presentation transformer oil
TRANSCRIPT
TESTING AND ANALYSIS OF TRANSFORMER OIL
Delivered by: Er. Harkiranjit Kaur Asstt. Director /P&D ( TS) Dated 30.08.2004
TRANSFORMER FLUID IS POWERFUL
DIAGNOSTIC TOOL
1. Characterization : Which gives parameters that can be used to identify the oil.
2. Ageing status : Which gives parameters relevant to the ageing process.
3. Dielectric Status : Which gives parameters used to determine the dielectric safety margin and dielectric characteristics of the insulation spaces.
4. Degradation status : which gives parameters relevant faults failure and wear.
CHEMISTRY AND COMPOSITION OF OIL
Transformer oils are made from a mixture of Paraffinic (CP), Naphthenic (CN) and Aromatic (CA) molecules in varying proportions and all the three components are essential in certain proportion for good and long performance of the transformers .
Difference between Naphthenic oil and Paraffinic Base oil :
Pour point of Paraffinic base oil is more than Naphthenic base oil.
Naphthenic based oils are more easily oxidized as compared to paraffinic oils
the Naphthenic based oil has 25% reduced viscosity at 70ºCdue to which it act as a better coolant
AROMATIC MOLECULES:
It is that component which give the oil its oxidation and ageing stability.
It is considered maximum upto 8%.
CHARACTERSTICS OF OIL:
Sr.No
Characteristics Requirement as per ISS-335
1. Appearance Clear & transparent
2. Density at 29.5 deg. C (Max.)
0.89 g/cm3
3. Kinematic viscosity at 27 °C (Max)
27 cSt
4. Interfacial tension at 27 °C (Min.)
0.04 N/M
5. Flash Point (Min.) 140 °C
6. Pour Point (Max.) -6 °C
7. Neutralization valueTotal acidity (Max.)
0.03 mg KOH/g
8. Corrosive Sulphur Non-corrosive
9. Electric strength (Break down voltage) Min.New Unfiltered oil
30KV (rms) (Min.)If the above value is not obtained the oil shall be filtered.
After filtration 60KV(r.m.s) (Min.)
10. Dielectric dissipation factor (Tan-delta) at 90 ° C
0.002 (Max.)
11. Water content (Max.) 50ppm
12. Specific resistance (Resistivity) a) At 90 °C (Min.) b) At 27 °C (Min.)
35X1012 ohm-cm1500X1012 ohm-cm
13. Oxidation stability (after oxidation for 164 hours @ 100 °CNeutralization value after oxidation (Max.)Total sludge after oxidation (Max.)
0.40 mg KOH/g0.10% by weight
14. Ageing characteristics after accelerated ageing (open beaker method with copper catalyst) i.e. 96 hours at 115 °C
a. Specific resistance (resistivity) i) At 27 °C (min.)ii) At 90 °C (min.)
25X1012 ohm-cm0.2X1012 ohm-cm
b. Dielectric dissipation factor (Tan delta) at 90 °C
i) Total acidity, mg. KOH/gii) Total sludge value percent
by weight.
0.20 Max.
0.05 Max 0.05 Max
15. Presence of oxidation inhibitor Absent
PERMISSIBLE VALUES OF OIL CHARACTERISTICS FOR
IN SERVICE TRANSFORMER OIL AS PER ISS 1866:2000
Sr. No.
Name of Characteristics
Equipment voltage
Permissible limit for in service T/F
Oil ISS:1866-2000
1. Electric Strength (Break down voltage (KV) (Minimum)
A)>170KV B)>72.5KV-
170KVC) 72.5KV and
below
5040
30
2. Specific resistance (Resistivity at 90degC) ohm-cm (Minimum)
All voltages 0.1X1012
3. Neutralization value
All voltages 0.3mg
3. Water Content (PPM) (Max)
A)>170KVB)>72.5KV-170KVC) 72.5KV and below
2040No free moisture at Room Temperature
4. Dielectric dissipation factor max (Tan Delta) at 90°C
A)>170KVB&C) Upto 170KV
0.20.1
6. IFT at 27°C (m N/m) Min
All voltages 15
7. Flash Point °C - 15 ° C (Max.) decrease from initial value
CONDITION MONITORING OF TRANSFORMER OIL
ELECTRICAL PARAMETRS
DIELECTRIC STRENGTH
Popularly known as BDV. BDV of oil is the AC voltage which causes spark between two electrodes placed in the oil under test at the standard distance of 2.5mm.
Indicator of solid impurities and water content present in the oil
BDV of the oil within transformer goes down slowly as the water content and conducting impurities increase as a result of oxidation of oil
The minimum value of BDV is (30KVrms) for new unfiltered oil and 60KV(rms)(min.) after filtration
SPECIFIC RESISTANCE (resistivity)
Also called resistivity . It is the DC resistance of volume of oil of unit cross sectional area and unit length
It should be as high as possible .
An increase in temperature reduces the resistivity .
The value of resistivity is considered as 35x1012 ohm-cm at 90ºC and 1500x1012 ohm-cm at 27ºC. The resistivity of the used oil at 90ºC may be taken as 0.1x1012 ohm- cm(min.).
DIELECTRIC DISSIPATION FACTOR
Popularly known as Tan delta or loss factor Reveals presence of contaminants picked by oil ,derived
due to oxidation, poor manufacture or bad use of equipment.
High value of DDF leads to increased 1. heating leading to thermal runway 2. corrosion & oxidation 3. water solubility and emulsifying power. Low value of DDF– ensures freedom from moisture, polar
compounds, soluble impurities and minimum energy loss.
Limits (Max) at 90° C new oil 0.002 oil in service less than 170 KV 0.2 for upto 170KV class 1.0 SK VALUE SK value prescribes the behavior of insulating oils in the
presence of concentrated Sulfuric acid
It furnishes the information on the refining degree of mineral oil.
SK value % by weight – 4 to 8% (max). Under consideration as per IS
:
CHEMICAL PARAMETRS
WATER CONTENT Presence of water in oil adversely affect the
dielectric properties of the oil. Water present in oil is absorbed by the solid
insulation of the transformer. The water present in oil is measured in ppm and
measured with sophisticated instruments like Karl/Fischer
The max. value of water in new transformer oil may be taken as 50ppm followed by 20ppm in used oil.
ACIDITY/ NEUTRALISATION NUMBER : Measure of acidity in new & used mineral Insulating
oils Expressed in number of mg of KOH required to
neutralize 1g of oil. Limits 1) New oil -- --- 0.03mg KOH/g (max)
2) Service oil --- 0.3 mg KOH/g
CORROSION TEST: To detect any traces of free or combined sulphur
that may be present in an oil . The presence of sulphur promotes oxidation and
also corrodes the copper and silver metal points of the equipment.
Colour of copper after test : Orange red , Multi coloured ---New corrosive Black, grey or brown--- Corrosive New insulating oil is required to be non Corrosive.
OXIDATION STABILITY : Another method to determine the quality of New
insulating oil with respect to oxidative Degradation. IS consists in ageing 25g of the oil at 100ºC for 164
hours during which oxygen at the rate of one litre/ hour is bubbled into the oil.
The maximum limits fixed for new oils are acidity
0.4mg KOH/gm and sludge 0.1 percent by weight. PRESENCE OF OXIDATION INHIBITER: The Indian Standards IS:335 (1993) is applicable to
only unhibited oils .
Oil containing any amine or phenolic type of inhibitors is not accepted.
PHYSICAL PARAMETERS: DENSITY: The ratio of the weight of a given volume of the oil
to the weight of the same volume of water. TEST METHOD: IS: 1448 (Part 16) – 1997 Evaluating methods -Hydrometer method & Density bottle method Density range: 0.85 – 0.89 g/CC (max)
VISCOSITY : Measurement of resistance to gravity flow of a liquid,
the pressure head being proportional to its density UNIT : CENTISTOKES (cSt) Test method – is : 1448(Part 25) 01976 VISCOSITY – TEMP. RELATIONSHIP Low viscosity at low temp. Efficient heat removal from windings Prevents localized over heating. Kinematic viscosity at 27 °C (Max) is 27 cSt.
POUR POINT : TEST METHOD – IS-1448(P-10)-1970 The sample oil is cooled and the temperature at
which it does not flow when held horizontally in a tube for 5 seconds is noted.
High pour point- Increase in viscosity ,When exposed to weather, hinder convection currents & poor cooling of windings.
The limit of pour point (max) as per IS is -6°C.
FLASH POINT The minimum temp at which oil gives so much vapors
that this vapor when mixed with & forms and ignitable mixture and gives a momentary f lash on application of small pilot flame.
TEST METHOD – IS : 1448 (P:21)-1970 Low Value – Risk of fire in transformer Min. Limit as per IS: 335 – 140°C Max. reduction for in service oils as per IS 1866– 15 deg
C
INTERFACIAL TENSION: Measurement of molecular attractive force between
their unlike molecules at the interface Of oil and water. Unit = N/m TEST METHOD – IS:6104 – 1971 It is the force required to lift a planar ring of
platinum from the Oil. Limit as per IS: 335- 0.040 N/m (min) For oil in service IS: 1866 – 0.015 N/m (min)
SLUDGE: Sludge deposits itself on windings, tank walls and in
cooling ducts. The deposition of sludge in the oil ducts blocks the
free circulation of oil thereby/impairing cooling,
increased temperature and more sludge.
TESTS TO BE PERFORMED ON IN SERVICE OILS:
Tests for Electrical properties and DGA of the oil of the transformer of the age below 10 years should be done after every two years and of more than 10 years, it should be done every year. These tests are also required to
be carried out after every dehydration.
DIAGNOSTIC TESTS: Dissolved gas analysis in oil Furanic compounds in oil Metals in oil Water content in oil and relative saturation
DISSOLVED GAS ANALYSIS: The causes for the generation of gases are classified
as : Thermal degradation/Insulation Decomposition Arcing Partial discharge
Oxidation Vaporization
Major and Minor gases produced are:
Major Gas Minor Gas Nature of fault
C2H4 CH4 Thermal decomposition
CH4 H2 Hot spot
H2 , CH4 C2H6, C2H2, C2H4
Electrical discharge
H2 CH4, C2H6 Internal Corona
CO, CO2 - Cellulous insulation Decomposition
The sensitivity limits for gases dissolved in oil shall meet the following requirements :
Hydrogen : 5ppm Hydrocarbons : 1ppm (Methane, Ethane, Acetylene, Propane, Ethylene,
Propylene) CO,C O2 : 25ppm O2, N2 : 50ppm Before considering that any gas is present in significant
quantity, its concentration shall be at least 10 times these sensitivity level
As per Morgan and Morse, the recommended safe gas levels in oil immersed equipment are:
Gas Dissolved Gas Concentration
H2 <20n+50
CH4 <20n+50
C2H6 <20n+50
C2H4 <20n+50
C2H2 <5n+10
CO <25n+500
CO2 <100n+1500
TCG <105n+710
Here n = number of years in service of transformer TCG= Total Combustible Gas GAS GENERATION RATE :
Rate of gas generation is different for every transformer due to its unique loading condition & design.
Transformer Rating TCG/ppm/year >275KV >10MVA 350 <10MVA 250 500KV - 150
INTERPRETATION SCHEMES; IEC 599 Method: Code of range of Ratios C2H2 CH4 C2H4 C2H4 H2 C2H6 Ratios of Characteristic Gases
<0.1 0 1 0
0.1-1 1 0 0
1-3 1 2 1
>3 2 2 2
Case No. Diagnosis of
faults/Characteristic fault Typical examples
0 No fault 0 0 0 Normal ageing 1 Partial discharges 0 1 0
of low energy density Discharge in gas-filled cavities
2 Partial discharges 1 1 0 of high energy density
As above, but leading to tracking or per formation of solid insulation.
3 Discharge of low 1-2 0 1-2
energy
Continuous
sparking in oil
4 Discharge of high 1 0 2
energy Arcing breakdown of oil between coils to earth
5 Thermal fault of low 0 0 1Temp.150°C
General insulated conductor overheating.
6 Thermal fault of 0 2 0low temp. 150°C –300°C
Local overheating of the core
7 Thermal fault of 0 2 1Medium temp. 300°C –700°C
-do-
8 Thermal fault of 0 2 2High temp. 700°C
-do-
Rogers Method
CH4H2
C2H6CH4
C2H4C2H6
C2H2C2H4
Analysis
0 0 0 0 If CH4/H2 is =0 or 0.1 P.D. otherwise normal
deterioration 1 0 0 0 Slight overheating below
150°C
1 1 0 0 Slight overheating 150°C -200° C
0 1 0 0 Slight overheating 200°C -300°C
0 1 1 0 General conductor overheating
1 0 1 0 Circulating current overheated joints
0 0 0 1 Flash over without power flow.
0 1 0 1 Tap changer breaking current
0 0 1 1 Arc with persistent sparking
TDCG Method: ( Total Dissolved Combustible Gas (TDCG) Limits in PPM)Fault Gases :H2 CH4 C2H6 C2H4, C2H CO CO 100 120 65 50 35 350 2500
TCG=720(PPM) TDCG LIMITS ACTION
≤720 Satisfactory operation 721-1920 Normal ageing/ slight decomposition 1921-4630 Significant decomposition
>4630 Substantial decomposition
SAMPLING: Properly retrieving a sample of oil is important to ensure
that it is a true representative of oil in the equipment sample should be drawn when the equipment is warm. For Forced oil cooled transformers , the oil pumps should
be run for at least 10 minutes before sample is drawn . Two samples instead of one drawn at a time . Sample containers must be full , wrapped, labeled and
sealed. CELULOSE DEGRADATION : For a transformer with healthy cellulose insulation the
ratio of the CO2/CO is expected to be in the range of 3 to11 . CO2 and CO are also produced due to oil break down, moisture content and temperature of degradation and some times this ratio may lead to wrong indications
FURANIC COMPOUNDS: Test have been developed which detect oil soluble
breakdown products of the cellulose chain called furanic compounds.
The 5 compunds namely are: 5-Hydroxymethyl-2- furaldehyde 2-furfural alcohol 2-furfuralhyde 2-acetylfuran 5-methyle-2-furalhydeAmong these 2-furfural is the most significant
Relationship between DP(Degree of Polymerization) value and the amount of furanic concentration in the oil:
Lower DP values indicate increased furfural content when paper samples were subjected to heating over a long period.
Filtration of oil removes already existing furan temporarily and they re-appear in their original concentration levels after 6 months.
Limits of furan are as prescribed by CPRI are:
TOTAL FURAN (PPB) CONDITION
0-100 Normal
101-250 Questionable
251-1000 Deteriorated
1001-2500 Low reliable>2500 Replace the windings
ANALYSIS OF METALS IN OIL: Diagnostic or investigative tool when other system
indicate an incipient-fault condition. The most common metals dissolved in the oil could be
iron copper or aluminum depending upon the coil construction.
Since new oil in transformers should not have significant quantities of any dissolved or particulate metals any appreciable increase of metals in the oil could be an indicator of where a problem may exists
MAINTENANCE PROCEDURE FOR THE INSULATING OIL IN TRANSFORMERS :
Oil level of the transformer should be checked at frequent interval and leakage of oil should be investigated.
All leaks should be repaired as quick as possible . The oil for topping up should preferably be from the
some source as the original oil . Samples of oil should be taken at regular intervals
and tested Don’t rely upon the dielectric strength of the oil. Reconditioning by centrifugal separation or filtration
doesn’t remove the acidity from oil but will remove sludge, dust, dirt etc
Filter with fullers earth will help the reduce acidity in the oil and in addition improve the resistivity.
If BDV is below 40KV and 50KV for HV & EHV respectively the oil should be reconditioned by passing through filter machine. If acidity is increasing rapidly or exceeds above 0.5mg, KOH/gm of oil, the oil should be treated for improvement to 0.5 of less.
If the Tan delta of oil is increasing rapidly and exceeds above 0.01 to 0.2, oil should be treated for improvement to 0.01 or less.
CONCLUSIONS; All tests have to be carried out as per IS:1866
systematically and periodically, as a part of maintenance schedule.
The periodic testing will help O&M personnel to build up databank and case histories of Power Transformers.
Periodic testing will help to know the oil condition as well to know growing of any incipient faults by Dissolved Gas Analysis.