    Short Circuit Calculations

    Calculation method: IEC 60909 (International Electrotechnical Commisson)

    Standard for radial and mesh LV and HV network

    Why Short Circuit Analysis:

    Short circuit currents must be calculated in the network for sizing an electrical

    installation and the required equipment, as well as determining the meansrequired for the protection of life and property

    Two values of short-circuit current must be evaluated:1) The maximum short-circuit current. It is used to determine

    i. The breaking capacity of the circuit breakers.

    ii. The making capacity of the circuit breakers.

    iii. The electrodynamic withstand capacity switchgear.

    2) The minimum short-circuit current. It is required for selecting the time-

    current curve for circuit breakers and fuses. They are more important when

    i. Cables are long and the source impedance is relatively high.

    ii. Protection of life depends on circuit breaker or fuse operation.

  • 8/12/2019 Pre ShortCircuit

    2/13

    Short Circuit Calculations

  • 8/12/2019 Pre ShortCircuit

    3/13

    Short Circuit Calculations

    The protection device must clear

    the short-circuit current within atime that is compatible with the

    thermal stresses that can be

    withstood by the protected cable.

    Permissible limit under steady-state

  • 8/12/2019 Pre ShortCircuit

    4/13

    Short Circuit Calculations

    Circuit protection using a Circuit Breaker

  • 8/12/2019 Pre ShortCircuit

    5/13

    Short Circuit Calculations

    Short-Circuit Types

    80%

    15%5%

  • 8/12/2019 Pre ShortCircuit

    6/13

    Short Circuit Calculations

    Concequences of Short Circuit

    1) At the fault location, electrical arcs

    i. Damage to insulation

    ii. Welding of conductors

    iii. Fire and danger to life

    2) On the faulty circuit

    i. Electrodynamic forcesii. Excessive temperature rise

    3) On other circuits nearby

    i. Voltage dips

    ii. Shut down of a part of network

    iii. Dynamic instability

    iv. Disturbances in control/monitoring circuits

  • 8/12/2019 Pre ShortCircuit

    7/13

    Short Circuit Calculations

    Short Circuit Calculations based on IEC 60909 (VDE 0102)

    It can be applied to all networks (radial or meshed) up to 550 kV.

    The method is based on Thevenin theorem. An equivalent voltage source

    and impedance at the short-circuit location is determined and short-

    circuit current is calculated from them.

    All network feeders as well as the synchronous and asynchronous

    machines are replaced in the calculation by their impedances (positive,

    negative, and zero sequence impedances).

    All line capacitances and the parallel admittances of non-rotating loads,except those of the zero-sequence system, are neglected.

  • 8/12/2019 Pre ShortCircuit

    8/13

    Short Circuit Calculations

    Short circuit current near a generator

  • 8/12/2019 Pre ShortCircuit

    9/13

    Short Circuit Calculations

  • 8/12/2019 Pre ShortCircuit

    10/13

    Short Circuit Calculations

    Standardised short-circuit voltage for public distribution system

    Conductor resistivity values

  • 8/12/2019 Pre ShortCircuit

    11/13

  • 8/12/2019 Pre ShortCircuit

    12/13

    Short Circuit Calculations

  • 8/12/2019 Pre ShortCircuit

    13/13

    Short Circuit Calculations

    EXAMPLE: