 2250 X191 277 130 65 65 1/4 MKK-FK211-400 / 191 300 800 x 620 x 2250 X192 279 195 65 – 1/4 MKK-FK310-400 / 192 300 800 x 620 x 2250 X289 417 260 130 – 2/6 MKK-FK420-400 / 289 470 1600 x 620 x 2250 X336 485 260 130 65 2/7 MKK-FK421-400 / 336 520 1600 x 620 x 2250 X337 487 325 130 – 2/7 MKK-FK520-400 / 337 520 1600 x 620 x 2250 X383 553 260 130 130 2/8 MKK-FK422-400 / 383 580 1600 x 620 x 2250 X431 622 325 130 130 3/9 MKK-FK522-400 / 431 700 2400 x 620 x 2250 X433 625 390 195 – 3/9 MKK-FK630-400 / 433 700 2400 x 620 x 2250 X527 761 390 195 130 3/11 MKK-FK632-400 / 527 830 2400 x 620 x 2250 X578 834 520 260 – 3/12 MKK-FK840-400 / 578 870 2400 x 620 x 2250 X766 1105 520 260 260 4/16 MKK-FK844-400 / 766 1170 3200 x 620 x 2250 X908 1311 585 390 260 5/19 MKK-FK964-400 / 908 1450 4000 x 620 x 2250 X

120 100 80 – – 1/2 MKK-FK200-690 / 120 220 800 x 620 x 2250 X179 149 80 40 – 1/3 MKK-FK210-690 / 179 260 800 x 620 x 2250 X357 298 160 80 – 2/6 MKK-FK420-690 / 357 470 1600 x 620 x 2250 X415 346 160 80 40 2/7 MKK-FK421-690 / 415 510 1600 x 620 x 2250 X592 496 240 80 80 3/10 MKK-FK622-690 / 592 760 2400 x 620 x 2250 X711 595 280 120 80 3/12 MKK-FK732-690 / 711 870 2400 x 620 x 2250 X713 597 320 160 – 3/12 MKK-FK840-690 / 713 870 2400 x 620 x 2250 X945 791 320 160 160 4/16 MKK-FK844-690 / 945 1170 3200 x 620 x 2250 X1113 931 360 240 160 5/19 MKK-FK964-690 /1113 1450 4000 x 620 x 2250 X

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

Druge nazivne napetosti in 60 Hz na zahtevo.Other rated voltages and 60 Hz on request.Prikljuèni preseki dovodnih kablov in varovanje, glej stran 46.Cross sections for feeding cables and fusing see page 46.Pri omarah z nazivno moèjo 250 kvar je pri montaži ob steni potrebno zagotoviti minimalnorazdaljo 100 mm (montaža hrbet proti hrbtu na zahtevo).Equipment having a rated output 250 kvar has to be installed at a distance of more than 100mm from the wall (installation back to back on request).

N A P R AV E Z U G L A Š E N I M I F I LT R IT U N E D F I LT E R C I R C U I T S E Q U I P M E N T

Slika 16 / Fig. 16

Page 28: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

28

Sistemi z aktivnimi filtri

SplošnoAktivni mrežni energetski filtri se v osnovi razlikujejo od pa-sivnih kompenzacijskih in filterskih naprav. Delujejo kot krmil-jeni tokovni izvori. To dovoljuje, da se v mrežo pošilja tok spoljubno fazo, amplitudo in frekvenco. Jalova moè, spre-membe bremen in višji harmoniki so kompenzirani po princi-pu dušenja.

TehnologijaSistemi z aktivnimi filtri se v osnovi sestojijo iz vmesnika, kije narejen kot IGBT napetostni pretvornik. Ta vmesnik je namrežo, ko jo želimo kompenzirati, prikljuèen preko mrežnegafiltra. Z njim je eliminirana frekvenca takta pulza. V vmesnikuse nahaja kondenzator za enosmerno napetost, ki služi kotshranjevalec energije. Krmilna elektronika stalno primerja tre-nutno stanje v mreži z vnaprej doloèenim idealnim stanjem inistoèasno in loèeno v vsako fazo dodaja doloèen tok (faznatokovna regulacija)..

Kompenzacija reaktivne moèiNaprava lahko na svojih prikljuènih sponkah pošilja v mrežokakršnokoli jalovo moè osnovne frekvence, induktivno ali ka-pacitivno. To se dogaja loèeno v vsaki fazi posebej, kar imaza posledico tudi simetriranje porabe toka.

Kompenzacija harmonikovTok bremena, ki ga želimo kompenzirati, teèe preko tokovne-ga transformatorja. Aktivni filter iz tega signala izolira delež zvišjimi harmoniki in ga ponovno pošilja v mrežo vendar znasprotno fazo. To ima za posledico dušenje harmonikov, tokmreže je sestavljen samo še iz èistega dela z osnovno frek-venco. Regulacija lahko v realnem èasu kompenzira vse har-monike, lahko pa samo posamezne izbrane harmonike intudi jalovo moè.

Slika 17: Principielna vezna shema aktivnih filtrov (štirižiènaizvedba èrtkano)

Fig. 17: Principle circuit diagram of active filters (four-con-ductor model shown with broken lines).

L1

L2

L3

N

Filter v mrežiLine filter

Napetostni usmernik IGBTIGBT power block

Enosmerni kondenzatorDC link capacitor

S I S T E M I Z A K T I V N I M I F I LT R IA C T I V E F I LT E R S Y S T E M S

Active filter systems

GeneralActive power capacity filters differ fundamentally from pas-sive compensation and filter circuit systems. They functionlike a controlled current source. This permits current in anyphase, amplitude and frequency to be supplied to the net-work. Reactive power, changes in load and harmonics areactively compensated by the principle of suppression.

TechnologyActive filter systems basically consist of an (IGBT) voltagesource DC link converter. To eliminate the clock pulse fre-quency, this is connected via a power filter to the power to becompensated. The DC link is equipped with a direct currentcapacitor as the source of power. The control electronics con-tinuously compare the actual value on the network with thespecified ideal value and simultaneously update the currentflow for each phase separately (phase current control).

Reactive power compensation The device can supply any basic harmonic reactive power in-ductively and capacitively at the connection point to the net-work. This is done separately for each phase which also con-tributes to the symmetry of current consumption. Harmonics compensation The load current to be compensated is acquired via a currentconverter. The active filter isolates the harmonics portionfrom this signal and feeds this during phase opposition backto the network. This causes a suppression and the networkcurrent now only consists of the pure basic harmonics por-tion. The controller can both suppress all harmonics in realtime or, as an alternative, compensate individually selectedharmonics as well as reactive power.

Page 29: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

ElektroenergetskoomrežjeNetwork

Tok omrežjaNetwork current

Aktivni filterActive filter

Tok bremenaLoad current

Nelinearno breme

Nonlinear load

Kompenzirani tokCompensating current

29

Sistemi z aktivnimi filtri

Kompenzacija nièelnega vodnikaKot posebna izvedba za štirižiène mreže se naprava sestojiiz štirih moènostnih tokokrogov. To je potrebno zato, da se vnièelnem vodniku kompenzira harmonike 3. harmonika innjegove mnogokratnike. Dimenzioniranje kroga za nièelnivodnik je mogoèe izbrati do trikratne vrednosti bremena zu-nanjega vodnika.

Kompenzacija flikerjevPri hitrem porastu bremena, ki ga hoèemo kompenzirati, ak-tivni filter v napajalno mrežo kratkotrajno oddaja shranjenoenergijo iz vmesnega tokokroga s kondenzatorjem. Pri zman-jšanju bremena pa obratno aktivni filter iz mreže potegneenergijo v vmesni tokokrog. Na ta naèin je sprememba bre-mena, gledano s strani mreže, zglajena, s èimer je delovanjeflikerja (zaznavanje nihanja svetlobe) znižano pod mejo zaz-navanja (Pst = 1). Za kompenzacijo flikerja morajo imeti na-prave poveèano kapaciteto vmesnega tokokroga.

Slika 18: Princip delovanja aktivnega filtra Fig. 18: Function principle of active filter

Slika 19: Poraba pulznega tokabremena (rdeèe), aktivnega filtra(modro) in glajena iz mreže (zele-no)

Fig. 19: Pulsed current consump-tion of a load (red), of the activefilter (blue) and smoothed out ofthe network (green).

S I S T E M I Z A K T I V N I M I F I LT R IA C T I V E F I LT E R S Y S T E M S

Active filter systemsNeutral conductor compensation In the special model for four-conductor networks, the deviceconsists of four power circuits. This is necessary for the com-pensation of harmonics of the 3rd harmonic and their multi-ples on the neutral conductor. The design of the neutral con-ductor circuit can be selected up to three times the load ofthe outer conductor.

Flicker compensationWith a fast increase in the load to be compensated, the ac-tive filter briefly feeds the power stored in the DC link capaci-tor to the power network. When the load drops, the active fil-ter pulls power in reverse from the network into the DC link.Using this principle, the network-side change in load issmoothed and the flicker effect (perceptible light fluctuations)is reduced to below perception (Pst = 1). The devices mustbe equipped for flicker compensation with an enlarged DClink capacity.

Page 30: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

30

Sistemi z aktivnimi filtri

Tipièna podroèja uporabe so mreže z:

- veliko obremenitvijo s harmoniki- harmonskimi tokovi v nièelnem vodniku- nesimetrièno obremenitvijo- hitro spreminjajoèimi bremeni- obremenitvijo s flikerji

Active filter systems

Typical application areas are networks with:

- High harmonic load- Harmonic currents on the neutral conductor- Asymmetrical load- Quickly changing loads- Flicker load

Druge nazivne napetosti in frekvence na zahtevo. Other rated voltages and frequencies on request.

Aktivni filter, IP 20 B Active filter, IP 20 B

Nazivna napetost 400 V / 50 Hz – Rated voltage 400 V / 50 Hz

Moè Koda za naroèilo Tok Tok v Dimenzije teža Priporoèeni tok. Potrebna Ventilator(kvar) po fazi (A) nièelnem vodn.(A) B x T x H (mm) (kg) transformator varovalka (A)Power Order code Current Current neutral- Dimensions Weight Recommended Fuse Fan(kvar) per phase (A) conductor (A) W x D x H (mm) (kg) CT (A)

Trižièna izvedba / Three-conductor model17 AcF-20-400 / 17-3 25 600 x 500 x 1800 130 250/1 63 X35 AcF-20-400 / 35-3 50 600 x 500 x 1800 150 500/1 63 X70 AcF-20-400 / 70-3 100 600 x 500 x 1800 240 1000/1 125 X105 AcF-20-400 / 105-3 150 1200 x 500 x 1800 390 1500/1 125 + 63 X140 AcF-20-400 / 140-3 200 1200 x 500 x 1800 480 2000/1 2 x 125 X175 AcF-20-400 / 175-3 250 1800 x 500 x 1800 630 2500/1 2 x 125 + 63 X210 AcF-20-400 / 210-3 300 1800 x 500 x 1800 720 3000/1 3 x 125 X280 AcF-20-400 / 280-3 400 2400 x 500 x 1800 960 4000/1 4 x 125 XŠtirižièna izvedba / Four-conductor model20 AcF-20-400 / 20-4x2 30 60 600 x 500 x 1800 290 250/1 63 X40 AcF-20-400 / 40-4x2 60 120 600 x 500 x 1800 325 500/1 63 X70 AcF-20-400 / 70-4x1 100 100 600 x 500 x 1800 400 1000/1 125 X110 AcF-20-400 / 110-4x1 160 160 1800 x 500 x 1800 725 1500/1 125 + 63 X140 AcF-20-400 / 140-4x1 200 200 1800 x 500 x 1800 800 2000/1 2 x 125 X210 AcF-20-400 / 210-4x1 300 300 2400 x 500 x 1800 1200 3000/1 3 x 125 X

Štirižièna izvedbaFour-conductor model

Trižièna izvedba (v veè poljih)Three-conductor model (multiple span)

S I S T E M I Z A K T I V N I M I F I LT R IA C T I V E F I LT E R S Y S T E M S

Page 31: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

31

Aktivni filter AcF

Podatki za projektiranje

Nadmorska višina:do 1000 m nad morjem pri nazivnem delovanjuNazivna napetost in frekvenca:400 V +10 % / -20 %50 Hz / 60 Hz ±2 %druge nazivne napetosti na zahtevoNazivni efektivni tok:glej tabele v nadaljevanjuHistereza toka:okrog 10 % nazivnega efektivnega tokaDinamièna obremenljivost:1,2 x nazivni efektivni tokKonièna vrednost zaèetnega toka:2 x nazivni efektivni tokTok nièelnega vodnika (štirižièna izvedba):opcionalno 1x (2x, 3x) tok faznega vodnikaStopnja zašèite:IP 20Preklopna frekvenca:10 kHz srednja vrednostReakcijski èas:< 1 ms, dušenje tranzientnih tokovIzgubna moè/stopnja izkoristka:< 3 % nazivne moèi / > 97 % stopnja izkoristkaOkoljski pogoji:0° C - 40° C temperatura okolicedo 85 % zraène vlage brez orositve-25° C - 70° C temperatura pri transportu-25° C - 55° C temperatura pri skladišèenjuHlajenje:vgrajen ventilator s filtromBarva:lakiranje: gramozno siva RAL 7032Nivo hrupa naprave:< 60 dB pri zaprti napravi pri nazivnem obratovanjuCE certifikat:preizkušeno v skladu z EN 50081-2 in EN 50082-2Javljanje okvare:displej na vratih, optièno izoliran I/O

Active Filter AcF

Configuration data

AltitudeUp to 1000 m above sea levelRated voltage and frequency400 V + 10 % / -20 %50 Hz / 60 Hz ± 2 %Other rated voltages on requestRMS-value of rated currentSee selection tablesCurrent hysteresisApprox. 10 % of the RMS-value of rated currentDynamically overload capability1.2 x RMS-value of rated currentOutput peak current2 x RMS-value of rated currentNeutral current (four wire version)Optional 1x (2x, 3x) phase-currentProtectionIP 20Switching frequency10 kHz in averageDelay time< 1 ms, transient current suppressionPower dissipation / Efficiency< 3 % of the rated power / > 97 % efficiencyEnvironmental conditions0° C to 40° C temperature limitsUp to 85 % humidity, no dew-25° C to 70° C temperature of transport-25° C to 55° C temperature of storageCoolingForced cooling with fanCoatingPanel: grey RAL 7032Noise emission< 60 dB in enclosed equipment at rated serviceCE certificationTested acc. to EN 50081-2 and EN 50082-2Fault indicatorDisplay element in the door, optically isolated I/O

S I S T E M I Z A K T I V N I M I F I LT R IA C T I V E F I LT E R S Y S T E M S

Page 32: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

32

Regulatorji reaktivne moèi CX, CMLastnosti:- Meritev in nadzor reaktivne moèi v 4 kvadrantnem delovanju - Meritev in nadzor moèi stopenj pri preklapljanju - Nastavitev prestavnega razmerja tokovnega transformatorja

ni potrebna (pri BLR-CM in BLR-CX...M je potreben vnosprestavnega razmerja za prikaz merjenih vrednosti)

- Nastavitev ciljnega cos ϕ v obmoèju 0,70 ind. - 1 - 0,90 kap.- Nastavljiv preklopni èas - Roèno preklapljanje po izbiri- Izklop delovanja zaradi izpada napetosti po prekinitvi mrežne

napetosti > 35 ms - Zaporni èas pri izpadu mrežne napetosti 90 s - Optièni prikaz stopenj - Javljanje motnje, èe ni dosežen ciljni cos ϕ

(po preteku 75 preklopnih ciklov)Napajalna napetost:90 … 132 V / 198 … 253 V, 45 … 65 Hz, 6 VA, maksimalna va-rovalka gL 6 AMerilna napetost:50 … 530 V, 45 … 65 Hz, prestavno razmerje 1 … 350Merilni tok:0 … 5 A, prag obèutljivosti 10 mA, breme 15 mW,Prestavno razmerje: 1 … 4000, preobremenitev 20 % trajno,50 A za 1 s Preklopne stopnje:delovni kontakt N/O, skupna osnova, maksimalno varovanjegL 6Apreklopna moè posameznih kontaktov 250 V AC 15 AJavljalni kontakt:preklopni kontakt, brez potenciala, normalno pritegnjen maksimalno varovanje gL 6A, preklopna moè 250 V AC 13 A,3O V DC 13 AKrmiljenje ventilatorja:delovni kontakt N/O, brez potenciala, maksimalno varovanjegL 6A, preklopna moè kontakta 250 V AC 15 AInterface: TTL, na zadnji straniTemperatura okolice:delovanje 0° C … + 70° C, skladišèenje -20 … +85° CRelativna vlaga zraka: 0 % … 95 %, orositev ni dopustna Prenapetostna kategorija:II, stopnja onesnaženja 3 (DIN VDE 0110, Teil1/IEC 60664-1) Veljavni standardi:DIN VDE 0110, Teil 1 (IEC 60664-1:1992), VDE 0411, Teil 1(DIN EN 61010-1/IEC 61010-1:2001), VDE 0843, Teil 20 (DINEN 61326/IEC 61326: 1997 +A1:1998 +A2:2000), konformnostin navajanje po CE, UL, cULPrikljuèek: vzmetne sponke, maks. 2,5 kv. mm Ohišje: instrumentno ohišje Stopnja zašèite:èelna stran IP50 (opcija lP54 in zaklepanje), zadnja stranIP20 Teža: okrog 800 g Dimenzije:144 x 144 x 58 mm V x Š x GIzrez: 138 + 0,5 x 138 + 0,5 mm

Power factor controllers CX, CMCharacteristics:- 4-quadrant measurement and constant supervision of in-

ductive/capacitive load- Measurement and supervision of each step during swit-

chingprocess- Adjustment of current transformer ratio for control purpo-

ses is not required. (BLR-CM und BLR-CX..M requires pro-gramming of the transformer ratio for indication of measu-red values)

- Adjustment of target cos ϕ in the range 0.70 (lag)-1-0.90 (lead)

- Adjustable switching time - Manual switching selectable- No-volt release after voltage drop longer than 35 ms- 90 s no-volt lockout time- Optical indication of steps - Alarm when target cos ϕ is not achieved

(after process of 75 switching cycles) Supply voltage90 … 132 V / 198 … 253 V, 45 … 65 Hz, 6 VA, max. fusinggL 6 AMeasuring voltage50 … 530 V, 45 … 65 Hz, transformer ratio 1 … 350Measuring current0 … 5 A, operating threshold 10 mA, burden 15 mW, ct-ratio 1 … 4000, overload 20 % constantly, 50 A for 1 sec StepsNO-contact, common root, max. fusing gL 6A,switching current of single contact 250 V AC 15 AAlarm-contactChangeover contact, volt-free, normal active, max. fusing gL6A, max. switching current 250 V AC 13 A, 3O V DC 13 AFan control:NO-contact, volt-free, max fusing gL 6A, max switching current 250 V AC 15 AInterface: TTL, backsideAmbient temperatureOperating 0°C … + 70°C, storing -20 … +85°CHumidity: 0 % … 95 %, no dewOvervoltage classII, pollution degree 3 (DIN VDE 0110, part1/IEC 60664-1) StandardsDIN VDE 0110, part 1 (IEC 60664-1:1992), VDE 0411, part1(DIN EN 61010-1/IEC 61010-1:2001), VDE 0843, part 20 (DINEN 61326/IEC 61326: 1997 +A1:1998 +A2:2000), conformityand listing: CE, UL, cULTerminals: cage clamps, max. 2.5 sqmm Casing: instrument casingProtection degree:front IP50 (optional lP54 and lockable), rearIP20 Weight: approx. 800 g Dimensions:144 x 144 x 58 mm H x B x TCut-out 138 + 0.5 x 138 + 0.5 mm

R E G U L AT O R J I R E A K T I V N E M O È IP O W E R FA C T O R C O N T R O L L E R S

Page 33: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

33

Regulator jalove moèi CX, CM Power factor controllers CX, CM

Regulator jalove moèi CX

standarden

Reactive power controller

CX standard

Regulator jalove moèi CX

-M z osnovnimi merilnimi

funkcijami

Reactive power controller CX

-M with basic measuring func-

tions

Regulator rjalove moèi z

vgrajenim analizatorjem

mreže

Reactive power controller

CM with integrated network

analyzer

Tip regulatorja CX CM

Preklopni izhodi 06 / 80 / 12 06 / 08 / 12 / 16Program za kombifilterske naprave o xRoèno preklapljanje x xRegulacija izklopljena / z izklopom stopenj x / x x / xAvt. prilagoditev na tok tr. / k-faktor / C/k-vred. x / x / - x / x / -Avt. prilagoditev kondenzatorjev / C/k-vrednost x / x x / xNastavitev toèke obrata (ciljni cos ϕ) i0,7 -1- c0,9 i0,7 -1- c0,9Nastavitev prekl. èasa (zakasnitev preklopa) 5 - 1200 s 3 - 9999 sIzklop pri izpadu mrežne napetosti (>35ms) x xIzklop pri prekinitvi toka (I=0) x xAlarm regulacije (cos ϕ ) optièen / zunanji x / x x / xAlarm harmonikov (du/dt) optièen / zunanji - / - x / xNadzor moèi kondenzatorjev x xResetiranje alarma avtomatsko / roèno x / x x / xSerijski interface TTL / RS232 x / - x / -Prikaz proporcionalne moèi konden. / kvar x / M - / xPrikaz števila preklopov x xPrikaz stopenj v okvari x xPrikaz napetosti, toka (U, I, I-termièni) - xPrikaz napetosti, toka (U, I) M -Prikaz moèi (P, Q, S) M xPrikaz harmonikov - xPrikaz smeri bremena - xKrmiljenje ventilatorja LT xNadzor temperature LT x2. toèka obrata s preklopom Import/Export - xAsimetrièen preklopni èas x xSpremenljiv zaporni èas obrata bremena x xAvtomatièen reset alarma - xPrikaz smeri pretoka bremena - xDaljinski prenos cos ϕ analog.(0-20mA)/digital. - c / -SUB-D-vtiènica na zadnji strani za interface - pSerijski interface RS485 - BSerijski interface RS485 z Modbus - MBSpomin podatkov notranji / zunanji - / DS-2 DSoftware WinBSTO -

x = je na razpolago- = ni na razpolagoo = po naroèiluÈrka = opcija

Controller type

Switching outputsProgram for combi-filter systemsManual switchingControl off / with step switchoffCurrent conv. adj. autom. / k-factor / C/k-valueCapacitor adjustment automatic / C/k-valueSetting reversal point (desired value-cos ϕ)Setting switching time (switching delay)Switchoff for power interruption (>35ms)Switchoff for current interruption (I=0)Control alarm (cos ϕ) optical / externalHarmonics alarm (du / dt) optical / externalPower monitoring capacitorsAlarm reset automatic / manualSerial interface TTL / RS232Indication of capacitor var. proportional / kvarIndication of switching operationsIndication of defective stepsIndication of voltage, current (U, I, I-thermal)Indication of voltage, current (U, I)Indication of capacities (P, Q, S)Indication of harmonicsIndication of load flow directionFan controlTemperature monitoring2nd revers. point with imp. / exp. switchoverAsymmetrical switching timeLoad reversal locking time variableAutomatic alarm resetIndication of load flow directioncos ϕ-remote transm. analog (0-20mA) /digitalSub D plug on back for ser. interfaceSerial interface RS485Serial interface RS485 with ModbusData memory integrated / externalSoftware

x = Included- = Not includedo = Can be orderedLetter = option

R E G U L AT O R J I R E A K T I V N E M O È IP O W E R FA C T O R C O N T R O L L E R S

Slika 20: Prikljuèna shema BLR-CX / BLR-CMFig. 20: Schematic connection diagram BLR-CX / BLR-CM

Slika 21: Merska skicaFig. 21: Dimensional drawing

Page 34: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

34

Regulator jalove moèi Pro-Con

Lastnosti:- Meritev in nadzor jalove moèi v 4 kvadrantnem delovanju- Doloèanje jalove moèi s pomoèjo DFT, tako da je regulator pri-

meren za uporabo v mrežah, obremenjenih s harmoniki - Meritev, prikaz in nadzor: napetost in tok mreže, aktivna in re-

aktivna moè, harmoniki U in I, frekvenca mreže, notranja tem-peratura

- Shranjevanje maksimalnih vednosti- Nastavitev ciljnega cos ϕ v obmoèju 0,80 ind. - 1 – 0,80 kap. - Zunanji preklop tarife preko vhoda - Programabilen èas praznjenja in zakasnitve izklopa− Nastavljivo roèno delovanje - Programabilne do tri fiksne stopnje- Izklop delovanja pri prekinitvi napetosti pri izpadu meže > 15

ms - Optièen prikaz stopenj - Javljanje motnje pri nedoseganju ciljnega cos ϕ

Merilna in pomožna napetost: 230 V ali 400 V, 45 .. 65 HzMerilni tok:0 .. 5 A, prag obèutljivosti 10 mA, poraba moèi 0,2 VA, pres-tavno razmerje 1 … 9999, preobremenitev 180 A za 2 sek. Preklopne stopnje:6 ali 12 delovnih kontaktov N/O, skupna osnova,Preklopna moè posameznega kontakta: 250 V AC, 1000 WKontakt javljanja motnje.1 delovni kontakt N/O, brez potenciala, preklopna moè kon-takta 250 V AC, 1000 WVmesnik:RS485 opcija, na zadnji strani, protokol za Profibus undModbusTemperatura okolice:delovanje -10°C .. + 55°C, skladišèenje -20 ..+60°CRealtivna zraèna vlaga: 0 % .. 95 %, orositev ni dopustna Prenapetostna kategorija:III, stopnja onesnaženja 2 (DIN VDE 0110, Teil1/IEC 60664-1) Prikljuèek: vzmetne sponke, maks. 2,5 kv. mm Dimenzije / teža144 x 144 x 58 mm V x Š x G, ca. 1000 g

Power factor controller Pro-Con

Characteristics:- 4-quadrant measurement and constant supervision of in-

ductive / capacitive load- Measurement of reactive power by DFT, applicable in net-

works with high harmonic distortion- Measurement, display and supervision of line voltage and

current, active and reactive power, harmonics of U and I,line frequency, inside temperature

- Storage of maximum values- Adjustment of target cos ϕ in range 0.80 (lag) - 1 - 0.80

(lead) - External tariff change via port- Discharge time and switch-off delay programmable- Manual switching selectable- Up to three fixed steps programmable- No-volt release after network interruption longer than 15

ms. - Optical indication of steps - Alarm when target cos ϕ is not achieved

Supply and measuring voltage: 230 V or 400 V, 45 … 65 HzMeasuring current: 0 … 5 A, operating threshold 10 mA,power consumption 0.2 VAct-ratio: 1 … 4000, overload 180 A for 2 secSteps: 6 or 12 NO-contacts, common root, switching current single contact 250 V AC, 1000 WAlarm-contact: 1 NO-contact, volt-free, normal activeswitching current contact 250 V AC, 1000 WInterfaceRS485 optional, backside, Profibus and Modbus protocolAmbient temperatureOperating 10° C … + 55° C, storing -20° C … +60° CAmbient humidity0 % … 95 %, moisture condensation not allowedOver voltage classIII, pollution degree 2 (DIN VDE 0110, part1/IEC 60664-1) Terminals: Cage clamps, max. 2.5 qmm Dimensions / weight: 144 x 144 x 58 mm H x B x T, approx.1000 g

R E G U L AT O R J I R E A K T I V N E M O È IP O W E R FA C T O R C O N T R O L L E R S

Slika 22: Shematska prikljuèna shema Pro-Con

Fig. 22: Schematic connection diagram Pro-Con

Page 35: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

35

Pribor za modularne kompenzacijske na-prave

V nadaljevanju opisani sestavni deli pribora so predvideni zato, da z njimi kompenzacijske naprave prilagodimo za poseb-ne pogoje uporabe.Med seboj prilagojene sestavne dele -sestavljene iz modulov,regulatorjev jalove moèi, montažnega pribora itd. - je mogoèeuporabiti za integracijo kompenzacijskih naprav v splošnesisteme stikalnih naprav. - prikljuèni kabel za 6 stopenjski regulator jalove moèi. Dolžina 1 m; 2,5 m ali 3,5

m

- prikljuèni kabel za 12 stopenjski regulator jalove moèi. Dolžina 1 m; 2,5 m ali 3,5

m

- krmilna prikljuèna letev za 6, 8 ali 12 stopenjski regulator jalove moèi, kompletna

s krmilnimi varovalkami in sponkami za tokovni transformator.

- prilagoditveni transformator 525 V / 230 V ali 690 V / 230 V- 500 VA ali

1000 VA

- krmilni transformator 525 V / 400 V ali 690 V / 400 V za regulator jalove moèi

- adapterski sklop za montažo modula v stikalno omaro (na razpolago za stan-

dardne sisteme omar)

- stropni ventilator, IP20, 230V AC, 900 m3/h

- etažni ventilator, 230V AC, 900 m3/h, predviden za module z rasterjem 400

mm, širino omare 800 mm, za montažo z adapterskim sklopom za module,

prikljuèek preko prikljuène letvice na sprednji strani.

Sistem natiènih krmilnih vodnikov Za hitro montažo sestavnih delov v stikalno omaro nudimokompletne sklope s sistemom natiènih vodnikov. Zato v naj-veèji meri ni potrebno individualno ožièenje. Sklopi vsebujejo:- regulator jalove moèi s prikljuènim vodnikom - kompletne krmilne prikljuène letvice za krmiljenje prve gru-

pe - natiène krmilne vodnike med moduli - module z natiènimi krmilnimi prikljuènimi letvicami - ventilatorje ali drug pribor

Plug-in control line systemFor quick mounting of the components in the switching cabi-net, we offer complete mounting kits with plug-in control linesystem. This eliminates the need for most of the individualwiring. The sets consist of:- Power factor controller with connection line - Complete control terminal strips with control line to first

module - Plug-in control lines between the modules - Modules with plug-in control terminal strips - Fans or other accessories

P R I B O RA C C E S S O R I E S

Accessories for modular PFC-equipment

The accessory components described below are designed toadjust compensation systems to special application condi-tions. The coordinated module components – consisting of built-inmodules, power factor controllers, mounting accessories, etc.– can be used to integrate compensation systems in generalswitching systems.- Connection cable for power factor controller, 6-step.

Length: 1 m; 2.5 m or 3.5 m

- Connection cable for power factor controller, 12-step.

Length: 1 m; 2.5 m or 3.5 m

- Control terminal strip for power factor controller, 6, 8 or 12-step, complete

with control fuses and current converter terminals

- Adjustment transformer 525 V / 230 V or 690 V / 230 V- 500 VA or 1000 VA

- Control transformer 525 V / 400 V or 690 V / 400 V for power factor control-

ler

- Adapter set for mounting a module in the switching cabinet (available for

widely-used cabinet systems)

- Roof fan, IP20, 230 V AC, 900 m3/h

- Tier fan, 230 V AC, 900 m3/h, designed for modules with 400 mm grid, ca-

binet width: 800 mm, for mounting with the adapter set for modules, con-

nection via terminal strip on front

Page 36: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

36

Moduli za vgradnjo

Podatki za projektiranjeNadmorska višina:do 2000 m nad morjem pri nazivnem obratovanjuNazivna napetost in frekvenca:400 V, 50 Hz690 V, 50 Hzdruge nazivne napetosti oziroma 60 Hz na zahtevoMaksimalno dopustna delovna napetost:1,0 x UN trajno1,1 x UN do 8 ur na danNazivni tok:glej tabele v nadaljevanjuMaksimalno dopustne harmonske napetosti:po EN 61000-2-4, razred 2 za kondenzatorje z dušilkamiKrmilna napetost in frekvenca:230 V, 50 Hz (60 Hz); pri drugaèni delovni napetosti in frek-venci je potreben krmilni transformator (npr. 525 / 230 V ali690 / 230 V)Nazivna moè:glej tabele v nadaljevanjuPraznjenje:standardno: z dušilkami t 8 sopcionalno: z upori t 3 minStopnja zašèite:IP 00Izgubna moè:kondenzatorji 0,4 W / kvar(merjeno na sponkah kondenzatorjev),moduli za vgradnjo brez dušilk 2,0 W / kvar

s Thyro-C 5,0 W / kvarmoduli za vgradnjo z dušilkami 5,0 W / kvar

s Thyro-C 8,0 W / kvarMejne temperature:v notranjosti omar:+ 45° C povpreèno v 24 urah+ 35° C letno povpreèje+ 55° C maksimalna vrednost, kratkotrajno– 10° C minimalna vrednostHlajenje:naravno hlajenjepo potrebi je zahtevano klimatiziranje stikalne omareNadzor temperatureStandard: ne obstajaOpcija: stikalo s termostatom ali termistorji znotraj filterskihdušilkPrikljuèni preseki in varovanje:glej tabele v nadaljevanjuNivo hrupa: 60 dB pri zaprti napravi pri nazivnem obrato-vanju na razdalji 1m

Assemblies

Configuration dataAltitudeUp to 2000 m above sea levelRated voltage and Frequency400 V, 50 Hz690 V, 50 HzOther rated voltages resp. 60 Hz on requestMax. permissible operating voltage1.0 x UN permanent1.1 x UN for 8 h dailyRated currentSee selection tablesMax. permissible harmonic voltage distortionAccording to EN 61000-2-4, class 2 for reactor-protectedequipmentControl voltage and frequency230 V, 50 Hz (60 Hz); a control transformer is required forother operating voltages and frequencies (for example 525 /230 V or 690 / 230 V)Rated power:See selection tablesDischarge:Standard: with chokes 8 sOption: with discharge resistors t 3 minProtection: IP 00Power dissipationCapacitors 0.4 W / kvar (measured at the capacitor termi-nals)Assemblies without reactor-protection 2.0 W / kvar

With Thyro-C 5.0 W / kvarAssemblies reactor-protected less or equal 5.0 W / kvar

With Thyro-C 8.0 W / kvarTemperature limitsPanels inside:+ 45° C average in 24 hours+ 35° C annual average+ 55° C max. short time– 10° C low limitCooling: Self coolingClimatization may become essentialTemperature-controlStandard: WithoutOptional: Thermo-switches or thermistors placed insideof filter-reactorsWire cross sections and fuses:See selection tablesNoise emission: 60 dB in enclosed equipment at ratedservice in 1 m distance

M O D U L I Z A V G R A D N J OA S S E M B L I E S

Page 37: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

37

Moduli za vgradnjo Assemblies reactor-protected,z dušilkami, raster 300 mm grid 300 mmUporaba: vgradnja v stik. naprave oz. Application: Installation into switchboards or omare, stopnja zašè. IP00 z zbiralkami cubicle, prot. deg. IP00 with bus-barsin NN varovalkami and low H.R.C. voltage fuses

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

Moè(kvar) Koda za naroèanje, polje 600 mm Slika Koda za naroèanje,polje 800mm Slika

Power (kvar) Order code, panel width 600 mm Fig. Order code, panel width 800 mm Fig.

5 MKK-00-400 / 5 / 604 23 MKK-00-400 / 5 / 804 292 x 5 MKK-00-400 / 2x5 / 604 23 MKK-00-400 / 2x5 / 804 2912,5 MKK-00-400 / 12,5 / 604 23 MKK-00-400 / 12,5 / 804 292 x 12,5 MKK-00-400 / 2x12,5 / 604 23 MKK-00-400 / 2x12,5 / 804 2925 MKK-00-400 / 25 / 604 23 MKK-00-400 / 25 / 804 292 x 25 MKK-00-400 / 2x25 / 604 23 MKK-00-400 / 2x25 / 804 2950 MKK-00-400 / 50 / 604 23 MKK-00-400 / 50 / 804 2975 MKK-00-400 / 75 / 604 23 MKK-00-400 / 75 / 804 2925 + 50 MKK-00-400 / 25+50 / 604 23 MKK-00-400 / 25+50 / 804 29

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

12,5 MKK-00-690 / 12,5 / 604 23 MKK-00-690 / 12,5 / 804 292 x 12,5 MKK-00-690 / 2x12,5 / 604 23 MKK-00-690 / 2x12,5 / 804 2925 MKK-00-690 / 25 / 604 23 MKK-00-690 / 25 / 804 292 x 25 MKK-00-690 / 2x25 / 604 23 MKK-00-690 / 2x25 / 804 2950 MKK-00-690 / 50 / 604 23 MKK-00-690 / 50 / 804 2975 MKK-00-690 / 75 / 604 23 MKK-00-690 / 75 / 804 2925 + 50 MKK-00-690 / 25+50 / 604 23 MKK-00-690 / 25+50 / 804 29

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

12,5 MKK-00-400 / 12,5 / 604-400 36 MKK-00-400 / 12,5 / 804-400 352 x 12,5 MKK-00-400 / 2x12,5 / 604-400 36 MKK-00-400 /2x12,5 /804-400 3525 MKK-00-400 / 25 / 604-400 36 MKK-00-400 / 25 / 804-400 3512,5 + 25 MKK-00-400/12,5+25/604-400 36 MKK-00-400/12,5+25/804-400 352 x 25 MKK-00-400 / 2x25 / 604-400 36 MKK-00-400 / 2x25 / 804-400 3550 MKK-00-400 / 50 / 604-400 36 MKK-00-400 / 50 / 804-400 3525 + 50 – 36 MKK-00-400 /25+50 /804-400 352 x 50 – 36 MKK-00-400 / 2x50 / 804-400 35

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

12,5 MKK-00-690 / 12,5 / 604-400 36 MKK-00-690 / 12,5 / 804-400 352 x 12,5 MKK-00-690 / 2x12,5 / 604-400 36 MKK-00-690 /2x12,5 /804-400 3525 MKK-00-690 / 25 / 604-400 36 MKK-00-690 / 25 / 804-400 3512,5 + 25 MKK-00-690/12,5+25/604-400 36 MKK-00-690/12,5+25/804-400 352 x 25 MKK-00-690 / 2x25 / 604-400 36 MKK-00-690 / 2x25 / 804-400 3550 MKK-00-690 / 50 / 604-400 36 MKK-00-690 / 50 / 804-400 3525 + 50 – 36 MKK-00-690/25 + 50/804-400 352 x 50 – 36 MKK-00-690 /2 x 50 /804-400 35

Moduli za vgradnjo, z Assemblies reactor-protected,dušilkami, raster 400 mm grid 400 mm

Druge nazivne napetosti in 60 Hzna zahtevo. Na željo dobavimo mo-ènostno loèilno stikalo z varovalka-mi.Other rated voltages and 60 Hz onrequest. H.R.C. fuse load breakeravailable on request.

M O D U L I Z A V G R A D N J OA S S E M B L I E S

Page 38: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

38

Moduli za vgradnjo, 400 V, Assemblies, 400 V reactor-z dušilkami, raster 300 mm protected, grid 300 mmUporaba: Vgradnja v stikalne naprave oziroma Application: Installation into switchboards or

stikalne omare, stopnja zašèite IP00 z deli zbiralk cubicle, protection degree IP00 with bus bars

in NN varovalkami and low H.R.C. voltage fuses

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

Moè Koda za naroèanje, polja 600 mm Slika Koda za naroèanje, polja 800 mm Slika

Power (kvar) Order code, panel width 600 mm Fig. Order code, panel width 800 mm Fig.

z dušilko, uglašeno na 189 Hz (p = 7 %) / With reactor, detuned to 189 Hz (p = 7 %)

6,25 MKK-DR7-400 / 6,25 / 604 25 MKK-DR7-400 / 6,25 / 804 312 x 6,25 MKK-DR7-400 / 2x6,25 / 604 26 MKK-DR7-400 / 2x6,25 / 804 3212,5 MKK-DR7-400 / 12,5 / 604 25 MKK-DR7-400 / 12,5 / 804 312 x 12,5 MKK-DR7-400 / 2x12,5 / 604 26 MKK-DR7-400 / 2x12,5 / 804 3225 MKK-DR7-400 / 25 / 604 25 MKK-DR7-400 / 25 / 804 3112,5 + 25 MKK-DR7-400 / 12,5+25 / 604 26 MKK-DR7-400 / 12,5+25 / 804 322 x 25 – MKK-DR7-400 / 2x25 / 804 3250 MKK-DR7-400 / 50 / 604 25 MKK-DR7-400 / 50 / 804 3175 – MKK-DR7-400 / 75 / 804 31

z dušilko, uglašeno na 210 Hz (p = 5,67 %) / With reactor, detuned to 210 Hz (p = 5,67 %)

6,25 MKK-DR5,67-400 /6,25 /604 25 MKK-DR5,67-400 /6,25 /804 312 x 6,25 MKK-DR5,67-400 /2x6,25 /604 26 MKK-DR5,67-400 /2x6,25 /804 3212,5 MKK-DR5,67-400 /12,5 /604 25 MKK-DR5,67-400 /12,5 /804 312 x 12,5 MKK-DR5,67-400 /2x12,5 /604 26 MKK-DR5,67-400 /2x12,5 /804 3225 MKK-DR5,67-400 /25 /604 25 MKK-DR5,67-400 /25 /804 3112,5 + 25 MKK-DR5,67-400/12,5+25/604 26 MKK-DR5,67-400/12,5+25/804 322 x 25 – MKK-DR5,67-400 /2x25 /804 3250 MKK-DR5,67-400 /50 /604 25 MKK-DR5,67-400 /50 /804 3275 – MKK-DR5,67-400 /75 /804 31

z dušilko, uglašeno na 141 Hz (p = 12,5 %) / With reactor, detuned to 141 Hz (p = 12,5 %)

6,25 MKK-DR12,5-400 /6,25 /604 25 MKK-DR12,5-400 /6,25 /804 312 x 6,25 MKK-DR12,5-400 /2x6,25 /604 26 MKK-DR12,5-400 /2x6,25 /804 3212,5 MKK-DR12,5-400 /12,5 /604 25 MKK-DR12,5-400 /12,5 /804 312 x 12,5 MKK-DR12,5-400 /2x12,5 /604 26 MKK-DR12,5-400 /2x12,5 /804 3225 MKK-DR12,5-400 /25 /604 25 MKK-DR12,5-400 /25 /804 3112,5 + 25 – MKK-DR12,5-400/12,5+25/804 322 x 25 – MKK-DR12,5-400 /2x25 /804 3250 MKK-DR12,5-400 /50 /604 25 MKK-DR12,5-400 /50 /804 3175 – MKK-DR12,5-400 /75 /804 31

z dušilko, uglašeno na 133 Hz (p = 14 %) / With reactor, detuned to 133 Hz (p = 14 %)

6,25 MKK-DR14-400 /6,25 /604 25 MKK-DR14-400 /6,25 /804 312 x 6,25 MKK-DR14-400 /2x6,25 /604 26 MKK-DR14-400 /2x6,25 /804 3212,5 MKK-DR14-400 /12,5 /604 25 MKK-DR14-400 /12,5 /804 312 x 12,5 MKK-DR14-400 /2x12,5 /604 26 MKK-DR14-400 /2x12,5 /804 3225 MKK-DR14-400 /25 /604 25 MKK-DR14-400 /25 /804 3112,5 + 25 – MKK-DR14-400 /12,5+25 /804 322 x 25 – MKK-DR14-400 /2x25 /804 3250 MKK-DR14-400 /50 /604 25 MKK-DR14-400 /50 /804 3166,7 – MKK-DR14-400 /66,7 /804 31

Druge nazivne napetosti in 60 Hz na zahtevo. Na željo dobavimo moènostno loèilnostikalo z varovalkami.Other rated voltages and 60 Hz on request. H.R.C. fuse load breaker available on re-quest.

M O D U L I Z A V G R A D N J OA S S E M B L I E S

Page 39: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

39

Moduli za vgradnjo, 690 V, Assemblies, 690 V, reactor-z dušilkami, raster 300 mm protected, grid 300 mmUporaba: Vgradnja v stikalne naprave oziroma Application: Installation into switchboards or

stikalne omare, stopnja zašèite IP00 z deli cubicle, protection degree IP00 with bus bars

zbiralk in NN varovalkami and H.R.C. low voltage fuses

Nazivna napetost 690 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 690 V / 50 Hz, control voltage 230 V / 50 Hz

Moè Koda za naroèilo, polja 600 mm Slika Koda za naroèilo, polja 800 mm Slika

Power (kvar) Order code, panel width 600 mm Fig. Order code, panel width 800 mm Fig.

z dušilkami, uglašenimi na 189 Hz (p = 7 %) / With reactor, detuned to 189 Hz (p = 7 %)

12,5 MKK-DR7-690 / 12,5 / 604 25 MKK-DR7-690 / 12,5 / 804 312 x 12,5 MKK-DR7-690 / 2x12,5 / 604 26 MKK-DR7-690 / 2x12,5 / 804 3225 MKK-DR7-690 / 25 / 604 25 MKK-DR7-690 / 25 / 804 312 x 25 – MKK-DR7-690 / 2x25 / 804 3237,5 – MKK-DR7-690 / 37,5 / 804 3150 – MKK-DR7-690 / 50 / 804 32

z dušilkami, uglašenimi na 210 Hz (p = 5,67%) / With reactor, detuned to 210 Hz (p = 5,67%)

12,5 MKK-DR5,67-690 / 12,5 / 604 25 MKK-DR5,67-690 / 12,5 / 804 312 x 12,5 MKK-DR5,67-690/2x12,5 /604 26 MKK-DR5,67-690/2x12,5/804 3225 MKK-DR5,67-690 / 25 / 604 25 MKK-DR5,67-690 / 25 / 804 312 x 25 – MKK-DR5,67-690 / 2x25 / 804 3237,5 – MKK-DR5,67-690 / 37,5 / 804 3150 – MKK-DR5,67-690 / 50 / 804 31

z dušilkami, uglašenimi na 141 Hz (p = 12,5 %) / With reactor, detuned to 141 Hz (p = 12, 5%)

12,5 MKK-DR12,5-690 / 12,5 / 604 25 MKK-DR12,5-690 / 12,5 / 804 312 x 12,5 MKK-DR12,5-690 /2x12,5 /604 26 MKK-DR12,5-690 /2x12,5 /804 3225 MKK-DR12,5-690 / 25 / 604 25 MKK-DR12,5-690 / 25 / 804 312 x 25 – MKK-DR12,5-690 / 2x25 / 804 3237,5 – MKK-DR12,5-690 / 37,5 / 804 3150 – MKK-DR12,5-690 / 50 / 804 31

z dušilkami, uglašenimi na 133 Hz (p = 14 %) / With reactor, detuned to 133 Hz (p = 14 %)

12,5 MKK-DR14-690 / 12,5 / 604 25 MKK-DR14-690 / 12,5 / 804 312 x 12,5 MKK-DR14-690 / 2x12,5 / 604 26 MKK-DR14-690 / 2x12,5 / 804 3225 MKK-DR14-690 / 25 / 604 25 MKK-DR14-690 / 25 / 804 312 x 25 – MKK-DR14-690 / 2x25 / 804 3237,5 – MKK-DR14-690 / 37,5 / 804 3150 – MKK-DR14-690 / 50 / 804 31

Na zahtevo dobavimo NN moènostno loèilno stikalo z varovalkami.H.R.C. fuse load breaker available on request.

M O D U L I Z A V G R A D N J OA S S E M B L I E S

Page 40: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

40

Moduli za vgradnjo, 400 V, Assemblies, 400 V, reactor-z dušilkami, raster 400 mm protected, grid 400 mmUporaba: Vgradnja v stikalne naprave oziroma Application: Installation into switchboards or

stikalne omare, stopnja zašèite IP00 z deli cubicle, protection degree IP00 with bus bars

zbiralk in NN varovalkami and H.R.C. low voltage fuses

Nazivna napetost 400 V / 50 Hz, krmilna napetost 230 V / 50 HzRated voltage 400 V / 50 Hz, control voltage 230 V / 50 Hz

Moè Koda za naroèanje, polja 600 mm Slika Koda za naroèanje, polja 800 mm Slika

Power (kvar) Order code, panel width 600 mm Fig. Order code, panel width 800 mm Fig.

z dušilko, uglašeno na 189 Hz (p = 7 %) / With reactor, detuned to 189 Hz (p = 7 %)

12,5 MKK-DR7-400 / 12,5 / 604-400 38 MKK-DR7-400 / 12,5 / 804-400 376,25 + 12,5 MKK-DR7-400/6,25 + 12,5/604-400 38 MKK-DR7-400/6,25 +12,5/804-400 372 x 12,5 MKK-DR7-400 / 2x12,5 / 604-400 38 MKK-DR7-400 / 2x12,5 / 804-400 3725 MKK-DR7-400 / 25 / 604-400 38 MKK-DR7-400 / 25 / 804-400 3712,5 + 25 MKK-DR7-400 /12,5+25 /604-400 38 MKK-DR7-400/12,5+25/804-400 372 x 25 MKK-DR7-400 / 2x25 / 604-400 38 MKK-DR7-400 / 2x25 / 804-400 3750 MKK-DR7-400 / 50 / 604-400 38 MKK-DR7-400 / 50 / 804-400 3725 + 50 – MKK-DR7-400 / 75 / 804-400 372 x 50 – MKK-DR7-400 / 2 x 50 / 804-400 37

z dušilko, uglašeno na 210 Hz (p = 5,67 %) / With reactor, detuned to 210 Hz (p = 5,67 %)

12,5 MKK-DR5,67-400/12,5 /604-400 38 MKK-DR5,67-400/12,5 /804-400 376,25 + 12,5 MKK-DR5,67-400/6,25+12,5/604-400 38 MKK-DR5,67-400/16,25+12,5 /804-400 372 x 12,5 MKK-DR5,67-400/2x12,5 /604-400 38 MKK-DR5,67-400/2x12,5 /804-400 3725 MKK-DR5,67-400/25/604-400 38 MKK-DR5,67-400/25/804-400 3712,5 + 25 MKK-DR5,67-400/12,5+25/604-400 38 MKK-DR5,67-400/12,5+25/804-400 372 x 25 MKK-DR5,67-400/2x25/604-400 38 MKK-DR5,67-400/2x25/804-400 3750 MKK-DR5,67-400/50/604-400 38 MKK-DR5,67-400/50/804-400 3725 + 50 – MKK-DR5,67-400/25 + 50/804-400 372 x 50 – MKK-DR5,67-400/2 x 50/804-400 37

z dušilko, uglašeno na 141 Hz (p = 12,5 %) / With reactor, detuned to 141 Hz (p = 12,5 %)

12,5 MKK-DR12,5-400/12,5 /604-400 38 MKK-DR12,5-400/12,5 /804-400 376,25 + 12,5 MKK-DR12,5-400/6,25+12,5/604-400 38 MKK-DR12,5-400/6,25+12,5/804-400 372 x 12,5 MKK-DR12,5-400/2x12,5 /604-400 38 MKK-DR12,5-400/2x12,5 /804-400 3725 MKK-DR12,5-400/25/604-400 38 MKK-DR12,5-400/25/804-400 3712,5 + 25 MKK-DR12,5-400/12,5+25/04-400 38 MKK-DR12,5-400/12,5+25/804-400 372 x 25 MKK-DR12,5-400/2x25/604-400 38 MKK-DR12,5-400/2 x 25 /804-400 3750 MKK-DR5,67-400/50/604-400 38 MKK-DR12,5-400/50/804-400 3725 + 50 – MKK-DR12,5-400/25 + 50/804-400 372 x 50 – MKK-DR12,5-400/2 x 50 /804-400 37

z dušilko, uglašeno na 133 Hz (p = 14 %) / With reactor, detuned to 133 Hz (p = 14 %)

12,5 MKK-DR14-400/12,5 /604-400 38 MKK-DR14-400/12,5 /804-400 376,25 + 12,5 MKK-DR14-400/6,25+12,5/604-400 38 MKK-DR14-400/6,25+12,5 /804-400 372 x 12,5 MKK-DR14-400/2x12,5 /604-400 38 MKK-DR14-400/2x12,5 /804-400 3725 MKK-DR14-400/25/604-400 38 MKK-DR14-400/25/804-400 3712,5 + 25 MKK-DR14-400/12,5+25/604-400 38 MKK-DR14-400/12,5+25/804-400 372 x 25 MKK-DR14-400/2x25/604-400 38 MKK-DR14-400/2x25/804-400 3750 MKK-DR14-400/50/604-400 38 MKK-DR14-400/50/804-400 3725 + 50 MKK-DR14-400/25 + 50/804-400 372 x 50 MKK-DR14-400/2 x 50 /804-400 37

Druge nazivne napetosti in 60 Hz na zahtevo. Na zahtevo dobavimo NN moènostnoloèilno stikalo z varovalkami.Other rated voltages and 60 Hz on request. H.R.C. fuse load breaker available on re-quest.

M O D U L I Z A V G R A D N J OA S S E M B L I E S

Page 41: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

41

Moduli za vgradnjo, preklopi Assemblies, thyristor-s tiristorji, raster 300 mm switched, grid 300 mmUporaba: Vgradnja v stikalne naprave oziroma Application: Installation into switchboards or

stikalne omare, stopnja zašèite IP00 z deli cubicle, protection degree IP00 with bus bars

zbiralk in NNv varovalkami ter s tiristorskim and H.R.C. low voltage fuses and thyristor-

preklopnikom Thyro-C switches Thyro-C

S tiristorskim preklapljanjem 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz ali 24 V / DC

Thyristor-switched 400 V / 50 Hz, control voltage 230 V / 50 Hz or 24 V / DC

Moè Koda za naroèanje, polja 600 mm Slika Koda za naroèanje, polja 800 mm Slika

Power (kvar) Order code, panel width 600 mm Fig. Order code, panel width 800 mm Fig.

12,5 DyC-00-400 / 12,5 / 604 24 DyC-00-400 / 12,5 / 804 3025 DyC-00-400 / 25 / 604 24 DyC-00-400 / 25 / 804 3050 DyC-00-400 / 50 / 604 24 DyC-00-400 / 50 / 804 30

S triristorskim preklapljanjem 400 V / 50 Hz, krmilna napetost 230 V / 50 Hz ali 24 V / DC

Thyristor-switched 400 V / 50 Hz, control voltage 230 V / 50 Hz or 24 V / DC

z dušilko, uglašeno na 210 Hz (p = 7 %) / With reactor, detuned to 210 Hz (p = 7 %)

12,5 DyC-DR7-400 / 12,5 / 604 24 DyC-DR7-400 / 12,5 / 804 3025 DyC-DR7-400 / 25 / 604 24 DyC-DR7-400 / 25 / 804 3050 DyC-DR7-400 / 50 / 604 24 DyC-DR7-400 / 50 / 804 3060 24 DyC-DR7-400 / 60 / 804 30

z dušilko, uglašeno na 210 Hz (p = 5,67 %) / With reactor, detuned to 210 Hz (p = 5,67 %)

12,5 DyC-DR5,67-400 / 12,5 / 604 24 DyC-DR5,67-400 / 12,5 / 804 3025 DyC-DR5,67-400 / 25 / 604 24 DyC-DR5,67-400 / 25 / 804 3050 DyC-DR5,67-400 / 50 / 604 24 DyC-DR5,67-400 / 50 / 804 30

z dušilko, uglašeno na 141 Hz (p = 12,5 %) / With reactor, detuned to 141 Hz (p = 12,5 %)

12,5 DyC-DR12,5-400 / 12,5 / 604 24 DyC-DR12,5-400 / 12,5 / 804 3025 DyC-DR12,5-400 / 25 / 604 24 DyC-DR12,5-400 / 25 / 804 3050 DyC-DR12,5-400 / 50 / 604 24 DyC-DR12,5-400 / 50 / 804 3060 – DyC-DR12,5-400 / 60 / 804 30

z dušilko, uglašeno na 133 Hz (p = 14 %) / With reactor, detuned to 133 Hz (p = 14 %)

12,5 DyC-DR14-400 / 12,5 / 604 24 DyC-DR14-400 / 12,5 / 804 3025 DyC-DR14-400 / 25 / 604 24 DyC-DR14-400 / 25 / 804 3050 DyC-DR14-400 / 50 / 604 24 DyC-DR14-400 / 50 / 804 3060 – DyC-DR14-400 / 60 / 804 30

Pribor:

Regulator jalove moèi DynamiC 6- ali 12-stopenjski, z elekronskimi stikalnimi izhodi za 24 V DC, glej tudi

stran 21.

Krmilna prikljuèna letvica za jalove moèi DynamiC 6- ali 12-stopenjski, kompletna za prikljuèevanje s krmilni-

mi varovalkami, sponkami za tokovni transformator in napajanje 24 V DC.

Druge nazivne napetosti in 60 Hz na zahtevo. Na željo dobavimo moènostno loèilno stikalo z varovalkami.

Pri opremljenosti s tiristorskimi moènostnimi preklopniki Thyro-C: glej poseben katalog.

Druga oprema na zahtevo.

Accessories:

Power factor controller DynamiC, 6 or 12-step, with electronic switching outputs for

24 V DC, see also page 21.

Control terminal strip for DynamiC power factor controller, 6 or 12-step, complete and ready to be connected

with control fuses, current transformer terminals and 24 V DC supply.

Other rated voltages and 60 Hz on request. H.R.C. fuse load breaker available on request.

Configured with thyristor power modules Thyro-C: See separate brochure.

Other accessories on request.

M O D U L I Z A V G R A D N J OA S S E M B L I E S

Page 42: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

42

Dimenzijske skice za module za vgradnjo

za širino omar 600 mm, raster 300 mm

Dimension drawings of assemblies

for 600 mm cubicle width, grid 300 mm

Slika 23: brez dušilk, s kontaktorjemFig. 23: without reactor-protection, with contactor

Slika 24: s tiristorskim preklopnikom Thyro-CFig. 24: with thyristor-module Thyro-C

Slika 25: enostopenjski, z dušilkami, s kontaktorjemFig. 25: single-step, reactor-protected, contactor

Slika 26: dvostopenjski, z dušilkami, s kontaktorjiFig. 26: double-step, reactor-protected, contactors

Slika 27: Omara s šestmoduli, IP40Fig. 27: cubicle with sixassemblies , IP40

Slika 28: Omara s šestmoduli, IP20Fig. 28: cubicle with sixassemblies, IP20

D I M E N Z I J S K E S K I C ED I M E N S I O N D R AW I N G S

Page 43: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

43

Merske skice za module

za širino omar 800 mm, raster 300 mm

Dimension drawings of assemblies

for 800 mm cubicle width, grid 300 mm

Slika 29: brez dušilk, s kontaktorjemFig. 29: without reactor-protection, with contactor

Slika 30: s tiristorskim preklopnikom Thyro-CFig. 30: with thyristor-module Thyro-C

Slika 31: enostopenjski, z dušilkami, s kontaktorjemFig. 31: single-step, reactor-protected, contactor

Slika 32: dvostopenjska, z dušilkami, s kontaktorjiFig. 32: double-step, reactor-protected, contactors

Slika 33: Omara IP20,maksimalno šest modulov

Fig. 33: cubicle IP20,max. six assemblies

Slika 34: Omara IP20s šestimi moduli, tiris-torskimi preklopniki inventilatorjemFig. 34: cubicle IP20with six assemblies,thyristor-modulesThyro-C and fan

D I M E N Z I J S K E S K I C ED I M E N S I O N D R AW I N G S

Page 44: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

44

Merske skice modulov

raster 400 mm

Dimension drawings of assemblies

Grid 400 mm

Slika 35: za širino omare 800 mm, brez dušilkFig. 35: for cubicle width 800 mm, without reactor-protection

Slika 36: za širino omar 600 mm, brez dušilkFig. 36: for cubicle width 600 mm, without reactor-protection

Slika 37: za širino omar 800 mm, z dušilkamiFig. 37: for cubicle width 800 mm, reactor-protected

Slika 38: za širino omar 600 mm, brez dušilkFig. 38: for cubicle width 600 mm, reactor-protected

Slika39: Omara IP20,širina 800 mm,maksimalno štiri mo-duli

Fig. 39: cubicle IP20,width 800 mm,max. four assemblies

Slika 40: Omara IP20,širina 600 mm,maks. štiri moduliFig. 40: cubicle IP20,width 600 mm,max. four assemblies

D I M E N Z I J S K E S K I C ED I M E N S I O N D R AW I N G S

Page 45: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

45Èrtkane linije morajo biti pri montaži naprave prikljuèene.Broken lines have to be connected with the equipment at site.

Principielna prikljuèna shema naprav zakompenzacijo reaktivne moèi

Schematic circuit diagram for automaticpower factor correction equipment

P R I N C I P E L N A P R I K L J U È N A S H E M AS C H E M AT I C C I R C U I T D I A G R A M

jalove moèi

jalove

Page 46: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

46

Nazivna moè Nazivni tok NN varovanje Dovodni kabel

Rated Rated Low-voltage Feeding cablepower current fuse-links(kvar) A A (Cu mm2 )

44 64 3 x 100 NYY 3 x 35 / 1650 72 3 x 125 NYY 3 x 35 / 1655 79 3 x 125 NYY 3 x 50 / 2562,5 90 3 x 125 NYY 3 x 50 / 2566 95 3 x 125 NYY 3 x 50 / 2575 108 3 x 160 NYY 3 x 50 / 2580 115 3 x 250 NYY 3 x 70 / 35100 144 3 x 250 NYY 3 x 95 / 50120 173 3 x 315 NYY 3 x 120 / 70125 180 3 x 315 NYY 3 x 120 / 70150 216 3 x 400 NYY 3 x 150 / 70160 231 3 x 400 2 x NYY 3 x 95 / 50167 241 3 x 400 2 x NYY 3 x 95 / 50180 259 3 x 400 2 x NYY 3 x 95 / 50187,5 270 3 x 400 2 x NYY 3 x 95 / 50200 288 3 x 400 2 x NYY 3 x 95 / 50210 302 3 x 500 2 x NYY 3 x 120 / 70225 325 3 x 500 2 x NYY 3 x 120 / 70240 346 3 x 500 2 x NYY 3 x 120 / 70250 361 3 x 500 2 x NYY 3 x 120 / 70267 385 3 x 630 2 x NYY 3 x 150 / 70300 432 3 x 630 2 x NYY 3 x 150 / 70333 480 3 x 800 2 x NYY 3 x 150 / 70360 520 3 x 800 2 x NYY 3 x 185 / 95375 540 3 x 800 2 x NYY 3 x 240 / 120400 576 3 x 800 2 x NYY 3 x 240 / 120450 650 3 x 1000 2 x NYY 3 x 240 / 120

Prikljuèni kabli in varovalke

Prikljuèni preseki prikljuènih dovodnih kablov in varovalke

za UN = 400 V / 50 Hz

Cross sections for feeding cables and fusing for UN = 400 V / 50 Hz

Connection cables and fuse protection

Prikljuèni preseki dovodnih kablov in varovalke

za UN = 690 V / 50 Hz

Cross sections for feeding cables and fusing for UN = 690 V / 50 Hz

Velike naprave, dinamièna kompenzacija Large equipment, Dynamic compensation equipment

Nazivna moè Nazivni tok NN varovanje Dovodni kabel

Rated Rated Low-voltage Feeding cablepower current fuse-links(kvar) A A (Cu mm2 )

50 42 3 x 80 NYY 3 x 25 / 1662,5 52 3 x 80 NYY 3 x 25 / 1675 63 3 x 100 NYY 3 x 35 / 16100 84 3 x 125 NYY 3 x 50 / 16125 105 3 x 160 NYY 3 x 70 / 35150 126 3 x 200 NYY 3 x 70 / 35175 146 3 x 250 NYY 3 x 70 / 35200 167 3 x 250 NYY 3 x 95 / 50225 188 3 x 315 NYY 3 x 120 / 70250 209 3 x 315 NYY 3 x 120 / 70275 230 3 x 400 2 x NYY 3 x 95 / 50300 251 3 x 400 2 x NYY 3 x 95 / 50325 272 3 x 500 2 x NYY 3 x120 /70350 293 3 x 500 2 x NYY 3 x120 / 70375 314 3 x 500 2 x NYY 3 x120 / 70400 335 3 x 630 2 x NYY 3 x120 / 70

Tip Nazivna NN varovanje Dovodni kabelmoè

Type Rated Low-voltage Feeding cablepower fuse-links(kvar) A (Cu mm2 )

MKK-FK200-400 / 97 97 3 x 315 NYY 3 x 120 / 70MKK-FK210-400 / 144 144 3 x 500 2 x NYY 3 x 150 / 70MKK-FK300-400 / 145 145 3 x 500 2 x NYY 3 x 150 / 70MKK-FK211-400 / 191 191 3 x 630 2 x NYY 3 x 185 / 95MKK-FK310-400 / 192 192 3 x 630 2 x NYY 3 x 185 / 95MKK-FK420-400 / 289 289 2 x 3 x 500 4 x NYY 3 x 150 / 70MKK-FK421-400 / 336 336 2 x 3 x 500 4 x NYY 3 x 150 / 70MKK-FK520-400 / 337 337 2 x 3 x 500 4 x NYY 3 x 150 / 70MKK-FK422-400 / 383 383 2 x 3 x 630 4 x NYY 3 x 185 / 95MKK-FK522-400 / 431 431 3 x 3 x 500 6 x NYY 3 x 150 / 70MKK-FK630-400 / 433 433 3 x 3 x 500 6 x NYY 3 x 150 / 70MKK-FK632-400 / 527 527 3 x 3 x 630 6 x NYY 3 x 185 / 95MKK-FK840-400 / 578 578 4 x 3 x 630 6 x NYY 3 x 185 / 95MKK-FK844-400 / 766 766 4 x 3 x 630 8 x NYY 3 x 185 / 95MKK-FK964-400 / 908 908 5 x 3 x 630 10 x NYY 3 x 185 / 95

Uglašeni filterski krogi

Tip Nazivna NN varovanje Dovodni kabelmoè

Type Rated Low-voltage Feeding cablepower fuse-links(kvar) A (Cu mm2 )

MKK-FK 200-690 / 120 120 3 x250 NYY 3 x95 / 50MKK-FK 210-690 / 179 179 3 x 315 NYY 3 x 120 / 70MKK-FK 420-690 / 357 357 2 x 3 x 315 2 x NYY 3 x 120 / 70MKK-FK 421-690 / 415 415 2 x 3 x 400 2 x NYY 3 x 150 / 70MKK-FK 622-690 / 592 592 3 x 3 x 315 3 x NYY 3 x 120 / 70MKK-FK 732-690 / 711 711 3 x 3 x 400 3 x NYY 3 x 150 / 70MKK-FK 840-690 / 713 713 3 x 3 x 400 3 x NYY 3 x 150 / 70MKK-FK 844-690 / 945 945 4 x 3 x 400 4 x NYY 3 x 150 / 70MKK-FK 964-690 / 1113 1113 5 x 3 x 400 5 x NYY 3 x 150 / 70

Tuned filter circuits

R A Z N OM I S C E L L A N E O U S

Page 47: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

47

Power Quality Management = Dober nasvet

Pri nas dobite vse na enem mestu: Od svetovanja in meritevdo planiranja in izraèunov do dajanja v obratovanje komplet-nih naprav. Naša dolgoletna izkušnja jamèi za prvovrstnokvaliteto. Takorekoè dobro delo za èiste mreže.

Obmoèje naših storitev obsega:– analize mreže in meritve kakovosti mreže v javnih in indus-

trijskih distribucijskih mrežah po EN 50160 in EN 61000– planiranje kompenzacijskih naprav in naprav s filterskimi

tokokrogi – študije simulacij z našim numeriènim raèunalniškim progra-

mom za izraèun mrež Salomon© in drugih– dajanje v obratovanje– seminarje in šolanja

Poklièite nas!

Power Quality Management = In goodhandsPQM Customers get it all from a single source: from consult-ing and measuring to design and calculation, all the way tothe comissioning of the complete system. Our long-standingexperience is synonymous for top-notch quality. Decent workfor decent networks, so to speak.Our range of services comprehends:– Network analyses and measurements of voltage quality in

public and industrial distribution networks acc. to EN 50160and EN 61000

– Planning of power factor correction equipment and filter cir-cuits

– Simulation studies with our numeric network-calculation-programm Salomon©

– Commissioning– Workshops and training courses

Feel free to contact us!

Page 48: PQM – POWER QUALITY MANAGEMENT®. 07.pdf · Avtomatske nizkonapetostne kondenzatorske naprave za kompenzacijo jalove moèi Automatic Power Factor Correction Equipment for Low Voltage

Prosimo upoštevajte: Podatki, ki se nahajajo v tej publikacij, se v detajlih lahko razlikujejo od detajlov pridejansko dobavljeni napravi. Pravica do sprememb pridržana brez predhodnega obvestila.Please note: The data in our publications may differ from the data of products delivered. We reserve theright to make changes without notice.

www.elim.si

©ELIM d.o.o. Ljubljana Šlandrova 10, SI - 1000 LJUBLJANA, SLOVENIJATel.: 01 563 1462Fax: 01 563 1463E-mail: [email protected]