Pressure Control System: Root Locus Plotting. Team Green: X Y Z. Outline. Pressure System Background Previous Work: Transfer Function Root Locus Theory Modeling Results Conclusions. Background: Schematic Diagram. Background: Block Diagram. Manipulated Variable. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Pressure Control System: Root Locus Plotting

Pressure Control System:Root Locus Plotting

Team Green:

X

Y

Z

Page 2: Pressure Control System: Root Locus Plotting

Outline

Pressure System Background Previous Work: Transfer Function Root Locus Theory Modeling Results Conclusions

Page 3: Pressure Control System: Root Locus Plotting

Background: Schematic Diagram

Page 4: Pressure Control System: Root Locus Plotting

Background: Block Diagram

Manipulated Variable

M System C

Controlled Variable

% Motor Speed Pressure in cm-H2O

Page 5: Pressure Control System: Root Locus Plotting

Background: SSOC

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

0 10 20 30 40 50 60 70 80 90 100

% Motor

Operating Range: 30 – 70%

Ou

tpu

t: 1.3 –3.8 cm

H2O

Page 6: Pressure Control System: Root Locus Plotting

Background: FOPDT Parameters

K = 0.061 cm of H2O / %

to = 0.25 sec = 0.4 sec

Page 7: Pressure Control System: Root Locus Plotting

Feedback Control

Page 8: Pressure Control System: Root Locus Plotting

Root Locus Theory

Where is the damping ratio.

Decay Ratio =

Page 9: Pressure Control System: Root Locus Plotting

Effects of

Overdamped = monotonic and stable

Underdamped = oscillatory and stable

Undamped = sustained oscillations

Unstable = growing oscillations

Run-away = monotonic and unstable

Page 10: Pressure Control System: Root Locus Plotting

Four Possible Responses

Stable, Monotonic

Unstable, Oscillatory Unstable, Monotonic

Stable, Oscillatory

Page 11: Pressure Control System: Root Locus Plotting

Root Locus Parameters

KCD = highest value of KC that provides monotonic and stable output (critically damped)

KQD = value of KC that produces one-

quarter oscillating decay KCU = highest value of KC that causes

oscillatory and stable output (marginally stable)

Page 12: Pressure Control System: Root Locus Plotting

Root Locus Parameters

KCD is found where the roots go from real to complex

KQD is found where the ratio of the imaginary root to the real root is 4.5

KCU is found where the real portion of the root goes from negative to positive.

Page 13: Pressure Control System: Root Locus Plotting

Parameter Locations

ROOT LOCUS PLOT

-10

-8

-6

-4

-2

0

2

4

6

8

10

-6 -5 -4 -3 -2 -1 0 1

REAL AXIS

IMA

GIN

AR

Y A

XIS

KCD

KCUKQD

Dr Henry’s Suggestion:Put the VALUES of the Kc’sfor the different choices you have on this graph

Page 14: Pressure Control System: Root Locus Plotting

Locations ROOT LOCUS PLOT

-10

-8

-6

-4

-2

0

2

4

6

8

10

-6 -5 -4 -3 -2 -1 0 1

REAL AXIS

IMA

GIN

AR

Y A

XIS

DR=0

DR=1/500

DR=1/10

DR=1/4

DR=1/1

Page 15: Pressure Control System: Root Locus Plotting

Results from Root Locus

Ultimate Kcu= 37

Quarter Decay Kc = 24.

Critically Damping Kc = 0.1

Underdamped 0.1< Kc < 37

Overdamped 0 < Kc < 0.1

*all units are % / cm H2O

Page 16: Pressure Control System: Root Locus Plotting

Conclusions

For Kc needed

Overdamped 0 < Kc < 0.1

Critically Damped Kc = 0.1

Underdamped 0.1< Kc < 36.9

Quarter Decay Kc = 24.2

*all units are % / cm H2O

Page 17: Pressure Control System: Root Locus Plotting

Questions?