Preamble The following document is a compilation of the existing conditions of the South Hunterdon Regional School District Facilities – Lambertville Public School and West Amwell Township Elementary School. During the Summer of 2019, USA Architects was asked to join a series of facilities meetings that included council members and mayors from the surrounding school district’s regions. USA Architects was tasked with offering advice and knowledge of facility requirements, code regulations relative to building construction, and related facility matters. A series of pictures presented herein display the architect’s observations and provide visual representation of the facilities’ existing conditions. In general, Lambertville Public School core and shell is in good condition. The facility cannot be expanded nor can an upper level be added to the building. The facility’s interior is lacking ADA requirements which creates a host of challenges with any reconstruction project. The facility is aging and in need of restoration. In general, West Amwell Elementary core and shell is in very poor condition. The entire façade, block and windows require improvements to the insulation barrier. The facility cannot be expanded due to existing septic fields in the rear and parking on the northern and eastern sides of the property. An upper level cannot be added to the building. The facility interior is lacking ADA requirements which creates a host of challenges with any reconstruction project. The facility is aging and in need of restoration. The costs associated at the end of this document are meant solely for magnitude and are therefore, not based on an actual detailed scope of work. This document is divided into four parts: PART 1 includes a series of pictures from the architect’s on site observations. They represent specific findings of existing conditions. PART 2 denotes the existing conditions of the elementary schools regarding program space and compares the facilities’ conditions to New Jersey Department of Education’s “guidelines.” (not a mandated minimum requirement) The information provides a sense of understanding regarding the adequacy of the buildings when compared against the state model. PART 3 provides paths to consider as the district contemplates any future actions for scope of work. PART 4 provides basic cost assumptions in order to compare the considerations outlined in Part 3.

Upload: others

Post on 02-May-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Preamble - South Hunterdon Regional School District

PreambleThe following document is a compilation of the existing conditions of the South

Hunterdon Regional School District Facilities – Lambertville Public School and

West Amwell Township Elementary School.

During the Summer of 2019, USA Architects was asked to join a series of facilities

meetings that included council members and mayors from the surrounding

school district’s regions. USA Architects was tasked with offering advice

and knowledge of facility requirements, code regulations relative to building

construction, and related facility matters. A series of pictures presented herein

display the architect’s observations and provide visual representation of the

facilities’ existing conditions.

In general, Lambertville Public School core and shell is in good condition. The

facility cannot be expanded nor can an upper level be added to the building. The

facility’s interior is lacking ADA requirements which creates a host of challenges

with any reconstruction project. The facility is aging and in need of restoration.

In general, West Amwell Elementary core and shell is in very poor condition.

The entire façade, block and windows require improvements to the insulation

barrier. The facility cannot be expanded due to existing septic fields in the rear

and parking on the northern and eastern sides of the property. An upper level

cannot be added to the building. The facility interior is lacking ADA requirements

which creates a host of challenges with any reconstruction project. The facility

is aging and in need of restoration.

The costs associated at the end of this document are meant solely for magnitude

and are therefore, not based on an actual detailed scope of work.

This document is divided into four parts:

PART 1 includes a series of pictures from the architect’s on site observations.

They represent specific findings of existing conditions.

PART 2 denotes the existing conditions of the elementary schools regarding

program space and compares the facilities’ conditions to New Jersey Department of

Education’s “guidelines.” (not a mandated minimum requirement) The information

provides a sense of understanding regarding the adequacy of the buildings when

compared against the state model.

PART 3 provides paths to consider as the district contemplates any future actions

for scope of work.

PART 4 provides basic cost assumptions in order to compare the considerations

outlined in Part 3.

Page 2: Preamble - South Hunterdon Regional School District

FACILITY OBSERVATIONS OFWest Amwell Township Elementary School + Lambertville Elementary School SOUTH HUNTERDON REGIONAL SCHOOL DISTRICTDate: 10.2.2019

Page 3: Preamble - South Hunterdon Regional School District

3

1. OBSERVATIONS

2. PROGRAM - N.J.D.O.E. GUIDELINES

3. CONSIDERATIONS

4. FEASIBILITY

AGENDA

Page 4: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 4

OBSERVATIONS

Page 5: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 5

LAMBERTVILLE ELEMENTARY

Page 6: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 6

SITE PLAN

Page 7: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 7

FACADE CONDITIONS

Page 8: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 8

FACADE CONDITIONS

Page 9: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 9

FACADE CONDITIONS

Page 10: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 10

DEFICIENCIESPNEUMATIC CONTROLS

TYP. 30” WIDE DOOR W/ STEPS

NON-APPROVED GATE FIRE EGRESS

SMALL KITCHEN

TOILET ROOMS CANNOT RENOVATE TO BE ADA

ASBESTOS BEHIND WALLS (PIPES)

NOT ADA ACCESSIBLE

NO ADA TOILETNO A/C

(3) SPECIAL EDUCATION TEACHERS IN 1 CLASSROOM

INTERIOR CLASSROOM NO A/C, SUB-STANDARD

NO ADA TOILETS

NON-RATED WALLS

WINDOW UNIT A/C (MOISTURE CONCERNS) RECIRCULATES AIR -NO FRESH AIR

ENERGY HOG

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

TYP. 30” WIDE DOOR

HVAC REPLACE

TABLES POOR

Speech

Classroom

Storage

Storage

Page 11: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 11

MULTIPURPOSE ROOM

HVAC REPLACE

TABLES POOR

Speech

Classroom

Storage

Storage

Page 12: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 12

MULTIPURPOSE ROOM

Page 13: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 13 LAMBERTVILLE ELEMENTARY

TOILET ROOMS

TOILET ROOMS CANNOT RENOVATE TO BE ADA

ASBESTOS BEHIND WALLS (PIPES)

NO ADA TOILET

NO ADA TOILETS

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Speech

Classroom

Storage

Speech

Classroom

Storage

Storage

Page 14: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 14

TOILET ROOMS

Page 15: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 15

TOILET ROOMS

Page 16: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 16

TOILET ROOMS

Page 17: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 17 LAMBERTVILLE ELEMENTARY

TYPICAL DOORS

TYP. 30” WIDE DOOR W/ STEPS

TYP. 30” WIDE DOOR

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Speech

Classroom

Storage

Storage

Page 18: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 18

TYPICAL DOORS

Page 19: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 19 LAMBERTVILLE ELEMENTARY

PNEUMATIC CONTROLS PNEUMATIC CONTROLS

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Speech

Classroom

Storage

Storage

Page 20: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 20

PNEUMATIC CONTROLS

Page 21: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 21 LAMBERTVILLE ELEMENTARY

GATE FIRE EGRESS + NON-RATED WALLSNON-APPROVED GATE FIRE EGRESS

NON-RATED WALLS

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Speech

Classroom

Storage

Speech

Classroom

Storage

Storage

Page 22: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 22

GATE FIRE EGRESS + NON-RATED WALLS

Page 23: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 23 LAMBERTVILLE ELEMENTARY

SPECIAL EDUCATION + SPEECH CLASSROOMS

Speech

Classroom

Storage

(3) SPECIAL EDUCATION TEACHERS IN 1 CLASSROOM

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Storage

Page 24: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 24

SPECIAL EDUCATION + SPEECH CLASSROOMS

Page 25: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 25 LAMBERTVILLE ELEMENTARY

NURSE’S OFFICENOT ADA ACCESSIBLE

Speech

Classroom

Storage

Storage

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Page 26: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 26

NURSE’S OFFICE

Page 27: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 27 LAMBERTVILLE ELEMENTARY LAMBERTVILLE ELEMENTARY

STORAGE ROOMS

Speech

Classroom

Storage

Storage

NO A/C

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Page 28: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 28

STORAGE ROOMS

Page 29: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 29

STORAGE ROOMS

Page 30: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 30

BOOK ROOM

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Page 31: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 31

BOOK ROOM

Page 32: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 32

MEDIA CENTER

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Page 33: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 33

MEDIA CENTER

Page 34: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 34

MUSIC ROOM

GENERAL NOTES:

CLASSROOM UNITS - MORE THAN 10 YRS. OLD

THERMOSTAT, RESTAT. CANNOT CONTROL (PNEUMATICS)

UNIT NOT RUNNING

NO FRESH AIR - OCCUPY - CYCLE, VIBRATION - NOISY

Page 35: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 35

MUSIC ROOM

Page 36: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 36

WEST AMWELL ELEMENTARY

Page 37: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 37

SITE PLAN

Page 38: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 38

INADEQUATE BUILDING ENVELOPE/ WALL INSULATION

TYPICAL CONSTRUCTION IS SINGLE WYDTH CONCRETE BLOCK

SITE PLAN

Page 39: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 39

FACADE CONDITIONS

Page 40: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 40

FACADE CONDITIONS

Page 41: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 41

GROUNDS CONDITIONS

Page 42: Preamble - South Hunterdon Regional School District

42

TRAILER +/- 2012 NO UPGRADES/ORIGINAL

TOILET ROOMS NOT ADA ACCESSIBLE

ROOF +/- 2” INSULATION

SMALL (NOT EQUITABLE W/ LAMBERT- VILLE) NO BASKET- BALL NO A/C

WINDOW A/C +\- 10+ YRS. OLD PROBLEMATIC ENERGY HOG

TOILET ROOMS NOT ADA ACCESSIBLE

WEST AMWELL ELEMENTARY

DEFICIENCIES

ACCESS ISSUE

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

Trailer

Page 43: Preamble - South Hunterdon Regional School District

43 WEST AMWELL ELEMENTARY

ROOF +/- 2” INSULATION

ACCESS ISSUE

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

MULTIPURPOSE ROOM

SMALL (NOT EQUITABLE W/ LAMBERT- VILLE) NO BASKET- BALL NO A/C

Trailer

Page 44: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 44

MULTIPURPOSE ROOM

Page 45: Preamble - South Hunterdon Regional School District

45

NOT ACCESSIBLE

NJAC 6A:26=6.3(C)6

DOORS FROM ALL SPACES USED BY STUDENTS AND SCHOOL STAFF, EXCLUDING LAVATORIES, STORAGE ROOMS, JANITOR’S CLOSETS, INSTRUCTIONAL SPACES UNDER 300 GROSS SQUARE FEET, AND LOCKER ROOMS, SHALL SWING INTO THE CORRIDOR AND SHALL HAVE A SAFETY VISION PANEL OF 1/4 INCH GLAZING WHICH IS NOT LESS THAN 100 SQUARE INCHES.

LIBRARY

WEST AMWELL ELEMENTARY

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

Trailer

Page 46: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 46

LIBRARY

Page 47: Preamble - South Hunterdon Regional School District

47 WEST AMWELL ELEMENTARY

NURSE’S OFFICE

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

Trailer

Page 48: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 48

NURSE’S OFFICE

Page 49: Preamble - South Hunterdon Regional School District

49 WEST AMWELL ELEMENTARY

TOILET ROOMS

TOILET ROOMS NOT ADA ACCESSIBLE

TOILET ROOMS NOT ADA ACCESSIBLE

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

Trailer

Page 50: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 50

TOILET ROOMS

Page 51: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 51

TOILET ROOMS

Page 52: Preamble - South Hunterdon Regional School District

52

TRAILER +/- 2012 NO UPGRADES/ORIGINAL

WEST AMWELL ELEMENTARY

DEFICIENCIES

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

Trailer

Page 53: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 53

BOILER ROOM

Page 54: Preamble - South Hunterdon Regional School District

54 WEST AMWELL ELEMENTARY

CORRIDOR

BUILDING - WIDE ISSUES:

UNIT VENTILATORS +/- 20 YRS. OLD

PROBLEMATIC ACTUATORS

EXISTING 600 AMP 3 PHASE SERVICE

PROBLEMATIC/ UNDERSIZED

Trailer

Page 55: Preamble - South Hunterdon Regional School District

WEST AMWELL ELEMENTARY 55

CORRIDOR

Page 56: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 56

PROGRAM - N.J.D.O.E. GUIDELINES

Page 57: Preamble - South Hunterdon Regional School District

57

PROGRAM

EXISTING CONDITIONS F.E.S GUIDELINES

Lambertville Elementary

31,000 SF Populations between 450-500 (w/ Pre-K +/- 130 SF/FTE student)West Amwell

Elementary24,800 SF

55,800 SF OR 58,500-65,000 SF standard

N.J.D.O.E Guidelines Department of Education F.E.S (Facility Efficiency Standards)

(Below F.E.S Guidelines by 3,000-10,000 SF)

Gross S.F. Example

Page 58: Preamble - South Hunterdon Regional School District

58

LAMBERTVILLE E.S. MODEL SPACE

Classrooms (18) 850 SF Classrooms 850 SF

Kindergarten (2)

1,000 SF Kindergarten1,000 SF (1,200 SF)*

Music 590 SF Music 1,250 SF

Art 800 SF Art 1,250 SF

SC Special Education

400 SFSC Special Education

600 SF

Media Center 1,400 SF Media Center 4,000 SF

Multipurpose Room

3,600 SFComputer Room

850 SF

- -Maker Space (Tech) *

- - Cafetorium 6,200 SF

- - Gymnasium 4,200 SF

PROGRAMN.J.D.O.E Guidelines Department of Education F.E.S (Facility Efficiency Standards)

PROGRAM SPACE EXAMPLE

Page 59: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 59

CONSIDERATIONS

Page 60: Preamble - South Hunterdon Regional School District

60

UCC CODE 5:23-6.1

5. In alternation work, the configuration of the building is changed in some manner. The definition of “alteration” in N.J.A.C. 5:23-6.10 through 6.3 provides the information needed to fully understand this term. Because improper alteration work could create a safety hazard in the building, this subcode contains specific requirements which define these hazards. These are the basic requirements of the subcode which can be found in N.J.A.C 5:23-6.10 through 6.30.

8.(e) Reconstruction Work: The requirements that apply to reconstruction work are in N.J.A.C. 5:23-6.7. Reconstruction is defined in N.J.A.C 5:23-6.3. Unlike repair, renovation, and alteration, reconstruction is not a kind of work. A reconstruction may, as the definition of the term makes clear, include a combination of repair, renovation, and alteration work. It is the extent and nature of the work which makes a project a reconstruction. There are no quantitative criteria which determine whether a project is a reconstruction. A project becomes a reconstruction when the area where the project is taking place cannot be occupied while the work is in progress and when a new certificate of occupancy is required before the area can be re-occupied. Both criteria must be met.

Page 61: Preamble - South Hunterdon Regional School District

61

CONSIDERATIONS

CONSIDERATION #1 CONSIDERATION #2 CONSIDERATION #3

“Status Quo” “Reconstruct” “Build New”Maintain/Maintenance Same Square Footage Cost for Site

Lambertville E.S. Built 1968West Amwell E.S. Built 1951

Lambertville E.S Cannot Expand West Amwell E.S. Problematic to Expand

Maintain Existing Schools During Construction until New School is Complete

Small Improvements Costs for Off Site Education Temp. Facilities -

Costs Associated with Maintenance Same Educational Program Limitations -

Page 62: Preamble - South Hunterdon Regional School District

LAMBERTVILLE ELEMENTARY 62

FEASIBILITY

Page 63: Preamble - South Hunterdon Regional School District

63

STATUS QUO RECONSTRUCTION

OF 2 EXISTING FACILITIES

BUILD NEW

1 NEW FACILITY

Reoccurring Maintenance CostsProjected $20 million (Could Vary, Based on Final Scope of Work)

Projected $30 million (Projected Estimate)

HVAC - both schools passed life expectancy - to be replaced

$6 Million (Construction Aid) $6 Million (Construction Aid)

Rent Educational Space (?) ▪ Alternative Sites, Location of Temp Schools Unknown (No Aid)

Busing/Transportation/(2) years

$24 Million (Local Funding)

2 Buildings 1 Building

2 Sites 1 Site

55,800 SF Elementary Areas 65,000 SF Elementary Areas

FEASIBILITY

Page 64: Preamble - South Hunterdon Regional School District

64

QUESTIONS