PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’ S.No . Name of the company Clause No. Tender Clause Company Request Reply by PEDA 1. Lanco Solar Energy Pvt Ltd. GCC clause 16.1 (iv) , SCC clause no 11 The remaining 10% of the contract price of the goods shall be paid within 30 days after the date of final acceptance certificate issued by the purchaser’s representative & CUF performance test and its compliance after one year of continuous operations after the commissioning 10 % is retained for one year despite taking performance security for 10 % value . We suggest the following alternate payment terms - 10 % advance payment against ABG - 70 % payment on supply of material on pro-rata basis - 10% on progressive installation of plant on pro-rata basis - Balance 10 % of the contract price after final commissioning & performance testing for 1 month Performance Security is to cover the warranty and O&M period also. ABG is to cover only the period between award of contract and equipment supply. No further changes 2. GCC clause 7.4 , SCC clause no 3 Performance Security BG : 10% (Ten Percent) of the contract price excluding annual maintenance cost valid upto 60 days after completion of performance obligation including warranty obligation and 10 years Operation and maintenance period We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance period should be valid up to 1 year of commissioning . For O & M period BG of value equal to 10 % of O & M contract value should be taken RFP clause will prevail 3. GCC clause 16.1 (iv) , SCC clause no 11 Payment shall be released within 30 days of claim Payment may be released though LC . We shall bear the LC charges -do- 4. Section 1 , Invitation of Bid Bid Security : INR Rs 80 Lac . ( 25 % through e –banking /e –payment and for balance 75% bank guarantee may be submitted . Scanned copy of BG of 75 % value must be uploaded at the time of online bid submission ) We suggest that 100 % of the Bid security value may be accepted against Bank Guarantee No change, e-bidding guidelines

Upload: others

Post on 26-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

S.No.

Name of the company

Clause No. Tender Clause Company Request Reply by PEDA

1. Lanco Solar Energy Pvt Ltd.

GCC clause 16.1 (iv) , SCC clause no 11

The remaining 10% of the contract price of the goods shall be paid within 30 days after the date of final acceptance certificate issued by the purchaser’s representative & CUF performance test and its compliance after one year of continuous operations after the commissioning

10 % is retained for one year despite taking performance security for 10 % value . We suggest the following alternate payment terms - 10 % advance payment against ABG - 70 % payment on supply of material on pro-rata basis - 10% on progressive installation of plant on pro-rata basis - Balance 10 % of the contract price after final commissioning & performance testing for 1 month

Performance Security is to cover the warranty and O&M period also. ABG is to cover only the period between award of contract and equipment supply. No further changes

2. GCC clause 7.4 , SCC clause no 3

Performance Security BG : 10% (Ten Percent) of the contract price excluding annual maintenance cost valid upto 60 days after completion of performance obligation including warranty obligation and 10 years Operation and maintenance period

We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance period should be valid up to 1 year of commissioning . For O & M period BG of value equal to 10 % of O & M contract value should be taken

RFP clause will prevail

3. GCC clause 16.1 (iv) , SCC clause no 11

Payment shall be released within 30 days of claim

Payment may be released though LC . We shall bear the LC charges

-do-

4. Section 1 , Invitation of Bid

Bid Security : INR Rs 80 Lac . ( 25 % through e –banking /e –payment and for balance 75% bank guarantee may be submitted . Scanned copy of BG of 75 % value must be uploaded at the time of online bid submission )

We suggest that 100 % of the Bid security value may be accepted against Bank Guarantee

No change, e-bidding guidelines

Page 2: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

5. PES Engineers Pvt. Ltd.

Section 7A,1(a) The bidder should be a manufacturer/EPC company , who has designed, manufactured , tested supplied ,erected , commissioned at least similar SPV Power plant of unit capacity in the range of 15 MW and above, in any one of the last three years and which is/are in successful operation on the date of bid opening.

we request you to kindly revise the eligibility to the 5 MW and 1 year O & M period.

RFP clause will prevail

6. Rajasthan Electronics & Instruments limited

Section 7A,1(a) The bidder should be a manufacturer/EPC company , who has designed, manufactured , tested supplied ,erected , commissioned at least similar SPV Power plant of unit capacity in the range of 15 MW and above, in any one of the last three years and which is/are in successful operation on the date of bid opening.

The bidder should be a manufacturer/EPC company , who has designed, manufactured , tested supplied ,erected , commissioned at least similar SPV Power plant of unit capacity in the range of 1 MW and above, in any one of the last three years and which is/are in successful operation on the date of bid opening.

RFP clause will prevail

7. Exempt REIL from submission of EMD of amt. Rs. 80 Lac being a PSU.

No exemption

8. Bharat Heavy Electricals Ltd.(BHEL)

GCC Clause 7): GCC 7.1(Pg No. 39)

(Within 21 days after the Supplier’s receipt of Notification of Award, the Supplier shall furnish Performance Security to the Purchaser for an amount of 10% of the contract value, excluding annual maintenance costs valid upto 60 days after the date of completion of performance obligations including warranty obligations and 10 years operation and maintenance contract period.

We request you to kindly modify the terms to "…..the validity of Performance Security upto 60 days after the date of completion of performance obligations including warranty obligations and 5 years operation and maintenance contract period."

RFP clause will prevail

Page 3: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

9. Bharat Heavy Electricals Ltd.(BHEL)

GCC 7.4(Pg No. 39)

The Performance Security will be discharged by the Purchaser and returned to the Supplier not later than 60 days following the date of completion of the Supplier’s performance obligations, including any warranty obligation and after completion of 10 years operation & maintenance period, under the contract as stated in clause 11 of S.C.C.

We request you to kindly modify the terms to "Performance Security will be discharged by the Purchaser and returned to the Supplier not later than 60 days following the date of completion of the Supplier’s performance obligations, including any warranty obligation and after completion of 5 years operation & maintenance period"

RFP clause will prevail

10. GCC 11(Pg No. 49)

"An all risk covered insurance, “Fire Policy ‘C’ along with equipment failure policy for full value of the plant & equipment shall be taken out by the supplier for the full O&M period of 120 months on annual renewal basis. "

The clause may please be modified and restricted for Insurance till commissioning of the plant as BHEL will be taking comprehensive insurance, until the project is commissioned and handed over. Beyond which, the plant will be asset for PEDA, and BHEL shall be responsible the insurance for its workmen, and the workmen of sub-contractors to BHEL engaged in O&M.)

RFP clause will prevail

11. GCC 13.1(Pg No. 50)

Incidental Services (GCC Clause 13): (e): Operation and maintenance of 6MWp Grid Interactive SPV power plant for a period of 10 years from date of commissioning as per section X

We request you to kindly modify the terms to "Operation and maintenance of 6MWp Grid Interactive SPV power plant for a period of 5 years from date of commissioning as per section X"

RFP clause will prevail

Page 4: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

12. Bharat Heavy Electricals Ltd.(BHEL)

GCC 15.7.1(Page No.51)

15.7 OPERATION AND MAINTENANCE SERVICE: Operation &Maintenance services shall be provided by the supplier during the period of 10 years from the COD. Annual maintenance and repairs of the entire system including supply of spares etc. for next 120 months will be done by the supplier.

We request you to kindly modify the terms to "Operation &Maintenance services shall be provided by the supplier during the period of 5 yrs from the COD. Annual maintenance and repairs of the entire system including supply of spares etc. for next 60 months will be done by the supplier."

RFP clause will prevail

13. GCC 16.1(Pg No.52)

"Payment (GCC Clause 16) (c) Payment for annual maintenance charges: The annual maintenance and repair cost shall be paid in year end in equal yearly installments within thirty days of receipt of claim at the end of each year, after completion of operation &maintenance obligations of that year, at the rates quoted in the price schedule. The performance security of 10% value of the contract amount excluding operation & maintenance costs shall be valid throughout the 10 years operation & maintenance period."

We request you to kindly modify the terms to "Payment for annual maintenance charges: The annual maintenance and repair cost shall be paid in equal quarterly installments within thirty days of receipt of claim at the end of each quarter, after completion of operation &maintenance obligations of that quarter, at the rates quoted in the price schedule. The performance security of 10% value of the contract amount excluding operation & maintenance costs shall be valid throughout the 5 years operation & maintenance period."

RFP clause will prevail

14. GCC 16.1(Pg no. 51-52)

"Terms of payment: Payment for Goods and Services (excluding Annual Maintenance Charges) (i) Advance Payment: Ten (10) percent of the contract price shall be paid within thirty (30) days of signing of the contract and upon submission of claim against a simple receipt and a bank guarantee for the equivalent amount valid until the goods/ equipment are delivered at plant site and in the form provided

"We request you to consider the below payment terms for Goods and Services (excluding Annual Maintenance Charges) a) 10% of the contract price as Advance upon furnishing of Contract Performance Security for 10% value of the contract for the specified period; b) 70% of the contract price will be paid within 30 days on receipt and acceptance of the major equipments/material in good

RFP clause will prevail

Page 5: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

in the bidding documents or another form acceptable to be purchaser. (ii) On delivery : Seventy (70) percent of the contract price shall be paid within 30 days upon submission of documents specified in Clause 6(a) of SCC including (i) Packing list and (ii) Supplier certificate that the amount shown in the invoice are correct in terms of the contract after delivery of equipment at the plant site.(Major equipment/item wise price break up schedule shall be provided by the supplier) (iii) On Commissioning :the ten (10)% of the contract price of the goods shall be paid within thirty (30) days after the date of the commissioning certificate issued by the purchaser after completion of performance guarantee tests and achievement of required PR. (iv) On Final Acceptance: the remaining ten (10)% of the contract price of the goods shall be paid within thirty (30) days after the date of the final Acceptance Certificate issued by the Purchaser’s representative in the Performa given in Section VIII - Form 8 after successful completion and achievement of the CUF performance tests and its compliance after one year of continuous operations after the commissioning."

condition at site; c) 15% of the contract price will be paid within 30 days on successful Erection and Commissioning of the plant; d) 5% of the contract price will be paid after 30 days from the taking over of the plant after Operational Acceptance (PR test demo.)"

Page 6: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

15. Bharat Heavy Electricals Ltd.(BHEL)

GCC Clause 23.1(Pg no. 53)

" Liquidated Damages The applicable rate is 0.5 percent per week or part thereof; and the Maximum Deduction is 10% of contract price."

We request you to Limit the Liquidated Damages value to 5% as followed by other Government Agencies

RFP clause will prevail

16. SECTION VI- 6(Pg No. 61)

"SECTION VI- 6. SCHEDULE OF REQUIREMENTS Transmission Line:4 km (approx.)"

We request you to clarify the scope of transmission line

Erection testing and commissioning of 66 KV transmission line from project yard to PSPCL grid about 4 KM away from project yard complete in all respects including arranging land for towers etc as per standard utility practices adopted by state licensee/PSPCLis not in the scope of bidder.

17. SECTION VI- 6(Pg No. 63-65)

The illustrative Schedule of requirements: Make/Vendors as specified for the detailed description of items/scope for setting up of 6MW SPV project

"BHEL being a PSU, shall finalize the Vendors after tendering process, this proof of documents shall be submitted to PEDA after the finalization of the Contract. We request you to kindly consider the vendors finalized by BHEL in addition to the Make/Vendors specified in the illustrative Schedule of requirements. "

Bidders must specify the vendors/makes in the bid which should be as per the RFP

Page 7: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

18. 164-165, various pages

LIST OF PROPOSED MAKE FOR 66 KV SWITCHYARD EQUIPMENTS and other equipments as specifically asked in the tender

BHEL being a PSU, shall finalize the Vendors after tendering process, this proof of documents shall be submitted to PEDA after the finalization of the Contract. We request you to kindly consider the vendors finalised by BHEL in addition to the Make/Vendors specified in the tender requirements.

Bidders must specify the vendors/makes in the bid which should be as per the RFP

19. Bharat Heavy Electricals Ltd.(BHEL)

SECTION – VII A (Pg No. 200)

Qualification requirements 1. (a) The bidder should be a manufacturer/EPC company, who has designed, manufactured, tested supplied, erected, commissioned at least similar SPV Power plant of unit capacity in the range of 15 MW and above ,in any one of the last three years and which is/are in successful operation on the date of bid opening.

Currently BHEL has Solar PV plant projects of various ratings like 10MW, 15MW, 20 MW & 50 MW respectively under various stages of execution/operation. However, we do not have the experience certificate for having executed at least similar SPV Power plant of unit capacity in the range of 15MW and above, in any one of the last three years and which is/are in successful operation on the date of bid opening. In view of the above, we request you to consider our request for modification of the clause for “having executed one grid connected solar project with capacity of 6MW and above, running successfully without any major problem as on the date of bid opening”.

RFP clause will prevail

Page 8: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

20. FORM 11(Pg No. 222)

11. TECHNICAL DETAIL FORM (Clause 14 of ITB)

BHEL being a PSU, shall finalize the Vendors after tendering process, this proof of documents shall be submitted to PEDA after the finalization of the Contract. We request you to kindly consider the vendors finalized by BHEL in addition to the Make/Vendors specified in the tender requirements.

Bidders must specify the vendors/makes in the bid which should be as per the RFP

21. Bharat Heavy Electricals Ltd.(BHEL)

cl. 1.5 a page no. 30

1) Raw materials(solar Cells) and technology employed in the module production processes shall have to be certified and a certificate giving details of major materials i.e. cells, Glass, back sheet, their makes and data sheets to be submitted for the modules being supplied by the bidder

Offered PV modules are IEC certified which contains make of glass, cell, etc. Please confirm whether this shall suffice.

RFP clause will prevail

22. cl. 1.5 a page no. 30

The glass used to make the crystalline silicon modules shall be toughened low iron glass with minimum thickness of 4.0 mm for 72 cell module and 3.2 mm for 60 cell module. The glass used shall have transmittance of above 90% and with bending less than 0.3% to meet the specifications

OFFERED PV modules are IEC approved with 3.2 mm thick glass for 72 cell configuration. This module, during IEC certification, type tests has passed through Hail impact test and static wind load test of 5400 Pa. Hence please allow 3.2 mm thick top glass for 72 cell configuration.

RFP clause will prevail

23. Ref. Cl. 2 (1)

wherever required, suitable number of PV panel structures shall be provided. Structures shall be of flat-plate design either I or L sections

Cold formed “C “sections shall also be allowed.

Cold formed “C “sections allowed.

Page 9: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

24. Ref. Cl.2 .

Each structure shall have a provision to adjust its angle of inclination to the horizontal as per the site conditions (six manual seasonal tilt adjustments

Considering the time involved in tilting of structures at site, and also considering the fact that tilting of structures yield better energy generation, it is requested to consider 3 ( three) manual seasonal tilt adjustments instead of 6 .i.e. Latitude , Latitude +15 and latitude -15DEG.

RFP clause will prevail

25. Ref page 73

Modules shall be clamped / bolted with the structure properly. The material of construction shall be GI / Al / Steel. Clamps / bolts shall use EPDM rubber and shall be designed in such a way so as not to cast any shadow on the active part of a module

EPDM rubber for bolts may be removed as ss304 bolts are used which is good corrosion resistant material.

SS304 Bolts are also acceptable.

26. 3.24

In the design and fabrication of the INVERTER the site temperature (5O to 55O C), incident sunlight and the effect of ambient temperature on component life shall be considered carefully. Similar consideration shall be given to the heat sinking and thermal for blocking diodes and similar components.

Beyond 50DEGC, the inverter output gets derated. Hence the clause may please be accordingly changed.

Derating be taken into consideration during design

27. pg 85

Each Array Junction Box will have suitable Reverse Blocking Diodes of maximum DC blocking voltage of 1000V with suitable arrangement for its connecting. The bypass & reverse blocking diodes should work for temperature extremes and should have efficiency of 99.98%, confirmed by appropriate IEC standards

: It is national and international practice to have DC fuse for each string so as to avoid circulating current amongst the PV strings hence diodes are not considered as this is a lossy component. PEDA to ensure grid availability during generation hours. Approximate power loss per string on account of string diode is about 8.0W. BHEL has installed several MW gird

Use of DC fuse is acceptable.

Page 10: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

connected PV plants with only DC fuse which are working satisfactorily. In view of this it is requested to do away with the blocking diodes.

28. Bharat Heavy Electricals Ltd.(BHEL)

Page 91 /230 13.1.4

Type and Rating of Transformer

Based on the no. of LV windings percentage impedance varies up to 6.25% age so also the vector group.. Hence the transformer parameters can be asked as GTP to be furnished by Bidder.

Please refer to Sheet-3, page 185 for technical particulars of transformers to be submitted by the bidders. Similar particulars have to be submitted for 66KV transformer also.

29. Page no. 102 of 203

Inverter, SMB makes and Transformer Make of accessories

BHEL request – Shall furnish the vendor details for approval during detailed engineering.

Bidders must specify the vendors/makes in the bid which should be as per the RFP

30. page 46 /62

Performance Ratio

Refer page 46 .Min. PR of 0.76 has been called where as in page 62 is 0.78. Please clarify the value

Typographic error, should be read as 0.78, please see the corrigendum on Pb. Govt. e-tender website.

Page 11: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

31. page 46 clause e VII

During the performance demonstration period after the commissioning of the plant and during the O&M period, the bidders need to maintain 100% uptime of the plant to achieve the proposed CUF at the end of each year. This shall not take into consideration any downtime caused due to plant tripping’s associated with the UTILITY GRID.

GRID NON AVAILABILITY period is not in the purview of EPC contractor. It is not possible to estimate realistically non availability of gird as depends on many parameters.

The issue with regard to grid down time is already explained in the Clause. The uptime calculation shall not take into consideration plant tripping / down time associated with utility grid.

32. Bharat Heavy Electricals Ltd.(BHEL)

Page 63

Array Junction Boxes WITH Remote PLC link

Array junction box shall have RS 485 link which shall get connected to a centralized SCADA thus enabling monitoring of SMB parameters in the SCADA. Considering the increased size, cabling and cost with PLC in each SMB this may please be removed.

AJBs must convey the array data to the Central PLC. RFP clause will prevail.

33.

Page no. 63

Schedule of requirements:

The make of each equipment shall be approved by PEDA during detailed engineering.

Bidders must specify the vendors/makes in the bid which should be as per the RFP

34. Page no. 89

One no. 6 MVA 11/66KV step transformer with OLTC, control panel. Two number transformers of 2 MVA each and 1 no. transformer of 1 MVA 300V/11KV.The transformers of shall be used for 6.0 MW SPV Power Plant

BHEL request – 66KV transformer shall be OCTC ( OFF circuit type) only considering the increased cost and the down time of OLTC.

RFP clause will prevail

Page 12: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

35. Sterling & Wilson Pvt Ltd

IFB 50 All bids must be accompanied by a bid security of Rs. 80.00 lacs. Bidders must deposit 25% of the Bid Security (EMD) amount through e-banking/e-payment and for the balance 75% of the Bid Security (EMD) amount, Bank Guarantee may be submitted. Scanned copy of Bank Guarantee for the 75% of the Earnest Money must be uploaded at the time of online bid submission.

SWPL requests PEDA to provide the option to the Bidder of submitting the whole 100% amount of EMD as a Bank Guarantee since it is a huge amount to be submitted the e-payment

RFP clause will prevail. This is as per Pb. Govt. E-bidding guidelines.

36. Sterling & Wilson Pvt Ltd

ITB 13.3 (a) That, in the case of a Bidder offering to supply goods under the contract which the Bidder did not manufacture or otherwise produce, the Bidder has been duly authorized by the goods' manufacturer or producer to supply the goods in the Purchaser’s country.

As this is turnkey based tender, EPC should be responsible for assurance of material, when it’s about authorization. If that is the case, there need to be multiple authorization letter as it can’t be on single manf’ basis due to the reason of price control. Request PEDA to leave this to EPC's discretion.

PEDA is not seeking authorization certificates from EPC. But EPC to ensure that it has manufacturer’s authorization to supply imported equipment / goods in India, so that long term service, technical support for the said equipment is available from the manufacturer. RfP clause will prevail.

37. ITB 14.3 A list giving full particulars, including available sources and current prices, of all spare parts, special tools, etc., necessary for the proper and continued functioning of the goods for a period to be specified in the Bid Data Sheet, following commencement of the goods by the Purchaser; and

In turnkey EPC these all are part of detailed engg after project award, current price can only be disclosed for the items mentioned in PRICE BID. Request PEDA to amend the same accordingly.

RFP clause will prevail These are required to evaluate the price bids on equal level

Page 13: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

38. ITB 15.5 Unsuccessful Bidder's bid security will be discharged/returned as promptly as possible but not later than thirty (30) days after the expiration of the period of bid validity prescribed by the purchaser, pursuant to ITB Clause 16.

Request PEDA to incorporate this line as well to the clause : On issue of LoI to successful bidder, whichever is earlier.

RFP clause will prevail. RfP ITB Clause 15.6 relates to successful bidder’s bid security.

39. ITB 22.3 - f) f. The projected operation and maintenance costs during the life of the equipment;

This will only consider the O&M duration for the project from bidder side as the component life consideration in PV Module case is 25years. Request PEDA to amend the same accordingly.

RFP clause will prevail.

40. Sterling & Wilson Pvt Ltd

ITB 22.4 - b) The Purchaser requires that the goods under the invitation for bids shall be delivered (shipped) at the time specified in the Schedule of Requirements. No credit will be given to earlier delivery. Bids offering any deviation from the scheduled delivery period shall be liable for rejection.

This is usually a part of the detailed scheduled activity chart for the project, after issuance of LoI. Request PEDA to amend the same accordingly.

RFP clause will prevail

41. Scope of Work BID-SUBJECT-Design, manufacture, supply, erection, testing and commissioning along with operation & maintenance for 10 years for a 6MWp SOLAR PV power plant at Village Handaya,Tehsil &Distt. Barnala,Punjab, India

SWPL requests PEDA to reduce the O&M period to 5 years as per the industry standards. Also, since the Warranty period have been stated as 5 years, request PEDA to amend the same accordingly.

RFP clause will prevail

Page 14: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

42. BDS ITB 14.3 (g) A confirmation that the bidder is either the owner of the intellectual Property Rights in the equipment/hardware and the software items offered, or that it has proper authorization and /or license from the owner to offer them. An authorization from the OEM shall be furnished. Willful misrepresentation of these facts will lead to the cancellation of the contract without prejudice of other remedies that the Purchaser /implementing agency may take.

As this is turnkey based tender, EPC should be responsible for assurance of material, when it’s about authorization. If that is the case, there need to be multiple authorization letter as it can’t be on single manf’ basis due to the reason of price control. Request PEDA to leave this to EPC's discretion.

RFP clause will prevail

43. GCC 16.3 Payments shall be made promptly by the Purchaser within sixty (60) days of submission of the invoice/claim by the Supplier.

The period for payment is too high This will have major impact on working capital of project, should be 15 or 21days as most of PSU’s follow the same. Request PEDA to kindly amend the clause accordingly.

RFP clause will prevail This is as per CERC Regulations

44. Sterling & Wilson Pvt Ltd

SCC GCC 7.1 Within 21 days after the Supplier’s receipt of Notification of Award, the Supplier shall furnish Performance Security to the Purchaser for an amount of 10% of the contract value, excluding annual maintenance costs valid upto 60 days after the date of completion of performance obligations including warranty obligations and 10 years operation and maintenance contract period.

According to SWPL understanding, this is 10% of EPC Price to be kept for 180 days(Execution)+ 10 Years(O&M) as Performance Security • Request PEDA to take O&M BG equivalent to 10% of O&M Charges on return of Performance security at operational acceptance.

RFP clause will prevail

Page 15: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

45. SCC 8.1.19 - vi) During O&M contract, the plant performance will be evaluated based on annual Capacity Utilization Factor. The Capacity Utilization Factor will be determined based on annual radiation measured at the plant and the guaranteed PR by the bidder. Second year onwards plant deration factor also will be considered to evaluate the CUF.

Request PEDA to kindly consider the degradation of PV Module as well. Kindly specify the formula to be used to calculate CUF

Constant total Deration of 20% in 25 yrs be considered

46. SCC 8.1.19 - vii) During the performance demonstration period after the commissioning of the plant and during the O&M period, the bidders need to maintain 100% uptime of the plant to achieve the proposed CUF at the end of each year.

100% uptime needs to be maintained, except when attributable because of the grid. 99% is industrial practice. Kindly amend the same accordingly. Request PEDA to specify the LD for not meeting along with Top Cap

Clause 8.1.19 e)-(ix) Specifies the compensation in case of non- achievement of CUF and PR. For LD calc in SCC clause 14 (ii), any delay after 48 hrs, Clause 23.1 GCC shall apply.

47. SCC 8.1.19 - viii) Bidder to access the corresponding solar insolation values and related factors of solar plant along with expected grid availability. The Bidder should access all related factors about the selected Site for the Project before giving commitments of PR and CUF of the proposed Project.

Whether PEDA will specify source for irradiation whether Meteonorm or NASA or Solar GIS. Kindly clarify.

Meteonorm , solar GIS Or other reliable industry standard source

48. Sterling & Wilson Pvt Ltd

SCC 10-Warranty GCC 15.2

– In partial modification of the provisions, the OEM / Supplier warranty period shall be 60 months from date of commissioning of the SPV Power plant or 72 months from the date of shipment, whichever occurs earlier.

Accordingly to SWPL understanding, the warranty for OEM is 5 years, Request PEDA to specify the warranty mechanism for the next 5 years totalling to a period of 10 years with respect to the O&M.

Warranty period for plant has been specified as 60 months from the date of commissioning and other manufacturer warranties for

Page 16: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

equipments like modules etc which are beyond 60 months shall continue as per OEM standards.

49. SCC 15.7.1 Operation &Maintenance services shall be provided by the supplier during the period of 10 yrs from the COD. Annual maintenance and repairs of the entire system including supply of spares etc. for next 120 months will be done by the supplier.

According to SWPL understanding, Defect Liability Period is till the end of contract period (10 Years). No clear mentioning of DLP but defects needs to incurred by the Bidder for complete 10 years, even though warranty is for 5 years. DLP of 10years is not backed by any manufacturer, these are normally for 1 or max 2years. Request PEDA to kindly specify the DLP clearly as it puts the contractor under and open ended liability and amend the same accordingly

RFP clause will prevail

50. SCC 15.7.3 Failure to arrange for the immediate repair/replacement will be liable for penalty of 0.5% of the item/items cost per day per item.

This is too high % as standard is for 0.1% per week. Request PEDA to amend the same accordingly.

RFP clause will prevail

Page 17: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

51. Sterling & Wilson Pvt Ltd

SCC GCC 16.1 - i)

(i) Advance Payment: Ten (10) percent of the contract price shall be paid within thirty (30) days of signing of the contract and upon submission of claim against a simple receipt and a bank guarantee for the equivalent amount valid until the goods/ equipment are delivered at plant site and in the form provided in the bidding documents or another form acceptable to be purchaser.

Request PEDA to kindly reduce the payment time to 15 or 21days to allow the Bidder to stick to the specified schedule at the time of Detailed Engineering.

RFP clause will prevail

52. SCC GCC 16.1 - ii)

(ii) On delivery : Seventy (70) percent of the contract price shall be paid within 30 days upon submission of documents specified in Clause 6(a) of SCC including (i) Packing list and (ii) Supplier certificate that the amount shown in the invoice are correct in terms of the contract after delivery of equipment at the plant site.(Major equipment/item wise price break up schedule shall be provided by the supplier)

Request PEDA to kindly split the 70% into two parts, as follows: 1) 30% against dispatch proof 2) 40% against delivery Kindly accept our proposal

RFP clause will prevail

52.

SCC GCC 16.1 - iv)

On Final Acceptance: the remaining ten (10)% of the contract price of the goods shall be paid within thirty (30) days after the date of the final Acceptance Certificate issued

According to SWPL understanding, there is an overlapping of PBG of 10 % and 10% of payment left, totaling to 20% for 1 year, as final acceptance is after 1 year. Request PEDA to kindly provide the 10% payment at the time fo operational acceptance. Kindly accept our proposal

See reply to query at Sr No 1

53.

SCC GCC 23.1 The applicable rate is 0.5 percent per week or part thereof; and the Maximum Deduction is 10% of contract price.

Request PEDA to kindly providethe top cap as 5% of the Contract Price as per the standard industry practice

RFP clause will prevail

Page 18: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

54. Sterling & Wilson Pvt Ltd

SCC 14-iii)

(iii) Liquidity Damages shall be charged at a rate of:Difference in units derived from committed and achieved CUF x Rs. [Tariff as per SECI’s PPA] for period after commissioning till the O&M contract closure . LD shall be recovered from the due annual O&M payments or from Bank Guarantee.

Request PEDA to define the Upper Cap of the LD to be put. Tariff as per SECI’s PPA mentioned. Kindly provide clarification for the same and request PEDA to define the tariff as it is important for the bidder to understand the liability upon him.

Tariff shall be as per PSERC generic tariff for 2016-17. Pl substitute in place of SECI, typographical error.

55.

SCC 33.1

No ‘C’ / ‘D’ form shall be issued by the purchaser

Request PEDA to provide the S-form in order to benefit from the tax impact in terms of CST.

RFP clause will prevail

56.

SCC 33.2

Income / Corporate Taxes in India: SWPL request PEDA to provide clarification on wether the increase in Tax will be reimbursed/payable by PEDA in case of change of law during the contractual period. Eg: With the news of GST being implemented, the tax will increase to 17% - 18%. Request PEDA to kindly provide clarity on the same.

All applicable taxes shall have to be paid as per laws and regulations in force.

Page 19: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

57. Sterling & Wilson Pvt. Ltd

Schedule of Requirement

The illustrative Schedule of requirements is in accordance with the specifications contained in this document

As turnkey project EPC should be given flexibility for selection of Makes complaining to IEC / IS standard as the case may be. Request PEDA to provide the Bidder wit relaxation for the same.

See Sr No 33

58.

Schedule of Requirement Inverters as per specifications Request PEDA to include HITACHI/TiMEC

RFP clause will prevail

59.

Schedule of Requirement

15. 2.00 MVA , 300V-415V /11KV, 3 Phase, 50 Hz transformer 16. 6.00 MVA, 11KV/66KV,3 phase,transformer 17. 50KVA, 415 V /11 KV, 3 PHASE 50 Hz transformer, Hpole mounted with GO switch,LA for Auxiliary supply.

Request PEDA to provide flexibility for bidder to choose Tier 1 manufacturer

RFP clause will prevail

60.

General

At the time of Site Visit, it was noted that the there is no Bay availability at the PSPCL 66kv Substation. We were told the 220kv substation will be provided. Request PEDA to provide clarification on the evacuation mehtodology.

Evacuation and transmission lines not in the scope of bidder.

Page 20: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

61. Sterling & Wilson Pvt. Ltd

General

At the Site Visit, it was noted that a11kv Transmission line passing through the site, around 15 m from the Boundary inside the plot. Request PEDA to provide clarification on what would be the course of action to not let the transmission line intervene with the capacity being put up.

11KV line will be shifted, otherwise, there is enough land space for plant installation.

62.

General

There is a 1.5 km approach road from the Highway to the site which is not steady enough to sustain the transportation of heavy loads. Request PEDA to clarify wether PEDA would be developing the road.

There is an alternate road also.

63. Array Structure: 2)

2.Structural material shall be corrosion resistant and electrolytically compatible with the materials used in the module frame, its fasteners, nuts and bolts. Galvanizing should meet ASTM A-123 hot dipped galvanizing or equivalent which provides at least spraying thickness of 80 microns on steel as per IS5905, if steel frame is used. Aluminum frame structures with adequate strength and in accordance with relevant BIS/international standards can also be used.

It is requested that Pegal & Galvalume sheets be allowed for materials of MMS. Kindly Confirm.

RFP clause will prevail

Page 21: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

64. Sterling & Wilson Pvt. Ltd

Array Structure: 5)

5.Each structure shallhave a provisionto adjust its angle of inclination to the horizontal as per the site conditions (six manual seasonal tilt adjustments) .

It is requested that TWO TILT ANGLES be considered for Seasonal Tilt Structures.Kindly confirm.

Four manual seasonal tilt adjustments

65. Array Structure: 6)

6.Each panel frame structure be so fabricated as to be fixed on the ground. The structure should be capable of withstanding a wind load of 200 km/hr after grouting & installation. Grouting material for SPV structure shall be as per M15 (1:2:4) concrete specification.

It is requested that for the design consideration wind speed to be as per IS-875-Part-III. Kindly confirm.

Be kept as per IS-875-Part-III

66. Array Structure: 11)

11.Modules shall be clamped / bolted with the structure properly. The material of construction shall be GI / Al / Steel. Clamps / bolts shall use EPDM rubber and shall be designed in such a way so as not to cast any shadow on the active part of a module.

Use of EPDM rubber to be as per Module manufacturer. Kindly confirm.

These are for module clamping.

67. 13.12.4 For the operation & maintenance of Solar Photovoltaic Power Plant, office cum store building and security house along with other buildings have been proposed. The building shall be constructed with RCC framed structure with brick partition walls. Bidder shall furnish the drawing showing the proposed buildings. The construction of the same shall be as under) RCC Works All RCC works shall be as per IS 456 and the materials used viz.

It is requested that Pre-Fabricated structures be considered for Inverter room, Security room & Control Room Building. Kindly confirm.

RFP clause will prevail

Page 22: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

Cement rein- forcement, steel etc. shall be as per relevant standards.

68. Sterling & Wilson Pvt Ltd

13.15 The contractor shall provide stone pillars of about 1.5 meter height at the distance of 25 meter intervals for the entire land area of Solar Power Plant. All documents/records regarding test data, oscillographs and other measured values of important parameters finalized after site adjustment shall be handed over to purchaser in the form of test reports (in bound volume) for their future use and reference.

It is requested that instead of Stone pillars Steel posts be used for peripheral boundary pillars. Kindly confirm.

RFP clause will prevail

69. Technical Specification 13.2 Pg 89-90 Step Up Transformers 300V/11KV and 11KV/415VAuxiliary Transformer

— One no. 6 MVA 11/66KV step transformer with OLTC, control panel. — Two number transformers of 2 MVA each and 1 no. transformer of 1 MVA 300V/11KV. — Transformer LV side should be of same voltage as that of output of PCU and HV side should be 11 KV. — These transformers shall be of either five/three winding depending upon design 3) One number Auxiliary transformer mounted on H pole ofsuitable cap, 415 V/11 KV for meeting the captive loads with suitable control panel.

1) Power Transformer shall be rated for 100% of plant out put power as in case of solar max generation on peak radiation(which will happens once in a day for few minutes ) of the power will never exceed 5MVA so we request to consider % MVA transformer in place of 6 MVA . 2) For Clause no. '13.2' (page 89) LV voltage of Inverter Transformer is mentioned 300 Volts but in contrast to clause no. '13.1.4' (page 91) LV voltage of Inverter Transformer is demanded between 280 to 415 volts.SWPL requests you to take LV voltage rating of Inverter Transformer equally to or in accordance to the output voltage of

RFP clause to prevail LV voltage rating of inverter transformer to match with output voltage of inverter. Already stated in bidding document.

Page 23: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

Inverter as per Inverter make selected and manufacturer recommendation. 3) SWPL recommends to consider indoor type Air Natural Aux Transformer of Voltage ratio: (Inverter transformer LV)/ 415 V for captive loads

70. Sterling & Wilson Pvt Ltd

Technical Specification 13.14 Types and ratings

(i) The transformers shall be of copper wound 280-415V/11kV, 3 phase, natural cooled, double wound, core type construction, oil immersed and shall be suitable for outdoor service as step-up transformers a) Maximum continuous rating at reference : 2000 kVA(equivalent capacity as per design) ambient temperature specified d) Rated primary Voltage on principal tap : 11 kV e) Rated secondary Voltage : 0.280/0.415 kV f) Winding connections: i) HV side : Star ii) LV side : Delta iii) Vector group reference : YNd-11 g) Type of cooling : ONAN h) Percentage impedance at normal : 4.0 % k) Type of terminal : On HV side to suitable size of cable for inter connection to indoor HT panel /Panther" Conductor on HV sides as per design & LV Side: suitable for connecting cable thimble of suitable size cable on LV side/LT BUS as per design of bidder.

SWPL recommends to use vector group of Inverter Transformer as per the recommendation of Inverter manufacturer or we prefer to use vector group as Dyn11yn11

Will be considered as per detailed Engg. design

Page 24: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

71. Sterling & Wilson Pvt Ltd

Technical Specification 13.2.3 Pg No. 113 " Indicating and Integrating Meters/Instruments: "

c) Relays : — For 11 kV Incoming feeders to the 630kVA Oil filled transformers, 630 A VCB equipped with following protection functions as a minimum: Restricted Earth fault protection (87N) — 630kVA transformer feeder to 415V Main LT panel Outgoing (ACB with Microprocessor based release SR21i (L&T make or equivalent) with following protection functions as a minimum): Standby EF protection (51G)

As the general practice is,Inverter Transformer neutral at LV side is always kept floating so SWPL recommends that Restricted Earth Fault Protection in Inverter transformer is not required.

Will be considered as per detailed Engg. design

72. Technical Specification 13.2.26 Pg No. 123 Ratings and specifications (11V / 66kV Transformer)

Particulars 11KV / 66kV Transformer Specs. (Outdoor type transformer) Continuous kVA ratings - As per design ; Type - Oil immersed ; Frequency - 50 Hz ; Type of cooling - Oil Natural Air Natural (ONAN) ; No. of phases - 3 (Three) ; Rating voltage - H.V. side 66 kV ; Highest System voltage on H.V. side- 72.5 kV r.m.s. ; Rated voltage on L.V. side - 11 kV r.m.s. ; Vector Group - DyN11 ; Connections : a. H.V. Winding - Delta b. L.V. winding - Star with Neutral solidly earthed . On load taps on H.V. Side - + 5 to – 10.0 % (in steps of 1.25%) (for H.V. Variation) ; Impedance voltage (%)as per - 4% IS 2026 ; Minimum Creep age distance at 400 - 32 mm/kV phase to earth ; Transformer connections -LV side – Cables/ Bus Duct withweather proof enclosure as per design&

Impedance of transformer shall be inline to IS & shall be such which will be inline to the loss requirements

HV Side –Bushing with enclosure

Will be considered as per detailed Engg. design

Page 25: PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT ... to Pre-bid querries.pdf · We suggest that Performance security BG for 10 % of the contract price excluding annual maintenance

PRE Bid meeting reply for 6MWp SOLAR PV POWER PLANT AT Village .HANDIAYA, Distt. BARNALA’’

73. Sterling & Wilson Pvt Ltd

Technical Specification

**Note : Interconnection for power evacuation through single circuit 66 KV overhead transmission line systems shall be provided by the project EPC in 66KV ODY of the plant by installing suitable 66KV bayalong with required 66KV VCB.

**SWPL requests you to please clearly mention scope and confirm the evacuation methodology from SPV plant end to DISCOM substation,whether evacuation is done by using Cable or by Overhead Transmission system

Full 66 KV switch yard at project end with in the battery limit of bidder and 66 KV transmission line from project yard to PSPCL grid not in the scope of bidder.

74. Technical Specification 13.11.1 Pg No. 174 11kV/66KV HT Cables:

**11kV/66KV Grade, Al. Conductor XLPE cable shall be used between outgoing feeder panel and overhead mounting structure for termination of line.

— The cable should confirm to relevant ISS. Please clarify that transmission of power will be through 66kV Cable or conductor if conductor than please clarify the requirement of 66kV Cable

Transmission is through 66 KV conductors, bidder has the option to use 66KV conductors

75. Technical Specification 13.11.1 Pg No. 174 11kV/66KV HT Cables:

"— 11kV/66KV Grade, Al. Conductor XLPE cable shall be used between outgoing feeder panel and overhead mounting structure for termination of line. — cables shall be laid on structural supports and using Galvanized Cable trays of adequate strength."

76. Special Conditions for Contract Clause 4 Pg No. 46 (e) Performance Guarantee , (ii)

The minimum acceptable PR of the plant is 0.76 and CUF shall be 18% against installed DC capacity at STC.

SWPL requests PEDA to specify the correct PR value required for SPV plant as PR value mentioned under given two clauses are mismatching. Request to have CUF of 17% as CUF of 18% not achievable as per meteonorm satellite calc.

PR is 0.78, typo error -correction corrigendum already issued. CUF of 17% allowed.