Climate control in Finnish Pig farms
v.d. Voorst Klimaatbeheersing ing. Peter van der Voorst
15-02-2012
![Page 2: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/2.jpg)
A pig can live without:
Feed: for 3 weeksWater: for 3 daysAir: for 3 minutes
Therefore a good climate is very important
![Page 3: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/3.jpg)
Ventilation in pig houses
Ventilation in a pig house is based on five important principals: The 5 A’s
-Air-inlet outside-Air-inlet inside-Air-movement-Air-quality-Air-outlet
![Page 4: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/4.jpg)
![Page 5: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/5.jpg)
Too coldRoom temperature below set temperature
Too much ventilationHeating system doesn’t work wellInsulation too lessWrong place of the temperature sensorMeasuring fan doesn’t work wellAir-inlet too big (wind influence)Wrong air movementWrong installed climate curve
![Page 6: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/6.jpg)
![Page 7: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/7.jpg)
Too warmRoom temperature depends on outside temperature
Too less ventilationHeating system doesn’t work wellNo insulated roofWrong place of the temperature sensorAir-inlet too smallWrong air movementWrong installed climate curve
![Page 8: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/8.jpg)
![Page 9: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/9.jpg)
![Page 10: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/10.jpg)
Draught
Too much ventilationWrong air movementAir leaksWrong installed ventilation system
![Page 11: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/11.jpg)
Air quality
Too less ventilationVery dirty pensAir movement in the slurry pit
Humidity: 60 – 80%Ammonia: < 20 ppmCarbon dioxide: 2000 – 3000 ppm
![Page 12: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/12.jpg)
Climate control
What can be controlled?Air- inlet from outsideAir- inlet system inside Temperature sensorNH3CO2Measuring fan Rotations per minute of the ventilatorThe air movement of the incoming fresh air.Air leaks and bad insulation with infrared camera
![Page 13: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/13.jpg)
![Page 14: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/14.jpg)
![Page 15: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/15.jpg)
![Page 16: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/16.jpg)
![Page 17: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/17.jpg)
![Page 18: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/18.jpg)
![Page 19: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/19.jpg)
![Page 20: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/20.jpg)
![Page 21: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/21.jpg)
Windinfluence is very bad
The air-inlet must be calculated with 1,5 cm²/m3 maximum ventilation.
We need this max. opening for about 2 weeks a year (high temperature + max. weight pigs)
Very important: The air-inlet must be automatically regulated!!
![Page 22: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/22.jpg)
![Page 23: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/23.jpg)
![Page 24: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/24.jpg)
![Page 25: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/25.jpg)
The inlet valve system:
Problems with the inlet valves:The openings of the inlet valves within one
room are not the same.Installation settings are quite difficult.
Many mistakes are made.Motors get broken.Cables get broken.Wrong place in the room.
![Page 26: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/26.jpg)
![Page 27: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/27.jpg)
![Page 28: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/28.jpg)
![Page 29: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/29.jpg)
![Page 30: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/30.jpg)
![Page 31: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/31.jpg)
![Page 32: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/32.jpg)
Recommendations for existing farms:
Beware of good installation settings.Beware of that all the inlets within one
room has the same opening.For example 10% opening must be the
same for all the same rooms.Extra air inlet above the corridor
![Page 33: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/33.jpg)
![Page 34: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/34.jpg)
The best inlet system for Finnish circumstances
Animal group
System 1 System 2
Nursery Diffuse ceiling
Farrowing Combi diffuse ceiling
Ground channel
Gestation/ insemination
Combi diffuse ceiling
Inlet valves
Fatteners/ rearing gilts
Combi diffuse ceiling
Inlet valves
![Page 35: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/35.jpg)
Diffuse Air-inlet system
Diffuse ceiling on 2.80 m. ± 1/3 of the ceiling must be closed and
insulated. Opening in ceiling panels: 0,8 cm²/m3 Two layers of 6 cm. special glass wool. Install strips of plastic bubble foil (20 cm.)
between the perforated plates and beams to prevent air leaks and “cold bridges”. Solid floor in the corridor.
![Page 36: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/36.jpg)
![Page 37: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/37.jpg)
![Page 38: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/38.jpg)
![Page 39: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/39.jpg)
![Page 40: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/40.jpg)
![Page 41: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/41.jpg)
Combi-diffuse Air-inletsystem
Above the corridor an opening of 2 cm. made of a hollow pvc-panel.
20 cm above the insulation and 40 cm below the ceiling.
Pvc panel exactly in the middle of the corridor.
![Page 42: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/42.jpg)
![Page 43: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/43.jpg)
![Page 44: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/44.jpg)
![Page 45: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/45.jpg)
![Page 46: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/46.jpg)
![Page 47: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/47.jpg)
![Page 48: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/48.jpg)
Groundchannel-ventilation
- Air comes from an air-channel under the walkway through a slatted floor.
- The temperature cools down in summer (3-4 °C) - The temperature warms up in winter - 25 % less ventilation
![Page 49: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/49.jpg)
![Page 50: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/50.jpg)
![Page 51: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/51.jpg)
![Page 52: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/52.jpg)
Climate computer
SettingsTemperature set pointHeating set pointMinimum ventilationMaximum ventilationBandwidthClimate curve
![Page 53: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/53.jpg)
Avoid mistakes in climate controlChoose the inlet system depending on the
animals.After that make the drawings and
calculations depending on that inlet system.Ask for 2 or 3 offers and choose not the
cheapest but the best company to make the ventilation system.Install the right settings. Very important are
the settings for 100% ventilation
![Page 54: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/54.jpg)
Laying behavior
![Page 55: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/55.jpg)
![Page 56: Presentation finland](https://reader036.vdocuments.net/reader036/viewer/2022062514/55875005d8b42a7c718b4579/html5/thumbnails/56.jpg)